Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Airtrol Tank Fittings: Air Control

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

SUBMITTAL

A-320C
JOB: REPRESENTATIVE:

UNIT TAG: ORDER NO. DATE:


ENGINEER: SUBMITTED BY: DATE:
CONTRACTOR: APPROVED BY: DATE:

Airtrol Tank Fittings


Air Control

TANK FITTINGS DESCRIPTION CONSTRUCTION


Airtrol Tank Fittings help establish the proper initial liquid Body: Cast Iron
level in the compression tank when filling the hydronic Tubes: Copper and Copper Plated
system. They help maintain proper system pressurization by Vent Tube Fitting: Brass
directing released air to the compression tank during system Ball Check: ATFL (only), Stainless Steel
operation and permit cooler liquid flow to the boiler during
the off cycle as system liquid cools. Airtrol Tank Fittings PERFORMANCE CHARACTERISTICS
must be used with the appropriately sized In-Line Airtrol or Max Working Pressure -
Rolairtrol air separator. All Tank Fittings: 175 psig (1206 kPa)
ATFL Drain-O-Tank Valve: 125 psig (862 kPa)
Max Operating Temperature -
All Fittings: 250°F (121°C)

SCHEDULE Tank Fittings


MODEL PART COMPRESSION TANK TAGGING
NUMBER NUMBER DIAMETER-INCHES (mm) INFORMATION QUANTITY

ATF-9 112008 9 (228.6)

12 (304.8), 13 (330.2),
ATF-12 112010
or 14 (355.6)
16 (406.4) to
ATF-16 112011
18 (457.2)
20 (508) to
ATF-20 112026 22 (558.8)

ATF-24 112013 24 (609.6)

100 gallons (378.5 liters)


ATFL 112014
or larger
Airtrol Tank Fittings A-320C
DIMENSIONS AND WEIGHTS - INCHES (mm)

Tank Fittings
CONNECTIONS (NPT) APPROX. SHIP.
WT. Each
MODEL NUMBER TANK BOILER LBS. (KG)

ATF-9 1/2" M 3/4" F 2-1/4


(1.0)
2-1/2
ATF-12 1/2" M 3/4" F
(1.1)
2-3/4
ATF-16 1/2" M 3/4" F
(1.2)

ATF-20 1/2" M 3/4" F 2-3/4


(1.2)
2-3/4
ATF-24 1/2" M 3/4" F
(1.2)
14
ATFL 1" F 1" F
(6.4)

TYPICAL SPECIFICATION - TANK FITTINGS


Furnish and install a compression tank fitting as shown on plans. It must contain an air separating trap and liquid control baffle
to assure unrestricted air flow to the tank and air-free liquid flow from the tank. It must include a manual vent for adjustment of
air volume in the tank. Cast iron ________psi (________kPa) working pressure.
All units shall be Bell & Gossett Model No. ________ Airtrol Tank Fitting.

Xylem Inc.
8200 N. Austin Avenue
Morton Grove, IL 60053
Phone: (847)966-3700
Fax: (847)965-8379
www.xyleminc.com/brands/bellgossett

Bell & Gossett is a trademark of Xylem Inc. or one of its subsidiaries.


© 2012 Xylem Inc.