13-BCcontroller.qx:13-BCcontroller.

qx 25/4/08 15:20 Page 1

R410A Data G4

CITY MULTI™
BC controller CMB-P-V-G
CMB-P-V-GA, CMB-P-V-HA
CMB-P-V-GB, CMB-P-V-HB
CMB-P-V-G,GA,GB BC
A
1. SPECIFICATIONS BC-2
2. EXTERNAL DIMENSIONS BC-11 B
3. WIRING DIAGRAMS BC-16
C

V-A

V-B

BC

CT

BC CONTROLLER BC - 1
13-BCcontroller.qx:13-BCcontroller.qx 25/4/08 15:20 Page 2

1. SPECIFICATIONS R410A Data G4

Model name CMB-P104V-G CMB-P105V-G

Number of branch 4 5
A
1N ~ 220/230/240V
Power source
50Hz 60Hz 50Hz 60Hz
B
Cooling : 0.067/0.076/0.085 Cooling : 0.054/0.061/0.067 Cooling : 0.082/0.093/0.104 Cooling : 0.066/0.074/0.082
Power input kW
C Heating : 0.030/0.034/0.038 Heating : 0.024/0.027/0.030 Heating : 0.038/0.043/0.048 Heating : 0.030/0.034/0.038

D Cooling : 0.31/0.34/0.36 Cooling : 0.25/0.27/0.28 Cooling : 0.38/0.41/0.44 Cooling : 0.30/0.33/0.35


Current A
Heating : 0.14/0.15/0.16 Heating : 0.11/0.12/0.13 Heating : 0.18/0.19/0.20 Heating : 0.14/0.15/0.16
E
Galvanized steel plate
External finish
F (Lower part drain pan painting N1.5)
Connectable outdoor unit PURY-P200/250/300/350YHM-A(-BS) / PQRY-P200/250YGM-A
G
Model P140 or smaller
H Indoor unit capacity (Use optional joint pipe combining 2 branches when the total
connectable to 1 branch kW capacity exceeds 141.)
V-A (Use the reducer (standard accessory) when the indoor unit Model
50 or smaller is connected.)
V-B
External dimension H x W x D mm(in.) 284 x 648 x 432 (11-3/16” x 25-9/16” x 17-1/16”)
BC Connectable outdoor unit capacity
To P200 P250/P300 P350
CT outdoor
unit High press. pipe ø15.88 (ø5/8”) Brazed ø19.05 (ø3/4”) Brazed ø19.05 (ø3/4”) Brazed
Refrigerant
Low press. pipe ø19.05 (ø3/4”) Brazed ø22.2 (ø7/8”) Brazed ø28.58 (ø1-1/8”) Brazed
piping
diameter ø9.52 (ø3/8”) Flare
To Liquid pipe
(ø6.35 (ø1/4”) with attached reducer used, ø12.7 (ø1/2”) with optional joint pipe used.)
indoor
unit ø15.88 (ø5/8”) Flare
Gas pipe
(ø12.7 (ø1/2”) with attached reducer used, ø19.05 (ø3/4”) with optional joint pipe used.)
Field drain pipe size O.D. 32mm (1-1/4”)
Net weight kg(lb) 24 (53) 27 (60)

Accessories
·Drain Connection pipe (with flexible hose and insulation)
·Reducer
Note: *1. Installation/foundation work, electrical connection work, duct work, insulation work, power source switch,
and other items shall be referred to the Installation Manual.
*2. The equipment is for R410A refrigerant.
*3. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the
neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
*4.Indoor units P100,P125,P140 can be connected to 1 branch. (In this case, cooling capacity decrease a little.)

Ref.: M-WYNCO-6883&6884

BC CONTROLLER BC - 2
13-BCcontroller.qx:13-BCcontroller.qx 25/4/08 15:20 Page 3

1. SPECIFICATIONS R410A Data G4

Model name CMB-P106V-G CMB-P108V-G

Number of branch 6 8
A
1N ~ 220/230/240V
Power source
50Hz 60Hz 50Hz 60Hz
B
Cooling : 0.097/0.110/0.123 Cooling : 0.078/0.088/0.097 Cooling : 0.127/0.144/0.161 Cooling : 0.102/0.115/0.127
Power input kW
Heating : 0.045/0.051/0.057 Heating : 0.036/0.041/0.045 Heating : 0.060/0.068/0.076 Heating : 0.048/0.054/0.060 C

Cooling : 0.45/0.48/0.52 Cooling : 0.36/0.39/0.41 Cooling : 0.58/0.63/0.68 Cooling : 0.47/0.50/0.53 D


Current A
Heating : 0.21/0.23/0.24 Heating : 0.17/0.18/0.19 Heating : 0.28/0.30/0.32 Heating : 0.22/0.24/0.25
E
Galvanized steel plate
External finish
(Lower part drain pan painting N1.5) F
Connectable outdoor unit PURY-P200/250/300/350YHM-A(-BS) / PQRY-P200/250YGM-A
G
Model P140 or smaller
Indoor unit capacity (Use optional joint pipe combining 2 branches when the total H
connectable to 1 branch kW capacity exceeds 141.)
(Use the reducer (standard accessory) when the indoor unit Model V-A
50 or smaller is connected.)
V-B
External dimension H x W x D mm(in.) 284 x 648 x 432 (11-3/16” x 25-9/16” x 17-1/16”)
Connectable outdoor unit capacity BC
To P200 P250/P300 P350
outdoor CT
unit High press. pipe ø15.88 (ø5/8”) Brazed ø19.05 (ø3/4”) Brazed ø19.05 (ø3/4”) Brazed
Refrigerant
Low press. pipe ø19.05 (ø3/4”) Brazed ø22.2 (ø7/8”) Brazed ø28.58 (ø1-1/8”) Brazed
piping
diameter ø9.52 (ø3/8”) Flare
To Liquid pipe
(ø6.35 (ø1/4”) with attached reducer used, ø12.7 (ø1/2”) with optional joint pipe used.)
indoor
unit ø15.88 (ø5/8”) Flare
Gas pipe
(ø12.7 (ø1/2”) with attached reducer used, ø19.05 (ø3/4”) with optional joint pipe used.)
Field drain pipe size O.D. 32mm (1-1/4”)
Net weight kg(lb) 29 (64) 34 (75)

Accessories
·Drain Connection pipe (with flexible hose and insulation)
·Reducer
Note: *1. Installation/foundation work, electrical connection work, duct work, insulation work, power source switch,
and other items shall be referred to the Installation Manual.
*2. The equipment is for R410A refrigerant.
*3. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the
neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
*4.Indoor units P100,P125,P140 can be connected to 1 branch. (In this case, cooling capacity decrease a little.)

Ref.: M-WYNCO-6885&6886

BC CONTROLLER BC - 3
13-BCcontroller.qx:13-BCcontroller.qx 25/4/08 15:20 Page 4

1. SPECIFICATIONS R410A Data G4

Model name CMB-P1010V-G CMB-P1013V-G

Number of branch 10 13
A
1N ~ 220/230/240V
Power source
50Hz 60Hz 50Hz 60Hz
B
Cooling : 0.156/0.177/0.198 Cooling : 0.126/0.141/0.156 Cooling : 0.201/0.228/0.255 Cooling : 0.162/0.182/0.201
Power input kW
C Heating : 0.075/0.085/0.095 Heating : 0.060/0.068/0.075 Heating : 0.097/0.110/0.123 Heating : 0.078/0.088/0.097

D Cooling : 0.71/0.77/0.83 Cooling : 0.58/0.62/0.65 Cooling : 0.92/1.00/1.07 Cooling : 0.74/0.80/0.84


Current A
Heating : 0.35/0.37/0.40 Heating : 0.28/0.30/0.32 Heating : 0.45/0.48/0.52 Heating : 0.36/0.39/0.41
E
Galvanized steel plate
External finish
F (Lower part drain pan painting N1.5)
Connectable outdoor unit PURY-P200/250/300/350YHM-A(-BS) / PQRY-P200/250YGM-A
G
Model P140 or smaller
H Indoor unit capacity (Use optional joint pipe combining 2 branches when the total
connectable to 1 branch kW capacity exceeds 141.)
V-A (Use the reducer (standard accessory) when the indoor unit Model
50 or smaller is connected.)
V-B
External dimension H x W x D mm(in.) 284 x 648 x 432 (11-3/16” x 25-9/16” x 17-1/16”) 284 x 1,098 x 432 (11-3/16” x 43-1/4” x 17-1/16”)

BC Connectable outdoor unit capacity


To P200 P250/P300 P350
CT outdoor
unit High press. pipe ø15.88 (ø5/8”) Brazed ø19.05 (ø3/4”) Brazed ø19.05 (ø3/4”) Brazed
Refrigerant
Low press. pipe ø19.05 (ø3/4”) Brazed ø22.2 (ø7/8”) Brazed ø28.58 (ø1-1/8”) Brazed
piping
diameter ø9.52 (ø3/8”) Flare
To Liquid pipe
(ø6.35 (ø1/4”) with attached reducer used, ø12.7 (ø1/2”) with optional joint pipe used.)
indoor
unit ø15.88 (ø5/8”) Flare
Gas pipe
(ø12.7 (ø1/2”) with attached reducer used, ø19.05 (ø3/4”) with optional joint pipe used.)
Field drain pipe size O.D. 32mm (1-1/4”)
Net weight kg(lb) 39 (86) 47 (104)

Accessories
·Drain Connection pipe (with flexible hose and insulation)
·Reducer
Note: *1. Installation/foundation work, electrical connection work, duct work, insulation work, power source switch,
and other items shall be referred to the Installation Manual.
*2. The equipment is for R410A refrigerant.
*3. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the
neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
*4.Indoor units P100,P125,P140 can be connected to 1 branch. (In this case, cooling capacity decrease a little.)

Ref.: M-WYNCO-6887&6888

BC CONTROLLER BC - 4
13-BCcontroller.qx:13-BCcontroller.qx 25/4/08 15:20 Page 5

1. SPECIFICATIONS R410A Data G4

Model name CMB-P1016V-G

Number of branch 16
A
1N ~ 220/230/240V
Power source
50Hz 60Hz
B
Cooling : 0.246/0.279/0.312 Cooling : 0.198/0.222/0.246
Power input kW
Heating : 0.119/0.135/0.151 Heating : 0.096/0.108/0.119 C

Cooling : 1.12/1.22/1.30 Cooling : 0.90/0.97/1.03 D


Current A
Heating : 0.55/0.59/0.63 Heating : 0.44/0.47/0.50
E
Galvanized steel plate
External finish
(Lower part drain pan painting N1.5) F
Connectable outdoor unit PURY-P200/250/300/350YHM-A(-BS) / PQRY-P200/250YGM-A
G
Model P140 or smaller
Indoor unit capacity (Use optional joint pipe combining 2 branches when the total H
connectable to 1 branch kW capacity exceeds 141.)
(Use the reducer (standard accessory) when the indoor unit Model V-A
50 or smaller is connected.)
V-B
External dimension H x W x D mm(in.) 284 x 1,098 x 432 (11-3/16” x 43-1/4” x 17-1/16”)
Connectable outdoor unit capacity BC
To P200 P250/P300 P350
outdoor CT
unit High press. pipe ø15.88 (ø5/8”) Brazed ø19.05 (ø3/4”) Brazed ø19.05 (ø3/4”) Brazed
Refrigerant
Low press. pipe ø19.05 (ø3/4”) Brazed ø22.2 (ø7/8”) Brazed ø28.58 (ø1-1/8”) Brazed
piping
diameter ø9.52 (ø3/8”) Flare
To Liquid pipe
(ø6.35 (ø1/4”) with attached reducer used, ø12.7 (ø1/2”) with optional joint pipe used.)
indoor
unit ø15.88 (ø5/8”) Flare
Gas pipe
(ø12.7 (ø1/2”) with attached reducer used, ø19.05 (ø3/4”) with optional joint pipe used.)
Field drain pipe size O.D. 32mm (1-1/4”)
Net weight kg(lb) 54 (120)

Accessories
·Drain Connection pipe (with flexible hose and insulation)
·Reducer
Note: *1. Installation/foundation work, electrical connection work, duct work, insulation work, power source switch,
and other items shall be referred to the Installation Manual.
*2. The equipment is for R410A refrigerant.
*3. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the
neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
*4.Indoor units P100,P125,P140 can be connected to 1 branch. (In this case, cooling capacity decrease a little.)

Ref.: M-WYNCO-6889

BC CONTROLLER BC - 5
13-BCcontroller.qx:13-BCcontroller.qx 25/4/08 15:20 Page 6

1. SPECIFICATIONS R410A Data G4

Model name CMB-P108V-GA CMB-P1010V-GA

Number of branch 8 10
A
1N ~ 220/230/240V
Power source
50Hz 60Hz 50Hz 60Hz
B
Cooling : 0.127/0.144/0.161 Cooling : 0.102/0.115/0.127 Cooling : 0.156/0.177/0.198 Cooling : 0.126/0.141/0.156
Power input kW
C Heating : 0.060/0.068/0.076 Heating : 0.048/0.054/0.060 Heating : 0.075/0.085/0.095 Heating : 0.060/0.068/0.075

D Cooling : 0.58/0.63/0.68 Cooling : 0.47/0.50/0.53 Cooling : 0.71/0.77/0.83 Cooling : 0.58/0.62/0.65


Current A
Heating : 0.28/0.30/0.32 Heating : 0.22/0.24/0.25 Heating : 0.35/0.37/0.40 Heating : 0.28/0.30/0.32
E
Galvanized steel plate
External finish
F (Lower part drain pan painting N1.5)
Connectable outdoor unit PURY-P200/250/300/350/400/450/500/550/600/650Y(S)HM-A(-BS) / PQRY-P200/250/400/500YGM-A
G
Model P140 or smaller
H Indoor unit capacity (Use optional joint pipe combining 2 branches when the total
connectable to 1 branch kW capacity exceeds 141.)
V-A (Use the reducer (standard accessory) when the indoor unit Model
50 or smaller is connected.)
V-B
External dimension H x W x D mm(in.) 289 x1,110 x 520 (11-7/16” x 43-3/4” x 20-1/2”)
BC Connectable outdoor unit capacity
To P200 P250/P300 P350 P400 - P500 P550 ~P650
CT outdoor
unit High press. pipe ø15.88 (ø5/8”) Brazed ø19.05 (ø3/4”) Brazed ø19.05 (ø3/4”) Brazed ø22.2 (ø7/8”) Brazed ø28.58 (ø1-1/8”) Brazed
Refrigerant
Low press. pipe ø19.05 (ø3/4”) Brazed ø22.2 (ø7/8”) Brazed ø28.58 (ø1-1/8”) Brazed ø28.58 (ø1-1/8”) Brazed ø28.58 (ø1-1/8”) Brazed
piping
diameter ø9.52 (ø3/8”) Flare
To Liquid pipe
(ø6.35 (ø1/4”) with attached reducer used, ø12.7 (ø1/2”) with optional joint pipe used.)
indoor
unit ø15.88 (ø5/8”) Flare
Gas pipe
(ø12.7 (ø1/2”) with attached reducer used, ø19.05 (ø3/4”) with optional joint pipe used.)
Total indoor unit capacity connected to this Sub BC controller
~P200 P201~P300 P301~P350
To
other BC High press. pipe ø15.88 (ø5/8”) Brazed ø19.05 (ø3/4”) Brazed ø19.05 (ø3/4”) Brazed
controller
Low press. pipe ø19.05 (ø3/4”) Brazed ø22.2 (ø7/8”) Brazed ø28.58 (ø1-1/8”) Brazed
Liquid pipe ø9.52 (ø3/8”) Brazed ø9.52 (ø3/8”) Brazed ø12.7 (ø1/2”) Brazed
Field drain pipe size O.D. 32mm (1-1/4”)
Net weight kg(lb) 44 (98) 49 (109)

Accessories
·Drain Connection pipe (with flexible hose and insulation)
·Reducer
Note: *1. Installation/foundation work, electrical connection work, duct work, insulation work, power source switch,
and other items shall be referred to the Installation Manual.
*2. The equipment is for R410A refrigerant.
*3. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the
neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
*4.Indoor units P100,P125,P140 can be connected to 1 branch. (In this case, cooling capacity decrease a little.)

Ref.: M-WYNCO-6890&6891

BC CONTROLLER BC - 6
13-BCcontroller.qx:13-BCcontroller.qx 25/4/08 15:20 Page 7

1. SPECIFICATIONS R410A Data G4

Model name CMB-P1013V-GA CMB-P1016V-GA

Number of branch 13 16
A
1N ~ 220/230/240V
Power source
50Hz 60Hz 50Hz 60Hz
B
Cooling : 0.201/0.228/0.255 Cooling : 0.162/0.182/0.201 Cooling : 0.246/0.279/0.312 Cooling : 0.198/0.222/0.246
Power input kW
Heating : 0.097/0.110/0.123 Heating : 0.078/0.088/0.097 Heating : 0.119/0.135/0.151 Heating : 0.096/0.108/0.119 C

Cooling : 0.92/1.00/1.07 Cooling : 0.74/0.80/0.84 Cooling : 1.12/1.22/1.30 Cooling : 0.90/0.97/1.03 D


Current A
Heating : 0.45/0.48/0.52 Heating : 0.36/0.39/0.41 Heating : 0.55/0.59/0.63 Heating : 0.44/0.47/0.50
E
Galvanized steel plate
External finish
(Lower part drain pan painting N1.5) F
Connectable outdoor unit PURY-P200/250/300/350/400/450/500/550/600/650Y(S)HM-A(-BS) / PQRY-P200/250/400/500YGM-A
G
Model P140 or smaller
Indoor unit capacity (Use optional joint pipe combining 2 branches when the total H
connectable to 1 branch kW capacity exceeds 141.)
(Use the reducer (standard accessory) when the indoor unit Model V-A
50 or smaller is connected.)
V-B
External dimension H x W x D mm(in.) 289 x1,110 x 520 (11-7/16” x 43-3/4” x 20-1/2”)
Connectable outdoor unit capacity BC
To P200 P250/P300 P350 P400 - P500 P550 ~P650
outdoor CT
unit High press. pipe ø15.88 (ø5/8”) Brazed ø19.05 (ø3/4”) Brazed ø19.05 (ø3/4”) Brazed ø22.2 (ø7/8”) Brazed ø28.58 (ø1-1/8”) Brazed
Refrigerant
Low press. pipe ø19.05 (ø3/4”) Brazed ø22.2 (ø7/8”) Brazed ø28.58 (ø1-1/8”) Brazed ø28.58 (ø1-1/8”) Brazed ø28.58 (ø1-1/8”) Brazed
piping
diameter ø9.52 (ø3/8”) Flare
To Liquid pipe
(ø6.35 (ø1/4”) with attached reducer used, ø12.7 (ø1/2”) with optional joint pipe used.)
indoor
unit ø15.88 (ø5/8”) Flare
Gas pipe
(ø12.7 (ø1/2”) with attached reducer used, ø19.05 (ø3/4”) with optional joint pipe used.)
Total indoor unit capacity connected to this Sub BC controller
~P200 P201~P300 P301~P350
To
other BC High press. pipe ø15.88 (ø5/8”) Brazed ø19.05 (ø3/4”) Brazed ø19.05 (ø3/4”) Brazed
controller
Low press. pipe ø19.05 (ø3/4”) Brazed ø22.2 (ø7/8”) Brazed ø28.58 (ø1-1/8”) Brazed
Liquid pipe ø9.52 (ø3/8”) Brazed ø9.52 (ø3/8”) Brazed ø12.7 (ø1/2”) Brazed
Field drain pipe size O.D. 32mm (1-1/4”)
Net weight kg(lb) 57 (126) 64 (142)

Accessories
·Drain Connection pipe (with flexible hose and insulation)
·Reducer
Note: *1. Installation/foundation work, electrical connection work, duct work, insulation work, power source switch,
and other items shall be referred to the Installation Manual.
*2. The equipment is for R410A refrigerant.
*3. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the
neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
*4.Indoor units P100,P125,P140 can be connected to 1 branch. (In this case, cooling capacity decrease a little.)

Ref.: M-WYNCO-6892&6893

BC CONTROLLER BC - 7
13-BCcontroller.qx:13-BCcontroller.qx 25/4/08 15:20 Page 8

1. SPECIFICATIONS R410A Data G4

Model name CMB-P1016V-HA

Number of branch 16
A
1N ~ 220/230/240V
Power source
B 50Hz 60Hz

Cooling :0.246/0.279/0.312 Cooling : 0.198/0.222/0.246


Power input kW
C
Heating : 0.119/0.135/0.151 Heating : 0.096/0.108/0.119

D Cooling : 1.12/1.22/1.30 Cooling : 0.90/0.97/1.03


Current A
Heating : 0.55/0.59/0.63 Heating : 0.44/0.47/0.50
E
Galvanized steel plate
External finish
F (Lower part drain pan painting N1.5)
Connectable outdoor unit PURY-P700/750/800YSHM-A(-BS)
G
Model P140 or smaller
H Indoor unit capacity (Use optional joint pipe combining 2 branches when the total
kW capacity exceeds 141.)
connectable to 1 branch
V-A (Use the reducer (standard accessory) when the indoor unit Model
50 or smaller is connected.)
V-B
External dimension H x W x D mm(in.) 289 x1,110 x 520 (11-7/16” x 43-3/4” x 20-1/2”)
BC Connectable outdoor unit capacity
To P700/P750/P800
CT outdoor
unit High press. pipe ø28.58(ø1-1/8”) Brazed
Refrigerant Low press. pipe
piping ø34.93 (ø1-3/8”) Brazed
diameter ø9.52 (ø3/8”) Flare
To Liquid pipe
(ø6.35 (ø1/4”) with attached reducer used,)
indoor
unit ø15.88 (ø5/8”) Flare
Gas pipe
(ø12.7 (ø1/2”) with attached reducer used, ø19.05 (ø3/4”), ø22.2 (ø7/8”)with optional joint pipe used.)
Total indoor unit capacity connected to this Sub BC controller
~P200 P201~P300 P301~P350 P351~P400 P401~P450
To
other BC High press. pipe ø15.88 (ø5/8”) Brazed ø19.05 (ø3/4”) Brazed ø22.2 (ø7/8”) Brazed
controller
Low press. pipe ø19.05 (ø3/4”) Brazed ø22.2 (ø7/8”) Brazed ø28.58 (ø1-1/8”) Brazed
Liquid pipe ø9.52 (ø3/8”) Brazed ø12.7 (ø1/2”) Brazed ø15.88 (ø5/8”) Brazed
Drain pipe O.D. 32mm (1-1/4”)
Net weight kg(lb) 73 (161)

Accessories ·Drain Connection pipe (with flexible hose and insulation)


·Reducer
Note: *1. Works Not Included:
Installation/foundation work, electrical connection work, insulation work, power source switch, and other
items are not specified in this specifications.
*2. The equipment is for R410A refrigerant.
*3. When using an outdoor unit –28HP(P700) or more, use this product.
*4. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the
neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
*5.Indoor units P100,P125,P140 can be connected to 1 branch. (In this case, cooling capacity decrease a little.)

Ref.: M-WYNCO-9168

BC CONTROLLER BC - 8
13-BCcontroller.qx:13-BCcontroller.qx 25/4/08 15:20 Page 9

1. SPECIFICATIONS R410A Data G4

Model name CMB-P104V-GB CMB-P108V-GB

Number of branch 4 8
A
1N ~ 220/230/240V
Power source
50Hz 60Hz 50Hz 60Hz
B
Cooling : 0.060/0.068/0.076 Cooling : 0.048/0.054/0.060 Cooling : 0.119/0.135/0.151 Cooling : 0.096/0.108/0.119
Power input kW
Heating : 0.030/0.034/0.038 Heating : 0.024/0.027/0.030 Heating : 0.060/0.068/0.076 Heating : 0.048/0.054/0.060 C

Cooling : 0.28/0.30/0.32 Cooling : 0.22/0.24/0.25 Cooling : 0.55/0.59/0.63 Cooling : 0.44/0.47/0.50 D


Current A
Heating : 0.14/0.15/0.16 Heating : 0.11/0.12/0.13 Heating : 0.28/0.30/0.32 Heating : 0.22/0.24/0.25
E
Galvanized steel plate
External finish
(Lower part drain pan painting N1.5) F
Main BC CMB-P108/1010/1013/1016V-GA, CMB-P1016V-HA
Connectable BC controller G
Sub BC CMB-P104/108V-GB, CMB-P1016V-HB
H
Model P140 or smaller
(Use optional joint pipe combining 2 branches when the total
Indoor unit capacity V-A
kW capacity exceeds 141.)
connectable to 1 branch
(Use the reducer (standard accessory) when the indoor unit Model
V-B
50 or smaller is connected.)
External dimension H x W x D mm(in.) 284 x 648 x 432 (11-3/16” x 25-9/16” x 17-1/16”) BC
Total indoor unit capacity connected to this Sub BC controller
CT
~P200 P201~P300 P301~P350

To High press. pipe ø15.88 (ø5/8”) Brazed ø19.05 (ø3/4”) Brazed ø19.05 (ø3/4”) Brazed
Main BC
controller Low press. pipe ø19.05 (ø3/4”) Brazed ø22.2 (ø7/8”) Brazed ø28.58 (ø1-1/8”) Brazed
Refrigerant
Liquid pipe ø9.52 (ø3/8”) Brazed ø9.52 (ø3/8”) Brazed ø12.7 (ø1/2”) Brazed
piping
diameter ø9.52 (ø3/8”) Flare
To Liquid pipe
(ø6.35 (ø1/4”) with attached reducer used, ø12.7 (ø1/2”) with optional joint pipe used.)
indoor
unit ø15.88 (ø5/8”) Flare
Gas pipe
(ø12.7 (ø1/2”) with attached reducer used, ø19.05 (ø3/4”) with optional joint pipe used.)
Field drain pipe size O.D. 32mm (1-1/4”)
Net weight kg(lb) 22 (49) 32 (71)

Accessories
·Drain Connection pipe (with flexible hose and insulation)
·Reducer
Note: *1. Installation/foundation work, electrical connection work, duct work, insulation work, power source switch,
and other items shall be referred to the Installation Manual.
*2. The equipment is for R410A refrigerant.
*3. For sub BC controller CMB-P-V-GB the connectable indoor unit capacities may sum to equal that of a
P350 unit or less. However, if two sub controllers are used the TOTAL sum of connectable units
connected to BOTH sub controllers must also not exceed that of a P350 unit.
*4. Can’t use singleness.(MAIN BC CONTROLLER is necessary)
*5. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the
neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
*6.Indoor units P100,P125,P140 can be connected to 1 branch. (In this case, cooling capacity decrease a little.)

Ref.: M-WYNCO-6894&6895

BC CONTROLLER BC - 9
13-BCcontroller.qx:13-BCcontroller.qx 25/4/08 15:20 Page 10

1. SPECIFICATIONS R410A Data G4

Model name CMB-P1016V-HB

Number of branch 16
A
1N ~ 220/230/240V
Power source
B 50Hz 60Hz

Power input Cooling :0.237/0.269/0.301 Cooling : 0.192/0.216/0.237


kW
C Heating : 0.119/0.135/0.151 Heating : 0.096/0.108/0.120

D Cooling : 1.08/1.17/1.26 Cooling : 0.88/0.94/0.99


Current A
Heating : 0.55/0.59/0.63 Heating : 0.44/0.47/0.50
E
Galvanized steel plate
External finish
F (Lower part drain pan painting N1.5)
Main BC CMB-P108/1010/1013/1016V-GA, CMB-P1016V-HA
G Connectable BC controller
Sub BC CMB-P104/108V-GB, CMB-P1016V-HB
H
Model P140 or smaller
(Use optional joint pipe combining 2 branches when the total
V-A Indoor unit capacity
kW capacity exceeds 141.)
connectable to 1 branch
(Use the reducer (standard accessory) when the indoor unit Model
V-B
50 or smaller is connected.)
BC External dimension H x W x D mm(in.) 284 x 1,098 x 432 (11-3/16” x 43-4/16” x 17-1/16”)
Total indoor unit capacity connected to this Sub BC controller
CT
~P200 P201~P300 P301~P350 P351~P400 P401~P450

To High press. pipe ø15.88 (ø5/8”) Brazed ø19.05 (ø3/4”) Brazed ø22.2 (ø7/8”) Brazed
Main BC
controller Low press. pipe ø19.05 (ø3/4”) Brazed ø22.2 (ø7/8”) Brazed ø28.58(ø1-1/8”) Brazed
Refrigerant
piping
Liquid pipe ø9.52 (ø3/8”) Brazed ø12.7 (ø1/2”) Brazed ø15.88 (ø5/8”) Brazed
diameter ø9.52 (ø3/8”) Flare
To Liquid pipe
(ø6.35 (ø1/4”) with attached reducer used.)
indoor
unit ø15.88 (ø5/8”) Flare
Gas pipe
(ø12.7 (ø1/2”) with attached reducer used, ø19.05 (ø3/4”), ø22.2 (ø7/8”)with optional joint pipe used.)
Drain pipe O.D. 32mm (1-1/4”)
Net weight kg(lb) 57 (126)
·Drain Connection pipe (with flexible hose and insulation)
Accessories
·Reducer
Note: *1. Works Not Included:
Installation/foundation work, electrical connection work, insulation work, power source switch, and other
items are not specified in this specifications.
*2. The equipment is for R410A refrigerant.
*3. For sub BC controller CMB-P1016V-HB the connectable indoor unit capacities may sum to equal that
or a P350 unit or less. However, if two sub controllers are used the TOTAL sum of connectable units
connected to BOTH sub controllers must also not exceed that of a P450 unit.
*4. Can’t use singleness.(MAIN BC CONTROLLER is necessary)
*5. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the
neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
*6. Indoor units P100,P125,P140 can be connected to 1 branch. (In this case, cooling capacity decrease a little.)

Ref.: M-WYNCO-9169

BC CONTROLLER BC - 10
<Accessories>
• Refrigerant<Low pressure> conn. pipe ··············· 2pcs.
Band (Accessory)
• Refrigerant<High pressure> conn. pipe ·············· 1pc.
Drain hose I.D. 32 (1-1/4") • Reducer(Large,Small) ········································· Quantity for all connections
• Drain hose I.D. 32 (1-1/4") ··································· 1pc.

30
12
• Hose band ··························································· 1pc.

ø31
• Tie band ······························································ 1pc.
Note1. Suspension bolt(ø10),washer(M10),and nut(M10)
13-BCcontroller.qx:13-BCcontroller.qx

14 prepare in the field.


2. Take notice of service space as follows.
(Please give attention not to occupy service
Detail of X section Detail of Y section space by letting ducts and pipes through.)
Drain pipe O.D. 32 (1-1/4")
Connection pipe of
25/4/08

outdoor unit
(High pressure)
2. EXTERNAL DIMENSIONS

ø19.05 <Brazed>
15:20

Y
Control box

70
X 200
CMB-P104,105,106,108,1010,1013,1016V-G
Page 11

Access
door

248
450■
298
362

181
Service
space

103
(Lifting bolt pitch)
700

64

64

BC CONTROLLER
250

130 23
A
Connection pipe of outdoor unit (Low pressure)
PURY-P200 : ø19.05 <Brazed> (use attachment pipe) B
(Lifting bolt pitch)
PURY-P250, P300 : ø22.2 <Brazed>
PURY-P350 : ø28.6 <Brazed> (use attachment pipe) 200
70 76 60XC=D Connection pipe of
indoor unit (Liquid)
60

27
ø9.52 <Flare> A B C D
CMB-P104V-G 3 180

58
CMB-P105V-G 4 240

128
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 CMB-P106V-G 648 702 5 300
CMB-P108V-G 7 420

255
284
CMB-P1010V-G 9 540
CMB-P1013V-G 12 720
1098 1152
Connection pipe of CMB-P1016V-G 15 900
indoor unit (Gas)
200 ø15.88 <Flare>
R410A Data

BC -
Unit : mm
Drw. : cmb-p104-1016v-g-W656-840A

11
G4

F
E

H
D
C
B
A

V-B
V-A

CT
BC
H
G
F
E
D
C
B
A

V-A

CT
BC
V-B
<Accessories>
• Refrigerant<High pressure>conn. pipe ··············· 2pcs.
• Reducer(Large,Small) ········································· Quantity for all connections
Band (Accessory) • Drain hose I.D. 32 (1-1/4") ··································· 1pc.
• Hose band ·························································· 1pc.
Drain hose I.D. 32 (1-1/4") • Tie band ····························································· 1pc.

30
12
A B Note1. Suspension bolt(ø10),washer(M10),and nut(M10) prepare in the field.
CMB-P108V-GA 7 420 2. Take notice of service space as follows.

ø31
CMB-P1010V-GA 9 540 (Please give attention not to occupy service
14 CMB-P1013V-GA 12 720 space by letting ducts and pipes through.)
CMB-P1016V-GA 15 900 3. Please take space to connect SUB BC CONTROLLER.
Detail of X section Detail of Y section
Connection pipe of
SUB BC CONTROLLER (High pressure)
Connection pipe of outdoor unit (High pressure)
Drain pipe O.D. 32 (1-1/4") Total capacity of indoor unit at SUB BC CONTROLLER
13-BCcontroller.qx:13-BCcontroller.qx

PURY-P350 : ø19.05 <Brazed> (use attachment pipe) 200 or less : ø15.88 <Brazed>
PURY-P400, P450, P500 : ø22.2 <Brazed> (use attachment pipe of SUB BC CONTROLLER)
PURY-P550, P600, P650 : ø28.6 <Brazed> (use attachment pipe) 200 over : ø19.05 <Brazed>
CMB-P108,1010,1013,1016V-GA

Y
2. EXTERNAL DIMENSIONS

Control box

70
25/4/08

X
Connection pipe of
128 SUB BC CONTROLLER (Liquid)
Total capacity of indoor unit at SUB BC CONTROLLER
15:20

300 or less : ø9.52<Brazed>


300 over : ø12.7<Brazed>

388
450
66 (use attachment pipe of SUB BC CONTROLLER)

333
(Lifting bolt pitch)

268
268
Connection pipe of

210
SUB BC CONTROLLER (Low pressure)
Page 12

103
103
Total capacity of indoor unit at SUB BC CONTROLLER
200 or less : ø19.05 <Brazed>

BC CONTROLLER
64

64
(use attachment pipe of SUB BC CONTROLLER)
1110 74 300 or less : ø22.2 <Brazed>
130 23 300 over : ø28.6 <Brazed>
1164 (use attachment pipe of SUB BC CONTROLLER)
Connection pipe of (Lifting bolt pitch)
outdoor unit Connection pipe of
(Low pressure) indoor unit (Liquid)
90 76 60XA=B ø9.52 <Flare>
ø28.6 <Brazed>
60 70 200 200

27
(Note 3. )
Access
door

74
450■

128
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Service

260
289
700

space
70
250

Connection pipe of
indoor unit (Gas)
200 ø15.88 <Flare>

200
R410A Data

BC -
Unit : mm
Drw. : cmb-p108-1016v-gA-W656-838A

12
G4
Band(Accessory) Note1.Suspension bolt( ø10),washer(M10),and nut(M10) <Accessories>
Drain hose(Accessory) prepare in the field. • Refrigerant<Low pressure> conn. pipe ·········1pc.
2.Take notice of service space as follows. • Reducer(Large,Small) ·········Quantity for all connections
(Please give attention not to occupy service • Drain hose(VP-25 connection) ·····················1pc.

30
12
space by letting ducts and pipes through.) • Hose band···················································1pc.
CMB-P1016V-HA

3.Please take space to connect SUB BC CONTROLLER. • Tie band······················································1pc.

ø31
14 4.When using an outdoor unit-28HP(P700) or more,use this product. Connection pipe of
5.Install this product in a location where noise (refrigerant noise) SUB BC CONTROLLER
(High pressure)
13-BCcontroller.qx:13-BCcontroller.qx

Detail of X section Dtail of Y section emitted by the unit will not disturb the neighbors.
(For use in quiet enviroments with low background noise,position Total capacity of indoor unit
at SUB BC CONTROLLER
the BC CONTROLLER at least 5m away from any indoor units.) 200 or less: ø15.88<Brazed>
Connection pipe of outdoor unit (use attachment pipe of
SUB BC CONTROLLER)
(High pressure) 350 or less:ø19.05<Brazed>
350 over:ø22.2<Brazed>
25/4/08

Drain piping ø28.58 <Brazed> (use attachment pipe of


VP-25 connection JOINT<option>)
2. EXTERNAL DIMENSIONS

Y Connection pipe of
SUB BC CONTROLLER

70
Control box (Liquid)
15:20

X Total capacity of indoor unit


at SUB BC CONTROLLER
128 300 or less :ø9.52<Brazed>
400 or less :ø12.7<Brazed>
(use attachment pipe of
SUB BC CONTROLLER)
400 over:ø15.88<Brazed>
Page 13

(use attachment pipe of

450

388
JOINT<option>)
66

333
Connection pipe of
SUB BC CONTROLLER

268
268
(Low pressure)
210

(Lifting bolt pitch)


Total capacity of indoor unit
103

103
at SUB BC CONTROLLER

BC CONTROLLER
200 or less:ø19.05<Brazed>
(use attachment pipe of

64

64
SUB BC CONTROLLER)
300 or less:ø22.2<Brazed>
130 23 74 300 over:ø28.58<Brazed>
1110
(use attachment pipe of
1164 SUB BC CONTROLLER)
(Lifting bolt pitch)
200 200 (Note 2.)
Connection pipe of outdoor unit(Low pressure) Access
door
ø34.93<Brazed>(use attachment pipe) Connection pipe of 450■
indoor unit(Liquid)
90 46 60X15=900 Service
ø9.52 <Flare> space
(700)

60 90

27
250

74
128
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

260
289
Connection pipe of
indoor unit(Gas)
(200)
ø15.88 <Flare>
60
200 76 60X15=900
R410A Data

BC -
Unit : mm
Drw. : cmb-p1016v-hA-WKB94-G932

13
G4

F
E

H
D
C
B
A

V-B
V-A

CT
BC
H
G
F
E
D
C
B
A

V-A

CT
BC
V-B
Band (Accessory) <Accessories>
Drain hose I.D. 32 (1-1/4") • Refrigerant<Low pressure>conn. pipe ················ 4pcs.
• Refrigerant<High pressure>conn. pipe ··············· 2pcs.

30
12
• Refrigerant<Liquid>conn. pipe ···························· 2pcs.

ø31
• Reducer(Large,Small) ········································· Quantity for all connections
• Drain hose I.D. 32 (1-1/4") ··································· 1pc.
14 • Hose band ··························································· 1pc.
CMB-P104,108V-GB

• Tie band ······························································ 1pcs.


Note1. Suspension bolt(ø10),washer(M10),and nut(M10)
Detail of X section Detail of Y section prepare in the field.
2. Take notice of service space as follows.
(Please give attention not to occupy service
13-BCcontroller.qx:13-BCcontroller.qx

Connection pipe of MAIN BC CONTROLLER Connection pipe of MAIN BC CONTROLLER


(High pressure) (Liquid) space by letting ducts and pipes through.)
3. Can't use singleness.(MAIN BC CONTROLLER is necessary.)
Total capacity of indoor units at SUB BC CONTROLLER Total capacity of indoor units at SUB BC CONTROLLER
200 or less : ø15.88 <Brazed> (use attachment pipe) 300 or less : ø9.52 <Brazed>
2. EXTERNAL DIMENSIONS

200 over : ø19.05 <Brazed> 300 over : ø12.7 <Brazed> (use attachment pipe)
25/4/08

Y
Control box

70
Drain pipe O.D. 32 (1-1/4")
15:20

45 X

200
298
362

Access

248
door
(Lifting bolt pitch)
Page 14

181
450■

169
103

BC CONTROLLER
700

64

64
648 Service space
130 23
250

Connection pipe of MAIN BC CONTROLLER 702


(Low pressure) (Lifting bolt pitch)
Connection pipe of
Total capacity of indoor units at SUB BC CONTROLLER indoor unit (Liquid)
200 or less : ø19.05 <Brazed> (use attachment pipe) 70 76 60XA=B
300 or less : ø22.2 <Brazed> 60 ø9.52 <Flare> 200

27
300 over : ø28.6 <Brazed> (use attachment pipe)

58
128
1 2 3 4 5 6 7 8

255
284
Connection pipe of
200 indoor unit (Gas)
ø15.88 <Flare>
A B
CMB-P104V-GB 3 180
CMB-P108V-GB 7 420
R410A Data

BC -
Unit : mm
Drw. : cmb-p104-108v-gB-W656-839A

14
G4
Band(Accessory) Note1.Suspension bolt(ø10),washer(M10),and nut(M10) <Accessories>
prepare in the field. • Refrigerant<Low pressure> conn. pipe·······4pcs.
Drain hose(Accessory)
2.Take notice of service space as follows. • Refrigerant<High pressure> conn. pipe······2pcs.
(Please give attention not to occupy service • Refrigerant<Liquid> conn. pipe··················2pcs.

30
12
space by letting ducts and pipes through.) • Reducer(Large,Small)···············Quantity for all connections
3.Can't use singleness.(MAIN BC CONTROLLER is necessary.) • Drain hose(VP-25 connection)···················1pc.
• Hose band·················································1pc.

ø31
4.Install this product in a location where noise (refrigerant noise)
14 • Tie band····················································1pc.
emitted by the unit will not disturb the neighbors.
CMB-P1016V-HB

Detail of X section Dtail of Y section (For use in quiet enviroments with low background noise,position
the BC CONTROLLER at least 5m away from any indoor units.)
Connection pipe of MAIN BC CONTROLLER
13-BCcontroller.qx:13-BCcontroller.qx

Connection pipe of MAIN BC CONTROLLER(Liquid)


(High pressure)
Total capacity of indoor units at SUB BC CONTROLLER
Total capacity of indoor units at SUB BC CONTROLLER
300 or less:ø9.52 <Brazed>
200 or less:ø15.88<Brazed>(use attachment pipe)
300 over :ø12.7 <Brazed>(use attachment pipe)
200 over :ø19.05<Brazed>
25/4/08

Y
70

Control box
2. EXTERNAL DIMENSIONS
15:20

Drain piping 45 X
VP-25 connection
362

298

248
Page 15

181
169
(Lifting bolt pitch)

103
64

64
Connection pipe of MAIN BC CONTROLLER

BC CONTROLLER
(Low pressure) 130 23
Total capacity of indoor units at SUB BC CONTROLLER 1098
200 or less:ø19.05<Brazed>(use attachment pipe) 1152
300 or less:ø22.2 <Brazed> (Lifting bolt pitch)
300 over :ø28.58<Brazed>(use attachment pipe)
Connection pipe of
indoor unit(Liquid)
90 46 60X15=900
ø9.52<Flare>
60

27
200

58
(Note 2.)

128
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Access
door

255
450■

284
Service
space

(700)
60 Connection pipe of
indoor unit(Gas)

250
200 76 60X15=900
ø15.88<Flare>
R410A Data

BC -
(200)
Unit : mm
Drw. : cmb-p1016v-hB-WKB94-G933

15
G4

F
E

H
D
C
B
A

V-B
V-A

CT
BC
H
G
F
E
D
C
B
A

V-A

CT
BC
V-B
Symbol explanation
TR TB02
S(SHIELD) Indoor/outdoor Symbol Name
20V~22V 220V~240V Transmission Line
M2 TR Transformer
CMB-P104V-G

CONT.B M1
TH11,12,15,16
Thermistor sensor
3 1 1 LEV1,3 Expansion valve
2 CNTR
PS1 2 3
1 3 2 1 2 1 (Red) PS1,3 Pressure sensor
3 1 1
CN03 CN02 1 1 Circuit BC controller
X2
CN26 CONT.B
CNP1 (Yellow) 1 2 2 SV1B
board
2 2
(Black) X1 3 3 3 T1 Terminal block
3 3 SV1A TB01 (for power source)
X30 5 4 4 SV1C Terminal block
3. WIRING DIAGRAMS

4 4
13-BCcontroller.qx:13-BCcontroller.qx

7
TB02 (for Transmission)
3 1 1 1 SV1~4A,B,C Solenoid valve
2 CN27(Red)
PS3 2 CNP3 X4 1 2 2 SVM1 Solenoid valve
1 5 5 SV2B
3 X3 3 3 3 T2 SV2A T1~4 Terminal
6 6
X31 4
25/4/08

1 CN13 5 4 SV2C F01 Fuse AC250V 6.3A F


7 7
2 (Red) 7
Note:1.TB02 is transmission terminal block.
1 1
CN28(Blue) Never connect power line to it.
1 X6 1 2 2
TH11 SV3B
15:20

8 8 2.The initial set values of switch on


2 X5 3 3 3 T3
9 9 SV3A CONT.B are as follows.
3 X32 5 4 4
TH12 10 10 SV3C SW1:0
4 CN10 7 SW2:0
5 1 1
CN29(Green)
Page 16

6 10 1 X8 1 2 2
11 11 SV4B
7 X7 3 3 3 T4
12 12 SV4A

BC CONTROLLER
8 X33 5 4 4
SW2 SW1 13 13 SV4C
1 8 7
1
TH15 ON 1 1
2 OFF CN36(Green)
CN11 X21 1 2 2
3 SW4 14 14 SVM1
TH16 1 8 3 3 3
4 ZNR01 ZNR02 15 15
ON
OFF DSA 16 16

SW5 F01 TO NEXT INDOOR UNIT


250VAC TB01
6.3A F L
N PULL BOX
CN07 CN05
(Yellow) (Red)
1 2 3 4 5 6 1 2 3 4 5 6 1 3 5 FUSE(16A)
PE
CN12 PE
BREAKER(16A)

LEV3 LEV1 POWER SUPPLY


~220V-240V
50Hz/60Hz
R410A Data

BC -
Drw. : cmb-p104v-g-W656-841

16
G4
TR TB02 Indoor/outdoor
20V~22V 220V~240V S(SHIELD)
M2
Transmission line

CONT.B M1 Symbol explanation


3 1
1
2 CNTR Symbol Name
PS1 2 3
3 2 1 2 1 (Red)
1 TR Transformer
3 CN03 CN02
1 1
(Yellow) CN26 1 1 TH11,12,15,16 Thermistor sensor
CNP1 X2
1 2 2 SV1B
(Black) 2 2 LEV1,3 Expansion valve
X1 T1
3 3 3 SV1A PS1,3 Pressure sensor
3 3
X30
CMB-P105,106V-G

5 4 4 SV1C Circuit BC
4 4
CONT.B board controller
7
3
13-BCcontroller.qx:13-BCcontroller.qx

1 1 Terminal block
1 TB01
2 CN27(Red) (for power source)
PS3 2 CNP3 X4
1 1 2 2 SV2B Terminal block
3 5 5
X3 T2
TB02 (for Transmission)
3 3 3 SV2A
3. WIRING DIAGRAMS

6 6
X31
5 4 4
SV1~6A,B,C Solenoid valve
1 CN13 7 7 SV2C
2 (Red) SVM1 Solenoid valve
25/4/08

1
T1~6 Terminal
1
CN28(Blue) F01 Fuse AC250V 6.3A F
1 X6
1 2 2 SV3B
TH11 8 8
2 X5 T3 Note: 1. TB02 is transmission terminal block.
3 3 3 SV3A
15:20

9 9
3 X32
Never connect power line to it.
5 4 4 SV3C
TH12 10 10
4 2. The initial set values of switch on
7
CN10 CONT.B are as follows.
5
1
1
CN29(Green) SW1:0
6 10 1 X8
1 2 2 SV4B
11 11
Page 17

7
SW2:0
X7 T4
3 3 3 SV4A
12 12
8 X33
SW2 SW1 5 4 4 SV4C
13 13
1 8 7
1
ON 1
TH15 1
2 OFF CN30(Black)

BC CONTROLLER
CN11 X10
1 2 2 SV5B
3 SW4 14 14
X9 T5
TH16 1 8 3 3 3 SV5A
4 15 15
DSA ZNR01 ZNR02
ON X34
5 4 4 SV5C
16 16
OFF
7
SW5 F01
1 CMB-P106V-G ONLY
1
250VAC CN31(Yellow)
X12
6.3A F 1 2 2 SV6B
1 1
X11 T6
3 3 3 SV6A
2 2
X35
5 4 4 SV6C
3 3
X21
1
4 4
CN07 CN05
(Yellow) (Red) 3

1 2 3 4 5 6 1 2 3 4 5 6 1 1
1 3 5
CN36(Green)
CN12 2 2
SVM1
3 3
TB01 TO NEXT INDOOR UNIT
L

LEV3 LEV1 N PULL BOX

PE FUSE(16A)
PE
BREAKER(16A)
POWER SUPPLY
~ 220V-240V
R410A Data

BC -
50Hz/60Hz
Drw. : cmb-p105-106v-g-W656-842

17
G4

F
E

H
D
C
B
A

V-B
V-A

CT
BC
H
G
F
E
D
C
B
A

V-A

CT
BC
V-B
Symbol explanation

Symbol Name
TR Transformer
Thermistor sensor
TH11,12,15,16
LEV1,3 Expansion valve
PS1,3 Pressure sensor Note:
TR TB02 Indoor/outdoor
S(SHIELD) REL.B Circuit Relay 1. TB02 is transmission
20V~22V 220V~240V Transmission line
M2 CONT.B board BC controller terminal block.
M1 Terminal block Never connect power
CONT.B TB01 (for power source)
line to it.
Terminal block
CMB-P108,1010V-G

7 6 5 4 3 2 1 TB02
3 1 1 (for Transmission) 2. The initial set values
CN50 CNTR
2 2
PS1 3 2 1 2 1 1 3 (Red) 3 SV1~10A,B,C Solenoid valve of switch on CONT.B
1 3
CN03 CN02 CN38 1 1 SVM1 Solenoid valve are as follows.
CN26 1 1
CNP1 (Yellow) X2 1 2 2
2 2 SV1B T1~10 Terminal SW1:0
(Black) X1
3. WIRING DIAGRAMS

3 3 3 T1 SV1A
13-BCcontroller.qx:13-BCcontroller.qx

3 3 F01 Fuse AC250V 6.3A F SW2:0


X30 5 4 4
4 4 SV1C
7
3 1
1 1 CMB-P1010V-G ONLY
2 2
CN27(Red)
PS3 CNP3 X4 1 2 2
1 5 5
SV2B
3
X3 3 3 3 T2 SV2A
25/4/08

6 6

SV9A
SV9B
SV8A
SV8B
SV7A
SV7B

SV9C
SV8C
SV7C

SVM1
SV10A
SV10B

SV10C
X31 5 4 4
1 CN13 7 7 SV2C
2 (Red) 7
1 T10 T9 T8 T7
1
CN28(Blue) 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
1 X6 1 2 2 SV3B
15:20

TH11 8 8
2 X5 T3
3 3 3 SV3A
9 9
3 X32 5 4 4 SV3C
TH12 10 10 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
4
7
CN10
5 1 1
CN29(Green) 16 15 14 13 12 11 10 9 8 7 6 5 4
6 10 1 X8 1 2 2 SV4B 16 15 14 13 12 11 10 9 8 7 6 5 4
Page 18

11 11
7 X7 T4
3 3 3 SV4A
12 12
8 X33
SW2 SW1 5 4 4 SV4C

BC CONTROLLER
13 13
1 8 7
1
ON 1
TH15 1
2 OFF CN30(Black) 1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7
CN11 X10 1 2 2 REL.B
3 SW4 14 14 SV5B
CN32

1 8 X9 3 3 3 T5
TH16 4 15 15 SV5A
ON X34 5 4 4
CN33(Red)

X20
X19
X39
X18
X17
X38
X16
X15
X37
X14
X13
X36

CN35(Blue)

16 16 SV5C
CN34(Black)

OFF
7
SW5 ZNR01 ZNR02 1 1
CN31(Yellow)
X12 1
DSA 2 2 SV6B CN39
1 1
X11 3 T6 3
F01 3 3 SV6A
2 2
X35 1
250VAC 5 4 4
3 3 SV6C
6.3A F 7 7 6 5 4 3 2 1

CN36(Green) CN52
CN07 CN05 X21
(Yellow) (Red) 1
1 2 3 4 5 6 1 2 3 4 5 6 1 3 5 3 TO NEXT INDOOR UNIT
CN12 TB01
L
N PULL BOX POWER SUPPLY
LEV3 LEV1
~220V-240V
50Hz/60Hz
PE
PE FUSE(16A) BREAKER(16A)
R410A Data

BC -
Drw. : cmb-p108-1010v-g-W656-843

18
G4
Symbol explanation

TR TB02
Indoor/outdoor
Symbol Name
20V~22V 220V~240V S(SHIELD)
M2 Transmission line TR Transformer
M1 TH11,12,15,16 Thermistor sensor
CONT.B LEV1,3 Expansion valve
3
1 CNTR 1 PS1,3 Pressure sensor
2
PS1 2 (Red)
1 3 2 1 3 2 1 2 1 1 3 3
3 CN38 1 1
REL.B Circuit Relay
CNVCC1 CN03 CN02 CN26 1 1
CMB-P1013,1016V-G

CNP1 (Blue) (Yellow) X2 2 2 CONT.B board BC controller


1 SV1B
13-BCcontroller.qx:13-BCcontroller.qx

2 2
(Black) X1 T1
3 3 3 SV1A Terminal block
3 3 TB01
X30 4 4 (for power source)
5 4 4 SV1C

SV9A
SV9B
SV8A
SV8B
SV7A
SV7B

SV9C
SV8C
SV7C

SV10A
SV10B

SV10C
7 TB02 Terminal block
3
3. WIRING DIAGRAMS

1 1 1 (for Transmission)
2 CN27(Red)
PS3 2 CNP3 CNOUT1 X4 T10 T9 T8 T7
1 1 2 2 SV2B SV1~16A,B,C Solenoid valve
3 5 5
X3 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
1 3 3 3 T2 SV2A
25/4/08

6 6 SVM1 Solenoid valve


2 X31 4 4
1 CN13 5 7 7 SV2C
2 (Red) 3 T1~16 Terminal
7 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
4 1 1 F01 Fuse AC250V 6.3A F
CN28(Blue)
1 5 X6 2 2
TH11 1 8 8 SV3B
16 15 14 13 12 11 10 9 8 7 6 5 4
15:20

2 6 X5 T3
3 3 3 SV3A
9 9 16 15 14 13 12 11 10 9 8 7 6 5 4
3 7 X32
TH12 5 4 4 SV3C
10 10
4 8
CN10 7
5 1 1
1
CN29(Green)
6 10 1 X8 2 2
1 SV4B
2 11 11 1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7 REL.B
7 X7 T4
3 3 3 SV4A CN40 1 1
3 12 12
Page 19

8 X33 (Yellow)
SW2 SW1 5 4 4 SV4C 1 3 3 2 1 1 2 2 SV11B
4 13 13 1 1
1 8 CNVCC2 X41 T113
3 3

CN33(Red)
SV11A

X20
X19
X39
X18
X17
X38
X16
X15
X37
X14
X13
X36

CN32
CN39

CN35(Blue)
1 7 (Blue) 2 2

CN34(Black)
TH15 ON CNOUT3 1 X40
1 5 4 4 SV11C
2 OFF CN30(Black) 3 3
CN11 X10 2 2 X42
SW4 1 SV5B 1
3 14 14 7 1
TH16 1 8 X9 3 3 T5 CN41(Green)
3 SV5A
4 15 15 1 2 2 SV12B
ON X34 4 4
5 4 4 SV5C X44 T12
OFF 16 16 3 3 3 SV12A
5 5

BC CONTROLLER
X43
SW5 7 5 4 4 SV12C
1 6 6
1 X45
ZNR01 ZNR02 CN31(Yellow) 1 1
X12 7
1 2 2 SV6B CN42
1 1
DSA X11 1 2 2 SV13B
3 3 3 T6 SV6A 7 7
2 2 X47 T13
F01 X35 3 3 3 SV13A
5 4 4 SV6C 8 8
250VAC 3 3 X46
5 4 4 SV13C
CN07 CN05 6.3A F CN36(Green) 9 9
X48
(Yellow) (Red) X21 7 1 1
1 TO NEXT
1 2 3 4 5 6 1 2 3 4 5 6 1 3 5 TB01 CN43(Red)
L INDOOR UNIT POWER SUPPLY 1 2 2 SV14B
CN12 3 10 10
~220V-240V X50 T14
N 3 3 3 SV14A
PULL BOX 50Hz/60Hz 11 11
X49
5 4 4 SV14C
12 12
X51
1 1
7
PE CN44(Yellow)
LEV3 LEV1 PE FUSE(16A) BREAKER(16A) 1 1 2 2
13 13 SV15B
2 X53
3 3 T15
3 SV15A
3 14 14
4 X52
5 4 4 SV15C
5 CNOUT2 15 15
X54
6 1 1
7 16 16
7 CN45(Green)
8 1 2 2 SV16B
1 1
X56 T16
3 3 3 SV16A
1 2 2
2 X55
5 4 4 SV16C
3 3
3 CNOUT4 X57
4 7 4 4
CMB-P1016V-G ONLY
Note: 1. TB02 is transmission terminal block. 1 1

2 2
Never connect power line to it. SVM1
3 3
2. The initial set values of switch on CONT.B are as follows.
SW1:0
SW2:0
R410A Data

BC -
Drw. : cmb-p1013-1016v-g-W656-844

19
G4

F
E

H
D
C
B
A

V-B
V-A

CT
BC
H
G
F
E
D
C
B
A

V-A

CT
BC
V-B
TR TB02
S(SHIELD)
Indoor/outdoor
20V~22V 220V~240V
M2 Transmission line
M1
Symbol explanation
CONT.B Symbol Name
7 6 5 4 3 2 1
3 1 TR Transformer
1 CN50
2 CNTR
PS1 2 1 3 (Red) 3 Thermistor sensor
TH11,12,15,16
1 3 2 1 2 1
3 CN38
CN03 CN02 1 1 LEV1~3 Expansion valve
CN26 1 1
(Yellow) X2
CNP1 1 2 2 SV1B Note:
2 2 PS1,3 Pressure sensor
(Black) X1 3 T1
3 3 SV1A
3 3 REL.B Circuit Relay 1. TB02 is transmission
CMB-P108,1010V-GA

X30 5 4 4
4 4
SV1C terminal block.
CONT.B board BC controller
7
3 1 Terminal block Never connect power
1 1 TB01
2 CN27(Red) (for power source)
PS3 2 CNP3 X4
1 1 2 2 SV2B line to it.
5 5
3. WIRING DIAGRAMS

3 Terminal block
13-BCcontroller.qx:13-BCcontroller.qx

X3 3 3 T2 TB02
3 SV2A (for Transmission) 2. The initial set values
6 6
X31 5 4
1 CN13 4 SV2C
7 7 SV1~10A,B,C Solenoid valve of switch on CONT.B
2 (Red)
7 SVM1,2 Solenoid valve
1 1
are as follows.
CN28(Blue)
1 X6 1 2 2
T1~10 Terminal SW1:0
TH11 8 8 SV3B
2 X5 T3 F01 Fuse AC250V 6.3A F
25/4/08

3 3 3 SV3A SW2:0
9 9
3 X32 5 4 4 SV3C
TH12 10 10
4
CN10 7
5 1
1
CN29(Green)
6 X8 1 2 2
15:20

11 11 SV4B
7 X7 3 3 T4
3 SV4A
12 12 CMB-P1010V-GA ONLY
8 X33 5 4 4 SV4C
13 13

1 7
1
SV9A
SV9B
SV8A
SV8B
SV7A
SV7B

1
SV9C
SV8C
SV7C

SVM2
SVM1
TH15
SV10A
SV10B

SV10C

2 CN30(Black)
CN11 X10 1 2 2 SV5B
Page 20

3 14 14
X9 3 3 T5 T10 T9 T8 T7
TH16 10 1 3 SV5A
4 15 15
X34 5 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
4 SV5C
16 16

BC CONTROLLER
7
SW2 SW1 1 1
1 8 CN31(Yellow)
X12 1 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
ON 2 2 SV6B
1 1
OFF X11 3 3 3 T6 SV6A
2 2
SW4 X35 5 4 3 2 1 16 15 14 13 12 11 10 9 8 7 6 5 4
4 4 SV6C
1 8 ZNR01 3 3 4 3 2 1 16 15 14 13 12 11 10 9 8 7 6 5 4
ON 7
OFF ZNR02
CN36(Green)
SW5 X21 1
DSA
F01 3
1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7
250VAC REL.B
CN46(Yellow)
CN07 CN06 CN05 6.3A F X60
CN32

1
(Yellow) (Blue) (Red) CN39
1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 3 5
3 3
X20
X19
X39
X18
X17
X38
X16
X15
X37
X14
X13
X36

TO NEXT INDOOR UNIT


CN33(Red)

CN35(Blue)
CN34(Black)

CN12 TB01 1
L
N PULL BOX 7 6 5 4 3 2 1
POWER SUPPLY
~220V-240V CN52
LEV3 LEV2 LEV1
50Hz/60Hz
PE
PE FUSE(16A) BREAKER(16A)
R410A Data

BC -
Drw. : cmb-p108-1010v-gA-W656-845

20
G4
TR TB02 Indoor/outdoor
20V~22V 220V~240V S(SHIELD)
M2 Transmission line Symbol explanation
M1

CONT.B
Symbol Name
3 TR Transformer
1 CNTR 1
2 TH11,12,15,16 Thermistor sensor
PS1 2 3 2 1 3 2 1 2 1 1 3 (Red)
1 3
3 CNVCC1 CN03 CN02 CN38 1 1 LEV1~3 Expansion valve
CN26 1 1
(Blue) (Yellow) X2
CNP1 1 2
2 2 2 SV1B PS1,3 Pressure sensor
(Black) X1
3 3 3 T1 SV1A
3 3 REL.B
10 1 X30
5 4
Circuit Relay
4 4 4 SV1C

SV9A
SV9B
SV8A
SV8B
SV7A
SV7B
CONT.B

SV9C
SV8C
SV7C
board BC controller

SV10A
SV10B

SV10C
7
3 1 Terminal block
1 SW2 SW1 1
2 CN27(Red) TB01
PS3 2 CNP3 1 8 X4 (for power source)
CNOUT1 T10 T9 T8 T7
13-BCcontroller.qx:13-BCcontroller.qx

1 2 2 SV2B
1 5 5
CMB-P1013,1016V-GA

3 ON X3 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 Terminal block
1 3 3 3 T2 SV2A TB02
OFF 6 6 (for Transmission)
SW4 X31
1 2 5 4 4 SV2C
CN13 7 7
2 (Red) 1 8
3
SV1~16A,B,C Solenoid valve
3. WIRING DIAGRAMS

7
ON 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 SVM1,2 Solenoid valve
4 1 1
OFF CN28(Blue)
1 X6
SW5 5 1 2 2 SV3B T1~16 Terminal
TH11 8 8
25/4/08

2 X5 16 15 14 13 12 11 10 9 8 7 6 5 4
6 3 3 3 T3 SV3A
9 9 16 15 14 13 12 11 10 9 8 7 6 5 4 F01 Fuse AC250V 6.3A F
3 X32
7 5 4 4 SV3C
TH12 10 10
4
CN10 8
7
5 1
CN29(Green) 1
1
15:20

6 X8
1 2 2 SV4B REL.B
11 11
7 2 X7 1 33 5 7 1 33 5 7 1 3 5 7 1 3 5 7
3 3 3 T4 SV4A
12 12
8 3 X33
5 4 4 SV4C 1 3 3 2 1
13 13
4 CNVCC2

CN33(Red)

CN35(Blue)
CN32
CN39

X20
X19
X39
X18
X17
X38
X16
X15
X37
X14
X13
X36

1 7

CN34(Black)
CNOUT3 1
(Blue)
TH15 CN30(Black) 1
2 CN40 1 1
CN11 X10
1 2 2 (Yellow)
Page 21

3 14 14 SV5B 1 2
X9 1 1 2 SV11B
TH16 3 3 3 T5 X41
4 15 15 SV5A 3 3T11
X34 2 2 3 SV11A
5 4 4 X40
16 16 SV5C 5 4
3 3 4 SV11C
1 X42
7
2 7 1 1
1 1
3 CN07 CN31(Yellow) CN41(Green)
LEV3 4 X12 1 2 2 SV12B
(Yellow) 1 2 2 4 4
5 1 1 SV6B X44
X11 3 3 3T12 SV12A

BC CONTROLLER
6 3 3 3 T6 5 5
2 2 SV6A X43
X35 5 4 4 SV12C
5 4 4 6 6
3 3 SV6C X45
1 1
7 1
2 7 CN42
3 ZNR01 ZNR02 1 2
CN06 7 7 2 SV13B
LEV2 4 CN36(Green)
(Blue) X21 X47 3
5 1 8 8 3 3T13 SV13A
DSA
6 X46 5
F01 9 9 4 4 SV13C
3 TO NEXT X48
250VAC
CN05 6.3A F CN46(Yellow) INDOOR UNIT 7 1 1
(Red) POWER SUPPLY CN43(Red)
X60 1
1 ~220V-240V 2 2 SV14B
1 2 3 4 5 6 1 3 5 TB01 10 10
PULL BOX 50Hz/60Hz X50
L 3 3 3T14
CN12 3 11 11 SV14A
N X49
5 4 4
12 12 SV14C
X51
7 1 1
FUSE(16A) BREAKER(16A)
LEV1 CN44(Yellow)
PE 1 2 2 SV15B
13 13
PE X53
1 3 3 3T15
14 14 SV15A
2 X52
3 5 4 4 SV15C
15 15
4 X54 1
CNOUT2 7 16 16 1
CMB-P1016V-GA ONLY

5
6 CN45(Green)
1 2 2
7 1 1 SV16B
X56 3 3T16
8 3 SV16A
2 2
X55 4
5 4
1 3 3 SV16C
2 X57
CNOUT4 7 4 4 1
3 1
4
2 2 SVM1
3 3 SVM2
Note: 1. TB02 is transmission terminal block.
Never connect power line to it.
2. The initial set values of switch on CONT.B are as follows.
R410A Data

SW1:0

BC -
SW2:0
Drw. : cmb-p1013-1016v-gA-W656-846

21
G4

F
E

H
D
C
B
A

V-B
V-A

CT
BC
H
G
F
E
D
C
B
A

V-A

CT
BC
V-B
(Symbol explanation)
TR TB02 Indoor/outdoor Symbol Name
20V~22V 220V~240V S(SHIELD)
M2 Transmission line
TR Transformer
M1
TH11,12,15,16Thermister sensor
LEV1~3 Expansion valve
3 1 CNTR(Red) 1
2 CN38 PS1,3 Pressure sensor
PS1 2 3
1 3 2 1 3 2 1 2 1 3 1
3 REL.B Circuit Relay

SV9C
SV9A
SV9B
SV8C
SV8A
SV8B
SV7C
SV7A
SV7B

SV10C
SV10A
SV10B
CNVCC1 CN03 CN02 1 1
1 1
CNP1 (Blue) (Yellow) CN26 2 2 SV1B CONT.B board BC controller
11 2 2
(Black) T10 T9 T8 T7
X02 3 3 T1 SV1A Terminal block
33 3 3 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 TB01
10 1 X01 4 4 SV1C
(for power source)
55 4 4
CMB-P1016V-HA

X30 Terminal block


77 TB02
3 (for Transmission)
1 SW2 SW1 1 1
4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
PS3 2 2 1 8 CONT.B CN27(Red) SV1~16A,B,C Solenoid valve
CNP3 1 2 2 SV2B
1 3 ON 5 5
X04 3 3 3 T2 SV2A
SVM1,2,1b,2b Solenoid valve
OFF 6 6 16 15 14 13 12 11 10 9 8 7 6 5 4
SW4 X03 5 4 4 SV2C 16 15 14 13 12 11 10 9 8 7 6 5 4 T1~T16 Terminal
1 CN13 7 7
2 (Red) 1 8 X31 7 F01
LD1:CPU in Fuse AC250V 6.3A F
ON
1 1
OFF operation
3. WIRING DIAGRAMS

1
CN28(Blue)
13-BCcontroller.qx:13-BCcontroller.qx

1 2 2 SV3B
TH11 SW5 8 8
2 1 8 X06 3 3 3 T3 SV3A 1 3 5 7 1 3 5 7 1 3 5 7
t˚ 1 3 5 7
9 9
3 ON CNOUT1 X05 4
5 4 SV3C
TH12 OFF 10 10 1 3 3 2 1
4 1 X32 7
t˚ CN10 SW6 CNVCC2

X20
X39
X18
X17
X38
X16
X15
X37
X14
X13
X36

X19
5 1

CN32
2 1 (Blue)

CN39

CN33(Red)

CN35(Blue)
CN34(Black)
6
CN29(Green) SV4B 1 1
3 1 2 2 CN40
11 11
25/4/08

7 (Yellow) 1 2 2 SV11B
4 X08 3 3 3 T4 SV4A 1 1
12 12 T11
8 X07 4 4 X41 3 3 3 SV11A
5 5 SV4C 2 2
13 13
X33 X40 5 4 4 SV11C
6 7 3 3
1 X42 7
TH15 7 1 1 1 1
2 CN30(Black)
t˚ 8 2 2 SV5B CN41(Green) 2 SV12B
15:20

CN11 1 1 2
3 14 14 4 4
TH16 X10 3 3 T5 SV5A T12 SV12A
3 X44 3 3 3
4 15 15 5 5

1 X09 4 4 SV5C SV12C
5 X43 5 4 4
2 16 16 6 6
X34 7 X45 7
1 1 1
2 3 1 1 CN42 1 2 2 SV13B
M 3 CN07 4 CN31(Yellow) 7 7
4 (Yellow) 1 2 2 SV6B T13
1 1 X47 3 3 3 SV13A
5 8 8
Page 22

CNOUT3 X12 3 3 3 T6 SV6A


LEV3 6 2 2 X46 5 4 4 SV13C
9 9
X11 5 4 4 SV6C
3 3 X48 7 1 1
1 X35

BC CONTROLLER
7
2 CN43(Red) 1 2 2 SV14B
REL.B 10 10
M 3 CN06 T14
4 (Blue) CN36(Green) X50 3 3 3 SV14A
1 11 11
5 SV14C
X49 5 4 4
LEV2 6 X21 3 12 12
TO NEXT X51 7 1 1
ZNR01 ZNR02 INDOOR UNIT
1 CN46(Yellow) POWER SUPPLY CN44(Yellow) 2 2 SV15B
1
2 1 TB01 ~220V-240V 13 13
3 CN05 U U PULL BOX 50Hz/60Hz 3 3 3T15 SV15A
M X60 3 L X53 14 14
4 (Red)
5 X52 5 4 4 SV15C
DSA N 15 15
LEV1 6 CN47 1
F01 X54 7 1
1 16 16
250VAC SV16B
6.3A F X62 3 FUSE(16A) BREAKER(16A) CN45(Green) 1 2 2
1 1 1
X61 5 X56 3 3T16 SV16A
2 2 2 3
1 3 5 3
6 X55 5 4 SV16C
CN12 4 3 3 4
5 CNOUT2 X57 7
4 4 1 1
6
7 5 5 2 2 SVM1
8
6 6 3 3 SVM2
1 7 7 SVM2b
4 4
2
3
CNOUT4 8 SVM1b
8 5 5
4
6 6

Note:1.TB02 is transmission terminal 2.The initial set values of switch


block.Never connect power line on CONT.B are as follows.
to it. SW1:0
SW2:0
R410A Data

BC -
Drw. : cmb-p1016v-hA-WKB94G-934

22
G4
TR TB02
Indoor/outdoor
20V~22V 220V~240V S(SHIELD)
M2 Transmission Line
Symbol explanation
CONT.B M1
Symbol Name
1
CNTR TR Transformer
3
CMB-P104V-GB

3 2 1 2 1 (Red) TH12,15 Thermistor sensor


CN03 CN02
1 1 LEV3 Expansion valve
(Yellow) CN26 1 1
X2 2 Circuit BC
1 2 SV1B
2 2 CONT.B
X1
3 3
T1 board controller
3 SV1A
13-BCcontroller.qx:13-BCcontroller.qx

3 3
X30 TB01 Terminal block
5 4 4 SV1C (for power source)
4 4

TB02 Terminal block


7 (for Transmission)
3. WIRING DIAGRAMS

1
1
CN27(Red) SV1~4A,B,C Solenoid valve
X4
1 2 2 SV2B
25/4/08

5 5 T1~4 Terminal
X3 T2
3 3 3 SV2A F01 Fuse AC250V 6.3A F
6 6
X31
1 5 4 4 SV2C Note: 1. TB02 is transmission terminal block.
CN13 7 7
2 (Red) Never connect power line to it.
15:20

7
1 1 2. The initial set values of switch on
CN28(Blue)
1 X6 CONT.B are as follows.
1 2 2 SV3B
8 8
2 X5 T3 SW1:0
3 3 3 SV3A
9 9
3 X32 SW2:0
5 4 4 SV3C
Page 23

TH12 10 10
4
CN10 7
5
1 1
CN29(Green)
6 10 1 X8
1 2 2 SV4B
11 11
7 X7 T4
3 3 3 SV4A
12 12

BC CONTROLLER
8 X33
SW2 SW1 5 4 4 SV4C
13 13
1 8
1 7
TH15 ON
2 OFF
CN11
3 SW4 14 14
1 8
4 15 15
ON ZNR01 ZNR02
DSA 16 16
OFF
SW5
F01 TO NEXT INDOOR UNIT
250VAC TB01
L
6.3A F
N PULL BOX
CN07
(Yellow)
1 2 3 4 5 6 1 3 5 FUSE(16A)
PE
CN12 PE

BREAKER(16A)

LEV3 POWER SUPPLY


220V~240V
50Hz/60Hz
R410A Data

BC -
Drw. : cmb-p104v-gB-W656-847

23
G4

F
E

H
D
C
B
A

V-B
V-A

CT
BC
H
G
F
E
D
C
B
A

V-A

CT
BC
V-B
Symbol explanation

Symbol Name
TR TB02 TR Transformer
Indoor/outdoor
20V~22V 220V~240V S(SHIELD) TH12,15 Thermistor sensor Note:
M2 Transmission line
LEV3 Expansion valve 1. TB02 is transmission
M1
REL.B Circuit Relay terminal block.
CONT.B
CMB-P108V-GB

CONT.B board BC controller Never connect power


7 6 5 4 3 2 1
1 Terminal block line to it.
CN50 CNTR TB01
3 2 1 2 1 1 3 (Red) 3 (for power source)
Terminal block
2. The initial set values
CN03 CN02 CN38 1 1 TB02
CN26 1 1 (for Transmission) of switch on CONT.B
X2 1 2 2 SV1B
2 2
X1 3 3 3 T1 SV1~8A,B,C Solenoid valve are as follows.
3 3 SV1A
X30 5
T1~8 Terminal SW1:0
4 4 SV1C
4 4
3. WIRING DIAGRAMS

F01 Fuse AC250V 6.3A F


13-BCcontroller.qx:13-BCcontroller.qx

7
SW2:0
1 1
CN27(Red)
X4 1 2
2 SV2B
5 5
X3 3 3 T2
3 SV2A
6 6
SV8A
SV8B
SV7A
SV7B

SV8C
SV7C

X31 5 4
1 CN13 4 SV2C
7 7
2 (Red)
25/4/08

7
1
T8 T7
CN28(Blue) 1
4 3 2 1 4 3 2 1
1 X6 1 2 2 SV3B
8 8
2 X5 T3
3 3 3 SV3A
9 9
3 X32 5 4 4
15:20

TH12 10 10 SV3C 4 3 2 1 4 3 2 1
4
CN10 7
5 1 1
CN29(Green) 16 15 14 13 12 11 10 9 8 7 6 5 4
6 10 1 X8 1 2 2 SV4B 16 15 14 13 12 11 10 9 8 7 6 5 4
11 11
7 X7 T4
3 3 3 SV4A
12 12
8 X33 5 4 4
Page 24

SW2 SW1 13 13 SV4C


1 8
1 7
ON 1
TH15 1

BC CONTROLLER
2 OFF CN30(Black) 1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7 REL.B
CN11 X10 1 2
SW4 2 SV5B
3 14 14
CN32

1 8 X9 3 3 T5
3 SV5A
4 15 15
ON X34 5 4
4
X20
X19
X39
X18
X17
X38
X16
X15
X37
X14
X13
X36

CN33(Red)

SV5C
CN35(Blue)

16 16
CN34(Black)

OFF
SW5 7
ZNR01 ZNR02 1 1
CN31(Yellow)
DSA X12 1 2 2 SV6B
1 1
F01 X11 3 T6 3
3 3 SV6A
2 2
250VAC X35 1
5 4 4
3 3 SV6C
6.3A F 7 6 5 4 3 2 1
7 CN39
CN52
CN07
(Yellow)
1 2 3 4 5 6 1 3 5 TO NEXT INDOOR UNIT
CN12 TB01
L
N PULL BOX POWER SUPPLY
LEV3
~220V-240V
50Hz/60Hz
PE
PE FUSE(16A) BREAKER(16A)
R410A Data

BC -
Drw. : cmb-p108v-gB-W656-848

24
G4
(Symbol explanation)
TR TB02 Indoor/outdoor
20V~22V 220V~240V S(SHIELD) Symbol Name
Transmission line
M2
M1 TR Transformer
TH12,15 Thermister sensor
CNTR(Red) LEV3 Expansion valve
1
CN38 REL.B
3 2 1 3 2 1 2 1 3 1 3 Circuit Relay

SV9C
SV9A
SV9B
SV8C
SV8A
SV8B
SV7C
SV7A
SV7B
1

SV10C
SV10A
SV10B
CNVCC1 CN03 CN02 1 CONT.B board BC controller
CMB-P1016V-HB

CN26 1 1
(Blue) (Yellow) 11 2 2 SV1B Terminal block
2 2 T10 T9 T8 T7 TB01
X02 3 T1 SV1A 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
33 3 (for power source)
3 3
10 1 X01 55 4 4 SV1C Terminal block
4 4 TB02
13-BCcontroller.qx:13-BCcontroller.qx

X30 77 (for Transmission)


SW2 SW1 CONT.B 1 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 SV1~16A,B,C Solenoid valve
1 8
CN27(Red)
1 2 2 SV2B T1~T16 Terminal
ON 5 5
X04
3. WIRING DIAGRAMS

3 3 3 T2 SV2A 16 15 14 13 12 11 10 9 8 7 6 5 4 F01
OFF 6 6 Fuse AC250V 6.3A F
LD1:CPU in X03 16 15 14 13 12 11 10 9 8 7 6 5 4
1 SW4 5 4 4 SV2C
CN13 operation 7 7
2 1 8 X31 7
25/4/08

(Red)
ON
CNOUT1 1 1
OFF CN28(Blue)
1 1 1 2 2 SV3B
SW5 8 8
2 1 8 2 X06 3 3 3 T3 SV3A 3
1 33 5 7 1 5 7 1 3 5 7 1 3 5 7
9 9
3 ON 3 X05 5 4 4 SV3C
15:20

TH12 OFF 10 10 1 3 3 2 1
4 4 X32 7

X20
X19
X39
X18
X17
X38
X16
X15
X37
X14
X13
X36
CN10 SW6 CNVCC2

CN32
5
CN39
5 1 1 (Blue)

CN33(Red)

CN35(Blue)
CN34(Black)
CN29(Green) 1 1
6 6 1 2 SV4B CN40
2
11 11 (Yellow) 2 2 SV11B
7 7 X08 SV4A 1
3 3 3 T4 1 1
12 12 X41 3 3T11 SV11A
8 8 X07 SV4C 3 2 2
5 4 4
13 13 X40 4 4 SV11C
5
Page 25

X33 7 3 3
1 1 X42 7 1 1
TH15 1 1
2 2 CN30(Black) CN41(Green)
t˚ CN11 1 SV5B 1 2 2 SV12B
2 2 4 4
3 3 14 14
X10 3 SV5A X44 3 3 3T12 SV12A
3 3 T5 5 5
4 4 15 15
X09 5 SV5C X43 5 4 4 SV12C
4 4 6 6
16 16
CNOUT3 X34 7 X45 7 1 1
1

BC CONTROLLER
2 CN42
1 1 1 2 2 SV13B
3 CN07 ZNR01 ZNR02 CN31(Yellow) 7 7
M 4 (Yellow) 1 2 2
SV6B X47 3 3 3T13 SV13A
5 1 1 8 8
U U X12 3 SV6A
LEV3 6 3 3 T6 X46 5 4 4 SV13C
2 2 9 9
X11 5 4 SV6C X48
4 7 1 1
DSA 3 3
F01 X35 7 CN43(Red)
REL.B 1 2 2 SV14B
250VAC 10 10
6.3A F TO NEXT X50 3 3 3T14 SV14A
11 11
1 3 5
INDOOR UNIT X49 4 4 SV14C
POWER SUPPLY 5
~220V-240V 12 12
CN12 TB01 X51 7
PULL BOX 50Hz/60Hz 1 1
L CN44(Yellow)
1 2 2 SV15B
N 13 13
X53 3 3 3T15 SV15A
14 14
X52 5 4 4 SV15C
FUSE(16A) BREAKER(16A) 15 15
X54 7 1
16 16 1
CN45(Green) 1 2 2 SV16B
1 1 1
2 X56 3 3 3T16 SV16A
2 2
3 X55 4 SV16C
5 4
4 3 3
5 CNOUT2 X57 7
6 4 4
7
8

1
2
3
CNOUT4
4

Note:1.TB02 is transmission terminal 2.The initial set values of switch


block.Never connect power line on CONT.B are as follows.
SW1:0
R410A Data

to it.

BC -
SW2:0
Drw. : cmb-p1016v-hB-WKB94G-935

25
G4

F
E

H
D
C
B
A

V-B
V-A

CT
BC
13-BCcontroller.qx:13-BCcontroller.qx 25/4/08 15:20 Page 26

R410A Data G4

V-A

V-B

BC

CT

BC CONTROLLER BC - 26