Installation manual
2 | nVent.com
1.1 INTRODUCTION
The nVent RAYCHEM NGC-30 is a fully wired and tested control and monitoring system used
with electric heat tracing. This manual provides information pertaining to the installation,
operation, testing, adjustment, and maintenance of all components of the RAYCHEM NGC-30
System. For information about how to program the RAYCHEM NGC-30, see the RAYCHEM
NGC-30 Programming Guide (H58186)
A typical RAYCHEM NGC-30 is made up of at least a User Interface Terminal (NGC-UIT2),
one Card Rack (NGC-30-CR), one Card Rack Module with connectors
(NGC-30-CRM or NGC-30-CRMS), and one Current Transformer Module (NGC-30-CTM).
Optional Remote Monitoring Module for Temperatures (RMM2), Power Line Carrier Interface
(PLI), RMC modules, Remote Monitoring Module for Digital Inputs (RMM-DI) and Voltage
Monitoring Module (NGC-30-CVM) may be used.
The information in this document coincides with the specific releases of firmware
(listed in Table 1.1) for the User Interface Terminal (NGC-UIT2) and Card Rack Module
(NGC-30-CRM/-CRMS) components. As nVent releases new firmware to significantly modify
or enhance any of these components, new documentation will accompany these releases.
To ensure that the correct documentation is being used for your particular version of the
RAYCHEM User Interface Terminal (NGC-UIT2), compare the firmware version number of
each component against the number listed in the table below. As subsequent changes are
made, supplements to this document will be included in manuals shipped after the firmware is
released. Supplements will make specific reference to the operation or functional change.
Copies of this manual and updates may be downloaded from the Literature section of
nVent.com.
nVent.com | 3
2.1 INTRODUCTION
WARNING:
Electrical Hazard! Ensure all personnel involved in installation, servicing, and programming are
qualified and familiar with electrical equipment, its ratings, and proper practices and codes.
Multiple voltages and signal levels may be present during the installation, operation, and
servicing of this product. Do not power the product until the safety provisions outlined in this
section have been observed.
This section includes information regarding the initial inspection, preparation for use,
and wiring instructions for the components of the RAYCHEM NGC-30.
WARNING:
Some wiring configurations will use more than one power source. All power sources must be
de-energized prior to performing any maintenance on a card rack module or its heating circuit.
The operating environment should be within the limitations specified for the RAYCHEM
NGC-30 components as outlined in Appendices B, C, and D.
4 | nVent.com
Always be sure that the intended location is classified as an area that the product is approved
for use in as defined by Article 500 of the National Electrical Code and/or Part I, Section 18 of
the Canadian Electrical Code.
Incomming service
Three phase, 4 wire, 60 Hz
ØA ØB ØC Main circuit
breaker
3-pole
Panelboard
neutral bus
Panelboard
ground bus
nVent.com | 5
TB*
CRM
X CTM
connector TB- (Y)
Cable-CT**
13
14
15
16
17
LP
L2 *–L2 *–T2 T2
Fig. 2.3 Single pole and two pole circuit breaker wiring diagrams
6 | nVent.com
RMM-DI
RMM2
PLI
NGC-UIT2-EX S2 0 S1
6
6 0-9
110
.
220
.
S + S +
36
S
H N/H G A B C N Norm Mixed
NGC-UIT2-EX
NGC-UIT2-EX
NGC-CRM/-CRMS
MSB LSB
TB 1 TB 2 TB 3 TB 4 TB 5
1 2 3
NGC-CRM/-CRMS
TB 19
TB 12 TB 7 TB 6
TB 13 TB 14 TB 15 TB 16 TB 17
MSB LSB
NGC-CRM/-CRMS
MSB LSB TB 1 TB 2 TB 3 TB 4 TB 5
1 2 3
TB 19
TB 12 TB 7 TB 6
TB 13 TB 14 TB 15 TB 16 TB 17
TB 1 TB 2 TB 3 TB 4 TB 5
NGC-CRM/-CRMS
1 2 3
TB 19
TB 12 TB 7 TB 6
TB 13 TB 14 TB 15 TB 16 TB 17
MSB LSB
PLI
TB 1 TB 2 TB 3 TB 4 TB 5
1 2 3
S2 0 S1
6
TB 19
6 0-9 TB 12 TB 7 TB 6
TB 13 TB 14 TB 15 TB 16 TB 17
110
.
220
NGC-CRM/-CRMS
.
S + S +
36
S
H N/H G A B C N Norm Mixed
RMM2
MSB LSB
Jumper
TB 1 TB 2 TB 3 TB 4 TB 5
1 2 3
0 TB 19
TB 12 TB 7 TB 6
TB 13 TB 14 TB 15 TB 16 TB 17
RMM-DI
NGC-30 Panel
5
* Reference panel drawing for terminal block number
4
TB*
S 3 1 1 1 1
S
4
S
S S S S S
+ + + +
(+) 2 2 2 2 2 5 BK
BK BK BK BK BK BK
– – – –
(–) 1 3 3 3 3 6 WH
WH WH WH WH WH WH
TB* TB* TB* TB*
RS-485 RS-485
NGC-UIT2 NGC-30-CRM/-CRMS #1 NGC-30-CRM/-CRMS #8 RS-485
RMM2
Jumper
Fig. 2.6 RMM2 RS-485 field wiring and termination jumper setting
8 | nVent.com
NGC-30 Panel
S2 5 S1
9
6 5
110
.
220
RS-485 connections
.
S + – S + –
S 3 1 1 1 1 36
S S S S S S
H N/H G A B C N Norm Mixed
+ +
(+) 2 2 2 2 2
BK BK BK BK BK
(–) 1 – –
3 3 3 3
WH WH WH WH WH
TB* TB* TB* TB*
RS-485 RS-485
NGC-UIT NGC-30-CRM/-CRMS #1 NGC-30-CRM/-CRMS #8 RS-485
J2
1 2 3
Default position (for all PLI Termination mode
units in network except first or last one) (first or last PLIin network)
J2 J2
1 2 3 1 2 3
Last PLI in network
Fig. 2.7 PLI RS-485 panel wiring and termination jumper setting
NGC-UIT2 Installation
The NGC-UIT2-EX will come pre-wired into any NGC-30 panel. Exceptions exist when a remote
mount NGC-UIT2 (NGC-UIT2-ORD-R) is used or the NGC-30 panel is wired to the NGC-UIT2
in another panel. Fig. 2.8 shows the wiring for the NGC-UIT2-ORD-R and Fig. 2.10 shows the
wiring between a separate panel and the NGC-UIT2.
nVent.com | 9
RS-485+
NGC-UIT2-ORD-R
RS-485–
SR 9 8 7 6
5 4 3 2 1
Field Remote
RS-485 Ports
RS-485
TB*
3 1 1 1 1
S S S S S
+ + + +
BK
2 BK
2 2 2 2
BK BK BK
– – – –
WH
1 WH
3 3 3 3
WH WH WH
TB* TB* TB* TB*
The following figure shows the RS-485 termination options for the NGC-30-CRM/-CRMS.
NGC-30-CRM/-CRMS
MSB LSB
TB 1 TB 2 TB 3 TB 4 TB 5
1 2 3
TB 19
TB 12 TB 7 TB 6
TB 13 TB 14 TB 15 TB 16 TB 17
10 | nVent.com
NGC-30 Panel #1
6
* Reference panel drawing for terminal block number
5
4
TB*
S 3 1 1 1 1
S
4
S
S S S S S
+ + + +
(+) 2 2 2 2 2 5 BK
BK BK BK BK BK BK
– – – –
(–) 1 3 3 3 3 6 WH
WH WH WH WH WH WH
TB6 TB6 TB6 TB6
RS-485 RS-485
NGC-UIT2 NGC-30-CRM/-CRMS #1 NGC-30-CRM/-CRMS #8 RS-485
RS-485
NGC-30 Panel #2
without UIT installed
TB*
1 1 1 1 1
S S S S S
+ + + +
BK
2 BK 2 2 2 2
BK BK BK
– – – –
WH
3 WH
3 3 3 3
WH WH WH
TB6 TB6 TB6 TB6
RS-485 RS-485
NGC-30-CRM/-CRMS #1 NGC-30-CRM/-CRMS #8
Fig. 2.10 RS-485 field wiring between two RAYCHEM NGC-30 panels
nVent.com | 11
NC NC NC
C C C
NO NO NO
The NGC-UIT2 has two other Form C alarm relays (configurable through the NGC-UIT2 program)
for external alarms. Each relay can be connected to an annunciator light or distributed control
system. Each relay’s contacts have been wired from the NGC-UIT2 to a terminal block in the
panel.
NGC-UIT2 Relay 2
Non-energized Energized without an alarm condition Energized with an alarm condition
NC NC NC
C C C
NO NO NO
NGC-UIT2 Relay 3
Non-energized Energized without an alarm condition Energized with an alarm condition
NC NC NC
C C C
NO NO NO
IMPORTANT: An energized relay with no alarm condition will change state with loss of power
or an alarm condition.
12 | nVent.com
PC Laptop
9-pin
female
9-pin
male
9-pin
female
5-foot 9-pin female D connector
RS-232
Side view
NGC-30 Panel
PC
TB*
6 3
S S
+ + RS-485 Converter
5 BK
2 BK
–
1
– 9-pin
4
WH WH male
S 3 RS-485 9-pin
S
female
(+) 2
BK
(–) 1 To NGC-30-CRM/-CRMS
WH
nVent.com | 13
Ethernet
Bottom view
Ethernet cable
3. C
onfirm all modules have been scanned into the Network database.
4. If a device or an RTD is installed but does not show up in the Network | Devices Screen,
turn the power off to the system and:
For Devices:
a. Confirm the device has a unique address (refer to section 3.2 on page 24)
b. Confirm the device is being powered
c. C
onfirm the RS-485 connection is in place with the correct polarity (refer to section 2.6.5)
For RTDs:
a. Confirm the RTD connection is in place with the correct polarity
b. P
erform a resistance check of the RTD. The resistance should be in a range of 70–250
ohms
Turn the power on to all devices (NGC-30-CRMs/-CRMSs and optional RMM2s & PLI) and the
NGC-UIT2. Once the NGC-UIT2 has booted up to the Main screen, Go to the Network | Device
Screen and press “Update Network.” Confirm all NGC-30-CRM s/ -CRMSs, RTDs, and/or RMM2s
and PLI modules have been scanned into the Network database.
14 | nVent.com
Fig. 3.1 Typical NGC-UIT2 model showing NGC-UIT2-ORD-R remote user interface terminal
The physical dimensions of each NGC-UIT2 model vary; the dimensions of the
NGC-UIT2-ORD-R shown in the figure are the largest of all NGC-UITs:
• Width: 15.21” (386 mm)
• Height: 13.21” (336 mm)
• Depth: 7.09” (180 mm)
NGC-UIT2 LCD Touch-Screen Display
The NGC-UIT2-EX and NGC-UIT2-ORD-R have a 7 inch wide x 5 ¼ inch high LCD
(17.5 cm X 13.3 cm) LCD color display. All NGC-UIT2 have touch-screen technology that
provides an user interface easy and efficient programming with no keyboards or cryptic labels.
nVent.com | 15
NGC-UIT2-EX
(not used)
CAN
Termination
Reset RS-485-1
Power USB (not used)
RS-485
Termination
RS-232
RS-485-2
(not used)
RS-485
Front view
Ethernet
RS-485 2 RS-485 1
Bottom view
Fig. 3.2 NGC-UIT2-EX touch-screen display, controls, and connections
16 | nVent.com
3 2 1 RS-485-1 RS-485-2
Termination Termination
ON
Pull-down
Pull-up
Termination
Pull-down (As-shipped default) RS-485 RS-485 network “–” signal One and only one device (typically
network “–” signal is forced is not forced to a determinate this NGC-UIT2-ORD) on the RS-485
to a determinate state when state when idle. network should force the network “-“
idle. signal to a determinate state.
Pull-up (As-shipped default) RS-485 network “+” signal One and only one device (typically
RS-485 network “+” signal is not forced to a determinate this NGC-UIT2-ORD) on the RS-485
is forced to a determinate state when idle. network should force the network
state when idle. “+“ signal to a determinate state.
Termination (As-shipped default) RS-485 RS-485 network is not Terminate the device (NGC-UIT2-ORD
network is terminated with terminated. or other) that is at each end of the
120-ohm resistor. RS-485 network, for a total of two
terminated devices. No other devices
on the network should be terminated.
Reset
nVent.com | 17
MSB LSB
3
SW2 SW1
MSB LSB
TB 1 TB 2 TB 3 TB 4 TB 5
1 2 3
TB 19
TB 12 TB 7 TB 6
TB 13 TB 14 TB 15 TB 16 TB 17
1 2 3 4 5 6 7 8
18 | nVent.com
Relay 1
Relay 3
Power
Alarm Energized upon Alarm Red
Tx
Power Energizes upon power to unit Green
Relays 1, 2, 3, 4, 5 Energizes upon relay closed Red
RX & TX Energizes upon received and Amber
transmit of RS-485 data
Alarm
Relay 2
Relay 4
Relay 5
Rx
LED functions
nVent.com | 19
Set the RS-485 address for the RMM2 using the rotary switch provided. Note the orientation of
the clear plastic cover, then remove the cover. Use a slotted screwdriver to rotate the selector
switches to the appropriate positions to select the RS-485 address. The single character visible
on the switch indicates the RS-485 address assigned.
0
0
20 | nVent.com
Set the RS-485 address for the PLI module using the rotary switches provided. Note the
orientation of the clear plastic cover, then remove the cover. Use a slotted screwdriver to rotate
the selector switches to the appropriate positions to select the RS-485 address. Each PLI
module must have a unique address, if two PLI modules, CRM or RMM are assigned the same
address, communication faults will result. The PLI module switch setting can be set from 1-99.
S2 0 S1
6
6 0-9
110
.
22 0
.
S + S +
36
S
H N/H G A B C N Norm Mixed
nVent.com | 21
5
48
RS
-12
DI
15 -11
DI- DI
14
DI- -10
DI
13
DI- DI
-9
0
DR DI
-8
AD H
0
DR
AD L DI
-7
: -6
23
0V
5V
: DI
11
N -5
L IN mA DI
10
VA V@ -4
N 1.5 12 DI
L Out ~ t: m
in
utpu -3
:O DI
ng
Wiri -2
DI DI
-1
DI
22 | nVent.com
Replacement Components
Description Catalog Number Part Number
User Interface Terminal NGC-UIT2-EX 10332-032
Hazardous and non hazardous C1D2, Zn2
User Interface Terminal with TYPE 4 Enclosure NGC-UIT2-ORD-R 10332-016
Nonhazardous (Unclassified) Locations; indoors or
outdoor, remote stand-alone mounting
NGC-30 Modules
Card Rack Module (for EMRs) NGC-30-CRM 10720-001
Card Rack Module (for SSRs) NGC-30-CRMS 10720-004
Current Transformer Module NGC-30-CTM 10720-002
Voltage Monitoring Module NGC-30-CVM 10720-005
NGC-30 Auxiliary
DB9F-DB9F Null Modem Cable 5 ft NGC-UIT2-RS232 20577020
Remote Monitoring Module RMM2 051778
Remote Monitoring Module with TYPE 4X Enclosure RMM2-4X 523420
Remote Monitoring Module for Zone 2 (ATEX) RMM2-EX-E 676040-000
Remote Monitoring Module for Digital Inputs RMM-DI 12444-016442
Remote Module for Control MONI-RMC-Base 309735-000
Power Line Carrier Interface: Smart End Seal Transmitter
120 V temperature/continuity transmitter SES-RTD-1 265212-000
208 – 277 V temperature/continuity transmitter SES-RTD-2 677596-000
120 V continuity transmitter SES-CONT-1 293536-000
208 – 277 V continuity transmitter SES-CONT-2 398720-000
120 V Smart End Seal replacement transmitter board SES-TT-1 815918-000
208 – 277 V Smart End Seal replacement SES-TT-2 771274-000
transmitter board
Smart End Seal Replacement RTD and stand assembly SES-RTD-Replace 693618-000
Power Line Carrier Interface: Auxiliary Equipment
Front End Filter – 480 V FEF-480 V 922847-000
Front End Filter – 600 V FEF-600 V P000000312
PLI Module PLI 488323-000
RTD lead wire, per 1000 ft reel MONI-RTD-WIRE 962661-000
RS-485 comm. wire, per 1000 ft reel MONI-RS485-WIRE 549097-000
nVent.com | 23
Panel Specifications
Table B.1 Panel Specifications
General
Area of use Nonhazardous Locations Hazardous Locations Hazardous Locations
(EMR purged version) (SSR version)
ETL LISTED ETL LISTED ETL LISTED
CONFORMS TO CONFORMS TO CONFORMS TO
ANSI/UL STD. 508 ANSI/UL STD. 508 UL STD 508A
UL STD. 508A UL STD. 508A ANSI/ISA STD 12.12.01
9700701 9700701 9700701 CERTIFIED TO
CERTIFIED TO CERTIFIED TO CSA STD C22.2 NO. 213
CAN/CSA C22.2 NO. 14 CAN/CSA C22.2 NO. 14 CSA STD C22.2 NO. 14
ETL LISTED
CONFORMS TO
NFPA STD 496
9700701
Approvals
Supply voltage 100 – 240 Vac, +5% / –10%, 50/60 Hz common supply for controller and heat-tracing
circuit Up to 600 Vac for heat-tracing circuit when controller is powered from a separate
circuit
Enclosure
Protection/materials TYPE 12 (indoors painted steel)
TYPE 4/3R (outdoors, painted steel)
TYPE 4X/3RX (outdoors, stainless steel)
Operating Temperature
NGC-UIT2-EX installed Without distribution: –40°F to 140°F (–40°C to 60°C)
Below –13°F (–25°C), space heater and thermostat must be used
Control
Heat-tracing circuits One NGC-UIT2 can configure and monitor up to 260 heat-tracing circuits
Relay types 3-pole, electromechanical (EMR versions)
1-, 2-, or 3-pole solid-state relays (SSR versions)
Voltage, maximum 240 Vac nominal, 50/60 Hz (standard), 600 Vac nominal (optional)
Current, maximum per circuit* EMR: 30 A @ 104°F (40°C) or 60 A @ 104°F (40°C)
* Depending on panelboard amperage SSR: 30 A @ 104°F (40°C) or 60 A @ 104°F (40°C)
rating, the maximum current may not be
used on all circuits.
Control algorithms EMR: On/Off, Ambient on/off, PASC (proportional ambient sensing control)
SSR: On/Off, Ambient on/off, PASC (proportional ambient sensing control),
Proportional (includes soft start for all SSR control modes)
Control range –99°F to 900°F (–73°C to 482°C)
Dead band 1°F to 50°F (1°C to 50°C) (On/Off control only)
24 | nVent.com
26 | nVent.com
28 | nVent.com
nVent.com | 29
30 | nVent.com
nVent.com
©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners.
nVent reserves the right to change specifications without notice.
Raychem-IM-H58585-NGC30UIT2-EN-180