TEST REPORT FOR TRANSFORMER

ELECTROTEST DOC. NO. : 01/ETEST/TPSSL/2023-24


DATE :- 25/06/2023
PVT. LTD. FEEDER : 20 KVA AUX TRAFO
DATE OF TESTING : 24/06/2023
CLIENT : Tata Power Solar
Sheet No. 1 of 4
LOCATION : COKE PLANT UPC

1. EQUIPMENT DETAILS:
Make AE Rating 20 KVA
Sl. No. 0322/T514653/01 Cooling AN
HV (Volt) 630 Gross Weight 155 KG
LV (Volt) 415 HV (Amps) 18.3 A
% Z Impedance 4 LV (Amps) 27.8 A
Qty of Oil NA Vector Group Dyn11
Mfg. Year 2022 Connection (HV) Delta
No of Taps NA Connection (LV) Star
Normal Tap NA Installation INDOOR

2.TESTING EQUIPMENT DETAILS:

CALIBRATION
INSTRUMENT MAKE SL. NO. RANGE
DUE DATE
Digital Insulation
Motwane A02747121 0 – 5 KV 12-01-2024
tester
Transformer Winding
Scope 2304.08AI1035 0-10 A/0-2000 Ω 13-01-2024
resistance
3 – Phase Variec AE 1221/D514323/2 0-415 V NA
Digital Multimeter Fluke 55030407 0-1000 V 12-01-2024
Milli Clamp Meter Multi B02850 30 mA – 300 Amp 12-01-2024

 Test Condition : Both side cable isolated. Temp:- 30ºC

3. INSULATION RESISTANCE TEST :

Description Voltage(KV) 1 Min 10 Min PI value Remarks

HV to LV 500 v 69.2 GΩ 77.6 GΩ 1.12 OK

HV to EARTH 500 v 41.2 GΩ 62.3 GΩ 1.51 OK

LV to EARTH 500 v 16.5 GΩ 21.3 GΩ 1.29 OK


TEST REPORT FOR TRANSFORMER
ELECTROTEST DOC. NO. : 01/ETEST/TPSSL/2023-24
DATE :- 25/06/2023
PVT. LTD. FEEDER : 20 KVA AUX TRAFO
DATE OF TESTING : 24/06/2023
CLIENT : Tata Power Solar
Sheet No. 2 of 4
LOCATION : COKE PLANT UPC

4. PI TEST :
Time HV to LV HV to EARTH LV to EARTH Remarks
15 Sec 55.1 GΩ 32.0 GΩ 12.3 GΩ
1 Min 69.2 GΩ 41.2 GΩ 16.5 GΩ
2 Min 71.6 GΩ 43.7 GΩ 16.6 GΩ
3 Min 72.0 GΩ 46.2 GΩ 16.7 GΩ
4 Min 72.2 GΩ 46.9 GΩ 16.9 GΩ
5 Min 72.2 GΩ 47.9 GΩ 17.0 GΩ OK
6 Min 72.5 GΩ 50.0 GΩ 17.2 GΩ
7 Min 72.8 GΩ 51.7 GΩ 17.9 GΩ
8 Min 72.9 GΩ 52.0 GΩ 18.4 GΩ
9 Min 73.2 GΩ 54.4 GΩ 19.3 GΩ
10 Min 77.6 GΩ 62.3 GΩ 21.3 GΩ

5. VOLTAGE RATIO TEST WITH MAGNETIZING CURRENT (IN NORMAL TAPS)


HIGH VOLTAGE SIDE
Applied Voltage (In Volts) Measured Magnetizing. Current in (mA)
R-Y Y-B B-R R Y B
399.3 400.3 401.4 175.4 144.2 122.8
LOW VOLTAGE SIDE
Measured Voltage (Volts) Measured Voltage (volt)
r-y y-b b-r r-n y-n b-n
262.8 263.7 262.6 151.3 152.9 151.6

6. NO LOAD LOSS : (Preferably From HV Side) ( In Normal Tap ) :


Applied Voltage (In Volts) Measured Current (A/mA) Total Loss Remarks
V RY V YB V BR IR IY IB (Watts) Loss Calculated at
400.4 402.2 398.9 171.6 179.2 168.6 rated voltage
TEST REPORT FOR TRANSFORMER
ELECTROTEST DOC. NO. : 01/ETEST/TPSSL/2023-24
DATE :- 25/06/2023
PVT. LTD. FEEDER : 20 KVA AUX TRAFO
DATE OF TESTING : 24/06/2023
CLIENT : Tata Power Solar
Sheet No. 3 of 4
LOCATION : COKE PLANT UPC

7. MAGNETIC BALANCE TEST :

HV / LV Side :( STAR WINDING )


Applied Voltage (In Volts) Measured Voltage (In Volts) Measured
current Remarks
r-n y-n b-n r-n y-n b-n
(mA)
101.7 ---- ---- ---- 76.5 24.50 168.6
---- 101.8 ---- 51.36 ---- 50.75 164.3 OK
---- ---- 102.1 28.45 72.4 ---- 134.6

8. WINDING RESISTANCE TEST : (In all tap)


HIGH VOLTAGE SIDE
HV
Between R-Y Between Y-B Between B-R Remarks
Winding
Tap. No. Asc Asc Asc
1 1230.2 mΩ 1235.4 mΩ 1362.5 mΩ OK

LOW VOLTAGE SIDE


Lv r-y y-b b-r r-n y-n b-n
Winding 2.512 mΩ 2.496 mΩ 2.470 mΩ 1.214 mΩ 1.325 mΩ 1.254 mΩ

9. VECTOR GROUP TEST (HV-LV) : (At normal Tap for Dyn11)


Applied Voltage (Volt) Measured Voltage (Volt)
R-Y 405.5 B-b 365.2 Y-b 364.5
Y-B 404.2 B-y 410.2 Y-y 361.4
B-R 405.6 R-N 235.5 R-b 52.30
b-N 182.6
Inference :
TEST REPORT FOR TRANSFORMER
ELECTROTEST DOC. NO. : 01/ETEST/TPSSL/2023-24
DATE :- 25/06/2023
PVT. LTD. FEEDER : 20 KVA AUX TRAFO
DATE OF TESTING : 24/06/2023
CLIENT : Tata Power Solar
Sheet No. 4 of 4
LOCATION : COKE PLANT UPC

VBb = VYb
VBy > VYy
VRb+ Vbn = VRN Heans it is Dyn11.

10. PERCENTAGE IMPEDANCE TEST : ( At Normal Tap )


Winding Shorted at L.V Side :- r, y, b shorted.

PHASE Current (A) Current (A) Calculated Average


Voltage (Volt) Remarks
REFERENCE HV Side LV Side Z %Z
R-Y 15.44 5.51 47.0 2.80
Y-B 15.30 6.00 46.9 2.55 6.32 OK
B-R 14.82 5.63 46.4 2.63

Remarks :- Test result found satisfactory.

TEST PERFORMED BY: TEST WITNESSED BY:


Name: VISHAL & MUKESH Name : Arijit Basu
Organization: Electrotest Pvt. Ltd Organization : Tata Power Solar

Organisation Electrotest Pvt ltd TPSSL TSL (E&P) ETD


Name
Designation

Signature