16 Samss 502
16 Samss 502
16 Samss 502
1 Scope............................................................ 2
2 Conflicts and Deviations............................... 2
3 References.................................................... 2
4 Information Required with Quotation............ 4
5 Definitions..................................................... 5
6 General......................................................... 6
7 Service Conditions........................................ 7
8 Construction Requirements.......................... 7
9 Power Circuit Breakers................................ 14
10 Instrument and Control Transformers.......... 16
11 Protective Relaying...................................... 17
12 Control.......................................................... 18
13 Metering and Indication............................... 19
14 Automatic Transfer Schemes...................... 21
15 Accessories................................................. 22
16 Tests............................................................ 23
Data Sheet......................................................... 25
1 Scope
1.1 This specification defines the mandatory requirements that shall apply to metal-
enclosed low-voltage, power circuit breaker switchgear and drawout power
circuit breakers. This equipment is designed, manufactured and tested to
International Electrotechnical Commission (IEC) Standards or North American
(NA) Standards. This equipment is to be used in three phase electrical systems
having a maximum rms AC voltage not higher than 600 volts.
1.2 This specification defines the basic features of the equipment required and shall
take precedence over all Standards and Codes as referenced. The equipment
manufacturer shall ensure that the applicable standards are adhered to in
addition to this specification. Requirements that specifically apply to equipment
manufactured to North American standards are identified as NA. Requirements
that specifically apply to equipment manufactured to International
Electrotechnical Commission standards are identified as IEC.
2.1 If there are any conflicts between this Specification and associated purchasing,
project or engineering documents, this specification shall take precedence.
2.2 Direct all requests to deviate from this Specification in writing to the Company
or Buyer Representative, who shall follow internal company waiver procedure.
3 References
The following is a summary of all the documents which have been mentioned within
this Specification. The specific part(s) of these documents which are applicable have
been identified throughout this Specification.
Page 2 of 25
Document Responsibility: Electrical Substations Equipment 16-SAMSS-502
Issue Date: 22 November 2008 Metal-Enclosed, Metal-Clad
Next Planned Update: 19 October 2013 Low-Voltage Switchgear Assemblies
Page 3 of 25
Document Responsibility: Electrical Substations Equipment 16-SAMSS-502
Issue Date: 22 November 2008 Metal-Enclosed, Metal-Clad
Next Planned Update: 19 October 2013 Low-Voltage Switchgear Assemblies
4.1 A detailed listing of all deviations from this standard with an explanation against
each item. In addition, written certification shall be provided that the proposed
equipment shall fully comply with all other items within this Standard.
Page 4 of 25
Document Responsibility: Electrical Substations Equipment 16-SAMSS-502
Issue Date: 22 November 2008 Metal-Enclosed, Metal-Clad
Next Planned Update: 19 October 2013 Low-Voltage Switchgear Assemblies
5 Definitions
86: Lock-out relay. Shall not require control power to maintain the locked-out
condition.
Bus Tie Breaker: A breaker used to connect the two busses of secondary-selective
system.
Discrete: Device which only performs one function. For example, a discrete voltmeter
only displays voltage.
Line: The terminal of the switching device to which the source of voltage/power is
connected.
Load: The terminal of the switching device to which the equipment receiving the
voltage/power is connected.
Page 5 of 25
Document Responsibility: Electrical Substations Equipment 16-SAMSS-502
Issue Date: 22 November 2008 Metal-Enclosed, Metal-Clad
Next Planned Update: 19 October 2013 Low-Voltage Switchgear Assemblies
Space: A compartment the same as a spare but without the power circuit breaker
installed.
Supervised: Used in the context of protective relay circuits. The supervised devices
shall be continuously checked for circuit continuity by having a small amount of current
pass through the device. Loss of this current flow shall change the status of either a
visual indicator or relay.
Switching assembly: The assembly of switching devices and associated control and
auxiliary equipment which controls or distributes power to a single load or via a single
circuit. For this specification, all switching assemblies are withdrawable circuit
breakers, therefore, the terms "switching assembly" and "withdrawable circuit breaker"
are synonymous.
6 General
6.2 The switchgear and air circuit breakers shall also fully comply with either IEC
or NA standards. Switchgear built utilizing a mixture of Standards is
unacceptable (e.g., It is not acceptable for devices only tested and rated by IEC
standards to be installed within a switchgear assembly tested and rated per NA
standards, or vice versa).
Page 6 of 25
Document Responsibility: Electrical Substations Equipment 16-SAMSS-502
Issue Date: 22 November 2008 Metal-Enclosed, Metal-Clad
Next Planned Update: 19 October 2013 Low-Voltage Switchgear Assemblies
6.4 Whenever this specification requires compliance to a third party document such
as ANSI or IEC standards this document shall be the edition which was in effect
on the date of the Quotation Request.
6.6 All temperatures expressed within this specification are in Celsius units.
6.7 The Buyer's nonmaterial requirements are presented within Saudi Aramco Form
NMR-7910. This form is included with the Quotation Request or the Purchase
Order documents.
7 Service Conditions
Switchgear shall be suitable for continuous operation under the following service
conditions:
a) A maximum of 40 degrees.
b) A minimum of 0 degrees.
7.3 Altitude is under 1000 meters, unless a higher altitude is specified within Data
Schedule 1.
8 Construction Requirements
8.1 General
Page 7 of 25
Document Responsibility: Electrical Substations Equipment 16-SAMSS-502
Issue Date: 22 November 2008 Metal-Enclosed, Metal-Clad
Next Planned Update: 19 October 2013 Low-Voltage Switchgear Assemblies
8.1.3 The switchgear assembly shall have a three-phase, rms symmetrical short
circuit current rating equal to the short circuit rating of the lowest rated
power circuit breaker utilized within the assembly.
8.1.4 The continuous rating of the complete switchgear assembly shall not be
dependent on the use of cooling fans or other auxiliary cooling means.
8.1.5 The main circuit bus systems of switchgear and controlgear shall not
be connected together.
Exception:
8.2.1 General
8.2.2 Compartments
Page 8 of 25
Document Responsibility: Electrical Substations Equipment 16-SAMSS-502
Issue Date: 22 November 2008 Metal-Enclosed, Metal-Clad
Next Planned Update: 19 October 2013 Low-Voltage Switchgear Assemblies
8.2.2.2 The bus tie breaker shall be in a separate vertical section (one-
high arrangement).
8.2.2.4 There shall be a minimum of one space on each bus section for
each secondary-selective switchgear lineup. Refer to Data
Schedule 1 or associated engineering documents for spare
requirements and space requirements beyond these minimums.
Commentary 8.2.2.4:
Note that per Section 8.2 and Section 4 all the feeder and
spare breakers shall be of the same rating.
Page 9 of 25
Document Responsibility: Electrical Substations Equipment 16-SAMSS-502
Issue Date: 22 November 2008 Metal-Enclosed, Metal-Clad
Next Planned Update: 19 October 2013 Low-Voltage Switchgear Assemblies
8.2.4.2 The racking mechanism shall move the circuit breaker between
the connected, test, and disconnect positions.
8.2.4.3 One circuit breaker lifting device shall be provided for each
switchgear assembly.
8.2.5 Space heaters shall not be installed within the switchgear assembly.
8.3 Buses
8.3.1 General
8.3.1.3 All buses shall be designed for future extension and it shall not
be necessary to disturb any equipment or wiring when an
extension is made.
Page 10 of 25
Document Responsibility: Electrical Substations Equipment 16-SAMSS-502
Issue Date: 22 November 2008 Metal-Enclosed, Metal-Clad
Next Planned Update: 19 October 2013 Low-Voltage Switchgear Assemblies
Exception:
8.3.2.4 The entire length of main power buses shall be equally rated.
Tapered bus sizing is prohibited.
Commentary 8.3.2.4:
Reduced bus size is permitted for the taps to the main power
bus.
8.3.2.5 Cable is not allowed for use as a power bus, either main
horizontal or vertical buses.
8.3.3.1 A solid copper ground bus shall be furnished and shall extend
the entire length of the switchgear. The ground bus shall be
capable of carrying the rated short circuit current.
Page 11 of 25
Document Responsibility: Electrical Substations Equipment 16-SAMSS-502
Issue Date: 22 November 2008 Metal-Enclosed, Metal-Clad
Next Planned Update: 19 October 2013 Low-Voltage Switchgear Assemblies
Feeder Tee-off connections from the main bus shall have the same short
circuit rating as the main bus.
8.4.4.1 The load side buses of each circuit breaker compartment shall
have provisions (be predrilled) for terminating 2-hole lugs for
the required number of cables as indicated on the Engineering
Drawings.
Page 12 of 25
Document Responsibility: Electrical Substations Equipment 16-SAMSS-502
Issue Date: 22 November 2008 Metal-Enclosed, Metal-Clad
Next Planned Update: 19 October 2013 Low-Voltage Switchgear Assemblies
8.5 Finish
8.5.1 General
All carbon steel metal parts shall be protected from rust and corrosion by
painting or plating.
8.5.2 Painting
8.5.3 Plating
Carbon steel switchgear and circuit breaker parts that are not painted
shall be plated with cadmium, yellow zinc-chromate or similar corrosion
resistant materials.
8.6 Nameplates
Device Nameplates
8.6.1 The Manufacturer's shop order number, date, and catalog designation
should be indicated on the switchgear nameplate in addition to the
nameplate information required by the Standards.
8.6.5 Device nameplates shall be engraved laminated plastic with black 6-mm
characters on a white 60-mm by 25-mm background as a minimum.
Page 13 of 25
Document Responsibility: Electrical Substations Equipment 16-SAMSS-502
Issue Date: 22 November 2008 Metal-Enclosed, Metal-Clad
Next Planned Update: 19 October 2013 Low-Voltage Switchgear Assemblies
9.1 Rating
Power circuit breaker maximum continuous current rating shall not exceed 4000
amperes. The interrupting rating shall not exceed a maximum of 85 kA rms
symmetrical amperes.
9.2 Design
9.2.1 Only dead-front, draw out design, low-voltage power circuit breakers
shall be used.
9.2.4 Insulated case (encased) and molded case circuit breakers shall not be
used in lieu of power circuit breakers.
9.2.5 The continuous current rating of each low-voltage power circuit breaker
shall not be dependent on fan cooling or other auxiliary cooling.
9.2.6 Feeder circuit breakers in the switchgear assembly shall have the same
ratings and be interchangeable.
Page 14 of 25
Document Responsibility: Electrical Substations Equipment 16-SAMSS-502
Issue Date: 22 November 2008 Metal-Enclosed, Metal-Clad
Next Planned Update: 19 October 2013 Low-Voltage Switchgear Assemblies
9.3 Construction
9.3.1 Low-voltage power circuit breakers shall be equipped with a spring type,
stored-energy mechanism (electrically and/or mechanically charged),
designed to close and latch the circuit breaker mechanism at rated short
circuit current conditions.
9.3.3 The power circuit breakers shall be equipped with the necessary
disconnecting contacts, wheels, rollers, slide plates etc, and interlocks for
draw out application.
9.3.4 Construction shall permit the compartment door to be closed with the
power circuit breaker in the connected, disconnected test, and fully
withdrawn or removed positions. The fully withdrawn position is the
position when the breaker is removed from the cubicle drawout rails.
9.4.2 Each circuit breaker shall have a minimum of four (4) convertible
auxiliary contacts or two normally open and two normally closed
contacts available for BUYER use, wired to terminal blocks. These
contacts shall be in addition to those required for circuit breaker
operation and indication.
Page 15 of 25
Document Responsibility: Electrical Substations Equipment 16-SAMSS-502
Issue Date: 22 November 2008 Metal-Enclosed, Metal-Clad
Next Planned Update: 19 October 2013 Low-Voltage Switchgear Assemblies
breaker is open, prevent manual or electrical closing and secure the breaker in
the test or disconnected position.
Commentary Note 9.5:
Page 16 of 25
Document Responsibility: Electrical Substations Equipment 16-SAMSS-502
Issue Date: 22 November 2008 Metal-Enclosed, Metal-Clad
Next Planned Update: 19 October 2013 Low-Voltage Switchgear Assemblies
11 Protective Relaying
11.1.2 The solid state trip systems shall be furnished with adjustable long-
time, short-time, and ground protective functions or their
combinations. The continuous current rating shall be adjustable from
100% to at least 50% of the current rating of the circuit breaker frame.
The instantaneous trip function shall only be provided if specified
within the Buyers engineering documents. Refer to the Buyers
engineering documents for the specific trip function requirements for
each breaker.
11.1.3 The integral, solid state trip systems shall be capable of being field
tested with a Buyer supplied portable test device capable of simulating
fault conditions and providing verification of the selected setting and
characteristics desired for all protective functions.
The protection schemes for Fire Pump Unit (FPU) packages shall comply with
NFPA 20 and NFPA 70. In general these standards require that the motor be
allowed to operate under locked rotor condition continuously and is only
automatically disconnected under short-circuit conditions.
Exception:
The exception to these requirements is that where a FPU package is fed from a
bus that has ground overcurrent protection on the incomers or supply
transformers, the feeder to the FPU package shall have ground overcurrent
protection, and all other feeders connected to the same buses or transformers
shall have ground overcurrent protection.
Page 17 of 25
Document Responsibility: Electrical Substations Equipment 16-SAMSS-502
Issue Date: 22 November 2008 Metal-Enclosed, Metal-Clad
Next Planned Update: 19 October 2013 Low-Voltage Switchgear Assemblies
12 Control
12.1 General
12.2.1 The control voltage level for all tripping circuits which are not integral
to the breaker shall be 125 VDC supplied by the Buyer.
12.2.3 A molded case circuit breaker or fuses shall be provided for protection
and isolation of tripping and closing circuits which are external to the
circuit breaker. A dedicated breaker or fuse set shall be used for both
the trip and close circuits for each electrically operated circuit breaker.
These shall be mounted within the low voltage compartment of each
operational circuit breaker, spare or space. Separate breakers or fuses
shall be provided for the auxiliary circuits (e.g., metering or
synchronizing devices).
12.2.4 Voltages and current signals to protective relays shall pass through a
set of isolation test switches either integral to the relay or mounted
within the low voltage compartment. These shall be configured to
allow isolation of the relays for testing purposes.
Exception:
12.2.5 The rated control voltage of all devices (e.g., protective relays) shall be
the same as the control supply voltage (i.e., intermediate voltage
converters shall not be used).
Page 18 of 25
Document Responsibility: Electrical Substations Equipment 16-SAMSS-502
Issue Date: 22 November 2008 Metal-Enclosed, Metal-Clad
Next Planned Update: 19 October 2013 Low-Voltage Switchgear Assemblies
12.3.1 Auxiliary lockout relays (Device 86) shall be hand-reset type and have
separate contacts connected in the closing and tripping circuits of the
circuit breakers
12.3.2 The electrical continuity of the Device 86 operating coil circuit shall be
supervised by a relay.
Trip-isolation test switches (not ganged) shall be installed in the lockout trip
circuits of the incoming circuit breakers. The test switches shall be mounted on
the front door of compartment containing the protective relaying.
12.5 Fuses
13.1 General
Meters and instruments shown on the drawings for each circuit breaker unit shall
be mounted in the compartment associated with the circuit breaker or in the
compartment directly above.
Page 19 of 25
Document Responsibility: Electrical Substations Equipment 16-SAMSS-502
Issue Date: 22 November 2008 Metal-Enclosed, Metal-Clad
Next Planned Update: 19 October 2013 Low-Voltage Switchgear Assemblies
green lights shall show the position of the power circuit breaker's main
contacts: red in closed position and green in open position.
13.2.2 Indicating lights shall be high intensity Light Emitting Diode (LED)
type. LED lamps shall provide a light intensity similar to a
incandescent fixture.
13.2.4 Indicating lights shall be installed in the front panel-door or the cubicle
frame next to the control switch they operate with and be replaceable
from the front.
13.3 Metering
13.3.1 Main incoming amperage and voltage metering shall be provided for
each main circuit bus of the switchgear assembly. This metering shall
have the following requirements:
13.3.2 Discrete meters (e.g., ammeters, voltmeters, pf meters, etc.) shall not
be installed within feeder breakers or bus tie breaker.
Page 20 of 25
Document Responsibility: Electrical Substations Equipment 16-SAMSS-502
Issue Date: 22 November 2008 Metal-Enclosed, Metal-Clad
Next Planned Update: 19 October 2013 Low-Voltage Switchgear Assemblies
13.4 Alarms
The contacts from the following shall be series connected to a termination point
within one of the low voltage compartments. These will be connected by the
Buyer to a local annunciator panel. Loss of continuity at these termination
points will be alarmed at this panel.
14.4.1 Allow time for motor residual voltage to decay to a negligible value or
the motors to be automatically disconnected.
14.5 All transfers shall be blocked and locked out by the switchgear bus or incoming
transformer 86 relays.
14.6 Loss/reduction of voltage shall be detected by a 27 relay on the line side of each
incoming breaker. The setting shall be 85% of nominal bus voltage and the time
delay shall be adjustable from 1 to 10 seconds.
Page 21 of 25
Document Responsibility: Electrical Substations Equipment 16-SAMSS-502
Issue Date: 22 November 2008 Metal-Enclosed, Metal-Clad
Next Planned Update: 19 October 2013 Low-Voltage Switchgear Assemblies
15 Accessories
15.1 Wiring
15.1.3 The numbering of the wire markers shall correspond to the numbering
of the connection points in the switchgear control and protection
system's schematic drawings.
15.1.4 Each control circuit shall be easily traceable for inspection checks and
modifications.
15.2.2 Insulated Ring type wire terminals shall be used in current transformer
wire terminations.
Page 22 of 25
Document Responsibility: Electrical Substations Equipment 16-SAMSS-502
Issue Date: 22 November 2008 Metal-Enclosed, Metal-Clad
Next Planned Update: 19 October 2013 Low-Voltage Switchgear Assemblies
15.3.2 Terminal blocks shall be open style, barrier type, with screw terminals,
rated 20 A, 600 volt minimum with prenumbered marking strips and
suitable for two(2) terminations per point.
All required special tools, such as nonstandard wrenches, sockets, etc., used to
latch/unlatch, bolt/unbolt the equipment supplied under this Specification, shall
be provided with each metal-enclosed low-voltage switchgear assembly.
16 Tests
16.1.2 At the time of delivery, the VENDOR shall furnish the BUYER with a
list of standards and specifications to which the metal-enclosed low-
voltage switchgear assemblies were tested.
16.1.4 Design or Type tests shall be provided for the switchgear and circuit
breakers. Tests on representative equipment may be submitted for
technical evaluation.
Page 23 of 25
Document Responsibility: Electrical Substations Equipment 16-SAMSS-502
Issue Date: 22 November 2008 Metal-Enclosed, Metal-Clad
Next Planned Update: 19 October 2013 Low-Voltage Switchgear Assemblies
Revision Summary
19 October 2008 Revised the "Next Planned Update". Reaffirmed the contents of the document and reissued
with editorial changes to replace the Electrical Substations Equipment Standards
Committees Chairman and Vice Chairman.
22 November 2008 Minor revision.
Page 24 of 25
Document Responsibility: Electrical Substations Equipment 16-SAMSS-502
Issue Date: 22 November 2008 Metal-Enclosed, Metal-Clad
Next Planned Update: 19 October 2013 Low-Voltage Switchgear Assemblies
Data Sheet
11 Feeder Circuit Breaker Mechanism Type Electrically and Manually Operated _______
(Control Voltage)
Note to Buyer:
(1)
This may be required if one of the buses receives it's primary power from, for example, a generator.~!
Page 25 of 25