Test Certificate of 11/0.433 KV Switch Gear Client:: Hindustan Coca Cola Beverages Pvt. Ltd. Goblej

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

TEST CERTIFICATE OF 11/0.

433 KV
SWITCH GEAR

Client:
HINDUSTAN COCA COLA BEVERAGES PVT. LTD.
GOBLEJ

Plant
UPS AREA
UPS INPUT PANEL

Tested by:

DWARKESH ELECTRICKAL
GF-6 , Pramukhswami Tower NR:Bhailal Hall,
Gorwa, Vadodara - 390016
Contacts :+91-99980-45674 / +91 97144-72376
E-mail : info@dwarkeshelec.in

Year of Testing:
FEBRUARY – 2020
TEST REPORT OF AIR CIRCUIT BREAKER For DWARKESH ELECTRICKAL
Client HINUSTAN COCA COLA BEVERAGES PVT. LTD – GOBLEJ Tested by JNA
Plant UPS AREA Tested on 06/02/2020
Location P-1 / INCOMER - 1 (2500A) – 415 V UPS I/P PANEL

1.0 Name Plate details of Circuit Breaker:


1.1 Serial No. : MS758255U
1.2 Make : L&T
1.3 Type : UW2-25N
1.4 Rated voltage :440 V
1.5 Rated current : 2500 A
1.6 Short Time Current :65 kA / 3 Sec

2.0 Insulation Resistance test :


Insulation Resistance test, Close condition Open condition
applied 5kV RY YB BR RE YE BE RR` YY` BB`
Values in Ω >1G >1G >1G >1G >1G >1G >1G >1G >1G
RN YN BN NE NN’
>1G >1G >1G >1G >1G

3.0 Contact Resistance measurement :


Contact Resistance of R – Phase Y – Phase B – Phase N - Phase
Value in μΩ 22.8 20.7 21.8 20.9

4.0 Control circuit and operational checks :


Sr. No. Description Remarks
4.1 Manual charging of spring OK
4.2 Mechanical closing and tripping OK
4.3 Mechanical interlocks of breaker OK
4.4 Tripping through release OK
4.5 Breaker close command blocking when Release is in operated condition OK
4.6 Abnormality, if any NONE

5.0 Remarks : TESTED AS ABOVE FIT FOR COMISSIONING


TEST CERTIFICATE OF CURRENT TRANSFORMER For DWARKESH ELECTRICKAL
Client HINUSTAN COCA COLA BEVERAGES PVT. LTD – GOBLEJ Tested by JNA
Plant UPS AREA Tested on 06/02/2020
Location P-1 / INCOMER - 1 (2500A) – 415 V UPS I/P PANEL

1.0 Name Plate details of current transformer :


Make of CT: Advance Engineering Works (P) Ltd.
Phase Ratio, Amps Serial No. Metering core VA Acc. class of Metering core
R 2500 / 5 AP1219/12811 15 1.0
Y 2500 / 5 AP1219/12813 15 1.0
B 2500 / 5 AP1219/12812 15 1.0

2.0 Insulation Resistance test :


IR test between R Y B
P-E (With 500 V) >1G >1G >1G
P-Sec 1 (With 500V) >1G >1G >1G
Sec 1-E (With 500V) >1G >1G >1G

3.0 Ratio, polarity and circuit checks :


3.1 Metering core:
Injected primary Measured secondary Winding
Phase Ratio Polarity
current, Amps current, Amps Resistance (Ω)
R 500 / 1000 / 1250 1.021 / 2.028 / 2.518 OK OK 1.2
Y 500 / 1000 / 1250 1.018 / 2.019 / 2.517 OK OK 1.1
B 500 / 1000 / 1250 1.014 / 2.017 / 2.516 OK OK 1.2

4.0 General check-up :


Sr. No. Description Remarks
4.1 Inspection for physical damage OK
4.2 Continuity check for ammeter circuits OK

5.0 Remarks : TESTED AS ABOVE FIT FOR COMISSIONING


TEST REPORT OF AIR CIRCUIT BREAKER For DWARKESH ELECTRICKAL
Client HINUSTAN COCA COLA BEVERAGES PVT. LTD – GOBLEJ Tested by JNA
Plant UPS AREA Tested on 06/02/2020
Location P-2A / TO UPS DISTRIBUTION PANEL (BY PASS - 2500A) – 415 V UPS I/P PANEL

1.0 Name Plate details of Circuit Breaker:


1.1 Serial No. : MS758270U
1.2 Make : L&T
1.3 Type : UW2-25N
1.4 Rated voltage :440 V
1.5 Rated current : 2500 A
1.6 Short Time Current :65 kA / 3 Sec

2.0 Insulation Resistance test :


Insulation Resistance test, Close condition Open condition
applied 5kV RY YB BR RE YE BE RR` YY` BB`
Values in Ω >1G >1G >1G >1G >1G >1G >1G >1G >1G
RN YN BN NE NN’
>1G >1G >1G >1G >1G

3.0 Contact Resistance measurement :


Contact Resistance of R – Phase Y – Phase B – Phase N - Phase
Value in μΩ 21.9 21.6 20.8 21.3

4.0 Coil Resistance Test :


Coil designation Resistance Value In Ω
Under Voltage Coil 0.641 KΩ

5.0 Control circuit and operational checks :


Sr. No. Description Remarks
5.1 Manual charging of spring OK
5.2 Mechanical closing and tripping OK
5.3 Mechanical interlocks of breaker OK
5.4 Tripping through release OK
5.5 Breaker close command blocking when Release is in operated condition OK
5.6 Abnormality, if any NONE

6.0 Remarks : TESTED AS ABOVE FIT FOR COMISSIONING


TEST REPORT OF AIR CIRCUIT BREAKER For DWARKESH ELECTRICKAL
Client HINUSTAN COCA COLA BEVERAGES PVT. LTD – GOBLEJ Tested by JNA
Plant UPS AREA Tested on 06/02/2020
Location P-3A / TO UPS-1 (400KVA - 800A) – 415 V UPS I/P PANEL

1.0 Name Plate details of Circuit Breaker:


1.1 Serial No. : MS758265U
1.2 Make : L&T
1.3 Type : UW1-08N
1.4 Rated voltage :440 V
1.5 Rated current : 800 A
1.6 Short Time Current :65 kA / 3 Sec

2.0 Insulation Resistance test :


Insulation Resistance test, Close condition Open condition
applied 5kV RY YB BR RE YE BE RR` YY` BB`
Values in Ω >1G >1G >1G >1G >1G >1G >1G >1G >1G

3.0 Contact Resistance measurement :


Contact Resistance of R – Phase Y – Phase B – Phase
Value in μΩ 30.8 29.9 30.7

4.0 Coil Resistance Test :


Coil designation Resistance Value In Ω
Under Voltage Coil 0.549 KΩ

5.0 Control circuit and operational checks :


Sr. No. Description Remarks
5.1 Manual charging of spring OK
5.2 Mechanical closing and tripping OK
5.3 Mechanical interlocks of breaker OK
5.4 Tripping through release OK
5.5 Breaker close command blocking when Release is in operated condition OK
5.6 Abnormality, if any NONE

6.0 Remarks : TESTED AS ABOVE FIT FOR COMISSIONING


TEST REPORT OF AIR CIRCUIT BREAKER For DWARKESH ELECTRICKAL
Client HINUSTAN COCA COLA BEVERAGES PVT. LTD – GOBLEJ Tested by JNA
Plant UPS AREA Tested on 06/02/2020
Location P-3B / TO UPS-2 (400KVA - 800A) – 415 V UPS I/P PANEL

1.0 Name Plate details of Circuit Breaker:


1.1 Serial No. : MS758262U
1.2 Make : L&T
1.3 Type : UW1-08N
1.4 Rated voltage :440 V
1.5 Rated current : 800 A
1.6 Short Time Current :65 kA / 3 Sec

2.0 Insulation Resistance test :


Insulation Resistance test, Close condition Open condition
applied 5kV RY YB BR RE YE BE RR` YY` BB`
Values in Ω >1G >1G >1G >1G >1G >1G >1G >1G >1G

3.0 Contact Resistance measurement :


Contact Resistance of R – Phase Y – Phase B – Phase
Value in μΩ 31.0 30.8 32.3

4.0 Coil Resistance Test :


Coil designation Resistance Value In Ω
Under Voltage Coil 0.547 KΩ

5.0 Control circuit and operational checks :


Sr. No. Description Remarks
5.1 Manual charging of spring OK
5.2 Mechanical closing and tripping OK
5.3 Mechanical interlocks of breaker OK
5.4 Tripping through release OK
5.5 Breaker close command blocking when Release is in operated condition OK
5.6 Abnormality, if any NONE

6.0 Remarks : TESTED AS ABOVE FIT FOR COMISSIONING


TEST REPORT OF AIR CIRCUIT BREAKER For DWARKESH ELECTRICKAL
Client HINUSTAN COCA COLA BEVERAGES PVT. LTD – GOBLEJ Tested by JNA
Plant UPS AREA Tested on 06/02/2020
Location P-4A / TO UPS-3 (400KVA - 800A) – 415 V UPS I/P PANEL

1.0 Name Plate details of Circuit Breaker:


1.1 Serial No. : MS758261U
1.2 Make : L&T
1.3 Type : UW1-08N
1.4 Rated voltage :440 V
1.5 Rated current : 800 A
1.6 Short Time Current :65 kA / 3 Sec

2.0 Insulation Resistance test :


Insulation Resistance test, Close condition Open condition
applied 5kV RY YB BR RE YE BE RR` YY` BB`
Values in Ω >1G >1G >1G >1G >1G >1G >1G >1G >1G

3.0 Contact Resistance measurement :


Contact Resistance of R – Phase Y – Phase B – Phase
Value in μΩ 30.7 32.3 31.8

4.0 Coil Resistance Test :


Coil designation Resistance Value In Ω
Under Voltage Coil 0.547 KΩ

5.0 Control circuit and operational checks :


Sr. No. Description Remarks
5.1 Manual charging of spring OK
5.2 Mechanical closing and tripping OK
5.3 Mechanical interlocks of breaker OK
5.4 Tripping through release OK
5.5 Breaker close command blocking when Release is in operated condition OK
5.6 Abnormality, if any NONE

6.0 Remarks : TESTED AS ABOVE FIT FOR COMISSIONING


TEST REPORT OF BUSBAR For DWARKESH ELECTRICKAL
Client HINUSTAN COCA COLA BEVERAGES PVT. LTD – GOBLEJ Tested by JNA
Plant UPS AREA Tested on 06/02/2020
Location UPS INPUT PANEL

1.0 Insulation Resistance test :


Insulation Resistance test, ACB in Close Condition
applied 5kV RY YB BR RE YE BE RN YN BN
Values in Ω >1G >1G >1G >1G >1G >1G >1G >1G >1G

2.0 Contact Resistance measurement :


Contact Resistance of R – Phase Y – Phase B – Phase N - Phase
Value in μΩ (P-1 to P-4) 48.9 45.7 51.2 53.2

3.0 Remarks : TESTED AS ABOVE FIT FOR COMISSIONING