GIS Test: 7UT612

Before start switch the switch to TEST

[DIFFRENTIAL RELAY TEST ]


The devices 7UT613/63x contain a series of protective and additional functions. The scope of hardware
and firmware is matched to these functions. Additionally, the control functions can be in accordance
with the system requirements.
D01A+R1
DISCRIPTION 7UT612 DIFFRENTIAL CABLE=STG
1. General Information
Designation No. F301-DIFF Rated Current 1A
Manufacture SIEMENS Rated Freq. 50-60 Hz
Type No. 7UT612 5DB92-4HN4 Aux. Voltage 48-250 VDC

2. Mechanical check and visual inspection


Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A

3. Elctrical Tests
1. Function Test
Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A

SIDE 1: CTR 2000/1A SIDE 2: CTR 1000/1A

4. Metering Check
SIDE 1 SIDE 2
Phase
Inject Observed Inject Observed
A 200 mA 200 A 500 mA 500 A
B 200 mA 200 A 500 mA 500 A
C 200 mA 200 A 500 mA 500 A

5. DIFF Check

SIDE 1
Phase
mA mSec
A 300 33
B 300 33
C 300 33

SIDE 2
Phase
mA mSec
A 600 29.5
B 600 46
C 600 29.5
D02B+R1
DISCRIPTION 7UT612 DIFFRENTIAL CABLE=CTG1B
1. General Information

Designation No. F301-DIFF Rated Current 1A


Manufacture SIEMENS Rated Freq. 50-60 Hz
Type No. 7UT612 5DB92-4HN4 Aux. Voltage 48-250 VDC

2. Mechanical check and visual inspection

Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A

3. Elctrical Tests

1. Function Test

Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A

SIDE 1: CTR 2000/1A SIDE 2: CTR 1000/1A

4. Metering Check

SIDE 1 SIDE 2
Phase
Inject Observed Inject Observed
A 200 mA 200 A 500 mA 500 A
B 200 mA 200 A 500 mA 500 A
C 200 mA 200 A 500 mA 500 A

5. DIFF Check

SIDE 1
Phase
Pick-Up mSec Drop-Out
A 305 mA 15 210 mA
B 305 mA 17 210 mA
C 305 mA 15 210 mA
SIDE 2
Phase
Pick-Up mSec Drop-Out
A 605 mA 23 420 mA
B 605 mA 19 415 mA
C 605 mA 15 415 mA
D03A+R1
DISCRIPTION 7UT612 DIFFRENTIAL CABLE=CTG1A
1. General Information

Designation No. F301-DIFF Rated Current 1A


Manufacture SIEMENS Rated Freq. 50-60 Hz
Type No. 7UT612 5DB92-4HN4 Aux. Voltage 48-250 VDC

2. Mechanical check and visual inspection

Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A

3. Elctrical Tests

1. Function Test

Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A

SIDE 1: CTR 2000/1A SIDE 2: CTR 1000/1A

4. Metering Check

SIDE 1 SIDE 2
Phase
Inject Observed Inject Observed
A 200 mA 200 A 500 mA 500 A
B 200 mA 200 A 500 mA 500 A
C 200 mA 200 A 500 mA 500 A

5. DIFF Check

SIDE 1
Phase
Pick-Up mSec Drop-Out
A 300 mA 33 210 mA
B 300 mA 33 210 mA
C 300 mA 33 210 mA
SIDE 2
Phase
Pick-Up mSec Drop-Out
A 600 mA 29.5 390 mA
B 600 mA 46 390 mA
C 600 mA 29.5 410 mA

6. Over Current

Phase Pick-Up Sec Drop-Out


A 500 mA 3.179 467 mA
B 500 mA 3.05 465 mA
C 500 mA 3.05 470 mA

7. Earth Fault

Phase Pick-Up Sec Drop-Out


A-B-C 70 mA 3.045 50 mA
2016
Middle Delta Electricity Production Company
MDEPC

GIS Test: 7VK610

Before start switch the switch to TEST

[BREAKER FAILURE RELAY TEST]


The 7VK61 relay contains a series of protective and additional functions. The hardware and firmware
provided is designed for this scope of functions. In addition, the command functions can be matched to
the system conditions
D01A+R1
DISCRIPTION 7VK610 BREAKER FAILURE STG
1. General Information
Designation No. F303-SYNCHROCHECK Rated Current 1A
Manufacture SIEMENS Rated Freq. 50-60 Hz
Type No. 7VK61015AB924YC0 Aux. Voltage 48-250 VDC

2. Mechanical check and visual inspection


Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A

3. Elctrical Tests
1. Function Test
Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A

VTR LINE: 220/√3 kV /100/√3 V VTR BUS: 220/√3 kV /100/√3 V

2. Metering Check
Inject Observed
A 1A 2000 A
B 1A 2000 A
C 1A 2000 A

3. BREKER FAILURE PICK UP AND TIMING CHECK STAGE 1

PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A 100 105 120 124 82
B 100 105 120 129 84
C 100 105 120 146 85
A-B-C 100 105 120 125 85
4. BREKER FAILURE PICK UP AND TIMING CHECK STAGE 2

PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A 100 105 240 255 82
B 100 105 240 270 84
C 100 105 240 261 85
A-B-C 100 105 240 260 85
D01B+R1
DISCRIPTION 7VK610 BREAKER FAILURE STG
1. General Information
Designation No. F303-SYNCHROCHECK Rated Current 1A
Manufacture SIEMENS Rated Freq. 50-60 Hz
Type No. 7VK61015AB924YC0 Aux. Voltage 48-250 VDC

2. Mechanical check and visual inspection

Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A

3. Elctrical Tests

1. Function Test

Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A

VTR LINE: 220/√3 kV /100/√3 V VTR BUS: 220/√3 kV /100/√3 V

2. Metering Check

Inject Observed
A 1A 2000 A
B 1A 2000 A
C 1A 2000 A

3. BREKER FAILURE PICK UP AND TIMING CHECK STAGE 1

PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A 100 100 120 140 70
B 100 110 120 124 70
C 100 110 120 127 70
A-B-C 100 110 120 133 70
4. BREKER FAILURE PICK UP AND TIMING CHECK STAGE 2

PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A 100 105 240 284 70
B 100 105 240 227 70
C 100 105 240 269 70
A-B-C 100 105 240 257 70

5. I-STUB

PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A-B-C 1000 1060 200 224.8 100
D02B+R1
DISCRIPTION 7VK610 BREAKER FAILURE CTG1B
1. General Information

Designation No. F303-SYNCHROCHECK Rated Current 1A


Manufacture SIEMENS Rated Freq. 50-60 Hz
Type No. 7VK61015AB924YC0 Aux. Voltage 48-250 VDC

2. Mechanical check and visual inspection

Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A

3. Elctrical Tests

1. Function Test

Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A

VTR LINE: 220/√3 kV /100/√3 V VTR BUS: 220/√3 kV /100/√3 V

2. Metering Check

Inject Observed
A 1A 2000 A
B 1A 2000 A
C 1A 2000 A

3. BREKER FAILURE PICK UP AND TIMING CHECK STAGE 1

PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A 100 100 120 149.8 85
B 100 105 120 137 85
C 100 100 120 138 85
4. BREKER FAILURE PICK UP AND TIMING CHECK STAGE 2

PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A 100 100 240 289 85
B 100 105 240 277 85
C 100 100 240 278.8 85

5. CIRCUIT BREAKER DEFFECT

PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A-B-C 100 150 133.2 153.5 100

5. I-STUB

PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A-B-C 1000 1000 200 226.9
D03B+R1
DISCRIPTION 7VK610 BREAKER FAILURE CTG1A
1. General Information

Designation No. F303-SYNCHROCHECK Rated Current 1A


Manufacture SIEMENS Rated Freq. 50-60 Hz
Type No. 7VK61015AB924YC0 Aux. Voltage 48-250 VDC

2. Mechanical check and visual inspection

Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A

3. Elctrical Tests

1. Function Test

Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A

VTR LINE: 220/√3 kV /100/√3 V VTR BUS: 220/√3 kV /100/√3 V

2. Metering Check

Inject Observed
A 1A 2000 A
B 1A 2000 A
C 1A 2000 A

3. BREKER FAILURE PICK UP AND TIMING CHECK STAGE 1

PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A 100 105 120 121 80
B 100 105 120 128 85
C 100 105 120 128 70
A-B-C 100 102 120 132 85

4. BREKER FAILURE PICK UP AND TIMING CHECK STAGE 2

PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A 100 105 240 272 70
B 100 105 240 262 70
C 100 105 240 268 70
A-B-C 100 102 240 272 70

5. I-STUB

PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A 1000 1000 200 240
B 1000 1100 200 238
C 1000 1000 200 241
A-B-C 1000 1000 200 246

6. CIRCUIT BREAKER DEFFECT

PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A-B-C 100 100 122 142
2016
Middle Delta Electricity Production Company
MDEPC

GIS Test: 7VK611

Before start switch the switch to TEST

[SYNCHROCHECK RELAY TEST]


The 7VK61 relay contains a series of protective and additional functions. The hardware and firmware
provided is designed for this scope of functions. In addition, the command functions can be matched to
the system conditions
D01A+R1
DISCRIPTION 7VK611 SYNCHROCHECK STG
1. General Information
Designation No. F306-SYNCHROCHECK Rated Current 1A
Manufacture SIEMENS Rated Freq. 50-60 Hz
Type No. 7VK61115AB924YN0 Aux. Voltage 48-250 VDC

2. Mechanical check and visual inspection


Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A

3. Elctrical Tests
1. Function Test
Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A

VTR LINE: 220/√3 kV /100/√3 V VTR BUS: 220/√3 kV /100/√3 V

2. Metering Check
Inject Observed
V (LINE) 100 V 220 kV
V (BUS) 100 V 220 kV

2. VOLTAGE DIFFERENCE CHECK with (constant FREQUENCY & ANGLE)

ΔV LINE BUS COMMAND


6 100 94 ok
6 94 100 ok

3. ANGLE DIFFERENCE CHECK with (constant FREQUENCY &VOLTAGE)

Δɸ LINE BUS COMMAND


11˚ 0 11˚ ok
11˚ 11˚ 0 ok

4. FREQUENCY DIFFERENCE CHECK with (constant ANGLE &VOLTAGE)

Δf LINE BUS COMMAND


0.2 50.2 50 ok
0.2 50 50.2 ok
0.2 50 49.8 ok
0.2 49.8 50 ok
D01B+R1
DISCRIPTION 7VK611 SYNCHROCHECK + A.R. KALYOUBIYA 1

1. General Information
Designation No. F306-SYNCHROCHECK Rated Current 1A
Manufacture SIEMENS Rated Freq. 50-60 Hz
Type No. 7VK61115AB924YN0 Aux. Voltage 48-250 VDC

2. Mechanical check and visual inspection

Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A

3. Elctrical Tests

1. Function Test

Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A

VTR LINE: 220/√3 kV /100/√3 V VTR BUS: 220/√3 kV /100/√3 V

2. Metering Check

Inject Observed
V (LINE) 100 V 220 kV
V (BUS) 100 V 220 kV

3. VOLTAGE DIFFERENCE CHECK with (constant FREQUENCY & ANGLE)

ΔV LINE BUS COMMAND


6 100 94 ok
6 94 100 ok
L-D 100 5 ok
D-L 5 100 ok
D-D 5 5 ok

4. ANGLE DIFFERENCE CHECK with (constant FREQUENCY &VOLTAGE)


Δɸ LINE BUS COMMAND
11˚ 0 11˚ ok
11˚ 11˚ 0 ok

5. FREQUENCY DIFFERENCE CHECK with (constant ANGLE &VOLTAGE)

Δf LINE BUS COMMAND


0.2 50.2 50 ok
0.2 50 50.2 ok
0.2 50 49.8 ok
0.2 49.8 50 ok
D02A+R1
DISCRIPTION 7VK611 SYNCHROCHECK KALIOUBIYA 2

1. General Information

Designation No. F306-SYNCHROCHECK Rated Current 1A


Manufacture SIEMENS Rated Freq. 50-60 Hz
Type No. 7VK61115AB924YN0 Aux. Voltage 48-250 VDC

2. Mechanical check and visual inspection

Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A

3. Elctrical Tests

1. Function Test

Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A

VTR LINE: 220/√3 kV /100/√3 V VTR BUS: 220/√3 kV /100/√3 V

2. Metering Check

Inject Observed
V (LINE) 100 V 220 kV
V (BUS) 100 V 220 kV

3. VOLTAGE DIFFERENCE CHECK with (constant FREQUENCY & ANGLE)

ΔV LINE BUS COMMAND


6 100 94 ok
6 94 100 ok
2 110 ↓ 108 ok
4 91 ↑ 95 ok
L-D 5 91 ok
D-D 5 5 ok
4. ANGLE DIFFERENCE CHECK with (constant FREQUENCY &VOLTAGE)

Δɸ LINE BUS COMMAND


11˚ 0 11˚ ok

5. FREQUENCY DIFFERENCE CHECK with (constant ANGLE &VOLTAGE)

Δf LINE BUS COMMAND


0.2 50.2 50 ok
0.2 50 49.8 ok
D02B+R1
DISCRIPTION 7VK611 SYNCHROCHECK CTG1B

1. General Information

Designation No. F306-SYNCHROCHECK Rated Current 1A


Manufacture SIEMENS Rated Freq. 50-60 Hz
Type No. 7VK61115AB924YN0 Aux. Voltage 48-250 VDC

2. Mechanical check and visual inspection

Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A

3. Elctrical Tests

1. Function Test

Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A

VTR LINE: 220/√3 kV /100/√3 V VTR BUS: 220/√3 kV /100/√3 V

2. Metering Check

Inject Observed
V (LINE) 100 V 220 kV
V (BUS) 100 V 220 kV

3. VOLTAGE DIFFERENCE CHECK with (constant FREQUENCY & ANGLE)

ΔV LINE BUS COMMAND


6 100 94 ok
6 94 100 ok
2 110 ↓ 108 ok
2 108 110 ↓ ok
1 92 91 ↑ ok
1 91 ↑ 92 ok
L-D 100 5 ok
D-L 5 100 ok
D-D 5 5 ok

4. ANGLE DIFFERENCE CHECK with (constant FREQUENCY &VOLTAGE)

Δɸ LINE BUS COMMAND


11˚ 0 11˚ ok
11˚ 11˚ 0 ok

5. FREQUENCY DIFFERENCE CHECK with (constant ANGLE &VOLTAGE)

Δf LINE BUS COMMAND


0.2 50.2 50 ok
0.2 50 50.2 ok
0.2 50 49.8 ok
0.2 49.8 50 ok
D03A+R1
DISCRIPTION 7VK611 SYNCHROCHECK CTG1A

1. General Information

Designation No. F306-SYNCHROCHECK Rated Current 1A


Manufacture SIEMENS Rated Freq. 50-60 Hz
Type No. 7VK61115AB924YN0 Aux. Voltage 48-250 VDC

2. Mechanical check and visual inspection

Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A

3. Elctrical Tests

1. Function Test

Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A

VTR LINE: 220/√3 kV /100/√3 V VTR BUS: 220/√3 kV /100/√3 V

2. Metering Check

Inject Observed
V (LINE) 100 V 220 kV
V (BUS) 100 V 220 kV

3. VOLTAGE DIFFERENCE CHECK with (constant FREQUENCY & ANGLE)

ΔV LINE BUS COMMAND


6 100 94 ok
6 94 100 ok
L-D 100 5 ok
D-L 5 100 ok
D-D 5 5 ok
4. ANGLE DIFFERENCE CHECK with (constant FREQUENCY &VOLTAGE)

Δɸ LINE BUS COMMAND


11˚ 0 11˚ ok
11˚ 11˚ 0 ok

5. FREQUENCY DIFFERENCE CHECK with (constant ANGLE &VOLTAGE)

Δf LINE BUS COMMAND


0.2 50.2 50 ok
0.2 50 50.2 ok
0.2 50 49.8 ok
0.2 49.8 50 ok
D03B+R1
DISCRIPTION 7VK611 SYNCHROCHECK QUESNA 2

1. General Information

Designation No. F306-SYNCHROCHECK Rated Current 1A


Manufacture SIEMENS Rated Freq. 50-60 Hz
Type No. 7VK61115AB924YN0 Aux. Voltage 48-250 VDC

2. Mechanical check and visual inspection

Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A

3. Elctrical Tests

1. Function Test

Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A

VTR LINE: 220/√3 kV /100/√3 V VTR BUS: 220/√3 kV /100/√3 V

2. Metering Check

Inject Observed
V (LINE) 100 V 220 kV
V (BUS) 100 V 220 kV

3. VOLTAGE DIFFERENCE CHECK with (constant FREQUENCY & ANGLE)

ΔV LINE BUS COMMAND


6 100 94 ok
6 94 100 ok
2 90 92
2 110 ↓ 108
D-L 5 91 ok
D-D 5 5 ok
4. ANGLE DIFFERENCE CHECK with (constant FREQUENCY &VOLTAGE)

Δɸ LINE BUS COMMAND


11˚ 0 11˚ ok
11˚ 11˚ 0 ok

5. FREQUENCY DIFFERENCE CHECK with (constant ANGLE &VOLTAGE)

Δf LINE BUS COMMAND


0.15 50.15 50 ok
0.1 49.9 50 ok
D01B+R2
DISCRIPTION 7VK611 SYNCHROCHECK + A.R. KALYOUBIYA 1

1. General Information

Designation No. F306-SYNCHROCHECK Rated Current 1A


Manufacture SIEMENS Rated Freq. 50-60 Hz
Type No. 7VK61115AB924YN0 Aux. Voltage 48-250 VDC

2. Mechanical check and visual inspection

Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A

3. Elctrical Tests

1. Function Test

Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A

VTR LINE: 220/√3 kV /100/√3 V VTR BUS: 220/√3 kV /100/√3 V

2. Metering Check

Inject Observed
V (LINE) 100 V 220 kV
V (BUS) 100 V 220 kV

3. VOLTAGE DIFFERENCE CHECK with (constant FREQUENCY & ANGLE)

ΔV LINE BUS COMMAND


6 100 94 ok
6 94 100 ok
L-D 100 5 ok
D-L 5 100 ok
D-D 5 5 ok
4. ANGLE DIFFERENCE CHECK with (constant FREQUENCY &VOLTAGE)

Δɸ LINE BUS COMMAND


11˚ 0 11˚ ok
11˚ 11˚ 0 ok

5. FREQUENCY DIFFERENCE CHECK with (constant ANGLE &VOLTAGE)

Δf LINE BUS COMMAND


0.2 50.2 50 ok
0.2 50 50.2 ok
0.2 50 49.8 ok
0.2 49.8 50 ok