VI-IMSP-O&M-01-F02
Pvt. Ltd.
First floor,Bella Vista,Oswal
Park,Pokharan
Road no.2,Thane RELAY TEST REPORT
west ,Thane,Maharashtra
Fax: +91 22 2543 7835
web:www.jbsepl.com
email: jbs@vsnl.com Date: 28/03/2023
CLIENT: Virescent Renewal Energy
1. Test Equipment’s:
NO. Device Name Device Type
1 Test kit make PONOVO
2 Type PW460
3 Version 2.5
4 Serial No IN127101202
3. General Check:
4. Measurement Test:
INJECTED
MEASURED VALUES (In terms of Primary
CURRENT(Amp)
Values)
R Y B
L1 0.254 0.291 46 45
L2 0.255 0.291 41 47
L3 0.255 0.291 42 45
L1,L2,L3 0.146 0.195 49 55
Injected current ( A )
S.NO STATUS Time (Sec)
HV SIDE LV SIDE
0.146∟0° 0.195 ∟180°
1. 0.146∟-120° 0.195∟60° Stable No –Trip
0.146∟+120° 0.195∟300°
0.146∟0° 0.195∟0° T
2. 0.146∟-120° 0.195∟60° Unstable rip
0.146∟+120° 0.195∟300°
8.SLOPE TEST:Is1=0.200
K1=30.0%
Is2=1.500
K2=80.0%
9. VOLT/HERTZ PROTECTION:
INJECTED INJECTED
S.NO STAGES CURRENT CURRENT AT N STATUS
AT 50Hz TIMES OF 50 Hz
1. 2nd HARMONICS HV Side 1A AT 50HZ 0.211 AT 100HZ BLOCKING
2 5th HARMONICS HV Side 1A AT 50HZ 0.191 AT 100HZ TRIP
3. 2nd HARMONICS LV Side 1A AT 50HZ 0.350 AT 100HZ BLOCKING
4. 5th HARMONICS LV Side 1A AT 50HZ 0.340 AT 100HZ TRIP
REMARKS NO