E82ZBC

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Show/Hide Bookmarks

E82ZBC
00408683 Communication module
06/99 Keypad and accessories
These instructions
é include the most important technical data.
é describe the installation, the handling of the keypad and keypad accessories.
é is valid only
- for Keypad labelled E82ZBC or E82ZBB,
- for hand-held terminals labelled E82ZBH,
- for mounting kits (door) labelled E82ZBHT,
- for connection cables labelled E82ZWLxxx,
- together with the Operating Instructions of the corresponding controller.
Description
The keypad enables the communication with Lenze controllers via a keypad.
Scope of application
The keypad can be used with controllers as from the nameplate labelling:
é 8200 frequency inverters
- E82xxxxxxxBxxxXXVx1x
Required accessories
Connection cable (for hand-held terminal and door installation only)
Function
é Parameterization
é Control (e.g. inhibit and enable)
é Display operating data
é Enter setpoints
é Transfer parameter sets to other controllers
General data and operating conditions of the keypad
Insulation voltage to ground/PE 50 V AC
Enclosure IP55
Ambient temperature during operation: -10 ... + 60 •C
Transport: -25 ... + 70 •C
Storage: -25 ... + 60 •C
Climatic conditions Class 3K3 acc. to EN 50178 (without condensation,
medium relative humidity 85 %)
Dimensions (L x W x H) 75 mm x 62 mm x 23 mm

 - 1- MA8200KEY
Show/Hide Bookmarks

Installation

The 8200 motec maintains its degree of protection even if the connection
cable is inserted and the sealing plug is removed.
The keypad can be connected or disconnected and parameterized during
operation.
The rear side of the keypad is bolted to the hand-held terminal (remove
rubber coating).
Use the kit E82ZBHT (cut-out 45.3 x 45.3 mm) to mount the keypad e.g. to
a control cabinet panel.

8200 vector

8200vec020

With hand-held terminal


1. Plug keypad into the hand-held terminal and bolt (for E82ZBC only).
2. Connect hand-held terminal to the AIF interface using the connection cable.
Without hand-held terminal
1. Plug keypad to the AIF interface.
The keypad is ready when the mains voltage is applied.

8200 motec

8200mot031

1. Plug keypad into the hand-held terminal and bolt (for E82ZBC only).
2. Remove sealing plug at the heatsink of the motec.
3. Connect hand-held terminal to the AIF interface using the connection cable.
The keypad is ready when the mains voltage is applied.

 - 2- MA8200KEY
Show/Hide Bookmarks

Display / Functions
0 Function keys
1 Status displays
2 Bargraph display
3 Function bar 1
4 Function bar 2
5 Parameter set to be changed Modificati
on
6 Code number possible,

7
if
Subcode number display
8 Parameter value with unit
fl hi
flashing

0 Function keys
u Enable controller (X3/28 must be applied to HIGH level)
s Inhibit controller
t Change function bar 1↔ function bar 2
xw To the right/left in the active function bar
zy Incrase/decrease value. Scroll: Keep key pressed
v p
Save parameters if flashing. Confirmation by672 F in the display.
1 Status displays
d Ready
c Pulse inhibit (power outputs inhibited)
b Set current limit exceeded (C0022 (motor mode) or C0023 (generator mode))
e Warning active
a Fault active
2 Bargraph display
Value set under C0004 in %. (Default setting: unit load capacity C0056).
Display range: - 180 % ... + 180 % (each bar = 20 %)
3 Function bar 1
j Setpoint input viayz (Not possible with active password protection
(display = °MOE°)
g display function: Display memory unit 1 of the user menu (C0517/1)
(active after every and active parameter set
mains connection)
f 6
Select codes (display )
k Select subcodes (display )7
i Change parameter of a (sub)code (display )8
h Display values with more than five digits
H: High values (Display °+,°)
L: Low values (Display°MO° )
4 Function bar 2
m Parameter set 1 ... Select parameter set 4 for change
5
(Display e.g. PS  ( ). The parameter sets can only be activated using digital
signals (configuration using C007 or C0410).)
n Select controller on the system bus (CAN) (remote parameterization)
(The selected controller (1 ... 63) can be parameterized from the momentary
drive.
r = function active)
o Select menu. The user menu is active after everyy mains connection. If
necessary change to DMM. ( RF : Code list in the user
necessary, ser menu (C0517) DMM:
men (C0517).
codes G EJ: Specific codes only for the function
List of all codes. f nction mod
modules
les INTERBUS,
INTERBUS
PROFIBUS-DP and LECOM-B.)

 - 3- MA8200KEY
Show/Hide Bookmarks

User menu
After every mains switching, you have access to the user menu with the ten most
important drive parameters to commission a standard application with linear V/f
characteristic. For the complete code list please refer to the operating instructions of the

g
controller.
The first code of the user menu (C0517/1) is displayed after mains connection or using
.
C0050 Output frequency
-480.00 {Hz} 480.00

C0034 Setpoint input standard I/O (X3/8)


-0- 0 ... 5 V / 0 ... 10 V / 0 ... 20 mA
-1- 4 ... 20 mA
-2- -10 V ... + 10 V
-3- 4 ... 20 mA with protection against open circuit (TRIP Sd5, if I < 4 mA)
C0034 Setpoint input application I/O
C0034/1 (Subcode 1 of C0034) : X3/1U, X3/1I
C0034/2 (Subcode 2 of C0034) : X3/2U, X3/2I
-0- 0 ... 5 V / 0 ... 10 V
-1- -10 V ... + 10 V
-2- 0 ... 20 mA
-3- 4 ... 20 mA
-4- 4 ... 20 mA with protection against open circuit (TRIP Sd5 when I < 4 mA)
C0007 Configuration digital inputs
E4 E3 E2 E1
-0- CW/CCW DCB JOG2/3 JOG1/3
-1- CW/CCW PAR JOG2/3 JOG1/3
-2- CW/CCW QSP JOG2/3 JOG1/3
-3- CW/CCW PAR DCB JOG1/3
-4- CW/CCW QSP PAR JOG1/3
-5- CW/CCW DCB TRIP-Set JOG1/3
-6- CW/CCW PAR TRIP-Set JOG1/3
-7- CW/CCW PAR DCB TRIP-Set
-8- CW/CCW QSP PAR TRIP-Set
-9- CW/CCW QSP TRIP Set JOG1/3
-10- CW/CCW TRIP Set UP DOWN
-11- CW/CCW DCB UP DOWN
-12- CW/CCW PAR UP DOWN
-13- CW/CCW QSP UP DOWN
-14- CCW/QSP CW/QSP DCB JOG1/3
-15- CCW/QSP CW/QSP PAR JOG1/3
-16- CCW/QSP CW/QSP JOG2/3 JOG1/3
-17- ... -51- enhanced settings (see operating instructions)
é CW = clockwise rotation, CCW = counter-clockwise rotation, DCB = DC injection braking,
PAR = change-over (PAR1 Ø PAR2) PAR1 = LOW; PAR2 = HIGH (The corresponding terminal must
be assigned to the function ”PAR” in PAR1 and in PAR2)
é JOG1/3, JOG2/3 = selection of fixed setpoints (JOG1: JOG1/3 = HIGH, JOG2/3 = LOW, JOG2:
JOG1/3 = LOW, JOG2/3 = HIGH, JOG3: JOG1/3 = HIGH, JOG2/3 = HIGH)
é QSP = Quick stop, TRIP Set = external fault, UP/DOWN = motor pot functions

 - 4- MA8200KEY
Show/Hide Bookmarks

User menu
C0010 minimum output frequency Operation with Lenze geared
motors,
t setting
tti range 1 : 6
0 00
0.00 480 00
480.00
Å C0010: 14.5
14 5 Hz
C0011 maximum output frequency Å C0011: 87.0 Hz
7.50 { 50.00 Hz } 480.00
C0012 Acceleration time main setpoint Reference:Frequency
q y change
g
0 00
0.00 { 5.00
5 00 s } 1300 00
1300.00 0 Hz
H ... C0011

C0013 Deceleration time main setpoint Reference:Frequency


q y change
g
0 00
0.00 { 5.00
5 00 s } 1300 00
1300.00 C0011 ... 0 Hz
H

C0015 V/f rated frequency Setting


g is valid for all permitted
p
mains voltages
7 50
7.50 { 50.00
50 00 Hz } 960 00
960.00
C0016 Umin boost
0 00
0.00 { depending on the controller} 40 0
40.0
C0002 see chapter ’Parameter set transfer’

Change entries in the user menu


Action
1. Change
g to the t
Key

wx
Result

o
Note
Change to function bar 2

yz
men ”ALL”
menu
2.
3.
4.
5. Select user
t
xz
DMM

å
f
Select menu ”ALL” (list of all codes)
Confirm selection, change to function bar 1

wx k
men
menu
6.  Code for user menu
7. Select memory Code saved under C0517/1 is displayed

zx
unit 
(default setting: output frequency C0050)
8.
9.
10.
Change
g entryy
yz i
  

;;;;;
Select subcode

Enter code number


The sytem does not check whether the code
number exists!

11. v 672 F
°° must be entered to delete the entry.

Confirm entry and restart


”loop” at step 7. to change other memory units

 - 5- MA8200KEY
Show/Hide Bookmarks

Edit parameters
Change and save parameters
The user menu is active after every mains switching.
Change to the menu DMM to call all codes.
If you should make a mistake during parameterization, load the default setting under
C0002 and start again.
Action
1. Plug in key-
pad
Key
g Result Note
The function g is active. The first code in the user
menu is displayed (C0517/1, default setting:

t
VVVV Hz
C0050 = output frequency).
2.
3.
If necessary,
y,
change to the
menu ”ALL”
ALL wx
yz o
 Change to function bar 2

4.
5.
6. Inhibit con-
t
s ådc
DMM Select menu ”ALL” (list of all codes)
Confirm selection and change to function bar 1
Necessary only, if you change C0002, C0148, C0174

7.
troller
Set parame-
p wx
yz f and/or C0469

x k i
ters
8. ;;;; Select code
9. For codes without subcodes: automatic jump to

10.
11.
yz
xyz i


;;; Select subcode

12.
13. v
w
;;;;;

672 F
Set parameters
Confirm entry, if
Confirm entry, if
pp is flashing
is not flashing; v is inactive
Change parameter set (PS)
You can use the keypad only to change over the parameter set, to modify parameters. To

g
activate a parameter set (PS) for operation, you must use digital signals (configuration
under C0410 or C0007)!
The function displays the currently active PS.
Action
1. Select t
Key

wx m

Result Note
Change to function bar 2

yz
f nction
function
2.


3. Select PS    Select PS to be changed
4. Confirm selection and change to function bar 1
5. Set Proceed as described in the table above
parameters

 - 6- MA8200KEY
Show/Hide Bookmarks

Parameter set transfer


The PS transfer also changes password-protected codes. For notes about password
protection please refer to the operating instructions of the controller.

Code C0002 PS transfer


-0- Function performed
PS of the controller
-1- ... -4- Default settingÕ PAR1 ... 4 Overwrite selected PS of the controller with
the default setting
-10- Keypad Õ PAR1 / 2 / 3 / 4 Overwrite all PS of the controller with the
keypad data
-11- ... -14- Keypad Õ PAR1 ... 4 Overwrite individual PS of the controller
with the keypad data
-20- PAR1 / 2 / 3 / 4 Õ Keypad Copy all PS of the controller to the keypad
PS of a function module on FIF(not for standard I/O or syste mbus (CAN))
-31- ... -34- Default settingÕ FPAR1 ... 4 Overwrite selected PS of the function with
the default setting
-40- Keypad Õ FPAR1 / 2 / 3 / 4 Overwrite all PS of the function module with
the keypad data
-41- ...-44- Keypad Õ FPAR1 ... 4 Overwrite individual PS of the function
module with the keypad data
-50- FPAR1 / 2 / 3 / 4 Õ Keypad Copy all PS of the function module to the
keypad
PS controller + function module on FIF (not for standard I/O or systembus (CAN))
Operation with application I/O: Always transfer PS of the controller and application I/O jointly!
-61- ... -64- Default settingÕ Overwrite individual PS with the default
PAR1 ... 4 + FPAR1 ... 4 setting
-70- Keypad Õ Overwrite all PS with the keypad data
PAR1 / 2 / 3 / 4 + FPAR1 / 2 / 3 / 4
-71- ... -74- Keypad Õ Overwrite individual PS with the keypad
PAR1 ...4 + FPAR1 ... 4 data
-80- PAR1 / 2 / 3 / 4 + FPAR1 / 2 / 3 / 4 Copy all PS to the keypad
Õ Keypad

Pl g in keypad and inhibit controller with


Plug s
Please carry out the following steps prior to every PS modification:
or via terminal (X3/28 = LOW)
Load default setting
é Set selection code under C0002, confirm with v
Transfer PS from controller to keypad
1.
2.
Set 20 or 50 or 80 under C0002, confirm with
If RD
v
F is not longer illuminated, all PS are transferred to the keypad.
TransferPS from keypad to controller
1.
2.
Set selection code under C0002, confirm with v
If MOD is no longer illuminated, the PS are transferred to the controller

 - 7- MA8200KEY