RS 310-610/M MZ Series
Modulating Gas Burners
www.riello.com
Modulating Gas Burners RS 310 - 610/M MZ Series
The high power monoblock Burners Series RS 310-410-510-610/M MZ, are the result of intensive activities of
technical research and considerable investments, carried out in recent years, that allowed the highest levels of
technological development to be achieved in the Industrial Burners context, confirming the historical leadership
of Riello in this important area of energy management.
The remarkable results of performance, quality and reliability, are now consolidated by the creation of new
models in the 3-6 MW range, RS 310-410-510-610/M MZ, able to summarize and concentrate the best technological
expertise of Riello.
The RS 310-410-510-610/M MZ burners series covers a firing range from 1200 to 6250 kW, and it has been
designed for use in low or medium temperature hot water boilers, hot air or steam boilers, diathermic oil
boilers. Operation can be “two stage progressive” or, alternatively, “modulating” with the installation of a PID
logic regulation.
The exclusive design ensures reduced dimensions, simple use and maintenance.
A wide range of accessories guarantees elevated working flexibility.
2
Technical Data
3
Modulating Gas Burners RS 310 - 610/M MZ Series
Reference conditions:
Temperature: 20°C - Pressure: 1013,5 mbar - Altitude: 0 m a.s.l. - Noise measured at a distance of 1 meter.
Sound pressure measured in manufacturer’s combustion laboratory, with burner operating on test boiler and
at maximum rated output. The sound power is measured with the “Free Field” method, as per EN 15036, and
according to an “Accuracy: Category 3” measuring accuracy, as set out in EN ISO 3746.
Firing Rates
20
Useful working field
for choosing the
18 burner
16
Modulation range
14
Test conditions
12 conforming to EN676
RS 610 Temperature: 20°C
hPa (mbar)
8
RS 510
6 RS 410
4
RS 310
2
-2
400 800 1200 1600 2000 2400 2800 3200 3600 4000 4400 4800 5200 5600 6000 6400 6800 kW
4
Gas train
Series: MB
MBC
DMV
DMV12
VGD
CB
CBH
MV
CG
Standard output
- without pressure governor
pressure range:
0 with governor and air/gas proportional pressure
2 with governor and output pressure up to 20 mbar
3 with governor and output pressure up to 30 mbar
4 with governor and output pressure up to 40 mbar
5 with governor and output pressure up to 50 mbar
6 with governor and output pressure up to 60 mbar
8 with governor and output pressure up to 80 mbar
15 with governor and output pressure up to 150 mbar
CB 5065 /1 CT F SM 3 0
BASIC DESIGNATION
EXTENDED DESIGNATION
5
Modulating Gas Burners RS 310 - 610/M MZ Series
GAS TRAINS
The burners are fitted with a butterfly valve to regulate the fuel, controlled by the main management module
of burner through a high precision servomotor.
Fuel can be supplied either from the right or left sides, on the basis of the application requirements.
A maximum gas pressure switch stops the burner in case of excess pressure in the fuel line.
The gas train can be selected to best fit system requirements depending on the fuel output and pressure in
the supply line.
The gas trains are with or without seal control.
MB “THREADED”
1 Gas input pipework
12 2 Manual valve
3 Anti-vibration joint
4 Pressure gauge with pushbutton cock
5 Filter
6A Includes:
- filter
8 - operation valve
P1 4
- safety valve
13 11 - pressure adjuster
9 7 7 Minimum gas pressure switch
8 Leak detection device, supplied as an
accessory or incorporated, based on
14 5 the gas train code.
3 2 1
P3 9 Gasket, for “flanged” versions only
6A P2 10 Pressure adjuster
11 Gas adjuster butterfly valve
L L1 12 Burner
13 Maximum gas pressure switch
14 Gas train-burner adaptor, supplied
separately
P1 Combustion head pressure
P2 Upstream pressure of valves
MBC “THREADED”
P3 Upstream pressure of the filter
L Gas train supplied separately, with
12
the code given in the table.
L1 Installer’s responsibility
8 7
P1 4
13 11
9
14 5
3 2 1
P3
6A
P2
L L1
6
MBC “FLANGED” 1 Gas input pipework
2 Manual valve
12 3 Anti-vibration joint
4 Pressure gauge with pushbutton
cock
5 Filter
6B Includes:
- operation valve
8 7 - safety valve
P1 4
- pressure adjuster
13 11 6C Includes:
9 - operation valve
9 - safety valve
6D Includes:
14 5 - operation valve
3 2 1
- safety valve
P3 7 Minimum gas pressure switch
6B P2 8 Leak detection device, supplied as an
accessory or incorporated, based on
L L1
the gas train code.
9 Gasket, for “flanged” versions only
CB “FLANGED OR THREADED” 10 Pressure adjuster
11 Gas adjuster butterfly valve
12 12 Burner
13 Maximum gas pressure switch
14 Gas train-burner adaptor, supplied
separately
P1 Combustion head pressure
P2 Upstream pressure of valves
8 7 P3 Upstream pressure of the filter
P1
L Gas train supplied separately, with
13 11 the code given in the table
9
L1 Installer’s responsibility
9
14
5 3 2 1
10
6D P2
L L1
12
8 7
P1
13 11
9
9
14
5 3 2 1
10
6C
P2
L L1
7
Modulating Gas Burners RS 310 - 610/M MZ Series
Gas trains are approved by standard EN 676 together with the burner.
The overall dimensions of the gas train depends on how they are constructed. The following table shows the
maximum dimensions of the gas trains that can be fitted to RS 650-800-1000-1200/M MZ burners, intake and
outlet diameters and seal control if fitted.
The maximum gas pressure of gas train “MULTIBLOC” type is 360 mbar, and that one of gas train “COMPOSED”
type is 500 mbar.
“MULTIBLOC” guarantees a range of pressure towards the burner from 4 to 60 mbar. For version DN 65 and DN 80
is from 20 to 40 mbar. For version DN 100 is from 40 to 80 mbar. The range of pressure in the “MULTIBLOC” with
flange can be modified choosing the stabiliser spring (see gas train accessory).
The maximum gas pressure of gas train “CB” series is 500 mbar. “CB” gas train guarantees a range of pressure
towards the burner from 10 to 30 mbar. The range of pressure can be modified choosing the stabilizer spring
(see accessories).
The maximum gas pressure of gas train “DMV” series is 500 mbar. “DMV” gas train is supplied without pressure
governor.
Y Y
Øout
Øout
Øin
Øin
Z X Z X
Example of gas train “COMPOSED” type
Example of gas train “MULTIBLOC” type without seal control (i.e. MBC 1900-3100-5000)
without seal control (i.e. MBC 1200)
Øin
Øout
Y Y
Z
Z X
X
Example of gas train “DMV” series
Example of gas train “CB” series with seal control
with seal control
GAS TRAIN
MODEL CODE Ø in Ø out X mm Y mm Z mm
MB 415/1 - RT 30 3970180 Rp 1-1/2” Rp 1-1/2” 523 250 100
MB 415/1 CT RT 30 3970198 Rp 1-1/2” Rp 1-1/2” 523 250 229
MB 415/1 - RT 52 3970250 Rp 1-1/2” Rp 1-1/2” 523 250 100
MB 415/1 CT RT 52 3970253 Rp 1-1/2” Rp 1-1/2” 523 250 229
MB 415/1 RSM 30 3970232 Rp 1-1/2” Rp 1-1/2” 523 250 100
MB 420/1 - RT 30 3970181 Rp 2” Rp 2” 523 289 100
MB 420/1 CT RT 30 3970182 Rp 2” Rp 2” 523 289 229
MB 420/1 - RT 52 3970257 Rp 2” Rp 2” 523 289 100
MB 420/1 CT RT 52 3970252 Rp 2” Rp 2” 523 289 229
MB 420/1 RSM 30 3970233 Rp 2” Rp 2” 523 289 100
MB 420/1 CT RSM 30 3970234 Rp 2” Rp 2” 523 289 229
8
GAS TRAIN
MODEL CODE Ø in Ø out X mm Y mm Z mm
MBC 1200/1 - RSM 60 3970221 Rp 2” Rp 2” 528 424 161
MBC 1200/1 CT RSM 60 3970225 Rp 2” Rp 2” 528 424 290
MBC 1900/1 - FSM 40 3970222 DN 65 DN 65 613 430 237
MBC 1900/1 CT FSM 40 3970226 DN 65 DN 65 613 430 298
MBC 3100/1 - FSM 40 3970223 DN 80 DN 80 633 500 240
MBC 3100/1 CT FSM 40 3970227 DN 80 DN 80 633 500 319
MBC 5000/1 - FSM 80 3970224 DN 100 DN 100 733 576 280
MBC 5000/1 CT FSM 80 3970228 DN 100 DN 100 733 576 348
GAS TRAIN
MODEL CODE Ø in Ø out X mm Y mm Z mm
CB 512/1 - RSM 30 3970145 Rp 1-1/2” Rp 1-1/2” 891 261 245
CB 512/1 CT RSM 30 20045589 Rp 1-1/2” Rp 1-1/2” 891 261 245
CB 520/1 - RSM 30 3970146 Rp 2” Rp 2” 986 328 255
CB 520/1 CT RSM 30 3970160 Rp 2” Rp 2” 986 328 255
CB 525/1 - RSM 30 20044659 Rp 2” Rp 2” 1025 356 285
CB 525/1 CT RSM 30 20044660 Rp 2” Rp 2” 1025 356 285
CB 5065/1 - FSM 30 3970147 DN 65 DN 65 906 356 285
CB 5065/1 CT FSM 30 3970161 DN 65 DN 65 906 356 285
CB 5080/1 - FSM 30 3970148 DN 80 DN 80 934 416 285
CB 5080/1 CT FSM 30 3970162 DN 80 DN 80 934 416 285
CB 50100/1 - FSM 30 3970149 DN 100 DN 100 1054 501 350
CB 50100/1 CT FSM 30 3970163 DN 100 DN 100 1054 501 350
CB 50125/1 - FSM 30 20015871 DN 125 DN 125 1164 780 400
CB 50125/1 CT FSM 30 3970196 DN 125 DN 125 1164 780 400
GAS TRAIN
MODEL CODE Ø in Ø out X mm Y mm Z mm
DMV 512/1 - RSM -0 20043035 Rp 1-1/2” Rp 1-1/2” 490 292 245
DMV 512/1 CT RSM -0 20043036 Rp 1-1/2” Rp 1-1/2” 490 292 245
DMV 512/1 CQ RSM -2 20043037 Rp 1-1/2” Rp 1-1/2” 490 292 245
DMV 520/1 - RSM -0 20043038 Rp 2” Rp 2” 490 292 255
DMV 520/1 CT RSM -0 20043039 Rp 2” Rp 2” 490 292 255
DMV 520/1 CQ RSM -2 20043040 Rp 2” Rp 2” 490 292 255
DMV 525/1 - RSM -0 20043053 Rp 2” Rp 2” 530 338 270
DMV 525/1 CT RSM -0 20043054 Rp 2” Rp 2” 530 338 270
DMV 525/1 CQ RSM -2 20043055 Rp 2” Rp 2” 530 338 270
DMV 5065/1 - FSM -0 20043041 DN 65 DN 65 290 338 270
DMV 5065/1 CT FSM -0 20043042 DN 65 DN 65 290 338 270
DMV 5065/1 CQ FSM -2 20043043 DN 65 DN 65 290 338 270
DMV 5080/1 - FSM -0 20043044 DN 80 DN 80 310 397 290
DMV 5080/1 CT FSM -0 20043045 DN 80 DN 80 310 397 290
DMV 5080/1 CQ FSM -2 20043046 DN 80 DN 80 310 397 290
DMV 50100/1 - FSM -0 20043047 DN 100 DN 100 350 449 307
DMV 50100/1 CT FSM -0 20043048 DN 100 DN 100 350 449 307
DMV 50100/1 CQ FSM -2 20043049 DN 100 DN 100 350 449 307
DMV 50125/1 - FSM -0 20043050 DN 125 DN 125 400 554 333
DMV 50125/1 CT FSM -0 20043051 DN 125 DN 125 400 554 333
DMV 50125/1 CQ FSM -2 20043052 DN 125 DN 125 400 554 333
9
Modulating Gas Burners RS 310 - 610/M MZ Series
The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can be matched
with them; at the value of these pressure drop add the combustion chamber pressure.
The value thus calculated represents the minimum required input pressure to the gas train.
The minimum input gas pressure required is 15 mbar while burner operating.
In particular, the pressure difference between gas train upstream and downstream has to remain always over
pressure drop values indicated below.
G20 G25
100
110
90
MB 415 1 100 MB 420 1
80
90
MB 420 1
70 80
60 70
p mbar
p mbar
50 60
50
40
40
30
30
20
20
10 10
1300 3900 1300 3900
0 0
1500 2000 2500 3000 3500 kW 1500 2000 2500 3000 3500 kW
G20 G25
160 240
150 220
140
130 200
MBC 1200 1 MBC 1200 1
120 180
110 160
100
140
p mbar
p mbar
90
80 MBC 1900 1 120 MBC 1900 1
70 100
60 MBC 3100 1 MBC 3100 1
50 80
MBC 5000 1 MBC 5000 1
40 60
30 40
20
10 20
1300 3900 1300 3900
0 0
1500 2000 2500 3000 3500 kW 1500 2000 2500 3000 3500 kW
10
RS 310/M MZ (NATURAL GAS)
G20 G25
360
360
340
340
320
320
300
300
280 CB 520 1 CB 525 1
280
260 260
240 240
220 CB 520 1
220
p mbar
p mbar
200 CB 525 1 200 CB 5065 1
180 CB 512 1
180
160 160
140 CB 5065 1 140
120 120 CB 5080 1
100 100 CB 50100 1
80 CB 5080 1
80 CB 50125 1
CB 50100 1
60 60
CB 50125 1
40 40
20 20
1300 3900 1300 3900
0 0
1500 2000 2500 3000 3500 kW 1500 2000 2500 3000 3500 kW
G20 G25
240
200
220
200 180
DMV 520 1 DMV 512 1 DMV 525 1
180 160 DMV 520 1
DMV 5065 1
160 140
p mbar
p mbar
140 120
120
DMV 512 1 DMV 525 1 100 DMV 5080 1
100 DMV 5065 1
80 DMV 50100 1
80 DMV 50125 1
DMV 5080 1 60
60 DMV 50100 1
DMV 50125 1 40
40
20 20
1300 3900 1300 3900
0 0
1500 2000 2500 3000 3500 kW 1500 2000 2500 3000 3500 kW
11
Modulating Gas Burners RS 310 - 610/M MZ Series
G20 G25
340
220
320
200 300
MBC 1200 1 280 MBC 1200 1
180
260
160 240
220
140
200
p mbar
p mbar
120 MBC 1900 1 180 MBC 1900 1
160
100
140
80 MBC 3100 1 120 MBC 3100 1
MBC 5000 1 100 MBC 5000 1
60
80
40 60
40
20
20
2000 4900 2000 4900
0 0
2500 3000 3500 4000 4500 kW 2500 3000 3500 4000 4500 kW
G20 G25
360 380
340 360
320 340
320
300
CB 525 1 300 CB 5065 1
280
280
260 CB 520 1 260 CB 525 1
240
240
220
220
p mbar
p mbar
200 CB 5065 1
200
180 180 CB 5080 1
160 160
140 140
120 CB 5080 1 120 CB 50100 1
100 100 CB 50125 1
80 CB 50100 1
CB 50125 1 80
60 60
40 40
20 20
2000 4900 2000 4900
0 0
2500 3000 3500 4000 4500 kW 2500 3000 3500 4000 4500 kW
12
RS 410/M MZ (NATURAL GAS)
G20 G25
200
260
180 240
DMV 520 1
DMV 525 1 220 DMV 5065 1
160
DMV 5065 1 200
140 DMV 525 1
180
120 160
p mbar
p mbar
DMV 520 1
140 DMV 5080 1
100
DMV 5080 1 120
80 DMV 50100 1
DMV 50100 1 100 DMV 50125 1
60 DMV 50125 1 80
60
40
40
20
20
2000 4900 2000 4900
0 0
2500 3000 3500 4000 4500 kW 2500 3000 3500 4000 4500 kW
G20 G25
440
280 420
260 400
380
240 360
MBC 1200 1 MBC 1200 1
220 340
320
200 300
180 280
260
p mbar
p mbar
160 240
MBC 1900 1 220 MBC 1900 1
140
200
120 180
100 MBC 3100 1 160 MBC 3100 1
140
80 MBC 5000 1 120 MBC 5000 1
100
60
80
40 60
40
20
2200 5600
20 2200 5600
0 0
3000 4000 5000 kW 3000 4000 5000 kW
13
Modulating Gas Burners RS 310 - 610/M MZ Series
G20 G25
360
340
340
320
320
300
CB 525 1 300 CB 5065 1
280 CB 520 1
280
260 CB 5065 1 260
240
240
220 220 CB 5080 1
p mbar
p mbar
200 CB 520 1 200 CB 525 1
180 180
160 160
140 CB 5080 1 CB 50100 1
140
120 120 CB 50125 1
100 CB 50100 1 100
80 CB 50125 1
80
60 60
40 40
20 20
2200 5600 2200 5600
0 0
3000 4000 5000 kW 3000 4000 5000 kW
G20 G25
260
260
240
240
220
220 DMV 5065 1
DMV 525 1
200
200
DMV 5065 1 DMV 520 1
180 180 DMV 525 1
DMV 5080 1
160 160
p mbar
p mbar
140 140
DMV 520 1 DMV 50100 1
120 DMV 5080 1 120 DMV 50125 1
100 100
DMV 50100 1
80 DMV 50125 1 80
60 60
40 40
20 20
2200 5600 2200 5600
0 0
3000 4000 5000 kW 3000 4000 5000 kW
14
RS 610/M MZ (NATURAL GAS)
G20 G25
380
360 420
340 400
380
320 360
300 MBC 1200 1 340 MBC 1200 1
280 320
260 300
240 280
220 260
p mbar
p mbar
240
200
MBC 1900 1 220 MBC 1900 1
180 200 MBC 3100 1
160 180
140 160 MBC 5000 1
MBC 3100 1
120 140
100 MBC 5000 1 120
80 100
80
60 60
40 40
20 20
2 4 00 6300 2400 6300
0 0
3000 4000 5000 6000 kW 3000 4000 5000 6000 kW
G20 G25
400 340
380
320
360
340 300
320 CB 5065 1 280 CB 5065 1 CB 5080 1
300 260
280 CB 525 1 240 CB 525 1
260 220
240
p mbar
p mbar
CB 520 1 200
220 CB 50100 1
200 180
180 CB 5080 1 160 CB 50125 1
160 140
140 120
120 CB 50100 1
CB 50125 1 100
100 80
80
60
60
40 40
20 20
2 4 00 6300 2400 6300
0 0
3000 4000 5000 6000 kW 3000 4000 5000 6000 kW
15
Modulating Gas Burners RS 310 - 610/M MZ Series
G20 G25
300 280
280 260
260 240
240 DMV 525 1
DMV 5065 1 220 DMV 5080 1
220 200 DMV 5065 1
200 DMV 525 1
180
180 DMV 50100 1
p mbar
p mbar
160
160 DMV 520 1 DMV 50125 1
DMV 5080 1 140
140
120
120
DMV 50100 1 100
100 DMV 50125 1
80 80
60 60
40 40
20 20
2 4 00 6300 2400 6300
0 0
3000 4000 5000 6000 kW 3000 4000 5000 6000 kW
16
GAS TRAIN VPS KIT ADAPTER
CODE
CODE MODEL u CODE
RS 310 RS 410 RS 510 RS 610
3000826 +
3970180 MB 415/1 - RT 30 - 3010123 l l l
20064220
3000826 +
3970198 MB 415/1 CT RT 30 CT - l l l
20064220
3000826 +
3970250 MB 415/1 - RT 52 - 3010123 l l l
20064220
3000826 +
3970253 MB 415/1 CT RT 52 CT - l l l
20064220
3000826 +
3970232 MB 415/1 - RSM 30 - 3010123 l l l
20064220
3000826 +
3970181 MB 420/1 - RT 30 - 3010123 l l l
20042324
3000826 +
3970182 MB 420/1 CT RT 30 CT - l l l
20042324
3000826 +
3970257 MB 420/1 - RT 52 - 3010123 l l l
20042324
3000826 +
3970252 MB 420/1 CT RT 52 CT - l l l
20042324
3000826 +
3970233 MB 420/1 - RSM 30 - 3010123 l l l
20042324
3000826 +
3970234 MB 420/1 CT RSM 30 CT - l l l
20042324
3970221 MBC 1200/1 - RSM 60 - 3010367 3000826 + 20042324
3970225 MBC 1200/1 CT RSM 60 CT - 3000826 + 20042324
3970222 MBC 1900/1 - FSM 40 - 3010367 3010221
3970226 MBC 1900/1 CT FSM 40 CT - 3010221
3970223 MBC 3100/1 - FSM 40 - 3010367 3010222
3970227 MBC 3100/1 CT FSM 40 CT - 3010222
3970224 MBC 5000/1 - FSM 80 - 3010367 3010223 - 3010370
3970228 MBC 5000/1 CT FSM 80 CT - 3010223 - 3010370
3970145 CB 512/1 - RSM 30 - 3010367 3000826 + 20064220 l l
17
Modulating Gas Burners RS 310 - 610/M MZ Series
18
Ventilation
Simplified Maintenance
for motor and fan by direct Air adjusting dampers
extraction through opening flange at air inlet side with ball bearings
Combustion Head
The combustion head adjustment system allows to adapt internal geometry of the head to the output of the
burner. This system guarantees excellent mix on all firing rates range as well as reducing noise and pollutants.
Example of hinged burner opening on
the left side of the burner
19
Modulating Gas Burners RS 310 - 610/M MZ Series
ax
Lm
n
L mi
combustion chamber (m)
Diameter of the
D max
D min
Example:
Burner thermal output = 6000 kW;
L Combustion Chamber (m) = 4,7 m (medium value);
D Combustion Chamber (m) = 1,2 m (medium value)
20
Operation
The RS 310-410-510-610/M series of burners can have “two-stage progressive” or “modulating” operation.
On “two-stage progressive” operation, the burner gradually adapts the output to the requested level, by varying
between two pre-set levels (see picture A).
On “modulating” operation, normally required in steam generators, in superheater boilers or diathermic oil
burners, a specific regulator and probes are required. These are supplied as accessories that must be ordered
separately. The burner can work for long periods at intermediate output levels (see picture B).
°C °C
bar bar
Controlled
Controlled
variable
variable
Time Time
MAX MAX
Output
Output
MIN MIN
Time Time
Picture A Picture B
21
Modulating Gas Burners RS 310 - 610/M MZ Series
The RS 310-410-510-610/M MZ series burners are fitted with the LFL 1.333 or RMG88.62 C2 microprocessor control
panel for the supervision during intermittent operation. The FS2 burners are fitted with the LGK16.333A27 control
panel.
For helping the commissioning and maintenance work, on the RMG/M control box, there are two main elements:
RMG 88.62 C2
The lock-out reset button is the central The multi-color LED is the central indication
operating element for resetting the burner element for visual diagnosis and interface
control and for activating / deactivating diagnosis.
the diagnostic functions.
Both elements are located under the transparent cover of lock-out reset button, as shown in the picture above.
VISUAL DIAGNOSIS
INTERFACE DIAGNOSIS
22
Noise Emissions
100
NOISE EMISSIONS
80
dB(A)
60
40
20
RS 310
RS 610
RS 510
RS 410
23
Modulating Gas Burners RS 310 - 610/M MZ Series
A B G
C M
H
E
Ø 200
F C O O
I
L
R
L
MODEL A B C D E F** G H I* L M N O P R
RS 310/M MZ 1178 519 178 306 520 DN65 890 790 177 1015 400 528 290 177 890
RS 410/M MZ 1178 519 178 306 520 DN65 930 790 177 1015 400 528 290 177 890
RS 510/M MZ 1178 519 178 306 520 DN65 908 790 177 1015 400 528 290 177 890
RS 610/M MZ 1178 500 178 330 520 DN65 980 790 177 1015 400 528 290 177 890
* Maximum position for the extraction of the servomotor cover in mechanical cam models.
** The gas adaptor is set also for DN 80 bore.
MODEL D1 D2 Ø
RS 310/M MZ 335 452 M18
RS 410/M MZ 335 452 M18
RS 510/M MZ 335 452 M18
RS 610/M MZ 350 452 M18
PACKAGING
MODEL X Y Z kg
Z RS 310/M MZ 2040 1180 1125 250
RS 410/M MZ 2040 1180 1125 250
Y RS 510/M MZ 2040 1180 1125 250
X
RS 610/M MZ 2040 1180 1125 280
24
Burner accessories
POWER CONTROLLER To obtain modulating operation, the RS/M MZ series of burners requires a
regulator with three point outlet controls.
The following table lists the accessories for modulating operation with their
application range.
PROBE The relative temperature or pressure probes fitted to the power controller
must be chosen on the basis of the application.
POTENTIOMETER
BURNER CODE
All models 20074487
CONTINUOUS VENTILATION KIT If the burner requires continuous ventilation in the stages without flame, a spe-
cial kit is available as given in the following table:
BURNER CODE
All models 20074542
25
Modulating Gas Burners RS 310 - 610/M MZ Series
UV CELL KIT A UV cell is available for the supervision of the flame alternatively to ionisation
probe for special applications.
BURNER CODE
All models 20074548
PC INTERFACE KIT To connect the control panel to a personal computer for the transmission of op-
eration, fault signals and detailed service information, an interface adapter with
PC software are available.
BURNER CODE
All models (*) 3002719
(*) Equipped with RMG/M control box
SOUND PROOFING BOX If noise emission needs reducing even further, sound-proofing boxes are
available. In case of generator heights, where a lower dimension “B” is required,
D E ask for the Box Support Kit code 20065135.
The useful dimensions are 40 mm less than the total dimensions indicated in the
table (A, D, E). Not suitable for outdoor use.
A
SPACER KIT If burner head penetration into the combustion chamber needs reducing, vary-
ing thickness spacers are available, as given in the following table.
26
Gas train accessories
ADAPTERS In certain cases, an adapter must be fitted between the gas train and the burner,
when the diameter of the gas train is different from the set diameter of the
burner.
Below are given the available adapters; please see on the Gas Train list the cor-
rect adapter codes to select.
DIMENSIONS
ADAPTER ADAPTER CODE
Ø1 DN Ø2 DN A mm B mm
1” 1/2 2” - - 65 - 20064220
2” 2” - - 65 - 20042324
65 80 400 - 3010221
Ø1 Ø2 80 80 400 - 3010222
100 80 400 - 3010223
125 80 320 - 3010224
STABILISER SPRING To vary the pressure range of the gas train stabilisers, accessory springs are avail-
able. The following table shows these accessories with their application range.
Please refer to the technical manual for the correct choice of spring.
SPRING PRESSURE
GAS TRAIN SPRING COLOUR SPRING CODE
RANGE mbar
White 4 - 20 3010381
MBC 1900/1 - 3100/1 Red 20 - 40 3010382
MBC 5000/1 Black 40 - 80 3010383
Green 80 - 150 3010384
Red 25 - 55 3010131
CB 512/1 Black 60 - 110 3010157
Pink 90 - 150 3090486
Red 25 - 55 3010132
CB 520/1 - 525/1 Black 60 - 110 3010158
Pink 90 - 150 3090487
Red 25 - 55 3010133
Black 60 - 110 3010135
CB 5065/1 - 5080/1
Pink 100 - 150 3090456
Grey 140 - 200 3090992
Red 25 - 55 3010134
Black 60 - 110 3010136
CB 50100/1
Pink 100 - 150 3090489
Grey 140 - 200 3092174
Red 25 - 55 3010315
Yellow 30 - 70 3010316
CB 50125/1
Black 60 - 110 3010317
Pink 100 - 150 3010318
27
Modulating Gas Burners RS 310 - 610/M MZ Series
SEAL CONTROL KIT To test the valve seals on the gas train, a special “seal control kit” is available.
The valve seal control device is compulsory (EN 676) on gas trains to burners with
a nominal output over 1200 kW.
The seal control is type VPS 504.
KIT CODE
GAS TRAIN
for 50 Hz operation
MB type 3010123
MCB - CB - DMV type 3010367
28
Specification
DESIGNATION OF SERIES
A specific index guides your choice of burner from the various models available in the RS/M MZ series. Below is
a clear and detailed specification description of the product.
Series: R
Size:
29
Modulating Gas Burners RS 310 - 610/M MZ Series
30
SPECIFICATION
STATE OF SUPPLY
Burner
Monoblock forced draught gas burner with modulating operation, fully automatic, made up of:
- High performance fan with low sound emissions, forward curve blades.
- Air suction circuit lined with sound-proofing material
- Air damper for air setting controlled by a high precision servomotor
- Air pressure switch
- Fan starting motor at 2900 rpm, three-phase 230/400 - 400/690 V with neutral, 50 Hz
- Combustion head, that can be set on the basis of required output, fitted with:
- stainless steel end cone, resistant to corrosion and high temperatures
- ignition electrodes; ionisation sensor for flame detection (or UV sensor on demand)
- flame stability disk
- Maximum gas pressure switch, with pressure test point, for halting the burner in the case of over pressure on
the fuel supply line
- Burner safety control box for controlling the system safety: RMG/M and LFL for FS1 intermittent operation and
LGK for FS2 continuous operation.
- Star/Delta starter for the fan motor (Direct starter fan motor for RS 310-410 models)
- Main electrical supply terminal board
- Burner on/off switch
- Manual or automatic output increase/decrease switch
- Contacts motor and thermal relay with release button
- Burner failure led signal and lighted release button
- Burner opening hinge
- Lifting rings
- IP 54 electric protection level
Standard equipment
- Gasket for gas train adaptor
- Adaptor for gas train
- M16x70 screws for fixing the gas train adaptor:
- Thermal insulation screen
- M18x60 screws to secure the burner flange to the boiler
- Cable grommets kit for optional electrical wiring input
- M16x6 studs for fixing the gas elbow to the pipe coupling
- M16 nuts to fix the gas elbow to the pipe coupling
- Instruction handbook for installation, use and maintenance
- Spare parts catalogue
Conforming to:
- 2014/30/EU directive (electromagnetic compatibility)
- 2014/35/EU directive (low voltage)
- 2016/426/EU (gas appliances regulation)
- 2006/42/EC directive (machine)
- EN 676 (gas burners)
31
Riello Burners a world of experience in every burner we sell.
04/2018
Across the world, Riello sets the standard in reliable and
TS0100UK02
high efficiency burner technology.
With burner capacity from 5 kW to 48 MW, Riello gas,
oil, dual fuel and Low NOx burners deliver unbeatable
performance across the full range of residential and
commercial heating applications, as well as in industrial
processes.
With headquarter in Legnago, Italy, Riello has been
manufacturing premium quality burners for over 90 year.
The manufacturing plant is equipped with the most
innovative systems of assembling lines and modern
manufacturing cells for a quick and flexible response to
the market.
[1]
Besides, the Riello Combustion Research Centre, located in
Angiari, Italy, represents one of the most modern facility
in Europe and one of the most advanced in the world for
the development of the combustion technology.
Today, the company’s presence on worldwide markets is
distinguished by a well-constructed and efficient sales
network, alongside many important Training Centres
located in various countries to meet its customers’ needs.
Riello has 13 operational branches abroad (in Europe,
America and Asia), with customers in over 60 countries.
[2]
Since the Company is constantly engaged in the production improvement, the aesthetic
and dimensional features, the technical data, the equipment and the accessories can be
changed. This document contains confidential and proprietary information of RIELLO S.p.A.
Unless authorised, this information shall not be divulged, nor duplicated in whole or in part.