Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

MIKRODEV HM RTU300 en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 22

RTU300

HARDWARE MANUAL
• RTU301
• RTU310
• RTU320
• RTU330
• RTU340
RTU Series

04 / 2022
MIKRODEV_HM_RTU300_EN
v1.2
CONTENTS
FIGURES LIST .................................................................................................................................. 2
Preface ........................................................................................................................................... 3
About Mikrodev ............................................................................................................................. 4
WARNING!...................................................................................................................................... 5
Mounting Information .................................................................................................................... 6
1 RTU300 GENERAL INFORMATION ...................................................................... 7

1.1 GA1 Board Type Physical Interface .............................................................. 7

1.2 GA2 Board Type Physical Interface .............................................................. 8

1.3 GA4 Board Type Physical Interface .............................................................. 9

1.4 GA5 Board Type Physical Interface .............................................................10

1.5 GA6 Board Type Physical Interface .............................................................11

1.6 GA7 Board Type Physical Interface .............................................................12

1.7 General Device Specifications ....................................................................13

1.8 Power Connection Diagram ........................................................................14

1.9 Digital Inputs ...........................................................................................15

1.10 Digital Outputs .........................................................................................16

1.11 Relay Outputs ..........................................................................................17

1.12 Analog Inputs ..........................................................................................18

1.13 Analog Outputs ........................................................................................19

1.14 Serial Ports ..............................................................................................20

1 RTU300 SERIES – HARDWARE MANUAL


FIGURES LIST

Figure 1 DIN Rail Mounting ..................................................................................... 6


Figure 2 Expansion Module Mounting ....................................................................... 6
Figure 3 GA1 Board Type Connector and Physical Interface ......................................... 7
Figure 4 GA2 Board Type Connector and Physical Interface ......................................... 8
Figure 5 GA4 Board Type Connector and Physical Interface ........................................10
Figure 6 GA5 Board Type Connector and Physical Interface ........................................11
Figure 7 GA6 Board Type Connector and Physical Interface ........................................12
Figure 8 GA7 Board Type Connector and Physical Interface ........................................12
Figure 9 RTU300 Power Connection Diagram ............................................................19
Figure 10 RTU300 Digital Input Connection Diagram .................................................15
Figure 11 RTU300 Digital OutputConnection Diagram ................................................16
Figure 12 RTU300 Relay Connection Diagram ...........................................................17
Figure 13 RTU300 Analog Input Connection Diagram ................................................18
Figure 14 RTU300 Analog Output Connection Diagram ..............................................19
Figure 15 RTU300 RS485 Serial Port Connection Diagram ..........................................20
Figure 16 RTU300 RS232 Serial Port Connection Diagram ..........................................21

2 RTU300 SERIES – HARDWARE MANUAL


Preface

Mikrodev RTU300 series RTUs can monitor and control Intelligent Electrical Devices
(protection relays, reclosing cutters, energy and quality analyzers ... etc) via industry
standard protocols like IEC 61850, Modbus TCP and Modbus RTU. Thay can also
communicate with SCADA or control center software via IEC 60870, DNP3 and MODBUS
TCP protocols. With its easy, flexible and fast programming capabilities and expandable
I/O capability up to 1024 points, Mikrodev RTU products are preferred for electrical
applications. Mikrodev RTU300 Series RTUs are programmed mainly using Function Block
Diagram - FBD language which is defined in IEC 61131-3 standard. Thanks to programming
with FBD language, you can develop applications easily and quickly with drag and drop
logic.

Please follow our website www.mikrodev.com for the up to date version of the document.

3 RTU300 SERIES – HARDWARE MANUAL


About Mikrodev

Since 2006, MIKRODEV has been developing and manufacturing industrial control and
communication products. MIKRODEV serves the system integrators in the public and
private sector, OEM and end users. Our products are manufactured complying with the
quality standards required by the industrial automation industry and the quality of our
products are proved on the field for many years MIKRODEV is one of the few companies in
the world that has its own designed IEC 61131- 3 compliant library for its programmable
logic control devices. In addition, the open, flexible, programmable SCADA solution
developed by MIKRODEV is also available to customers. MIKRODEV products' performance
and wide range of applications make them possible for customers to achieve faster,
simplified and cost-effective results.

4 RTU300 SERIES – HARDWARE MANUAL


WARNING!
✓ Please take care of the following issues when using Mikrodev devices.
✓ Since the unit operates with 24 VDC (12-36 VDC) voltage, you should take care of
the voltage level that the unit is connected to. If a voltage above this voltage level
is applied, the device may be damaged and may be out of warranty.
✓ Make sure that the energy connection of your device is connected to the ground or
to a properly grounded terminal.
✓ Make sure that the environment in which your device is being used is free of
moisture, electric shock, vibration and dust.
✓ Pay attention to the supply voltage and the connections of the product. Mikrodev is
not responsible for any issues due to power failure since there is no auxiliary supply
(UPS) on the device.
✓ The fuse to be used must be a FF super fast type and current limit value 1A.
✓ Do not use the device under conditions other than the environmental conditions
specified in the "Electrical Specifications" section (humidity, dust, liquid and
temperature, etc.)
✓ Removing the warranty label on the product or removing the protective case will void
the warranty.
✓ Products that are damaged, boxes have been changed and other brand labels are
affixed are not covered by the warranty.
✓ The appliance must not be cleaned with solvents (thinner, benzine, acid etc.) or with
abrasive cleaning agents.
✓ Only dry cloth should be used when cleaning the appliance.
✓ Do not open the device by removing the case of the appliance, do not interfere with
the electronic components and circuits. There is no user-replaceable part inside the
device.
✓ If there is a problem or malfunction on your device, it should only be repaired by
an authorized service. Installation and electrical connections must be made by
technical personnel in accordance with the instructions in the operating manual.

Failure to comply with these rules may result in death, serious injury or property
damage

5 RTU300 SERIES – HARDWARE MANUAL


Mounting Information
DIN Rail Mounting
First, the upper part of the device is mounted on the DIN rail. Then, with the help of the
springs behind the device, when a lightly force is applied to the lower part, the device
locates into the DIN rail easily and the montage is completed (See Figure 1).

Figure 1 DIN Rail Mounting

Expansion Installation
Assembly between RTU300 series RTU products and XIO211 series expansion modules is
carried out by sliding the tabs over the rail so that the tabs overlap each other

Figure 2 Expansion Module Mounting

6 RTU300 SERIES – HARDWARE MANUAL


1 RTU300 GENERAL INFORMATION

1.1 GA1 Board Type Physical Interface

Figure 3 GA1 Board Type Connector and Physical Interface

1 Digital Input GND Connection 16 Device Power (V+) Connection


2 Analog Output Connections 17 Device Power (V-) Connection
3 Analog GND Connection 18 Ethernet Port
4 Analog Input Connection 19 USB Port
5 RS485 Connections 20 Relay Status Information LED
6 RS232 GND Connections 21 Digital Output Status Information LED
7 RS232 TX-RX Connections 22 Digital Input Status Information LED
8 N/A 23 System Power LED
9 N/A 24 System Running LED
10 Relay Connections 25 System Error LED
11 CANBUS Connection 26 Protocol Data Transfer LED
12 Digital Input Connections 27 Antenna Connection
13 Digital Output Connections 28 SIM Card Slot
14 Digital Output Supply(Vin) Connection 29 SD Card Slot
15 Digital Output GND Connection

7 RTU300 SERIES – HARDWARE MANUAL


1.2 GA2 Board Type Physical Interface

Figure 4 GA2 Connector and Physical Interface

1 Digital Input GND Connection 14 Device Power (V+) Connection


2 Analog Input Connection 15 Device Power (V-) Connection
3 Analog Input GND Connection 16 Ethernet Port
4 RS485 GND Connections 17 USB Port
5 RS485 Port 1 Connections 18 Digital Output Status Information LED
6 RS485 Port 2 Connections 19 Digital Input Status Information LED
7 RS422 Connections 20 System Power LED
8 RS232 TX-RX Connection 21 System Running LED
9 CANBUS Connection 22 System Error LED
10 Digital Input Connections 23 Protocol Data Transfer LED
11 Digital Output Connections 24 Antenna Connection
12 Digital Output Supply(Vin) Connection 25 SIM Card Slot
13 Digital Output GND Connection 26 SD Card Slot

8 RTU300 SERIES – HARDWARE MANUAL


1.3 GA4 Board Type Physical Interface

Figure 5 GA4 Board Type Connector and Physical Interface

1 Digital Input GND Connection 16 Device Power (V+) Connection


2 Analog Output Connections 17 Device Power (V-) Connection
3 Analog GND Connection 18 Ethernet Port
4 Analog Input Connection 19 USB Port
5 RS485 Connections 20 Relay Status Information LED
6 N/A 21 Digital Output Status Information LED
7 RS485(2) Connections 22 Digital Input Status Information LED
8 N/A 23 System Power LED
9 N/A 24 System Running LED
10 Relay Connections 25 System Error LED
11 CANBUS Connection 26 Protocol Data Transfer LED
12 Digital Input Connections 27 Antenna Connection
13 Digital Output Connections 28 SIM Card Slot
14 Digital Output Supply(Vin) Connection 29 SD Card Slot
15 Digital Output GND Connection

9 RTU300 SERIES – HARDWARE MANUAL


1.4 GA5 Board Type Physical Interface

Figure 6 GA5 Board Type Connector and Physical Interface

1 Digital Input GND Connection 16 Device Power (V+) Connection


2 N/A 17 Device Power (V-) Connection
3 N/A 18 Ethernet Port
4 N/A 19 USB Port
5 RS485 Connections 20 Relay Status Information LED
6 RS232 GND Connections 21 Digital Output Status Information LED
7 RS232 TX-RX Connections 22 Digital Input Status Information LED
8 N/A 23 System Power LED
9 N/A 24 System Running LED
10 Relay Connections 25 System Error LED
11 CANBUS Connection 26 Protocol Data Transfer LED
12 Digital Input Connections 27 Antenna Connection
13 Digital Output Connections 28 SIM Card Slot
14 Digital Output Supply(Vin) Connection 29 SD Card Slot
15 Digital Output GND Connection

10 RTU300 SERIES – HARDWARE MANUAL


1.5 GA6 Board Type Physical Interface

Figure 7 GA6 Board Type Connector and Physical Interface

1 Digital Input GND Connection 16 Device Power (V+) Connection


2 N/A 17 Device Power (V-) Connection
3 Analog GND Connection 18 Ethernet Port
4 Analog Input Connection 19 USB Port
5 RS485 Connections 20 N/A
6 RS232 GND Connections 21 Digital Output Status Information LED
7 RS232 TX-RX Connections 22 Digital Input Status Information LED
8 N/A 23 System Power LED
9 N/A 24 System Running LED
10 N/A 25 System Error LED
11 CANBUS Connection 26 Protocol Data Transfer LED
12 Digital Input Connections 27 Antenna Connection
13 Digital Output Connections 28 SIM Card Slot
14 Digital Output Supply(Vin) Connection 29 SD Card Slot
15 Digital Output GND Connection

11 RTU300 SERIES – HARDWARE MANUAL


1.6 GA7 Board Type Physical Interface

Figure 8 GA7 Board Type Connector and Physical Interface

1 Digital Input GND Connection 16 Device Power (V+) Connection


2 N/A 17 Device Power (V-) Connection
3 Analog GND Connection 18 Ethernet Port
4 Analog Input Connection 19 USB Port
5 RS485 Connections 20 N/A
6 N/A 21 Digital Output Status Information LED
7 RS485(2) Connections 22 Digital Input Status Information LED
8 N/A 23 System Power LED
9 N/A 24 System Running LED
10 N/A 25 System Error LED
11 CANBUS Connection 26 Protocol Data Transfer LED
12 Digital Input Connections 27 Antenna Connection
13 Digital Output Connections 28 SIM Card Slot
14 Digital Output Supply(Vin) Connection 29 SD Card Slot
15 Digital Output GND Connection

12 RTU300 SERIES – HARDWARE MANUAL


1.7 General Device Specifications

SPECIFICATION ITEM DESCRIPTION


Processor ARM Cortex M4
Architecture
Processor Internal 196 KB
Processor RAM
CPU Speed 168 MHz
Adressing
Little Endian Addressing
Architecture
Supply 24 VDC (12-36VDC)
Electrical Power <13W @ 24V DC
Real Time Clock Integrated
Board Type GA1, GA4 GA2 GA5 GA6, GA7
Digital Input 16 Channel, PNP 16 Ch. 16 Ch. 16 Ch.
Digital Output 8 Channel, 2A@30V DC, PNP 8 Ch. 8 Ch. 8 Ch.
Input / Output
Analog Input 4 Channel, 0-20 mA, 4-20 mA 8 Ch. 4 Ch.
Analog Output 2 Channel, 0-20 mA, 4-20 mA
Relay Output 4 Channel, 3A@30VDC - 5A@250VAC 4 Ch.
Operating -25…+75 C
Temperature
Enviromental Storage -30…+85 C
Conditions Temperature
Humidity 5…95 RH
Operating Altitude 0…2000 m
SD Card Support* Micro SD
Retentive Memory 4 KB, 128 Block/Register
Memory
Max Event Log 20000
Program Memory 4 MBit
Board Type GA1, GA5, GA6 GA2 GA4, GA7
Ethernet Port 10/100 Mbps 10/100 Mbps 10/100 Mbps
2 Port, ESD
Protection, 8 kV 2 Port, ESD
1 Port, ESD Protection,
Communication Direct, 25 kV Air Protection, 8 kV
RS485 8 kV Direct, 25 kV Air
Ports Discharge or 1 port Direct, 25 kV Air
Discharge
RS485 and 1 port Discharge
RS422
1 Port (with flow
RS232 1 Port
control)
Wireless
GSM/LTE* LTE Modem
Communication
DIN Rail Type-
Expansion
CANBUS Up to 1024 I/O Points
Capacity
Expansion

*Optional selection

13 RTU300 SERIES – HARDWARE MANUAL


1.8 Power Connection Diagram

1.8.1 Supply Connection

Board Type: GA1, GA2, GA4, GA5, GA6, GA7


Supply: 12-36 VDC, Protected
Power: <13 W

Figure 9 RTU300 Power Connection Diagram

14 RTU300 SERIES – HARDWARE MANUAL


1.9 Digital Inputs

Board Type: GA1, GA2, GA4, GA5, GA6, GA7


Module Input: 16 Channel, PNP
Voltage Range: 0-36V DC
ON Voltage Level: 12-36V DC
OFF Voltage Level: 0-10V DC
Input Impedance: >2M
Isolation: Optical
OFF to ON Response: 20 us
ON to OFF Response: 90 us

Figure 10 RTU300 Digital Input Connection Diagram

15 RTU300 SERIES – HARDWARE MANUAL


1.10 Digital Outputs

Board Type: GA1, GA2, GA4, GA5, GA6, GA7


Module Output: 8 Channel, Mosfet Output
Module Output Type: PNP Transistor
Voltage Range: 12-36V DC
Max. Output Current: 2A @ 30V DC
Isolation: Optical

Figure 11 RTU300 Digital Output Connection Diagram

16 RTU300 SERIES – HARDWARE MANUAL


1.11 Relay Outputs

Board Type: GA1, GA4, GA5


Module Output: 4 Channel
Relay Contact Outputs: NO(Normally Open) Contact
Contact Max. Current: 3A@30VDC – 5A@250VAC
Isolation Dry Contact

Figure 12 RTU300 Relay Connection Diagram

17 RTU300 SERIES – HARDWARE MANUAL


1.12 Analog Inputs

Board Type: GA1, GA4 GA2 GA6, GA7


Module Input: 4 Channel 8 Channel 4 Channel
Analog Input Type: 0-20 mA, 4-20 mA 0-20 mA, 4-20 mA 0-20 mA, 4-20 mA
Analog Input Resolution: 16 Bit 16 Bit 12 Bit
Analog Input Precision: %1 Precision %1 Precision %1 Precision
Common Input GND: 1 GND (4 Point / 2 GND (8 Point / 1 GND (4 Point /
Common) Common) Common)

Figure 13 RTU300 Analog Input Connection Diagram

18 RTU300 SERIES – HARDWARE MANUAL


1.13 Analog Outputs

Board Type: GA1, GA4


Module Output: 2 Channel
Analog Output Type: 0-20 mA, 4-20 mA
Analog Output Resolution: 12 Bit
Current Output Precision: %1 Precision
Common Output GND: 1 GND (2 Point / Common)

Figure 14 RTU300 Analog Output Connection Diagram

19 RTU300 SERIES – HARDWARE MANUAL


1.14 Serial Ports

1.14.1 RS485 Serial Port

Board Type: GA1, GA5, GA6 GA2 GA4,GA7


RS485 Port Count: 1 Port 2 Port RS485 or 1 Port 2 Port
RS485 and 1 Port RS422
Maximum Slave Count Limited to Hardware
Isolation: ESD Protection, 8 kV Direct, 25 kV Air Discharge
Communication Distance: 1000 m
Data Bits: 7-8
Stop Bits: 1-2
Parity: None-Even-Odd
Baudrate: 300 bps to 200 kbps

Figure 15 RTU300 RS485 Serial Port Connection Diagram

20 RTU300 SERIES – HARDWARE MANUAL


1.14.2 RS232 Serial Port

Board Type: GA1, GA5, GA6 GA2


RS232 Port Count: 1 Port 1 Port (with flow control)
Communication Distance: 10 m
Data Bits: 7-8
Stop Bits: 1-2
Parity: None-Even-Odd
Baudrate: 300 bps to 200 kbps

Figure 16 RTU300 RS232 Serial Port Connection Diagra

21 RTU300 SERIES – HARDWARE MANUAL

You might also like