Relays Relays
Relays Relays
Relays Relays
3. Elctrical Tests
1. Function Test
Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A
4. Metering Check
SIDE 1 SIDE 2
Phase
Inject Observed Inject Observed
A 200 mA 200 A 500 mA 500 A
B 200 mA 200 A 500 mA 500 A
C 200 mA 200 A 500 mA 500 A
5. DIFF Check
SIDE 1
Phase
mA mSec
A 300 33
B 300 33
C 300 33
SIDE 2
Phase
mA mSec
A 600 29.5
B 600 46
C 600 29.5
D02B+R1
DISCRIPTION 7UT612 DIFFRENTIAL CABLE=CTG1B
1. General Information
Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A
3. Elctrical Tests
1. Function Test
Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A
4. Metering Check
SIDE 1 SIDE 2
Phase
Inject Observed Inject Observed
A 200 mA 200 A 500 mA 500 A
B 200 mA 200 A 500 mA 500 A
C 200 mA 200 A 500 mA 500 A
5. DIFF Check
SIDE 1
Phase
Pick-Up mSec Drop-Out
A 305 mA 15 210 mA
B 305 mA 17 210 mA
C 305 mA 15 210 mA
SIDE 2
Phase
Pick-Up mSec Drop-Out
A 605 mA 23 420 mA
B 605 mA 19 415 mA
C 605 mA 15 415 mA
D03A+R1
DISCRIPTION 7UT612 DIFFRENTIAL CABLE=CTG1A
1. General Information
Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A
3. Elctrical Tests
1. Function Test
Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A
4. Metering Check
SIDE 1 SIDE 2
Phase
Inject Observed Inject Observed
A 200 mA 200 A 500 mA 500 A
B 200 mA 200 A 500 mA 500 A
C 200 mA 200 A 500 mA 500 A
5. DIFF Check
SIDE 1
Phase
Pick-Up mSec Drop-Out
A 300 mA 33 210 mA
B 300 mA 33 210 mA
C 300 mA 33 210 mA
SIDE 2
Phase
Pick-Up mSec Drop-Out
A 600 mA 29.5 390 mA
B 600 mA 46 390 mA
C 600 mA 29.5 410 mA
6. Over Current
7. Earth Fault
3. Elctrical Tests
1. Function Test
Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A
2. Metering Check
Inject Observed
A 1A 2000 A
B 1A 2000 A
C 1A 2000 A
PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A 100 105 120 124 82
B 100 105 120 129 84
C 100 105 120 146 85
A-B-C 100 105 120 125 85
4. BREKER FAILURE PICK UP AND TIMING CHECK STAGE 2
PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A 100 105 240 255 82
B 100 105 240 270 84
C 100 105 240 261 85
A-B-C 100 105 240 260 85
D01B+R1
DISCRIPTION 7VK610 BREAKER FAILURE STG
1. General Information
Designation No. F303-SYNCHROCHECK Rated Current 1A
Manufacture SIEMENS Rated Freq. 50-60 Hz
Type No. 7VK61015AB924YC0 Aux. Voltage 48-250 VDC
Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A
3. Elctrical Tests
1. Function Test
Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A
2. Metering Check
Inject Observed
A 1A 2000 A
B 1A 2000 A
C 1A 2000 A
PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A 100 100 120 140 70
B 100 110 120 124 70
C 100 110 120 127 70
A-B-C 100 110 120 133 70
4. BREKER FAILURE PICK UP AND TIMING CHECK STAGE 2
PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A 100 105 240 284 70
B 100 105 240 227 70
C 100 105 240 269 70
A-B-C 100 105 240 257 70
5. I-STUB
PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A-B-C 1000 1060 200 224.8 100
D02B+R1
DISCRIPTION 7VK610 BREAKER FAILURE CTG1B
1. General Information
Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A
3. Elctrical Tests
1. Function Test
Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A
2. Metering Check
Inject Observed
A 1A 2000 A
B 1A 2000 A
C 1A 2000 A
PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A 100 100 120 149.8 85
B 100 105 120 137 85
C 100 100 120 138 85
4. BREKER FAILURE PICK UP AND TIMING CHECK STAGE 2
PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A 100 100 240 289 85
B 100 105 240 277 85
C 100 100 240 278.8 85
PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A-B-C 100 150 133.2 153.5 100
5. I-STUB
PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A-B-C 1000 1000 200 226.9
D03B+R1
DISCRIPTION 7VK610 BREAKER FAILURE CTG1A
1. General Information
Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A
3. Elctrical Tests
1. Function Test
Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A
2. Metering Check
Inject Observed
A 1A 2000 A
B 1A 2000 A
C 1A 2000 A
PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A 100 105 120 121 80
B 100 105 120 128 85
C 100 105 120 128 70
A-B-C 100 102 120 132 85
PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A 100 105 240 272 70
B 100 105 240 262 70
C 100 105 240 268 70
A-B-C 100 102 240 272 70
5. I-STUB
PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A 1000 1000 200 240
B 1000 1100 200 238
C 1000 1000 200 241
A-B-C 1000 1000 200 246
PICK UP TIMEING
DROP OUT
PHASE SETTING MEASURED SETTING MEASURED
mA mSec mA
A-B-C 100 100 122 142
2016
Middle Delta Electricity Production Company
MDEPC
3. Elctrical Tests
1. Function Test
Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A
2. Metering Check
Inject Observed
V (LINE) 100 V 220 kV
V (BUS) 100 V 220 kV
1. General Information
Designation No. F306-SYNCHROCHECK Rated Current 1A
Manufacture SIEMENS Rated Freq. 50-60 Hz
Type No. 7VK61115AB924YN0 Aux. Voltage 48-250 VDC
Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A
3. Elctrical Tests
1. Function Test
Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A
2. Metering Check
Inject Observed
V (LINE) 100 V 220 kV
V (BUS) 100 V 220 kV
1. General Information
Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A
3. Elctrical Tests
1. Function Test
Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A
2. Metering Check
Inject Observed
V (LINE) 100 V 220 kV
V (BUS) 100 V 220 kV
1. General Information
Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A
3. Elctrical Tests
1. Function Test
Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A
2. Metering Check
Inject Observed
V (LINE) 100 V 220 kV
V (BUS) 100 V 220 kV
1. General Information
Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A
3. Elctrical Tests
1. Function Test
Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A
2. Metering Check
Inject Observed
V (LINE) 100 V 220 kV
V (BUS) 100 V 220 kV
1. General Information
Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A
3. Elctrical Tests
1. Function Test
Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A
2. Metering Check
Inject Observed
V (LINE) 100 V 220 kV
V (BUS) 100 V 220 kV
1. General Information
Item Description
1 Inspect for physical damage/defects □ Yes □ N/A
2 Verify connections as per approved drawing □ Yes □ N/A
3 Check tightness of all connections □ Yes □ N/A
3. Elctrical Tests
1. Function Test
Item Description
1 LEDs indication checked □ Yes □ N/A
2 Alarm contacts checked □ Yes □ N/A
3 Trip Contacts checked □ Yes □ N/A
4 Reset of indications checked □ Yes □ N/A
5 Binary input checked □ Yes □ N/A
2. Metering Check
Inject Observed
V (LINE) 100 V 220 kV
V (BUS) 100 V 220 kV