SITE TEST REPORT Date :

Contractor’s name: Customer:

ALFANAR CO. NG-SA

Name of substation: Dammam Housing 115/13.8KV Substation # 1 NG-SA Contract No. :


DESCRIPTION : BREAKER FAIL RELAY (REQ 650) Test 4400006262
Page 1 of 6
Panel/ Bay No: Equip. No.: Dwg. Ref.: Record No.:

1. GENERAL INFORMATION:

A- Bay (Circuit) data:


Panel NO. Panel Name
CT Ratio Frequency 60 HZ

B- Relay data:
TYPE REQ 650 VERSION
Serial No. Ordering No
MAKE ABB SOFTWARE PCM 600
RATED VOLTAGE 125 VDC RATED FREQUENCY 50/60 HZ

ELECTRICAL TEST

DATE:
TESTING ENGINEER CSD- Engineer
Signature: ________________ Signature: ________________
Name : ________________ Name : ________________
SITE TEST REPORT Date :
Contractor’s name: Customer:

ALFANAR CO. NG-SA

Name of substation: Dammam Housing 115/13.8KV Substation # 1 NG-SA Contract No. :


DESCRIPTION : BREAKER FAIL RELAY (REQ 650) Test 4400006262
Page 2 of 6
Panel/ Bay No: Equip. No.: Dwg. Ref.: Record No.:

B. Operating DC Supply Currents:

Calculated Watts
DC Voltage DC Current w/o Fault (mA) DC Current During Fault (mA)
w/o fault During fault
125 156 166 19.5 20.75

C- MEASUREMENT:

INJECTED CURRENT EXPECTED CURRENT MEASURED CURRENT

R 3000 2996.471

Y 3000 2999.049

B 3000 2997.487

D- CBF PROTECTION FUNCTION:

1- PICK UP& DROP OFF TEST:

R Y B
SETTING
PICK UP DROP OFF PICK UP DROP OFF PICK UP DROP OFF
I=0.20, IN=0.20A 0.202 0.201 0.202 0.201 0.202 0.201
I=0.15, IN=0.15A 0.152 0.151 0.152 0.151 0.152 0.151
I=0.10, IN=0.10A 0.102 0.101 0.102 0.101 0.102 0.101

2- TIMING TEST:

Setting current (mA) Injected current (mA) SETTING(ms) R Y B


100 200 250 271.4 277.4 277.2
100 200 200 225.2 227.8 223.2

DATE:
TESTING ENGINEER CSD- Engineer
Signature: ________________ Signature: ________________
Name : ________________ Name : ________________
SITE TEST REPORT Date :
Contractor’s name: Customer:

ALFANAR CO. NG-SA

Name of substation: Dammam Housing 115/13.8KV Substation # 1 NG-SA Contract No. :


DESCRIPTION : BREAKER FAIL RELAY (REQ 650) Test 4400006262
Page 3 of 6
Panel/ Bay No: Equip. No.: Dwg. Ref.: Record No.:

100 200 150 177.1 170.7 175.9


Accuracy: operate current +/-1% reset ratio:95%
Operate time for current detection:20 mS / timers: +/-5%. / Technical manual SH: 140

4-CHECK THE BINARY INPUTS (With Relay Energized):


TEST METHOD RESULT CONFIGRATION AS
INPUT NO.
(Energize with 125V DC) PER SCHEME
BIO3 I/P 1 RELAY TB NO. X324:1,2 SPARE

BIO3 I/P 2 RElAY TB NO.X324:4,5 SPARE

BIO3 I/P 3 RElAY TB NO. X324:4,6 SPARE


BIO3 I/P 4 RElAY TB NO. X324:8,9 SPARE
BIO3 I/P 5 RELAY TB NO. X324:8,10 CBF INI
SPARE
BIO3 I/P 6 RELAY TB NO. X324:12,13
SPARE
BIO3 I/P 7 RELAY TB NO. X324:12,14

BIO3 I/P 8 RELAY TB NO. X324:16,17 SPARE

BIO3 I/P 9 RELAY TB NO. X324:16,18 SPARE

BIO4 I/P 1 RELAY TB NO. X329:1,2 CBF TRIP RLY OPTD

BIO4 I/P 2 RELAY TB NO.X329:4,5 AC MCB TRIPPED

BIO4 I/P 3 RELAY TB NO. X329:4,6 SPARE

BIO4 I/P 4 RELAY TB NO. X329:8,9 SPARE

BIO4 I/P 5 RELAY TB NO. X329:8,10 SPARE

BIO4 I/P 6 RELAY TB NO. X329:12,13 SPARE

BIO4 I/P 7 RELAY TB NO. X329:12,14 SPARE

BIO4 I/P 8 RELAY TB NO. X329:16,17 SPARE

BIO4 I/P 9 RELAY TB NO. X329:16,18 SPARE

DATE:
TESTING ENGINEER CSD- Engineer
Signature: ________________ Signature: ________________
Name : ________________ Name : ________________
SITE TEST REPORT Date :
Contractor’s name: Customer:

ALFANAR CO. NG-SA

Name of substation: Dammam Housing 115/13.8KV Substation # 1 NG-SA Contract No. :


DESCRIPTION : BREAKER FAIL RELAY (REQ 650) Test 4400006262
Page 4 of 6
Panel/ Bay No: Equip. No.: Dwg. Ref.: Record No.:

5-CHECK THE OUTPUTS (With Relay Energized):


OUTPUT RELAY CONFIGURATIONS AS Contact Checked
RELAY No. CONTACT NO. PER SCHEME Res <0.2 Ω
BIO3-B/O 1 X321:1,2 SPARE
BIO3-B/O 2 X321:3,4 SPARE
BIO3-B/O 3 X321:5,6 SPARE
BIO3-B/O 4 X321:7,8 SPARE
BIO3-B/O 5 X321:9,10 SPARE
BIO3-B/O 6 X321:11,12 SPARE
BIO3-B/O 7 X321:13,15 SPARE
BIO3-B/O 8 X321:14,15 SPARE
BIO3-B/O 9 X321:16,17,18 SPARE
BIO4-B/O 1 X326:1,2 SPARE
BIO4-B/O 2 X326:3,4 SPARE
BIO4-B/O 3 X326:5,6 SPARE
BIO4-B/O 4 X326:7,8 SPARE
BIO4-B/O 5 X326:9,10 SPARE
BIO4-B/O 6 X326:11,12 SPARE
BIO4-B/O 7 X326:13,15 SPARE
BIO4-B/O 8 X326:14,15 SPARE
BIO4-B/O 9 X326:16,17,18 SPARE
PSM2-TCS1 X317:1,2 CBF TRIPTO LO
PSM2-TCS2 X317:3,4 CBF TRIP TO LO
PSM2-TCS3 X317:5,6 CBF TRIP TO LO
PSM2-PO4 X317:7,8 CBF TRIP TO LO
PSM2-PO5 X317:9,10 CBF TRIP TO FR
PSM2-PO6 X317:11,12 SPARE
PSM2-PO7 X317:13,14 SPARE
PSM2-PO8 X317:15,16 SPARE
PSM2-PO9 X317:17,18 SPARE

6- LEDS CHECK:

LED NO. FUNCTION LED STATUS

DATE:
TESTING ENGINEER CSD- Engineer
Signature: ________________ Signature: ________________
Name : ________________ Name : ________________
SITE TEST REPORT Date :
Contractor’s name: Customer:

ALFANAR CO. NG-SA

Name of substation: Dammam Housing 115/13.8KV Substation # 1 NG-SA Contract No. :


DESCRIPTION : BREAKER FAIL RELAY (REQ 650) Test 4400006262
Page 5 of 6
Panel/ Bay No: Equip. No.: Dwg. Ref.: Record No.:

LED 1 CBF INI

LED 2 CBF TRIP

LED 3 SPARE

LED 4 SPARE

LED 5 SPARE

LED 6 SPARE

LED 7 SPARE

LED 8 SPARE

LED 9 SPARE

LED 10 SPARE

LED 11 SPARE

LED 12 SPARE

LED 13 SPARE

LED 14 SPARE

LED 15 SPARE

7- FINAL SETTING TEST:


Final setting issue no.: 12852
Final setting date: 20/11/2014

1- PICK UP& DROP OFF TEST:


R Y B
SETTING
PICK UP DROP OFF PICK UP DROP OFF PICK UP DROP OFF

DATE:
TESTING ENGINEER CSD- Engineer
Signature: ________________ Signature: ________________
Name : ________________ Name : ________________
SITE TEST REPORT Date :
Contractor’s name: Customer:

ALFANAR CO. NG-SA

Name of substation: Dammam Housing 115/13.8KV Substation # 1 NG-SA Contract No. :


DESCRIPTION : BREAKER FAIL RELAY (REQ 650) Test 4400006262
Page 6 of 6
Panel/ Bay No: Equip. No.: Dwg. Ref.: Record No.:

I=0.10, IN=0.10A 0.102 0.101 0.102 0.101 0.102 0.101

2- TIMING TEST

Setting current (mA) Injected current (mA) SETTING(ms) R Y B


100 200 150 177.1 170.7 175.9
Accuracy: operate current +/-1% reset ratio:95%
Operate time for current detection:20 mS / timers: +/-5%. / Technical manual SH: 140
- TEST EQUIPMENT:

EQUIPMENT SERIAL NO. DUE DATE


B10 1201752 20 DEC. 2015
FREJA 1402772 17 AUG. 2015
FLUKE MULTIMETER 4000009791 OCT2015

DATE:
TESTING ENGINEER CSD- Engineer
Signature: ________________ Signature: ________________
Name : ________________ Name : ________________