Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Pump Affinity (K0 SNW)

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 6

The Affinity Laws of centrifugal pumps or fans indicates the influence on volume capacity, head (pressure) and/o

(a) change in speed of wheel - revolutions per minute (rpm),


(b) geometrically similarity - change in impeller diameter.

If both diameter and speed are changed, the equations are combined to become:

Q2 = Q1 x [(D2 x N2) / (D1 x N1)]

H2 = H1 x [(D2 x N2) / (D1 x N1)] ^2

HP2 = HP1 x [(D2 x N2) / (D1 x N1)] ^3


city, head (pressure) and/or power consumption of a pump or fan due to
The Affinity Laws of centrifugal pumps or fans Programmed by SNW

Change in Pump speed Change in Pump Impeller Dia

Original Flow (Q1) 445 l/s Original Flow (Q1) 65 l/s

Original Speed (N1) 16000 rpm Original Dia (D1) 300 mm

New speed (N2) 19000 rpm New Dia (Dia 2) 350 mm

New Flow (Q2) 528.4 l/s New Flow (Q2) 75.8 l/s

Change in Pump speed Change in Pump Impeller Dia

Original Pump Head (∆P1) 50 m Original Pump Head (∆P1) 41 m

Original Speed (N1) 16000 rpm Original Dia (D1) 300 mm

New speed (N2) 19000 rpm New Dia (Dia 2) 350 mm

New Pump Head (∆P2) 70.5 m New Pump Head (∆P2) 55.8 m

Change in Pump speed Change in Pump speed

Original Power (P1) 8.1 kW Original Power (P1) 30 kW

Original Speed (N1) 16000 rpm Original Dia (D1) 300 mm

New Speed (N2) 19000 rpm New Dia (Dia 2) 350 mm

New Power (P2) 13.6 kW New Power (P2) 47.6 kW


FOR RPM - 1450 with 50 Hz Pump 1600
Frequency (Hz) RPM (N)
1400
50 htz 1450 rpm
49 htz 1421 rpm 1200
48 htz 1392 rpm 1000
47 htz 1363 rpm
800 Frequency (Hz)
46 htz 1334 rpm
RPM (N)
45 htz 1305 rpm 600
44 htz 1276 rpm
400
43 htz 1247 rpm
42 htz 1218 rpm 200
41 htz 1189 rpm 0
40 htz 1160 rpm 0 2 4 6 8 10 12
How to use

Input data

result
E 415
kW 15 15000
1000 639.0
pf 0.89 23
1.73

E 415
kW 30 30000
1000 639.0
pf 0.89 47
1.73

95
75

You might also like