TEST REPORT FOR HT BREAKER

ELECTROTEST DOC. No :
DATE :
PVT. LTD. TESTING DATE : 20-12-2023
FEEDER :- 2.5MVA TR-2 FOR ST MILL (NEW)
CLIENT : TSL, JAMSHEDPUR PANEL:- 6.6 KV HT SWBD
Page 1 of 2
LOCATION : NEW S/S ST MILLS FEEDER NO. :- 05

01. EQUIPMENT DETAILS :-

Make L&T Rated Volts 12kV


Name 2.5MVA TR-2 FOR ST MILL (NEW) Rated Current 1250 A
Sl. No. M-2022-35 Making Capacity 40kA
Installation INDOOR Breaking Capacity 40kA
Mfg. Year 2022 Operating Duty O-0.3s-CO-3MIN-CO
Type VK10M40H

02. TESTING EQUIPMENT DETAILS:-


CALIBRATION
INSTRUMENT MAKE SL. NO. RANGE
DUE DATE
Digital Insulation tester Motwane A02747J21 0 – 5 KV 12-01-2025
Digital Multimeter Fluke 55030407 0-1000 V 12-01-2025
CRM 100 Scope 2300.06AI0990 0-100 A/0-2000µΩ 12-01-2025
Breaker Time Interval Meter Scope 2100.02AI0832 ----- 12-01-2025

03. INSULATION RESISTANCE MEASUREMENT : ( 2.5 ) KV DC MEGGER FOR 1 MIN.


I.R. VALUE
Reference
Before Hi Pot After Hi Pot Limits
R – R’ 213 GΩ 215 GΩ
Y – Y’ 204 GΩ 211 GΩ
B – B’ 215 GΩ 217 GΩ
R–E 342 GΩ 345 GΩ
Y–E 352 GΩ 356 GΩ ≥100 MΩ
B–E 315 GΩ 319 GΩ
R–Y 413 GΩ 416 GΩ
Y–B 445 GΩ 454 GΩ
B–R 398 GΩ 399 GΩ

04. VCB TIMING TEST :-

PHASE CLOSING TIME ( in ms) TRIP TIME ( in ms) CLOSE – OPEN TIME ( in ms)
TC1 TC2 TC1 TC2
Rph 26 20 20 20 23
Yph 27 20 20 20 22
Bph 27 20 20 19 22
05. VCB CONTACT RESISTANCE TEST :-
REFERENCE MEASURED VALUE NO. OF JOINTS LIMIT REMARKS
TEST REPORT FOR HT BREAKER
ELECTROTEST DOC. No :
DATE :
PVT. LTD. TESTING DATE : 20-12-2023
FEEDER :- 2.5MVA TR-2 FOR ST MILL (NEW)
CLIENT : TSL, JAMSHEDPUR PANEL:- 6.6 KV HT SWBD
Page 2 of 2
LOCATION : NEW S/S ST MILLS FEEDER NO. :- 05

R – R’ 21 µΩ 05
Y – Y’ 21 µΩ 05 <100 µΩ OK
B – B’ 20 µΩ 05

06. COIL RESISTANCE TEST :


COIL No. MEASURED VALUE RATED VALUE DEVIATION REMARKS
Closing Coil 37.2 Ω 37.2 Ω 0% OK
Tripping Coil-1 37.5 Ω 37.2 Ω 0.80% OK
Tripping Coil-2 37.4 Ω 37.2 Ω 0.53% OK
Motor Coil 5.96 MΩ NA NA OK

a) Hi – Pot Test of Close Condition :-


Reference Applied voltage ( AC ) Time in Min Measured Leakage
in KV Current (mA)
R – Y+B+E 14.0 1.0 0.2
Y – R+B+E 14.0 1.0 0.2
B – R+Y+E 14.0 1.0 0.3

b) Hi – pot Test of Open Condition :-


Reference Applied voltage ( AC ) Time in Min Measured Leakage
in KV Current (mA)
R – R’+E 8.0 1.0 0.1
Y – Y’+E 8.0 1.0 0.1
B – B’+E 8.0 1.0 0.1

Remarks:- Test results found satisfactory, BREAKER is fit for service.

TEST PERFORMED BY: TEST WITNESSED BY:


Name : Vishal & Dhanai Name : Nandan Kumar
Organization: Electrotest Pvt. Ltd Organization : TSL E&P

Checked by/
ELECTROTEST TSL (E&P) TSL ETD
Approved By
Name: Abhishek Singh
Designation: Manager