NGC-30 / UIT2

Installation manual

Downloaded from www.Manualslib.com manuals search engine


Contents
Section I – Overview.................................................................................................................................. 3
1.1 Introduction............................................................................................................................... 3
Section 2 – Installation and Wiring............................................................................................................ 4
2.1 Introduction............................................................................................................................... 4
2.2 Initial Inspection....................................................................................................................... 4
2.3 Operating Environment............................................................................................................ 4
2.4 Installation Location................................................................................................................. 5
2.5 Mounting Procedures............................................................................................................... 5
2.6 Wiring Procedures.................................................................................................................... 5
2.6.1 Incoming Power With Distribution System.................................................................... 5
2.6.2 Outgoing Power With Distribution System.................................................................... 6
2.6.3 Incoming/Outgoing Power Without Distribution Panel Board ..................................... 6
2.6.4 Incoming Rtd Wiring........................................................................................................ 7
2.6.5 Connecting The RS-485 Device Network...................................................................... 7
2.7 Connections for Remote Annunciation — NGC-UIT2-EX...................................................... 12
2.8 RS-232, RS-485, or Ethernet Remote Port Connections to a Host Computer..................... 13
2.8.1 RS-232 Serial Connections........................................................................................... 13
2.8.2 RS-485 Serial Connections........................................................................................... 13
2.8.3 Ethernet Connections.................................................................................................... 14
2.9 Testing the NGC-30 System................................................................................................... 14
Section 3 – nVent RAYCHEM NGC-30 Components and Operation......................................................... 15
3.1 User Interface Terminal (NGC-UIT2)..................................................................................... 15
3.1.1 Multiple Ngc-Uit2 Models............................................................................................. 15
3.1.2 Ngc-Uit2 Local And Remote Network Connections.................................................... 16
3.1.3 RS-485 Configuration Switches................................................................................... 17
3.1.4 Ngc-Uit2-Ex Reset Switch............................................................................................. 17
3.2 C
 ard Rack Module (NGC-30-CRM/-CRMS) and
Current Transformer Module (NGC-30-CTM)������������������������������������������������������������������������ 18
3.3 Card Rack (NGC-30-CR)......................................................................................................... 19
3.4 Voltage Monitoring Module (NGC-30-CVM) – Optional ...................................................... 19
3.5 Remote Monitoring Module (RMM2) – Optional.................................................................. 20
3.6 Power Line Carrier Interface Module (PLI) – Optional......................................................... 21
3.7 The Remote Monitoring Module for Digital Inputs (RMM-DI).............................................. 22
Section 4 – Appendices........................................................................................................................... 23
Appendix A – Replacement Component Ordering Guide........................................................... 23
Appendix B – Panel Specifications............................................................................................. 24
Appendix C – NGC-30-CRM/-CRMS Specifications.................................................................... 27
Appendix D – NGC-UIT2 Specifications...................................................................................... 28
Appendix E – Device Address...................................................................................................... 29
Appendix F – RAYCHEM RMM-DI Technical Specification........................................................ 30

2 | nVent.com

Downloaded from www.Manualslib.com manuals search engine


SECTION I – OVERVIEW

1.1 INTRODUCTION
The nVent RAYCHEM NGC-30 is a fully wired and tested control and monitoring system used
with electric heat tracing. This manual provides information pertaining to the installation,
operation, testing, adjustment, and maintenance of all components of the RAYCHEM NGC-30
System. For information about how to program the RAYCHEM NGC-30, see the RAYCHEM
NGC-30 Programming Guide (H58186)
A typical RAYCHEM NGC-30 is made up of at least a User Interface Terminal (NGC-UIT2),
one Card Rack (NGC-30-CR), one Card Rack Module with connectors
(NGC-30-CRM or NGC-30-CRMS), and one Current Transformer Module (NGC-30-CTM).
Optional Remote Monitoring Module for Temperatures (RMM2), Power Line Carrier Interface
(PLI), RMC modules, Remote Monitoring Module for Digital Inputs (RMM-DI) and Voltage
Monitoring Module (NGC-30-CVM) may be used.
The information in this document coincides with the specific releases of firmware
(listed in Table 1.1) for the User Interface Terminal (NGC-UIT2) and Card Rack Module
(NGC-30-CRM/-CRMS) components. As nVent releases new firmware to significantly modify
or enhance any of these components, new documentation will accompany these releases.
To ensure that the correct documentation is being used for your particular version of the
RAYCHEM User Interface Terminal (NGC-UIT2), compare the firmware version number of
each component against the number listed in the table below. As subsequent changes are
made, supplements to this document will be included in manuals shipped after the firmware is
released. Supplements will make specific reference to the operation or functional change.
Copies of this manual and updates may be downloaded from the Literature section of
nVent.com.

Table 1.1 Component versions


Component versions
Component Version number
NGC-CRM/CRMS V1.0X
NGC-UIT2-EX V2.1.X or V4.X
RMM2 V1.0X
RMM-DI V1.0

IMPORTANT WARNINGS AND NOTES


The following icons are used extensively throughout this manual to alert you to important
warnings that affect safety and to important notes that affect the proper operation of
the unit. Be sure to read and follow them carefully.

nVent.com | 3

Downloaded from www.Manualslib.com manuals search engine


SECTION2 – INSTALLATION AND WIRING

2.1 INTRODUCTION
WARNING:

Electrical Hazard! Ensure all personnel involved in installation, servicing, and programming are
qualified and familiar with electrical equipment, its ratings, and proper practices and codes.
Multiple voltages and signal levels may be present during the installation, operation, and
servicing of this product. Do not power the product until the safety provisions outlined in this
section have been observed.
This section includes information regarding the initial inspection, preparation for use,
and wiring instructions for the components of the RAYCHEM NGC-30.

2.2 INITIAL INSPECTION


Inspect the shipping container for damage. If the shipping container or cushioning material
is damaged, it should be kept until the contents of the shipment have been verified for
completeness and the equipment has been checked mechanically and electrically. Procedures
for installing the RAYCHEM NGC-30 are given in this section. If the shipment is incomplete,
mechanically damaged, defective in any way, or does not pass the electrical performance tests,
notify the nearest nVent representative. If the shipping container is damaged, or the cushioning
material shows signs of stress, notify the carrier as well as your nVent representative. Keep the
shipping materials for the carrier’s inspection.

2.3 OPERATING ENVIRONMENT


There are three types of User Interface Terminals (UIT2s) available with the RAYCHEM
NGC-30 panel, as shown in Table 2.1. The term “NGC-UIT2” in this document refers to any of
the available NGC-UIT2s, regardless of which model is actually installed.

NGC-30 User Interface Terminals (UIT2s)


UIT2 type Area classification Usage
NGC-UIT2-EX Nonhazardous (Unclassified) Locations TYPE 4
Hazardous Locations (Indoors or
Class 1 Div. 2, Groups A, B, C & D Outdoors)
Class I Zone 2
NGC-UIT2-ORD-R Nonhazardous (Unclassified) Locations TYPE 4
The NGC-UIT2-ORD-R must be installed in a (Indoors or
nonhazardous, indoor or outdoor location. Outdoors)
The NGC-UIT2-ORD-R connects to NGC-30
panels using RS-485 communication wiring.

WARNING:
Some wiring configurations will use more than one power source. All power sources must be
de-energized prior to performing any maintenance on a card rack module or its heating circuit.
The operating environment should be within the limitations specified for the RAYCHEM
NGC-30 components as outlined in Appendices B, C, and D.

4 | nVent.com

Downloaded from www.Manualslib.com manuals search engine


2.4 INSTALLATION LOCATION
The wide Operating Temperature range of the RAYCHEM NGC-30 permits installation in almost
any convenient location. Considerations should include: expected atmospheric conditions
(weather), accessibility for maintenance and testing, the location of existing conduits, and
hazardous location rating. Ambient temperature conditions may affect load current ratings
. CAUTION:

Always be sure that the intended location is classified as an area that the product is approved
for use in as defined by Article 500 of the National Electrical Code and/or Part I, Section 18 of
the Canadian Electrical Code.

2.5 MOUNTING PROCEDURES


Each RAYCHEM NGC-30 panel includes a set of “As Built” drawings that have been engineered,
designed, and drafted based upon the model number and any special requirements that
were requested when ordering. The “As Built” drawings include an elevation/layout (with
bill of materials) and schematics. If these drawings are not included, contact your nVent
Representative and request the “As Built” drawings for your panel. Upon request, an electronic
copy of these drawings can be provided.
For mounting the panel, locate the elevation and layout drawing which includes a bill of
materials. The enclosure mounting information will be provided on the “As Built” drawings.

2.6 WIRING PROCEDURES


Refer to the “As Built” drawings for wiring of incoming/outgoing power and incoming RTD
connections. The RAYCHEM NGC-30 panel can be purchased with, or without, a distribution
panel board.

2.6.1 INCOMING POWER WITH DISTRIBUTION SYSTEM


Main Circuit Breaker
Locate the main circuit breaker in the panel by using the supplied elevation/layout drawing,
and connect per the associated schematic drawings. Depending upon the size and type of
main circuit breaker and voltage loss calculations, use the appropriate size and number of
wires to connect directly to the main circuit breaker, and panel board neutral and ground bus in
the panel.

Incomming service
Three phase, 4 wire, 60 Hz

ØA ØB ØC Main circuit
breaker
3-pole

Panelboard
neutral bus
Panelboard
ground bus

Power wiring diagram

Fig. 2.1 Main circuit breaker wiring

Branch Circuit Breakers


The branch circuit breakers are pre-wired to the contactors or solid- state relays in the panel,
so no further incoming power wiring is required.

nVent.com | 5

Downloaded from www.Manualslib.com manuals search engine


2.6.2 OUTGOING POWER WITH DISTRIBUTION SYSTEM
Load Power Terminal Blocks
Locate the outgoing heater terminal blocks using the supplied elevation/layout drawing, and
connect per the associated schematic drawings. Depending upon the size of the branch circuit
breaker and voltage loss calculations, use the appropriate size and number of wires to connect
from the panel’s Load Power Terminal Blocks to the heat-trace power junction box.
Branch EMR or Load Power Heat trace
circuit SSR Terminal junction
breaker contacts Block box
GF LC Heat trace cable

TB*
CRM
X CTM
connector TB- (Y)
Cable-CT**
13
14
15
16
17

* Reference panel drawing for terminal block number


** Represents HTC circuit number 1-40

Fig. 2.2 Heat trace power wiring diagram

2.6.3 INCOMING/OUTGOING POWER WITHOUT DISTRIBUTION PANEL BOARD


Line Power Terminal Blocks
Locate the incoming power terminal blocks in the panel using the supplied elevation/layout
drawings and connect per the associated schematic drawing. Depending upon size and type of
the remotely located branch circuit breakers, use the appropriate size and number of wires to
connect directly to the Line Power Terminal Blocks.
Load Power Terminal Blocks
Locate the outgoing power terminal blocks in the panel using the supplied elevation/layout
drawings and connect per the associated schematic drawing. Depending upon size and type of
the remotely located branch circuit breakers, use the appropriate size and number of wires to
connect from the Load Power Terminal Blocks to the heater’s power connection box.

Single pole C.B.


Line Power Load Power
Terminal Blocks CTM– Terminal Blocks
CB TB* * TB*
* LP
L1 *–L1
C
* *–T1
CT GF CT
T1 Heat trace cable
N
N *–N *–N N

Two pole C.B. Line Power Load Power


Terminal Blocks Terminal Blocks
CTM–
CB TB* * TB*
* LP
L1 *–L1
C
* *–T1
CT GF CT
T1 Heat trace cable

LP
L2 *–L2 *–T2 T2

* Reference panel drawing for terminal block number

Fig. 2.3 Single pole and two pole circuit breaker wiring diagrams

6 | nVent.com

Downloaded from www.Manualslib.com manuals search engine


2.6.4 INCOMING RTD WIRING
Nonhazardous and Hazardous Location Installations Wired to Terminal Block in Panel
The RTD wiring from the NGC-30-CRM/-CRMS have been pre-wired to RTD terminals. The field
RTD wiring (3-wire with shield) will be terminated by the installer at the RTD terminal blocks.
Refer to the Installation Drawings for the RTD Termination Schedule.
See Fig. 2.4 on page 8 for a typical RTD installation.
IMPORTANT: To meet the requirements for hazardous location installations, a separate RTD
terminal block must be installed and wired to the NGC-30-CRM/-CRMS RTD terminal connector.

NGC-30-CRM/-CRMS Panel Rear Field


Terminal Block Wiring
Card Rack Module
RTD- RTD-
CRM
TB*
WH (+) WH WH
1
RED RED RED RED
2 (–)
RED RED RED WH RED
3
SHLD SHLD (+) (–)
4 OPEN
CHASSIS GRD
* Reference panel drawing for terminal block number

Fig. 2.4 Typical RTD installation

2.6.5 CONNECTING THE RS-485 DEVICE NETWORK


The NGC-UIT2 display is typically linked to a network of RAYCHEM NGC-30-CRMs/-CRMSs and
optional nVent RAYCHEM RMM2s and PLIs. These are connected to the RAYCHEM NGC-UIT2
using an RS-485 communication cable (shielded, two conductor, twisted pair). The following
illustration shows how the RS-485 network for the NGC-UIT2 system may be configured.

Device must be mounted in series. Branching of the network is not allowed.


(Terminated devices are shown in gray) Connect no more than two RS-485 cables to any device.

RMM-DI

RMM2

PLI
NGC-UIT2-EX S2 0 S1
6

6 0-9
110
.

220
.

S + S +
36

S
H N/H G A B C N Norm Mixed

NGC-UIT2-EX

NGC-UIT2-EX
NGC-CRM/-CRMS
MSB LSB

TB 1 TB 2 TB 3 TB 4 TB 5

1 2 3

NGC-CRM/-CRMS
TB 19
TB 12 TB 7 TB 6
TB 13 TB 14 TB 15 TB 16 TB 17

MSB LSB

NGC-CRM/-CRMS
MSB LSB TB 1 TB 2 TB 3 TB 4 TB 5

1 2 3

TB 19
TB 12 TB 7 TB 6
TB 13 TB 14 TB 15 TB 16 TB 17

TB 1 TB 2 TB 3 TB 4 TB 5

NGC-CRM/-CRMS
1 2 3

TB 19
TB 12 TB 7 TB 6
TB 13 TB 14 TB 15 TB 16 TB 17

MSB LSB

PLI
TB 1 TB 2 TB 3 TB 4 TB 5

1 2 3

S2 0 S1
6

TB 19
6 0-9 TB 12 TB 7 TB 6
TB 13 TB 14 TB 15 TB 16 TB 17
110
.

220

NGC-CRM/-CRMS
.

S + S +
36

S
H N/H G A B C N Norm Mixed

RMM2
MSB LSB

Jumper

TB 1 TB 2 TB 3 TB 4 TB 5

1 2 3

0 TB 19
TB 12 TB 7 TB 6
TB 13 TB 14 TB 15 TB 16 TB 17

RMM-DI

Fig. 2.5 RS-485 network configuration for the NGC-UIT2 system


nVent.com | 7

Downloaded from www.Manualslib.com manuals search engine


In order for the RS-485 network to work properly, you must enable the termination resistor for
the first and last device. The devices shown in gray in Fig. 2.5 represent the devices for which
you must enable the termination resistors. The devices that are not grayed out represent the
devices for which you should not enable the termination resistors.
Optional RMM2 Installed in the Field
Refer to the RMM2 Installation Instructions (H56848) for field installation instructions.
You must connect a RS-485 connection from the RMM2 to an open RS-485 connector on the
NGC-30-CRM/-CRMS board in the RAYCHEM NGC-30 panel. To make this connection, a
pre-wired terminal block has been provided in the RAYCHEM NGC-30 panel. Connect the
RS-485 wire from the RMM2 to TB (per the panel drawing) while maintaining the correct
polarity. If the RMM2 is the first or last device in the RS-485 network, connect the
J17 termination jumper to pins 1 and 2. If the RMM2 is not the first or last device in the
RS-485 network, connect the J17 termination jumper to pins 2 and 3.

NGC-30 Panel

5
* Reference panel drawing for terminal block number

4
TB*

S 3 1 1 1 1
S
4
S
S S S S S
+ + + +
(+) 2 2 2 2 2 5 BK
BK BK BK BK BK BK
– – – –
(–) 1 3 3 3 3 6 WH
WH WH WH WH WH WH
TB* TB* TB* TB*
RS-485 RS-485
NGC-UIT2 NGC-30-CRM/-CRMS #1 NGC-30-CRM/-CRMS #8 RS-485

RMM2
Jumper

L N L N 230V: DI-13 DI-14 DI-15


Out IN 115V:
RS 485
~ ADDR
0 1.5 VA
H
DI Wiring: Output: min 12V @ 10mA
ADDR
L

DI -1 DI -2 DI -3 DI -4 DI -5 DI -6 DI -7 DI -8 DI -9 DI -10 DI -11 DI -12

Default position (for all RMM2 Termination mode


units in network except first or last one) (first or last RMM2/RMM-DI in network)
J17 J17
1 2 3 1 2 3

Fig. 2.6 RMM2 RS-485 field wiring and termination jumper setting

8 | nVent.com

Downloaded from www.Manualslib.com manuals search engine


Optional PLI Installed in the Panel
Refer to the PLI Installation Instructions (H56850). You must connect a RS-485 connection
from the PLI to an open RS-485 connector on the NGC-30-CRM/-CRMS board in the RAYCHEM
NGC-30 panel. IF the PLI is the first or last device in the RS-485 network, remove the shorting
block jumper location J2 from 1 and 2 and place it across pins 2 and 3.

NGC-30 Panel
S2 5 S1

9
6 5

5 * Reference panel drawing for terminal block number

110
.
220

RS-485 connections
.

S + – S + –
S 3 1 1 1 1 36
S S S S S S
H N/H G A B C N Norm Mixed
+ +
(+) 2 2 2 2 2
BK BK BK BK BK

(–) 1 – –
3 3 3 3
WH WH WH WH WH
TB* TB* TB* TB*
RS-485 RS-485
NGC-UIT NGC-30-CRM/-CRMS #1 NGC-30-CRM/-CRMS #8 RS-485

J2
1 2 3
Default position (for all PLI Termination mode
units in network except first or last one) (first or last PLIin network)
J2 J2
1 2 3 1 2 3
Last PLI in network

Fig. 2.7 PLI RS-485 panel wiring and termination jumper setting

NGC-UIT2 Installation
The NGC-UIT2-EX will come pre-wired into any NGC-30 panel. Exceptions exist when a remote
mount NGC-UIT2 (NGC-UIT2-ORD-R) is used or the NGC-30 panel is wired to the NGC-UIT2
in another panel. Fig. 2.8 shows the wiring for the NGC-UIT2-ORD-R and Fig. 2.10 shows the
wiring between a separate panel and the NGC-UIT2.

nVent.com | 9

Downloaded from www.Manualslib.com manuals search engine


NGC-UIT2-ORD-R Installation
You must make an RS-485 connection from the NGC-UIT2-ORD-R to the NGC-30-CRM/-CRMS
board in the NGC-30 panel. To make this connection, a pre-wired terminal block has been
provided in the NGC-UIT2-ORD-R and in the NGC-30 panel. Connect the RS-485 wire from TB3
in the NGC-UIT2-ORD-R and the other end to TB* in the NGC-30 panel maintaining the correct
polarity. If the NGC-UIT2-ORD-R and/or the NGC-30-CRM/-CRMS is the first or last device in the
RS-485 network, see Fig. 2.9 and Table 3.1 for details on how to terminate the RS-485 network.
* Reference panel drawing for terminal block numbers.

RS-485+
NGC-UIT2-ORD-R
RS-485–

SR 9 8 7 6

5 4 3 2 1

Field Remote
RS-485 Ports

RS-485

NGC-30 Panel #1 * Reference panel drawing for terminal block number

TB*
3 1 1 1 1
S S S S S
+ + + +
BK
2 BK
2 2 2 2
BK BK BK
– – – –
WH
1 WH
3 3 3 3
WH WH WH
TB* TB* TB* TB*

NGC-30-CRM/-CRMS #1 RS-485 NGC-30-CRM/-CRMS #8

Fig. 2.8 NGC-UIT2 RS-485 field wiring

The following figure shows the RS-485 termination options for the NGC-30-CRM/-CRMS.

NGC-30-CRM/-CRMS

MSB LSB

TB 1 TB 2 TB 3 TB 4 TB 5

1 2 3

TB 19
TB 12 TB 7 TB 6
TB 13 TB 14 TB 15 TB 16 TB 17

Normal End of Line


position position
End of Line (EOL) Jumper
If this device (NGC-30-CRM/-CRMS) is
1 2 3 1 2 3 the first or last device in the RS-485
network, move the J1 jumper from
terminals 2 & 3 to terminals 1 & 2.

Fig. 2.9 Termination of RS-485 network for NGC-30-CRM/-CRMS

10 | nVent.com

Downloaded from www.Manualslib.com manuals search engine


NGC-30 Panel with NGC-UIT2 Connected to an NGC-30 Panel without NGC-UIT2
This wiring is used when a single UIT2 in one panel is the central point for multiple
NGC-30 panels. Because the NGC-UIT2 can handle up to 260 heat tracing circuits, it can be
cost effective to use one NGC-UIT2 for multiple panels. An RS-485 connection must be made
from the panel that has the NGC-UIT2 (panel #1) installed to the NGC-30-CRM/-CRMS board
in NGC-30 (panel #2) that does not have the NGC-UIT2 installed (see Fig. 2.10). To make this
connection, a pre-wired terminal block has been provided in the panel #1 and in panel #2.
Connect the RS-485 wire from TB* in panel #1 and the other end to TB* in panel #2 maintaining
the correct polarity. If the NGC-30-CRM/-CRMS is the first or last device in the RS-485 network,
see Fig. 2.9 and Table 3.1 for details on how to terminate the RS-485 network.
* Reference panel drawing for terminal block numbers.

NGC-30 Panel #1

6
* Reference panel drawing for terminal block number
5

4
TB*

S 3 1 1 1 1
S
4
S
S S S S S
+ + + +
(+) 2 2 2 2 2 5 BK
BK BK BK BK BK BK
– – – –
(–) 1 3 3 3 3 6 WH
WH WH WH WH WH WH
TB6 TB6 TB6 TB6
RS-485 RS-485
NGC-UIT2 NGC-30-CRM/-CRMS #1 NGC-30-CRM/-CRMS #8 RS-485

RS-485

NGC-30 Panel #2
without UIT installed
TB*
1 1 1 1 1
S S S S S
+ + + +
BK
2 BK 2 2 2 2
BK BK BK
– – – –
WH
3 WH
3 3 3 3
WH WH WH
TB6 TB6 TB6 TB6
RS-485 RS-485
NGC-30-CRM/-CRMS #1 NGC-30-CRM/-CRMS #8

Fig. 2.10 RS-485 field wiring between two RAYCHEM NGC-30 panels

nVent.com | 11

Downloaded from www.Manualslib.com manuals search engine


2.7 CONNECTIONS FOR REMOTE ANNUNCIATION — NGC-UIT2-EX
Relay 1 on the NGC-UIT2-EX has been factory-configured and wired for “Any Alarms” unless
otherwise specified. It is powered by 12 Vdc and will energize a light on the front of the panel
if any alarm occurs. Relay 1 was also wired to a common alarm relay/terminal block for
remote annunciation of any alarms. Please see below the NGC-UIT2 Relay 1 in non-energized,
energized and in alarm condition.
NGC-UIT2 Relay 1
Non-energized Energized without an alarm condition Energized with an alarm condition
To alarm To alarm To alarm
light light light

NC NC NC

C C C

NO NO NO

Fig. 2.11 Relay 1 wiring

The NGC-UIT2 has two other Form C alarm relays (configurable through the NGC-UIT2 program)
for external alarms. Each relay can be connected to an annunciator light or distributed control
system. Each relay’s contacts have been wired from the NGC-UIT2 to a terminal block in the
panel.
NGC-UIT2 Relay 2
Non-energized Energized without an alarm condition Energized with an alarm condition

NC NC NC

C C C

NO NO NO

NGC-UIT2 Relay 3
Non-energized Energized without an alarm condition Energized with an alarm condition

NC NC NC

C C C

NO NO NO

Fig. 2.12 Relays 2 and 3 wiring

IMPORTANT: An energized relay with no alarm condition will change state with loss of power
or an alarm condition.

12 | nVent.com

Downloaded from www.Manualslib.com manuals search engine


2.8 RS-232, RS-485, OR ETHERNET REMOTE PORT CONNECTIONS TO A HOST COMPUTER
The NGC-UIT2 can communicate with a distributed control system (DCS) or other host
computer through the NGC-UIT2 external communication ports. The NGC-UIT2 provides ports
for RS-232,
RS-485, and Ethernet communication. All of these communication ports provide data read
access. However, only one port can be assigned read/write access. This is done using
the NGC-UIT2.

2.8.1 RS-232 SERIAL CONNECTIONS


The RS-232 port can be used as a direct connection to a single PC located within 50 feet of the
panel. (Refer to Fig. 2.14 on page 16). For an RS-232 connection, a 5-foot long 9-pin female D
connector to 9-pin female D-connector null modem cable has been provided with the
NGC-UIT2. Using the supplied cable, plug one end into the RS-232 port on the NGC-UIT2 and
the other end into the 9-pin male connector on the user’s computer.
NGC-UIT2-EX

PC Laptop

9-pin
female

9-pin
male

9-pin
female
5-foot 9-pin female D connector
RS-232

to 9-pin female D connector


null modem cable supplied with
NGC-UIT2-ORD

Side view

Fig. 2.13 RS-232 connection

2.8.2 RS-485 SERIAL CONNECTIONS


Use the RS-485 port when multiple NGC-UIT2 units are to be connected to a host computer or
the connection is longer than 50 feet. An RS-485 to RS-232 or RS-485 to USB converter may be
required to make the connection to the user’s PC.

NGC-30 Panel
PC
TB*
6 3
S S
+ + RS-485 Converter
5 BK
2 BK

1
– 9-pin
4
WH WH male
S 3 RS-485 9-pin
S
female
(+) 2
BK

(–) 1 To NGC-30-CRM/-CRMS
WH

* Reference panel drawing


NGC-UIT2 for terminal block number

Fig. 2.14 RS-485 connection

nVent.com | 13

Downloaded from www.Manualslib.com manuals search engine


2.8.3 ETHERNET CONNECTIONS
The Ethernet port can be used to connect multiple NGC-UIT2 units to a host computer by
connecting to the user’s LAN system.
Network node
NGC-UIT2-EX

Ethernet

Bottom view

Ethernet cable

Fig. 2.15 Ethernet connection (NGC-UIT2-EX)

2.9 TESTING THE NGC-30 SYSTEM


Once the wiring to the panel has been finished, confirm that it was done properly by completing
the following steps:
1. T
 urn the power on to all network devices (NGC-30-CRMs/-CRMSs and optional RMM2s &
PLI modules) and the NGC-UIT2.
2. O
 nce the NGC-UIT2 has booted up to the Main screen, Go to the Network | Device Screen
and press “Update Network.”

Fig. 2.16 Network|Devices screen

3. C
 onfirm all modules have been scanned into the Network database.
4. If a device or an RTD is installed but does not show up in the Network | Devices Screen,
turn the power off to the system and:
For Devices:
a. Confirm the device has a unique address (refer to section 3.2 on page 24)
b. Confirm the device is being powered
c. C
 onfirm the RS-485 connection is in place with the correct polarity (refer to section 2.6.5)
For RTDs:
a. Confirm the RTD connection is in place with the correct polarity
b. P
 erform a resistance check of the RTD. The resistance should be in a range of 70–250
ohms
Turn the power on to all devices (NGC-30-CRMs/-CRMSs and optional RMM2s & PLI) and the
NGC-UIT2. Once the NGC-UIT2 has booted up to the Main screen, Go to the Network | Device
Screen and press “Update Network.” Confirm all NGC-30-CRM s/ -CRMSs, RTDs, and/or RMM2s
and PLI modules have been scanned into the Network database.
14 | nVent.com

Downloaded from www.Manualslib.com manuals search engine


SECTION 3 – RAYCHEM NGC-30 COMPONENTS AND OPERATION
The RAYCHEM NGC-30 heat-trace system is comprised of a number of modular components,
allowing the ultimate in design flexibility. This section describes the NGC-30 control and
monitoring components (excluding the optional distribution section). Appendix B, C, and D
includes the specifications for these components.

3.1 USER INTERFACE TERMINAL (NGC-UIT2)


The NGC-UIT2 is a panel mounted color LCD display with touch-screen overlay. The NGC-UIT2
includes software that interfaces with the Card Rack Modules (NGC-30-CRM and NGC-30-CRMS)
and the Remote Monitoring Module for temperatures (RMM2), Remote Monitoring Module for
Digital Inputs (RMM-DI) and Power Line Carrier Interface (PLI) module.
The NGC-UIT2 is used as a control panel, setup device and user display.

3.1.1 MULTIPLE NGC-UIT2 MODELS


There are two versions of User Interface Terminals (UITs) available as specified in Table 2.1,
“NGC-30 User Interface Terminals (UIT2s),” on page 4. The term “NGC-UIT2” in this document
refers to any of the available NGC-UITs, regardless of which model is actually installed.

Fig. 3.1 Typical NGC-UIT2 model showing NGC-UIT2-ORD-R remote user interface terminal

The physical dimensions of each NGC-UIT2 model vary; the dimensions of the
NGC-UIT2-ORD-R shown in the figure are the largest of all NGC-UITs:
• Width: 15.21” (386 mm)
• Height: 13.21” (336 mm)
• Depth: 7.09” (180 mm)
NGC-UIT2 LCD Touch-Screen Display
The NGC-UIT2-EX and NGC-UIT2-ORD-R have a 7 inch wide x 5 ¼ inch high LCD
(17.5 cm X 13.3 cm) LCD color display. All NGC-UIT2 have touch-screen technology that
provides an user interface easy and efficient programming with no keyboards or cryptic labels.

nVent.com | 15

Downloaded from www.Manualslib.com manuals search engine


3.1.2 NGC-UIT2 LOCAL AND REMOTE NETWORK CONNECTIONS
The NGC-UIT2 communicates to both a local field network and optionally to a remote
monitoring and control network.
Local Field Network Connection
The local field network always uses an RS-485 serial connection running over shielded
twisted-pair cable. This network is used to connect the NGC-UIT2 to its control and monitoring
modules:
• RAYCHEM Mechanical Contactors Controller - NGC-30-CRM
• RAYCHEM Solid State Relay Controller - NGC-30-CRMS
• RAYCHEM Current Transformer Module Controller - NGC-30-CTM
• RAYCHEM Voltage Monitoring Module - NGC-30-CVM
• RAYCHEM Remote Monitoring Module for Temperature Measurement - RMM2
• RAYCHEM Remote Monitoring Module for Digital Inputs - RMM-DI
• RAYCHEM Power Line Carrier Interface Module - PLI
The local field network must follow configuration rules about topology and termination of
network end devices.
Remote Monitoring and Control Network Connection
The remote monitoring and control network communicates via a selectable network
connection port using either RS-485, RS-232, or 10/100Base-T Ethernet. This network is
used to connect to multiple NGC-UIT2 systems and communicate with a central PC running
RAYCHEM Supervisor software. The RAYCHEM Supervisor software provides centralized
status and alarm monitoring, data logging, and remote configuration control over all attached
NGC-UIT2 systems in the network. The remote monitoring and control network must also
follow configuration rules about topology and termination of the network end devices.

NGC-UIT2-EX
(not used)
CAN

Termination
Reset RS-485-1
Power USB (not used)
RS-485

Termination
RS-232

RS-485-2
(not used)
RS-485

Front view

USB device port


Open Collector Outputs (not used)
Side view Side view

Ethernet
RS-485 2 RS-485 1

Debug Port (not used)

Bottom view
Fig. 3.2 NGC-UIT2-EX touch-screen display, controls, and connections

16 | nVent.com

Downloaded from www.Manualslib.com manuals search engine


3.1.3 RS-485 CONFIGURATION SWITCHES
The configuration switches are found on the right side of the NGC-UIT2-ORD. Refer to table 3.1
for settings.
Table 3.1 NGC-UIT2-ORD Configuration Switch Functions

3 2 1 RS-485-1 RS-485-2
Termination Termination

ON

Pull-down
Pull-up
Termination
Pull-down (As-shipped default) RS-485 RS-485 network “–” signal One and only one device (typically
network “–” signal is forced is not forced to a determinate this NGC-UIT2-ORD) on the RS-485
to a determinate state when state when idle. network should force the network “-“
idle. signal to a determinate state.

Pull-up (As-shipped default) RS-485 network “+” signal One and only one device (typically
RS-485 network “+” signal is not forced to a determinate this NGC-UIT2-ORD) on the RS-485
is forced to a determinate state when idle. network should force the network
state when idle. “+“ signal to a determinate state.
Termination (As-shipped default) RS-485 RS-485 network is not Terminate the device (NGC-UIT2-ORD
network is terminated with terminated. or other) that is at each end of the
120-ohm resistor. RS-485 network, for a total of two
terminated devices. No other devices
on the network should be terminated.

3.1.4 NGC-UIT2-EX RESET SWITCH


The reset switch is located on the side of the NGC-UIT2-EX panel. A pointed object is required
to press the restart switch and restart the UIT2 software.

Reset

Fig. 3.3 Reset switch

nVent.com | 17

Downloaded from www.Manualslib.com manuals search engine


3.2 CARD RACK MODULE (NGC-30-CRM/-CRMS) AND CURRENT TRANSFORMER MODULE (NGC-30-CTM)
Each Card Rack Module (NGC-30-CRM and NGC-30-CRMS) and Current Transformer Module
(NGC-30-CTM) provide ground-fault and line current sensing, alarming, switching, and RTD
input for five Loops. The NGC-30-CRM is used with electromechanical relays. The NGC-30-
CRMS is used with solid-state relays. The NGC-30-CRM/-CRMS may be connected to one
User Interface Terminal (NGC-UIT2).
Each NGC-30-CRM/-CRMS must have a unique communication address. The valid address
switch range for the NGC-UIT2 is 1–99. SW1 is the ones digit (0–9) and SW2 is the tens digit
(0–9). See Fig. 3.6.
IMPORTANT: RMM2s use ModBus addresses 32 through 47 and PLIs use Modbus addresses
1-99. When using RMM2s and PLI modules in an NGC-30 system, care must be taken to not
assign the same addresses to an RMM2, PLI module or an NGC-30-CRM/-CRMS board.

MSB LSB

3
SW2 SW1

Fig. 3.4 Communication address switch

IMPORTANT: When adding an NGC-30-CRM/-CRMS to the system, power must be cycled to


the board and a network update on the NGC-UIT2 must be performed.
NGC-30-CRM/-CRMS 10

MSB LSB

TB 1 TB 2 TB 3 TB 4 TB 5

1 2 3

TB 19
TB 12 TB 7 TB 6
TB 13 TB 14 TB 15 TB 16 TB 17

1 2 3 4 5 6 7 8

1 Alarm output 6 End of Line (EOL) jumper


2 Relay outputs (5x) 7 RS-485 Communications
3 LEDs (9x) 8 Line & ground-fault sensor inputs (5x)
4 Fuse 9 RTD Inputs
5 12 Vdc Inputs (2x) 10 Address Switches

Fig. 3.5 NGC-30-CRM/-CRMS Board l Layout

18 | nVent.com

Downloaded from www.Manualslib.com manuals search engine


Each NGC-30-CRM/-CRMS has a cluster of nine LED lights to advise the status of the board.
Number 3 in Fig. 3.7 shows the location of the LED lights.

Relay 1
Relay 3
Power
Alarm Energized upon Alarm Red

Tx
Power Energizes upon power to unit Green
Relays 1, 2, 3, 4, 5 Energizes upon relay closed Red
RX & TX Energizes upon received and Amber
transmit of RS-485 data

Alarm
Relay 2
Relay 4

Relay 5
Rx
LED functions

Table 3.2 LED Display

3.3 CARD RACK (NGC-30-CR)


The Card Rack (NGC-30-CR) has the capability to house one to four Card Rack Modules (CRMs).

Fig. 3.6 NGC-30 card rack

3.4 VOLTAGE MONITORING MODULE (NGC-30-CVM) – OPTIONAL


The optional voltage sensor can monitor 80–290 Vac. This voltage sensor connects to one of
the five line current/ground-fault inputs of the NGC-30-CRM/-CRMS
(IMPORTANT: By using the optional voltage sensors, the NGC-30-CRM/-CRMS board looses
one circuit).

Fig. 3.7 NGC-30 voltage monitoring module

nVent.com | 19

Downloaded from www.Manualslib.com manuals search engine


3.5 REMOTE MONITORING MODULE (RMM2) – OPTIONAL
The RAYCHEM Remote Monitoring Module (RMM2) provides additional temperature
monitoring capabilities. Each RMM2 accepts up to eight RTDs that measure pipe, vessel,
or ambient temperatures. The RMM2 can be installed in the RAYCHEM NGC-30 enclosure or
can be located in the field to reduce RTD field wiring.The RAYCHEM NGC-30 system supports
260 temperature inputs via the CRM/CRMs boards. Sixteen (16) RMM2s can be connected
via a single, twisted pair RS-485 cable to provide up to 128 additional RTD inputs into the
RAYCHEM NGC-30 system.

Fig. 3.8 RMM2 module

Set the RS-485 address for the RMM2 using the rotary switch provided. Note the orientation of
the clear plastic cover, then remove the cover. Use a slotted screwdriver to rotate the selector
switches to the appropriate positions to select the RS-485 address. The single character visible
on the switch indicates the RS-485 address assigned.

0
0

Fig. 3.9 RMM2 rotary switch

Table 3.3 RMM2 Switch Settings

RMM2 Switch Settings


Switch Settings 0 1 2 3 4 5 6 7 8 9 A B C D E F
Device Address 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47

20 | nVent.com

Downloaded from www.Manualslib.com manuals search engine


3.6 POWER LINE CARRIER INTERFACE MODULE (PLI) – OPTIONAL
RAYCHEM PLI modules (Power Line Carrier Interface) together with RAYCHEM temperature
transmitters provide remote temperature-monitoring capability for heat-tracing control and
monitoring systems by communicating the temperature data to the control system over the
heat-tracing bus wires and the AC power line, eliminating the need for RTD wiring. Typical
savings on the installation costs of a heat-tracing system can be as much as 30% with PLI
technology, depending on the specifics of each application.
The PLI module typically resides in the NGC-30 panel and receives input from special
transmitters connected to the heat-tracing. The transmitters provide pipe temperatures from
RTDs and continuity confirmation; they are typically located at the front and/or end of the
heat-tracing circuit. The PLI special transmitters are: RAYCHEM SES (Smart End Seal),
RAYCHEM SPC (Smart Power Connection) and RAYCHEM 700-TT.
The NGC-30 system can accept up to 127 temperature inputs from SES/SPC transmitters or
255 temperature inputs from 700-TT transmitters, per PLI module. Up to four PLI modules can
be connected to one NGC-30 UIT2.

Fig. 3.10 PLI module

Set the RS-485 address for the PLI module using the rotary switches provided. Note the
orientation of the clear plastic cover, then remove the cover. Use a slotted screwdriver to rotate
the selector switches to the appropriate positions to select the RS-485 address. Each PLI
module must have a unique address, if two PLI modules, CRM or RMM are assigned the same
address, communication faults will result. The PLI module switch setting can be set from 1-99.

S2 0 S1
6
6 0-9
110
.

22 0
.

S + S +
36

S
H N/H G A B C N Norm Mixed

Fig. 3.11 PLI module rotary switch

nVent.com | 21

Downloaded from www.Manualslib.com manuals search engine


3.7 THE REMOTE MONITORING MODULE FOR DIGITAL INPUTS (RMM-DI)
Provides the capability for the RAYCHEM NGC controller family to read the status of devices
remotely and can link them back to the electrical heat-tracing circuits.
The RMM-DI has in total 15 digital inputs. Multiple RMM-DI units can communicate with a
single User Interface providing centralized monitoring capabilities.

5
48
RS
-12
DI
15 -11
DI- DI
14
DI- -10
DI
13
DI- DI
-9

0
DR DI
-8
AD H

0
DR
AD L DI
-7

: -6
23
0V
5V
: DI
11
N -5
L IN mA DI
10
VA V@ -4
N 1.5 12 DI
L Out ~ t: m
in

utpu -3
:O DI
ng
Wiri -2
DI DI
-1
DI

Fig. 3.12 RMM-DI 3D


Control and monitoring
A RAYCHEM NGC network controls up to 260 heat-tracing circuits per system based on
ambient or pipe temperatures. The RMM-DI module can be used to collect circuit breaker
status, contactor status or other digital information in the field. This information will be
communicated back to a central location via one communication cable, reducing installation
and wiring cost.

L N L N 230V: DI-13 DI-14 DI-15


Out IN 115V:
RS 485
~ ADDR
1.5 VA
H
DI Wiring: Output: min 12V @ 10mA
ADDR
L

DI -1 DI -2 DI -3 DI -4 DI -5 DI -6 DI -7 DI -8 DI -9 DI -10 DI -11 DI -12

Fig. 3.13 RMM-DI Front view

22 | nVent.com

Downloaded from www.Manualslib.com manuals search engine


SECTION 4 – APPENDICES

APPENDIX A – REPLACEMENT COMPONENT ORDERING GUIDE

Replacement Components
Description Catalog Number Part Number
User Interface Terminal NGC-UIT2-EX 10332-032
Hazardous and non hazardous C1D2, Zn2
User Interface Terminal with TYPE 4 Enclosure NGC-UIT2-ORD-R 10332-016
Nonhazardous (Unclassified) Locations; indoors or
outdoor, remote stand-alone mounting
NGC-30 Modules
Card Rack Module (for EMRs) NGC-30-CRM 10720-001
Card Rack Module (for SSRs) NGC-30-CRMS 10720-004
Current Transformer Module NGC-30-CTM 10720-002
Voltage Monitoring Module NGC-30-CVM 10720-005
NGC-30 Auxiliary
DB9F-DB9F Null Modem Cable 5 ft NGC-UIT2-RS232 20577020
Remote Monitoring Module RMM2 051778
Remote Monitoring Module with TYPE 4X Enclosure RMM2-4X 523420
Remote Monitoring Module for Zone 2 (ATEX) RMM2-EX-E 676040-000
Remote Monitoring Module for Digital Inputs RMM-DI 12444-016442
Remote Module for Control MONI-RMC-Base 309735-000
Power Line Carrier Interface: Smart End Seal Transmitter
120 V temperature/continuity transmitter SES-RTD-1 265212-000
208 – 277 V temperature/continuity transmitter SES-RTD-2 677596-000
120 V continuity transmitter SES-CONT-1 293536-000
208 – 277 V continuity transmitter SES-CONT-2 398720-000
120 V Smart End Seal replacement transmitter board SES-TT-1 815918-000
208 – 277 V Smart End Seal replacement SES-TT-2 771274-000
transmitter board
Smart End Seal Replacement RTD and stand assembly SES-RTD-Replace 693618-000
Power Line Carrier Interface: Auxiliary Equipment
Front End Filter – 480 V FEF-480 V 922847-000
Front End Filter – 600 V FEF-600 V P000000312
PLI Module PLI 488323-000
RTD lead wire, per 1000 ft reel MONI-RTD-WIRE 962661-000
RS-485 comm. wire, per 1000 ft reel MONI-RS485-WIRE 549097-000

nVent.com | 23

Downloaded from www.Manualslib.com manuals search engine


APPENDIX B – PANEL SPECIFICATIONS

Panel Specifications
Table B.1 Panel Specifications
General
Area of use Nonhazardous Locations Hazardous Locations Hazardous Locations
(EMR purged version) (SSR version)
ETL LISTED ETL LISTED ETL LISTED
CONFORMS TO CONFORMS TO CONFORMS TO
ANSI/UL STD. 508 ANSI/UL STD. 508 UL STD 508A
UL STD. 508A UL STD. 508A ANSI/ISA STD 12.12.01
9700701 9700701 9700701 CERTIFIED TO
CERTIFIED TO CERTIFIED TO CSA STD C22.2 NO. 213
CAN/CSA C22.2 NO. 14 CAN/CSA C22.2 NO. 14 CSA STD C22.2 NO. 14

ETL LISTED
CONFORMS TO
NFPA STD 496
9700701

Approvals
Supply voltage 100 – 240 Vac, +5% / –10%, 50/60 Hz common supply for controller and heat-tracing
circuit Up to 600 Vac for heat-tracing circuit when controller is powered from a separate
circuit
Enclosure
Protection/materials TYPE 12 (indoors painted steel)
TYPE 4/3R (outdoors, painted steel)
TYPE 4X/3RX (outdoors, stainless steel)
Operating Temperature
NGC-UIT2-EX installed Without distribution: –40°F to 140°F (–40°C to 60°C)
Below –13°F (–25°C), space heater and thermostat must be used

With distribution: 14°F to 140°F (–10°C to 60°C)


Below 14°F (–10°C), space heater and thermostat must be used
Storage Temperature
NGC-UIT2-EX installed –40°F to 176°F (–40°C to 80°C)
Relative humidity 0% to 90%, noncondensing

Control
Heat-tracing circuits One NGC-UIT2 can configure and monitor up to 260 heat-tracing circuits
Relay types 3-pole, electromechanical (EMR versions)
1-, 2-, or 3-pole solid-state relays (SSR versions)
Voltage, maximum 240 Vac nominal, 50/60 Hz (standard), 600 Vac nominal (optional)
Current, maximum per circuit* EMR: 30 A @ 104°F (40°C) or 60 A @ 104°F (40°C)
* Depending on panelboard amperage SSR: 30 A @ 104°F (40°C) or 60 A @ 104°F (40°C)
rating, the maximum current may not be
used on all circuits.
Control algorithms EMR: On/Off, Ambient on/off, PASC (proportional ambient sensing control)
SSR: On/Off, Ambient on/off, PASC (proportional ambient sensing control),
Proportional (includes soft start for all SSR control modes)
Control range –99°F to 900°F (–73°C to 482°C)
Dead band 1°F to 50°F (1°C to 50°C) (On/Off control only)

24 | nVent.com

Downloaded from www.Manualslib.com manuals search engine


Table B.1 Panel Specifications
Monitoring
Temperature
Low alarm range –99°F to 900°F (–73°C to 482°C) or OFF
High alarm range –99°F to 900°F (–73°C to 482°C) or OFF
Ground fault
Alarm range 10 mA to 200 mA
Trip range 10 mA to 200 mA or OFF
Current
Low alarm range 0 A to 100 A (where 0 equals OFF)
High alarm range 0 A to 100 A (where 0 equals OFF)
Voltage 100 – 277 Vac supply voltage to heat-tracing
(IMPORTANT: Requires the loss of one circuit)
Temperature Sensor Inputs
Monitoring RAYCHEM NGC-30 system can monitor up to 1040 (260 x 4) temperatures
Quantity per circuit Up to four temperature inputs can be assigned to one circuit
Temperature sources Hard-wired, optional RMM2 Module, optional PLI module
Temperature inputs per control point Standard:
One input standard per control point
Optional:
Up to three additional RTDs per control point connected via RMM2 and/or PLI Module
Temperature inputs per NGC-UIT2 Hard-wired:
Up to 260 hard-wired temperature inputs, one per circuit
RMM2 (optional):
Up to 128 RTD inputs via RMM2 Modules. Up to 8 RTDs per RMM2 Module and up to 16
RMM2 Modules per NGC-30 controller
PLI module (optional):
Up to 127 RTDs via SES Transmitter (per PLI Module)
Up to 127 RTDs via SPC Transmitter (per PLI Module)
Up to 255 RTDs via 700-TT Transmitter (per PLI Module)
Four PLI Modules per circuit, maximums 1040 RTDs
Types 100 W platinum RTD, 3-wire, a = 0.00385 ohms/ohm/°C
Can be extended with a 3-conductor shielded cable of 20 W maximum per conductor
(IMPORTANT: power wire and RTD wire should not be housed in the same conduit).
Alarm Outputs
Relay outputs 3 SPDT Form C. Rating: 3 A 100 – 277 Vac
Each relay may be assigned to alarm outputs
Programming and Setting
Method Via NGC-UIT2 (User Interface Terminal)
Units °F or °C
Digital display
NGC-UIT2-EX 7 inch x 5 ¼ inch LCD color touch screen (17.5 cm X 13.3 cm)
Memory Nonvolatile, restored after power loss
Stored parameters (measured) Minimum and maximum temperatures, contactor cycle count, heater time in use
Alarm conditions Low/high temperature, low/high current, ground-fault alarm and trip, RTD failure,
communications failure, relay failure, relay count, total time heater energized, contactor
failure
nVent.com | 25

Downloaded from www.Manualslib.com manuals search engine


Table B.1 Panel Specifications

User Interface Terminals (UITs)


NGC-UIT2-EX Area Classification: Nonhazardous (Unclassified) or Hazardous Locations
Usage: TYPE 4 (indoors or outdoors)
NGC-UIT2-ORD-R Area Classification: Nonhazardous (Unclassified) Locations
The NGC-UIT2-ORD-R must be installed in a
nonhazardous, indoor or outdoor location.
The NGC-UIT2-ORD-R connects to RAYCHEM NGC-30
panels using RS-485 communications wiring.
Usage: TYPE 4 (indoors or outdoors)
Connection Terminals
Heating cable output Screw terminals, 20–6 AWG
(30 A versions), 14–2 AWG
(60 A versions)
Ground 14–4 AWG ground bar
RTD / alarm / communications 28–12 AWG spring clamp terminals
Distribution (for RAYCHEM NGC-30 EMR only)
Load power 120 / 208 / 240 / 277 / 347 / 480 /
600 Vac
Standard circuit breakers US (United States country code in ordering details):
Square D type QOB 120 / 208 / 240
Square D type NF 277 / 480
CA (Canada country code in ordering details):
Cutler Hammer (Canada) type BAB 120 / 208 / 240
Cutler Hammer (Canada) type GBH 277 / 480 / 347 / 600
Circuit breaker amperage rating 120 Vac 120 Vac
208, 240, 277, 347, 480, 600 Vac 208, 240, 277, 347, 480, 600 Vac

26 | nVent.com

Downloaded from www.Manualslib.com manuals search engine


APPENDIX C – NGC-30-CRM/-CRMS SPECIFICATIONS

Table C.1 NGC-30-CRM/-CRMS Specifications


General
Approvals/certifications Class I, Div. 2, Groups A,B,C,D
Ex nC IIC T5
Class I, Zone 2, AEx nC IIC T5

Supply voltage 12 Vdc ± 10%


Internal power consumption < 5 W per NGC-30-CRM/-CRMS
Operating temperature –40°F to 140°F (–40°C to 60°C)
Storage temperature –40°F to 167°F (–40°C to 75°C)
Environment PD2, CAT III
Max. altitude 2000 m
Humidity 0–90% noncondensing
Electromagnetic Compatibility
Immunity Heavy industrial
Emission Residential, commercial, light industrial
Temperature Sensors
Type 100 W platinum RTD, 3 wire, a = 0.00385 ohms/ohm/°C
Can be extended with a 3-conductor shielded cable of 20 ohm maximum per conductor
Quantity Up to five wired directly to each NGC-30-CRM/-CRMS
Current Sensors
Mounting DIN Rail – 35 mm
Quantity per NGC-30-CTM Five for ground-current measurement. Five for line-current measurement
Line Current Sensors
Max. current 60 A
Accuracy ± 2% of reading
Ground-Fault Sensor
Range 10–200 mA
Accuracy ± 4% of range at 30 A line current
Voltage Sensor
Range 80–290 Vac 50/60 Hz
Accuracy ± 1% of span
Outputs
CRM output relays Form A 3-Amp @ 277 Vac max 50/60 Hz
CRMS SSR outputs 12 Vdc @ 30 mA max per output
Alarm relay Form C 3-Amp @ 277 Vac max 50/60 Hz
Communication to NGC-UIT2 or 200N
Type 2-wire RS-485
Cable One shielded twisted pair
Length 4000 ft. (1200 m) maximum*
*IMPORTANT: May require an RS-485 repeater if communication length is greater
than 4000 ft.
Quality Up to 52* NGC-30-CRM/-CRMS may be connected to one NGC-UIT2
Up to 16 NGC-30-CRM/-CRMS may be connected to one 200N
Connection Terminals
Power supply/pilot relay/RTD/ 18–12 AWG (0.8 - 3.3 mm2)
comm port (RS485)
nVent.com | 27

Downloaded from www.Manualslib.com manuals search engine


APPENDIX D – NGC-UIT2 SPECIFICATIONS

Table D.1 NGC-UIT2-EX Specifications


General
Approvals NGC-UIT2-EX
Nonhazardous Locations Hazardous Locations
|| 3G ITS15ATEX18221X
Ex nA IIC T5 Gc IECEx ETL 15.0015X RU C-BE-MЮ62.B.02850
Class | Div.2 Groups A,B,C,D T5 2Ex nA IIC T5 Gc X
RoHS
–40°C ≤Ta ≤ 60°C
4000758
LR67275

Area of use Ordinary (nonhazardous) and Hazardous locations,


indoors or outdoors (IP65, Type 4X)
Supply voltage 9 – 30 Vdc, 15 W Max, AWG 18-22 (0.9 mm - 0.52 mm )
2 2

Operating temperature –40°C to 60°C (–40°F to 140°F)


Minimum storage temperature –40°C to 80°C (–40°F to 176°F)
Dimensions 279 mm W X 229 mm H X 70 mm D (11 in. W X 9 in. H X 2.75 in. D)
Humidity Range 10 to 90% Non-Condensing
Approvals NGC-UIT2-ORD-R
Nonhazardous Locations

Area of use Nonhazardous, indoors or outdoors (IP65, TYPE4)


Supply voltage 9 – 30 Vdc, 3.6 – 1.2 A
Operating temperature –22°F to 140°F (–30°C to 60°C)
Minimum storage temperature –22°F to 176°F (–30°C to 80°C)
Dimensions 11" W X 9" H X 2.75" D (279 mm W X 229 mm H X 70 mm D)
Alarm Outputs
Transistor open collector outputs Three open collector outputs, with a range of 5 – 30 Vdc with a max.
sink current of 500 mA
Use to drive external relays Relays may be assigned for alarm outputs
LCD Display
Display LCD is a 8.4 inch XGA, color TFT transflective device with integral LED backlight
Touch screen 5-wire resistive touch screen interface for user entry
Network Connection
Local/Remote Port RS-232/RS-485 ports may be used to communicate with host computers
(RAYCHEM Supervisor Software) or DCS
Local RS-232 A non-isolated, 9 pin D sub male
Remote RS-485 #2 2-wire isolated, 9 pin D sub male
Data rate Data Rate 9600 to 57600 baud
Maximum cable length For RS-485 not to exceed 4,000 ft (1,200 m). Cable to be shielded twisted pair.
Field Port RS-485, 2-wire isolated. Used to communicate with external devices, such as
NGC-30-CRM and RMM2. Maximum cable length not to exceed 4,000 ft (1,200 m).
Cable to be shielded twisted pair.
Field RS-485 #1 2-wire isolated, 9 pin D sub male
Data rate Data Rate To 9600 baud
LAN 10/100 Base-T Ethernet port with Link and Activity Status LEDs
USB Ports USB 2.0 Host port Type A receptacle (X2)

28 | nVent.com

Downloaded from www.Manualslib.com manuals search engine


APPENDIX E – DEVICE ADDRESS

Table E.1 Device Address


Device Device Type Switch Setting Device Address
NGC-30-CRM/-CRMS Relay Output/RTD 1–99 1–99
(If RMM2s are equipped or
will be added in the future,
skip addresses 32–47)
RMM2 RTD 0 32
RMM2 RTD 1 33
RMM2 RTD 2 34
RMM2 RTD 3 35
RMM2 RTD 4 36
RMM2 RTD 5 37
RMM2 RTD 6 38
RMM2 RTD 7 39
RMM2 RTD 8 40
RMM2 RTD 9 41
RMM2 RTD A 42
RMM2 RTD B 43
RMM2 RTD C 44
RMM2 RTD D 45
RMM2 RTD E 46
RMM2 RTD F 47
PLI module RTD 1-99 1-99

nVent.com | 29

Downloaded from www.Manualslib.com manuals search engine


APPENDIX F – RAYCHEM RMM-DI TECHNICAL SPECIFICATION
Table F.1 RAYCHEM RMM-DI technical specification
General
Area of use Hazardous area when mounted in Ex-d enclosure
RMM-DI panel mount, safe area
Approval

(Russia, Kazakhstan, Belarus)


For other countries contact your local nVent representative.
Ambient operating temperature range –40°C to +60°C
Ambient storage temperature range –51°C to +60°C
Relative humidity Max. 95%, noncondensing
Supply voltage (Nominal) 115/230 Vac +10% -10%
50/60 Hz (jumper selectable)
Dimensions and mounting
Dimensions 125 mm x 75 mm x 60 mm, see drawing
Mounting DIN rail mountable
Digital input
Type 2 wire digital input
Supplied power Minimum power per DI connection supplied by RMM-DI module
12V 10mA (Sink/source)
Number of signals 15 Digital inputs
Communication to RAYCHEM NGC control system
Type RS-485
Protocol Modbus RTU
Cable type Shielded twisted pair
Length cable 1200 m max.
Address switch Selectable on RMM-DI, address range: 1-255
Connection terminals
Supply (in-out) 4 terminals for cables 0.2 mm2 to 4 mm2
RS-485 connection 2 x 3 terminals for cables 0.2 mm2 to 2.5 mm2
DI connections 15 x 2 terminals for cables 0.2 mm2 to 2.5 mm2
Electromagnetic compatibility
EN 60730-1: 2011
EN 61000-6-3:2007+A1:2011 EN 61000-3-2:2006 +A1:2009+A2:2009
EN 61000-3-3:2008
EN 61000-6-2:2005
Ordering details
Part Description RMM-DI
Product Number 1244-016442
EAN 5414506015560

30 | nVent.com

Downloaded from www.Manualslib.com manuals search engine


nVent.com | 31

Downloaded from www.Manualslib.com manuals search engine


North America Europe, Middle East, Africa Asia Pacific Latin America
Tel +1.800.545.6258 Tel +32.16.213.511 Tel +86.21.2412.1688 Tel +1.713.868.4800
Fax +1.800.527.5703 Fax +32.16.213.604 Fax +86.21.5426.3167 Fax +1.713.868.2333
thermal.info@nvent.com thermal.info@nvent.com cn.thermal.info@nvent.com thermal.info@nvent.com

nVent.com

©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners.
nVent reserves the right to change specifications without notice.
Raychem-IM-H58585-NGC30UIT2-EN-180