DATE :- 14/03/2023 PVT. LTD. Date of Testing:- 10/02/2023 Panel :- CRP CLIENT : TATA STEEL JAMSHEDPUR Feeder :- 33KV CRP#1 Page 1 of 1 Location : LD#1 Secondary Emission ‘0’ mtr 1. TESTING KIT DETAILS CALIBRATION INSTRUMENT MAKE SL. NO. RANGE DUE DATE Relay Test Set Metravi MIPL/43/21-22 0-200 Amp 12-01-2024 Digital Multimeter Fluke 55030407 0-1000 V 12-01-2024 2. RELAY DETAILS:- Name:- TRAFO TROUBLE TRIP RLY (30CD) Make:- GE Model No:- MVAAM23D1BA2541A Sl No :- 35372777/06/21 Auxiliary Supply :-Vx :- 110-125 V DC 220-250 V DC 3. RELAY TEST :- Coil-1 (30C) (Terminal No. 27-28) Output NO/NC Coil Resistance Pick Up Volts Drop Out Volts Remarks Contacts 5.469 KΩ 68.7 V DC 36.6 V DC OK OK
Coil-2 (30D) (Terminal No. 13-14)
Output NO/NC Coil Resistance Pick Up Volts Drop Out Volts Remarks Contacts 5.566 KΩ 71.8 V DC 43.6 V DC OK OK
Remarks :- Test Results found Satisfactory. Relay is fit to service.
TEST PERFORMED BY: TEST WITNESSED BY:
Name : Pradip & Vishal Name : Tanmay Mandal Organization: Electrotest Pvt. Ltd Organization : TSL (E&P