Station Platforms: Standard
Station Platforms: Standard
Station Platforms: Standard
Standard
Station Platforms
Version 2.0
Issue date: 16 December 2019
Important message
This document is one of a set of standards developed solely and specifically for use on
Transport Assets (as defined in the Asset Standards Authority Charter). It is not suitable for any
other purpose.
The copyright and any other intellectual property in this document will at all times remain the
property of the State of New South Wales (Transport for NSW).
You must not use or adapt this document or rely upon it in any way unless you are providing
products or services to a NSW Government agency and that agency has expressly authorised
you in writing to do so. If this document forms part of a contract with, or is a condition of
approval by a NSW Government agency, use of the document is subject to the terms of the
contract or approval. To be clear, the content of this document is not licensed under any
Creative Commons Licence.
This document may contain third party material. The inclusion of third party material is for
illustrative purposes only and does not represent an endorsement by NSW Government of any
third party product or service.
If you use this document or rely upon it without authorisation under these terms, the State of
New South Wales (including Transport for NSW) and its personnel does not accept any liability
to you or any other person for any loss, damage, costs and expenses that you or anyone else
may suffer or incur from your use and reliance on the content contained in this document. Users
should exercise their own skill and care in the use of the document.
This document may not be current and is uncontrolled when printed or downloaded. Standards
may be accessed from the Transport for NSW website at www.transport.nsw.gov.au
Standard governance
Owner: Lead Civil Engineer, Asset Standards Authority
Authoriser: Chief Engineer, Asset Standards Authority
Approver: Executive Director, Asset Standards Authority on behalf of the ASA Configuration Control
Board
Document history
Version Summary of changes
1.0 First issue 17 March 2016
2.0 Second issue
Preface
The Asset Standards Authority (ASA) is a key strategic branch of Transport for NSW (TfNSW).
As the network design and standards authority for NSW Transport Assets, as specified in the
ASA Charter, the ASA identifies, selects, develops, publishes, maintains and controls a suite of
requirements documents on behalf of TfNSW, the asset owner.
The ASA deploys TfNSW requirements for asset and safety assurance by creating and
managing TfNSW's governance models, documents and processes. To achieve this, the ASA
focuses on four primary tasks:
• publishing and managing TfNSW's process and requirements documents including TfNSW
plans, standards, manuals and guides
• collaborating with the Transport cluster and industry through open engagement
The AEO framework authorises engineering organisations to supply and provide asset related
products and services to TfNSW. It works to assure the safety, quality and fitness for purpose of
those products and services over the asset's whole-of-life. AEOs are expected to demonstrate
how they have applied the requirements of ASA documents, including TfNSW plans, standards
and guides, when delivering assets and related services for TfNSW.
Compliance with ASA requirements by itself is not sufficient to ensure satisfactory outcomes for
NSW Transport Assets. The ASA expects that professional judgement be used by competent
personnel when using ASA requirements to produce those outcomes.
This standard was originally developed from RailCorp standard ESC 350 Platforms and
Retaining Walls, version 2.3.
This document details the design requirements for station platforms on the heavy rail
metropolitan rail area and country rail area.
Table of contents
1. Introduction .............................................................................................................................................. 8
2. Purpose .................................................................................................................................................... 8
2.1. Scope ..................................................................................................................................................... 8
2.2. Application ............................................................................................................................................. 9
3. Reference documents ............................................................................................................................. 9
4. Terms and definitions ........................................................................................................................... 11
5. Risk and safety ...................................................................................................................................... 12
5.1. Risk assessment .................................................................................................................................. 12
5.2. Safe places .......................................................................................................................................... 13
5.3. Security ................................................................................................................................................ 13
6. Environment and sustainability ........................................................................................................... 14
6.1. Green infrastructure ............................................................................................................................. 14
6.2. Sustainability assurance requirements ................................................................................................ 14
6.3. Ambient environmental conditions ....................................................................................................... 14
7. Heritage .................................................................................................................................................. 14
7.1. Work at heritage listed platforms ......................................................................................................... 15
7.2. Work at platforms within heritage precincts ......................................................................................... 16
7.3. Heritage documentation....................................................................................................................... 16
8. Design standards................................................................................................................................... 17
8.1. Structure classification ......................................................................................................................... 18
9. Approved materials ............................................................................................................................... 18
9.1. New and infrequently used material .................................................................................................... 18
9.2. Formwork ............................................................................................................................................. 18
9.3. Prohibited materials ............................................................................................................................. 19
10. Durability ................................................................................................................................................ 19
10.1. Design life ........................................................................................................................................ 19
10.2. Stray current and electrolysis .......................................................................................................... 19
11. Clearances.............................................................................................................................................. 19
12. Platform configuration .......................................................................................................................... 19
12.1. Permanent platforms ....................................................................................................................... 20
12.2. Access category .............................................................................................................................. 20
12.3. Width and length .............................................................................................................................. 20
12.4. Platform coping and wall.................................................................................................................. 20
12.5. Platform ends ................................................................................................................................... 21
12.6. Steel framed platforms..................................................................................................................... 21
12.7. Temporary platforms........................................................................................................................ 22
12.8. Platform footings .............................................................................................................................. 22
12.9. Joints in platforms ............................................................................................................................ 23
13. Design loads .......................................................................................................................................... 24
1. Introduction
A station platform is a track-side structure built to provide safe public access to passenger
trains.
Platforms are designated as side platforms where constructed on the outside of tracks, or
designated as island platforms where constructed between tracks.
2. Purpose
This document specifies the design, upgrade, construction, maintenance and, decommissioning
and disposal requirements for station platforms on the heavy rail metropolitan rail area and
country rail area.
2.1. Scope
This standard covers the requirements for permanent and temporary station platforms, from
design through to decommissioning, on the heavy rail metropolitan rail area and country rail
area.
• structural slab where cantilever overhang (coping) is monolithic with the slab
• structural fill over the platform footing base required to provide stability
• platform ends
• platform slabs that are not constructed structurally monolithic with the cantilever or wall
stem
• platform drainage
• platform furniture
• platform fencing
For items not covered by this standard, refer to the following standards:
2.2. Application
This document applies to all persons and organisations engaged in the provision of services
relating to station platforms on the heavy rail metropolitan rail area and country rail area.
In addition to the requirements of this standard, asset decisions take into account the life cycle
cost considerations specified in T MU AM 01001 ST Life Cycle Costing.
If when using this standard, it is considered that the intent of stated requirements is unclear, a
clarification shall be sought from the Lead Civil Engineer, Asset Standards Authority (ASA).
3. Reference documents
The following documents are cited in the text. For dated references, only the cited edition
applies. For undated references, the latest edition of the referenced document applies.
Australian standards
T HR CI 12020 ST Underbridges
CV 0044220 Cityrail Platforms (All Lines) Platform Gap Reduction Brick Coping Treatment –
Tiled Platforms Steelwork Details
CV 0150228 Cityrail Platforms (All Lines) Platform Gap Reduction Insitu Coping Concrete
Treatment Steelwork Details
CV 0150229 Cityrail Platforms (All Lines) Platform Gap Reduction Brick Coping Treatment
Steelwork Details
CV 0150596 Cityrail Platforms (All Lines) Platform Gap Reduction Existing Coping - Plate
Treatment Steelwork Details
CV 0152305 Cityrail Platforms (All Lines) Platform Gap Reduction Existing Coping Angle to U/S
Treatment Steelwork Details
CV 0153011 Cityrail Platforms (All Lines) Platform Gap Reduction Brick Coping Cutback
Treatment Steelwork Details
CV 0157182 Cityrail Platforms (All Lines) Platform Gap Reduction Thin In-Situ Concrete
Steelwork Details
CV 0269094 Cityrail Platforms (All Lines) Platform Gap Reduction Thin In-Situ Concrete
Steelwork Details
CV 0261000 Standard – All Lines – Steel Stairway for Platform Ends – Miscellaneous Details
Legislation
MN A 00100 Civil and Track Technical Maintenance (extracted from formerly ESC 100)
NSW Heritage Office 1998, Heritage Information Series, How to Prepare Archival Records of
Heritage Items
Office of Environment and Heritage January 2005, State Agency Heritage Guide –
Management of Heritage Assets by NSW Government Agencies
Roads and Maritime Services Bridge Technical Direction BTD2007/11 Horizontal reinforcement
for crack control in walls and wall type piers
country rail area that part of the NSW rail network (as defined in the Transport Administration
Act) not within the metropolitan rail area (Transport Administration Act)
© State of NSW through Transport for NSW 2019 Page 11 of 35
T HR CI 12065 ST
Station Platforms
Version 2.0
Issue date: 16 December 2019
metropolitan rail area the rail freight network and the rail passenger network within the
metropolitan rail area bounded by Newcastle (in the north), Richmond (in the northwest),
Bowenfels (in the west), Macarthur (in the southwest) and Bomaderry (in the south), and all
connection lines and sidings within these areas, but excluding private sidings
RIM rail infrastructure manager; in relation to rail infrastructure of a railway, means the person
who has effective control and management of the rail infrastructure, whether or not the
person—
(b) has a statutory or contractual right to use the rail infrastructure or to control, or provide,
access to it
RIM approval / acceptance a written approval or acceptance issued by the RIM’s civil design
discipline head. In Sydney Trains this is the Professional Head Civil Engineering
The design of station platforms, including the upgrade of existing platforms, shall take into
account the safety and human factors considerations for construction, operational, maintenance
and decommissioning workers and of the potential users of the structure.
The designer shall establish and implement a design process system that manages safety
across the full life cycle of the structure. The design process system shall be developed in
accordance with T MU MD 20001 ST System Safety Standard for New or Altered Assets.
The risk assessment shall be site-specific and should consider at least the following platform
aspects:
• platform surface levels, platform cross-fall (towards or away from the track), platform ends
(ramped or vertical)
• type of structure, that is, the potential for collapse and damage to trains
• the risks associated with demolition of existing types of construction such as retaining, pre-
stressed or post tensioned structures
• track components in the approach direction of travel, for example, catchpoints, facing and
trailing turnouts, slips, diamonds or scissor crossovers
• track geometry, that is, straight or curved track, steep or flat gradient
• track speed (and potential out of control train speed) at the location
The risk assessment should also include any other relevant site-specific criteria and shall be
used to determine the extent of mitigation required.
Risk assessments shall be submitted for acceptance by the rail infrastructure manager (RIM).
To indicate a no safe place at track level adjacent to the platform ‘No safe place’ signs shall be
used. The sign shall be in accordance with the requirements specified in T HR CI 12073 ST
Safe Places.
5.3. Security
Requirements for security and crime prevention strategies shall be determined in consultation
with the RIM, in accordance with T MU SY 20001 ST Surface Transport Fixed Infrastructure
Physical Security Standard.
Plant species used in landscaping the precinct around the platform shall be carefully selected to
ensure that they do not accelerate the deterioration, or prevent the examination or operation of
a platform or adjacent track.
Only low maintenance species with non-invasive root systems shall be planted on areas
adjacent to rail infrastructure, for example, species with limited canopy spread to avoid
interference with overhead wiring (OHW) infrastructure, signals, and lighting.
7. Heritage
Transport agencies are responsible for maintaining and appropriately managing heritage items
under their stewardship and control. The Heritage Act 1977 is designed to protect, maintain and
manage environmental heritage in NSW, including items of archaeological significance.
Where changes are proposed to items with heritage significance, the following applies:
• for items listed on the State Heritage Register, the provisions of the Heritage Act shall be
met
• for items listed on a state agency RailCorp Section 170 Heritage and Conservation
Register, the principles and relevant guidelines contained within the State Agency Heritage
Guide – Management of Heritage Assets by NSW Government Agencies and Sydney
Trains Heritage Platforms Conservation Management Strategy shall be followed
Platforms with identified heritage significance are usually a part of a larger heritage listing for a
station building or precinct. Platforms can have important aesthetic, technical, or representative
value, and often support the overall aesthetic character and heritage value of a broader station
precinct. Identifying the significant features, values and characteristics of a heritage item or
precinct is an essential step in developing appropriate designs for new elements within heritage-
listed precincts. The identified significance of a particular item or precinct and its contributory
elements and values, shall not be compromised by construction and maintenance works.
Advice from a professional heritage practitioner shall be obtained early in a project’s scoping
and design stage to determine heritage constraints and opportunities, assess any potential
heritage impacts and to guide the nature and extent of all proposed works. Heritage advice shall
be sought not only during the options analysis and design/planning phases but also throughout
the duration of the project to facilitate best possible heritage outcomes.
Proposals for minor works to heritage listed platforms may be assessed using internal
regulatory authority in cases where heritage fabric does not have adverse impact on heritage
significance; in all cases the RIM shall direct works and advise regulatory approval paths. If
archaeological evidence is discovered during construction or maintenance works, works shall
cease immediately. The RIM shall be informed and professional heritage advice obtained, and
notification shall be made in accordance with the relevant legislation.
• maintenance shall include, but not limited to, pest control for timber component parts, anti-
corrosive coatings for metal component parts as applicable and stonework repairs and
maintenance
• during construction or maintenance works, fixtures and fittings with heritage significance
shall be protected and conserved
• due to the likelihood of hazardous materials within the fill of heritage listed platforms,
applicable work health and safety legislation shall be followed
• The aim should be to avoid or minimise impacts on the heritage significance of the platform
or precinct to the greatest extent feasible.
• Where platforms are wholly renewed or new platform structures are proposed within
heritage listed precincts or within the visual catchment of heritage listed items, a design
approach shall be developed in conjunction with a professional heritage practitioner that
respects the heritage significance of the precinct. New works shall be identifiable as new
and be visually complementary to the existing context.
• Many heritage listed platforms were built with ramped ends to provide access to the track.
Where upgrades to station precincts are proposed, existing ramped ends shall be retained,
subject to full risk assessment. The risk assessment shall be submitted to the TfNSW
heritage advisor for approval. Supports for the platform extension shall be constructed
behind the ramped wall.
• Fencing at platform ends shall prevent access to the rail corridor and shall not be visually
dominant in colour, style or material to the heritage significance of the station precinct.
Refer to Section 18.6 for additional requirements where stabilising works are proposed.
8. Design standards
The design of platform structures shall be in accordance with AS 5100 Bridge design and the
requirements of this standard for the following limit states:
• stability
• serviceability
• strength
• structure classification
The design of station platforms shall take into account associated requirements including the
following:
• track geometry
• clearances
• rolling stock
• service routes
• overhead wiring
• signalling infrastructure
• drainage
• architectural treatments
• site-specific requirements
Where conflict exists, the requirements of this standard shall take precedence.
9. Approved materials
Approved construction materials for main structural elements of permanent station platforms are
steel reinforced concrete, concrete masonry and steel in metropolitan areas as specified in
Section 12.6. Steel is permitted for structural elements for temporary platforms in all areas.
Fibre-composite materials are approved for use for permanent non-structural elements.
Brick masonry is approved for repair of existing platforms and for cladding of new structures
where it is required in special circumstances, for example, heritage considerations. Only
approved heritage details such as brick type and mortar shall be used.
9.2. Formwork
Permanent formwork may be used for station platforms. Permanent formwork shall not be taken
into account in determining the strength of the structure, unless it satisfies durability and design
life requirements and becomes structurally composite with the permanent part of the structure.
The design of steel permanent formwork shall include mitigation of the effects of stray currents.
See Section 10.2 for further requirements.
Formwork with a potential to affect the durability of the structure or, foul track if it fails, is not
permitted.
Temporary formwork left in place during train operations shall be inspected regularly during the
construction to ensure that it is not loose or unstable.
10. Durability
The durability requirements for permanent station platforms shall be in accordance with
T HR CI 12002 ST Durability Requirements for Civil Infrastructure.
The design shall incorporate mitigation against the effects of stray currents. Electrical
requirements shall be obtained from the Lead Electrical Engineer, ASA.
Requirements for ongoing monitoring shall be included in the durability plan and the technical
maintenance plan (TMP).
11. Clearances
Horizontal and vertical track clearance requirements for station platforms are in ESC 215.
The area extending one metre below design rail level shall be kept clear of structures and
structure footings, unless otherwise noted in this standard. Refer to Figure 1 and minimum
service requirements in ESC 215 for details.
Backfilled gravity type precast concrete U-shaped units are commonly used for platform
reconstruction within limited track possession.
Before the design of a suspended platform commences, approval shall be obtained from the
Lead Civil Engineer, ASA.
Track design requirements for station platforms in new rail corridors are set out in ESC 210
Track Geometry and Stability and the approved design horizontal and vertical track alignment
shall be used.
Proposed works on existing platforms shall comply with Section 18 of this standard.
The minimum length of new station platforms shall be 172 m for metropolitan suburban trains
and 200 m for intercity trains, unless otherwise advised by TfNSW. Provision shall also be made
for any proposed future rolling stock.
The platform length shall be confirmed by all the stakeholders (RIM, Lead Stations and
Buildings Engineer, ASA, Lead Rolling Stock Engineer, ASA, and the rail operator).
For brick, a platform without an overhang, the coping is defined as top course of brickwork.
The distance between the edge of the platform coping and platform wall or platform support
structure adjacent to the track shall not be less than 750 mm. This distance is to allow for track
drainage and track reconditioning.
Contact the Lead Electrical Engineer, ASA for the requirements of insulating materials. In
addition, Section 17 sets out earthing and bonding requirements.
Before any proposed works are undertaken, station platforms that are of heritage significance
shall be subject to the requirements set out in Section 7 of this standard.
The platform coping at the ends of new platforms shall have a 20 mm chamfer over a 200 mm
length.
Platform end walls shall be designed for the accidental impact load defined in Section 13.2 and
Section 13.4, as applicable.
• steel structure used for platform extension over a ramped platform end for driver access
The design shall include provision for ease of access for inspection and maintenance of
steelwork.
Durability requirements for steel platforms shall be in accordance with Section 10. Steel framed
platform structures shall be considered as ‘platform walls’ in T HR CI 12002 ST.
Any station platform that is intended to be in service for more than 24 months shall be
considered as permanent.
The access category, length and width of temporary platforms shall be in accordance with
project requirements and shall be submitted for approval by the RIM.
Footings for temporary platforms shall be in accordance with Section 12.8, unless otherwise
approved by the RIM.
For the determination of platform footing depth, the rail level shall be the lower of the design rail
level and the existing rail level.
The founding depth of the footing refers to the underside of the structural footing that is in direct
contact with the foundation material, or any blinding layer where provided.
• Footings, where not founded in sound rock, shall be founded at a minimum depth of
400 mm below the top of the adjacent capping level or 1200 mm below the adjacent rail
level, whichever is deeper. Sound rock shall be rock with unconfined compressive strength
(UCS) ≥ 3.0 MPa.
• Footings, where founded in sound rock, shall be founded at a minimum depth of 300 mm
below the top of the adjacent capping level or 1100 mm below the adjacent rail level,
whichever is deeper.
• The top of any footing projecting beyond the face of the platform wall shall be located at a
minimum of 1000 mm below rail level.
• Footings, where not founded in sound rock, shall be founded at a minimum depth of
250 mm below the underside of the adjacent track slab, or base slab where provided.
Sound rock shall be rock with unconfined compressive strength (UCS) ≥ 3.0 MPa.
• Footings, where founded in sound rock, may be founded at a minimum depth of 150 mm
below the underside of the track slab.
The top of the footings shall be finished at a minimum of 250 mm above the finished ground
level and the surface profiled to shed water away from the platform supports.
The supporting framework for suspended platforms may incorporate high-level footings located
at the rear of the platform with a spill-through embankment under the platform.
• Provision for the control of cracking caused by shrinkage and thermal effects shall be made
in new concrete platform walls and platform slabs.
• Horizontal reinforcement for crack control in walls shall comply with AS 5100 and Roads
and Maritime Services (RMS) Bridge Technical Direction BTD2007/11 Horizontal
reinforcement for crack control in walls and wall type piers.
• Movement joints shall be designed to accommodate both contraction and expansion due to
thermal and environmental conditions and to suit structural material employed.
• Isolation joints shall be provided around fixed objects located in slabs to prevent damage to
the slab, for example, structure footings.
• Movement joints in brickwork or blockwork facing shall be designed to suit the facing
material.
• Exposed joints shall be fitted with compressible filler and approved flexible sealant installed
in accordance with the manufacturer’s instructions.
Platforms shall also be designed for horizontal loads associated with accidental impact from
routine track maintenance activities.
Platforms are not required to be designed for train derailment collision loads. Refer to
T HR CI 12030 ST Overbridges and Footbridges for special requirements for platforms that
provide derailment collision protection to piers and columns located on platforms.
Surcharge pressure from the design rail traffic load on platform structural elements shall be
included where it results in adverse load effects. The design rail traffic load shall be in
accordance with T HR CI 12020 ST Underbridges.
The designer shall include compaction surcharge pressure on the back of retained platforms
during the construction stage.
• normal load acting towards the platform and applied simultaneously with the parallel load
applied at the end face of the platform in the most adverse position and direction
• normal load acting away from the platform and applied simultaneously with the parallel load
applied at the end face of the platform in the most adverse position and direction
• normal and horizontal loads applied at locations of structural joints in the platform acting in
the most adverse directions (dowel bars in joints shall be designed to resist these loads, in
additional to any other forces)
The serviceability design load for deflection and dynamic behaviour shall be the load specified
for the vertical platform load in Section 13.1 or Section 13.3.
The platform global elastic deformation of any part of the platform under the application of the
accidental loads shall be limited to h divided by 200, where h is the height of platform above
formation level.
14. Earthworks
Compaction and drainage of earthworks associated with the backfill of station platforms shall be
in accordance with AS 4678-2002 and Section 20 of this standard.
Battered earth slopes beneath open station platforms shall be designed to prevent spillage of
material within 3 m the track.
15. Drainage
Track drainage shall be specifically designed at station platforms, particularly in cases where
natural run-off from the track structure is interrupted by the platform wall. The drainage design
shall be in accordance with T HR CI 12130 ST Track Drainage standard and T HR CI 12130 MA
Track Drainage manual.
The slope of the platform surface shall be designed to ensure that run-off is directed away from
the track. A complete drainage system shall be provided to collect and transfer of all
stormwater.
Platform surface drainage water on existing platforms, including runoff from canopies and
footbridge decks, is permitted to discharge into track drainage systems, subject to
T HR CI 12130 ST requirements.
16. Services
For new station platforms, services shall be located inside utility ducts within the platform.
At existing station platforms, service cables and ducting may be attached to the platform wall
under the coping where there is sufficient overhang to accommodate the services. Services
shall be located at a maximum vertical distance of 500 mm from the underside of the coping
and extend to a maximum horizontal distance of 300 mm from the face of the platform wall
towards the track.
Services attached to an existing platform wall shall comply with the transit space requirements
set out in ESC 215.
Contact the Lead Electrical Engineer, ASA for the design requirements for earthing and bonding
of station platforms in the electrified areas.
• track geometry
• height of the platform above rail (the preferred height is for a level access platform)
• platform cross-fall (the preference is for the platform to slope away from the track)
• drainage
• station furniture
• platform fencing
• service conduits
• removal of trees
• heritage significance
• potential impact on existing buildings, structures, ticket machines, entrances and riser
height to bridge stairs, and Help Points
The following upgrade works may be undertaken at platforms and do not require upgrade of the
platform wall or coping to the current standard:
• platform resurfacing
• raising the surface level of a platform to comply with standard or level access
• installation of canopies
• installation of lifts
• drainage work that does not increase the volume of water entering the existing drainage
system
The following platform upgrade works do not require the entire length of the platform to be
upgraded to comply with the requirements of this standard, except where the cost of the
upgrade works exceeds 35% of the cost of upgrading the whole platform, for similar works:
• platform extensions
The minimum length for a fully reconstructed platform shall be in accordance with Section 12.3.
Platform extension or partial reconstruction that does not exceed 5 m in length may be
constructed to match the existing platform geometric configuration, subject to approval by the
RIM.
• gradual change in the platform surface level from the new to the existing, with a
longitudinal grade not exceeding 1 in 20 at non-door locations, and 1 in 40 at door
locations
• where change in platform cross-fall occurs, the platform surface shall be graded in two
directions, parallel and normal to the track, with a grade not exceeding 1 in 40
• the change in coping offset from the design track centreline shall be gradual and smooth
and shall be submitted for approval by the RIM
• a platform surface drainage system shall be provided and no water ponding shall occur in
the transition zone
The result of this incompatibility is a horizontal gap between the platform coping and the train
carriage vestibule that is wider than standard. Drawings have been prepared to provide
solutions to reduce the gaps and are listed in Table 1.
The use of drawings in Table 1 is not mandatory unless required in this standard, or another
TfNSW standard, or by the RIM.
Where the designer proposes to adopt a referenced design or detail for a specific platform
location, the designer shall assess the currency and suitability of the referenced designs for use
and where necessary, shall specify modified or alternative designs. Modified or alternative
designs shall comply with all relevant TfNSW and Australian standards, as applicable.
The referenced drawings do not include the non-conductive tip on the top of the coping angle as
specified in Section 12.4. Contact the Lead Electrical Engineer, ASA for earthing and bonding
requirements. See also Section 17.
Any platform extensions or alterations in level shall require a new survey to be carried out and
new survey markers installed.
Station platform reconstruction projects shall comply with the geometry design alignment
requirements set out in ESC 210 and Section 8 of this standard, and shall be submitted for
approval by the RIM.
Before any work is undertaken on or adjacent to an existing brick platform, a strength and
stability assessment shall be undertaken to determine the extent of any temporary or permanent
works required to ensure platform performance is not reduced. The passive resistance of
material in front of the platform shall be ignored where excavations in front of the platform is
undertaken.
TfNSW has standard drawings for stabilising existing brick station platforms. Where stabilising is
required, reference may be made to the following standard drawings:
The designer shall be satisfied that the standard design selected is appropriate for the location
and conditions and complies with other TfNSW standards referenced. Where the standard
designs do not comply, the designer shall prepare a compliant design.
For heritage listed sites, heritage practitioner advice should be sought early in the design
process to ensure that heritage impacts of any stabilisation works are minimised to the greatest
extent possible.
• Ground anchors and tie rods shall have a design life in accordance with Section 10.1.
• Glass reinforced polymer (GRP) anchors and tie rods shall not be used for permanent
installations.
• Ground anchors shall comply with the requirements of AS 4678-2002 and Roads and
Maritime Services (RMS) QA Specification B114 Ground Anchors (Lump Sum).
• The design of ground anchors and tie rods shall include the mitigation of the effects of stray
currents. Contact the Lead Electrical Engineer, ASA for electrical requirements.
• Anchor and tie rod heads shall be protected to ensure that they do not cause an
obstruction.
• Anchor and tie rod heads shall be recessed or protected against damage by a derailed
train or by maintenance activities.
• The designer shall specify the requirements for testing of ground anchors. Testing shall
comply with the requirements in RMS QA Specification B114.
• The designer shall specify the requirements for long-term monitoring of ground anchors.
• Ground anchors shall not extend under private property without the approval of the Lead
Civil Engineer, ASA.
Excavation in earth filled platforms may also damage ground anchors and tie rods that may
have been installed to support the wall. The anchors and rods are typically round steel bars or
old rails, extending either horizontally or vertically inclined downwards from the top of the wall
and terminating in a buried concrete block. Whilst it is useful to consult old platform details,
these are not reliable as ‘work as executed’ records and care shall be exercised when
excavating.
Existing platform may be propped to ensure stability during upgrading works on the platform.
Platforms with brick walls shall be propped for work involving the use of heavy motorised plant.
Platform walls shall be assessed by a structural engineer; see Section 18.6.
The sample design for propping detailed in Figure 1 is suitable for platform resurfacing works
involving the use of a two-tonne non-vibratory roller. Where a heavier roller or a vibratory roller
is required to be used, a propping system shall be designed by a structural engineer.
Where propping is from the track, the following track requirements shall be satisfied:
Control measures shall be implemented for work on the platform where propping is used.
The control measures for work involving propping shall include the following:
• Before placing any propping or commencing any works carry out a check survey with
photographic evidence to record the platform wall condition.
• Work on the platform shall cease during passage of any machinery on the track adjacent to
the platform.
• The machinery passing over the track shall be directly supervised and the propping
checked for any damage prior to work on the platform resuming.
• The platform coping shall be monitored by a surveyor for lateral movement during
construction. The defect category limit for wall movement shall be in accordance with
TMC 301 Structures Examination. Any movement in the platform wall shall be assessed by
the design engineer for effects on platform strength and stability. Any movement shall not
result in non-compliance to clearances specified in ESC 215.
• The track shall be inspected and certified by a qualified track examiner after completion of
the work. Any track movement or disturbance shall be reported to the RIM.
• On completion of the works and after propping has been removed and all track repair has
been carried out, the RIM shall inspect the site to ensure that no disturbance has occurred.
19. Drawings
Engineering drawings shall comply with T MU MD 00006 ST Engineering Drawings and CAD
Requirements. The construction drawings shall detail, record or reference the following
information:
• design loadings
• specifications
• surface cross-fall
• construction staging
• all information that is relevant to ensure that the new structure can be constructed and
maintained in accordance with the design
20. Construction
Station platforms shall be constructed in accordance with SPC 301 Structures Construction.
The design of station platforms, including the refurbishment of existing structures, shall take into
account construction constraints, particularly under live rail operating conditions and track
possession constraints.
Earthworks and excavation near structures shall comply with the requirements set out in
T HR CI 12110 ST Earthworks and Formation. The stability of excavations shall be maintained
at all times.
Approval shall be obtained from the RIM for any excavation within the zone of influence of an
existing footing.
21. Maintenance
The design of station platforms, including the refurbishment of existing structures, shall provide
ease of access to components for inspection and maintenance activities.
The designer shall carefully select components, materials and finishes that minimise
maintenance during the life of the structure. Stainless steel fasteners shall be specified where
access for inspection and replacement purposes is difficult.
Maintenance requirements shall be specified, in the form of a TMP, in the design documentation
of the structure. The requirements shall include examination tasks and frequencies, damage
limits and repair standards. In most cases MN A 00100 Civil and Track Technical Maintenance
(extracted from formerly ESC 100) and ESC 302 Structures Defect Limits apply. However, it
may be necessary to document site-specific maintenance requirements.
The requirements and high-level processes for the development of TMPs are detailed in T MU
AM 01003 ST Development of Technical Maintenance Plans.
Disposal is the process of physically removing an asset from the network; for example,
demolition of a station platform followed by removal and recycling.
The decommissioning or disposal of an asset is the final stage of the asset life cycle. Proper
planning of this part of the life cycle is an integral part of the strategic life cycle process.
The process for the disposal of a station platform, usually undertaken in conjunction with a
replacement, shall include the following:
After decommissioning and disposal, the asset database shall be updated by the RIM to reflect
network changes.
At least fifty per cent of construction and demolition waste by weight of the decommissioned
asset should be diverted from landfill.