Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
Download as pdf or txt
Download as pdf or txt
You are on page 1of 88

PRODIGY 2.

0
(M3 UNIT CONTROLLER)
SETUP GUIDE
507241-07
5/2022
Supersedes 10/2019

WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be properly grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies
before opening access panel. Unit may have multiple power supplies.

WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be
performed by a licensed professional HVAC installer or equivalent, service agency, or the gas supplier.

WARNING
To prevent serious injury or death:
1. Lock-out/tag-out before performing maintenance.
2. If system power is required (e.g., smoke detector maintenance), disable power to blower, remove fan belt where applicable, and ensure all controllers and
thermostats are set to the “OFF” position before performing maintenance.
3. Always keep hands, hair, clothing, jewelry, tools, etc. away from moving parts.

1
Table of Contents
1. Prodigy 2.0 – M3 Unit Controller 11. Thermal Protection Switches (S5, S7, 16. Parts and Kits...........................................36
Overview.....................................................3 S8, S31 and S180).....................................26
17. USB Service Report Example..................36
2. Start-Up Procedure....................................3 11.1. Energence Ultra-High Efficiency Units
(3- to 6-ton)............................................26 18. USB SmartAirflow Report........................37
3. M3 Unit Controller - Connections, 11.2. Tandem Compressors — Energence
Inputs / Outputs, Jumpers, and LEDs 19. Alarms ......................................................37
Ultra-High Efficiency Units (7-1/2 to
Locations....................................................3 19.1. Phase - Voltage Detection.....................37
12-1/2-ton).............................................26
4. System Status Screen................................5 11.3. Tandem Compressors — Energence 19.2. Service Relays.......................................38
4.1. Network Types.........................................6 Ultra-High Efficiency Units (15- and
20-ton) ..................................................26 20. M3 Unit Parameters..................................48
4.2. Unit Operation..........................................6
12. Blower Operation with Effective 21. M3 Unit Controller Signal References ... 73
4.3. Alarm Status Display...............................6
Occupancy ...............................................26
4.4. Normal Mode and Status Messages........6 22. M3 Unit Controller Connections
13. Economizer ..............................................29 Diagram.....................................................74
5. Firmware Update .......................................7
13.1. Enabling Economizer and Settings........29 23. M3 Unit Controller (A55)..........................75
5.1. Unit Controller USB Flash Drive
13.2. Damper Feedback Calibration...............29 23.1. GP3 Control (A187)...............................81
Update Capability....................................7
13.3. Damper Operation During Free 23.2. C3 Control (A178)..................................82
5.2. Files Needed for Firmware Updating.......7
Cooling ..................................................29
5.3. Where to Place the .P2F File on the 24. Quick Start Guide.....................................84
13.4. Free Cooling Compressor Lockout
USB Thumb Drive....................................7
Mode and Low Ambient Set Point..........29 25. Wiring Diagrams.......................................85
5.4. Updating Firmware..................................7
13.5. Outdoor Air Suitable for Free Cooling ...29
26. Prodigy 2.0 Release History....................87
6. Saving and Loading User Profile .............8 13.6. Enthalpy Set Point ................................30
7. Saving and Loading USB Profile .............8 13.7. Free Cooling Damper Maximum
Position .................................................30
8. Model Number and Configuration ID 1
and 2............................................................8 13.8. Minimum Damper Position ....................30

8.1. Model.......................................................8 13.9. Motorized Outdoor Air Damper .............30

8.2. Configuration ID 1....................................9 13.10. Economizer Checkout ...........................30

8.3. Configuration ID 2....................................9 14. Demand Control Ventilation ...................32


9. Menu Selection Overview........................10 14.1. Default Operation ..................................32
14.2. Maximum and Minimum Demand
10. Menu Navigation ...................................... 11 Control Ventilation Damper Settings .....32
10.1. Data....................................................... 11 14.3. Parameter Adjustments ........................33
10.2. Setup.....................................................15 14.4. Set Point Control Option........................33
10.3. Service...................................................20 14.5. Determining Indoor Air Quality Inputs....33
10.4. Settings..................................................22 14.6. BACNET................................................34
14.7. L CONNECTION....................................34

15. Abbreviations...........................................35
2
1. Prodigy 2.0 – M3 Unit Controller Overview • May be connected to a PC which has been loaded with unit controller
For all available Prodigy 2.0 documentation, go to the Lennox Commercial software,
website. • Accepts add-on controls to build variations according to application or
www.lennoxcommercial.com equipment type. Unit Sizes
The M3 unit controller: • USB verification and profile sharing.
• Provides control functions for both Energence® and Strategos® Rooftop Units,
• Includes a 4 x 20 LCD display, USB port, menu selection LED and various 2. Start-Up Procedure
navigation tools, a. Turn on unit and dismiss alarm messages as necessary by pressing the
BACK button.
• Provides status and diagnostic information for troubleshooting,
b. Press the SCROLL button down arrow repeatedly to navigate to the SETUP
• Allows adjustment of time delays and setpoints that enable advanced
option and press the SELECT button. Press the SELECT button again for the
features,
INSTALL option. This will start the configuration process.
• Is controlled by a standard room thermostat, direct digital controller (DDC),
NOTE: The system needs to be in a normal operating mode as seen on display
or a room sensor,
(NO DEMAND, COOLING, HEATING, IDLE, etc).
• Can be configured as a device on the network when daisy-chained to the L c. To verify operation navigate to SERVICE > TEST menu.
Connection® Network,
See “24. Quick Start Guide” on page 84 for additional start up information.
3. M3 Unit Controller - Connections, Inputs / Outputs, Jumpers, and LEDs Locations

A. TO DISCONNECT
TSTAT_COM FROM COM
JUMPER (CUT JUMPER)
B. TO DISCONNECT HMD_COM
FROM COM JUMPER (CUT
JUMPER)
C. USB INTERFACE
D. S-BUS INTERFACE
NO DEMAND - OAS E. RJ-11 PHONE JACK
ZAT: 56.0F F. SMART WIRE INTERFACES
DAT: 75.0F UNOCC
G. COMMUNICATION MODULE
INTERFACE
H. DEMAND STATUS LEDS
I. SYSTEM HEART BEAT LEDS
I E H K J. MODBUS CONNECTOR

B J (currently available only on


Energence Ultra-A Box M3
Unit Controller)

G C A K. MODBUS TX AND RX LEDS


(available only on Energence
Ultra-A Box M3 Unit Controller)

D F
Figure 1. M3 Unit Controller Interfaces and LEDs Locations

3
a. THERMOSTAT COMMON ISOLATION - TSTAT_COM Jumper A list of service connection kits is listed on “Table 14. Parts and Kits Available for
Thermostat (TSTAT) sensor commons are located on connector P298 and may M3 Unit Controller” on page 36.
be isolated if they are powered remotely. Remove jumper. f. SMARTWIRE™ FIELD WIRING CONNECTIONS (P297, P298 AND P299)
This jumper is located to the left of P297 connector. This jumper would be These connectors allow for easy field wiring connection points. The M3 unit
removed only in unique situations where the device supplying the thermostat controller connects to the rooftop unit using SmartWire™ connectors. Each
signals to the M3 unit controller has its own power source and does not share connector is keyed so that no connector can be installed in the incorrect location.
a common reference voltage with the M3 unit controller. Otherwise the jumper Be sure all connectors are in place and completely inserted. See “21. M3 Unit
would remain installed across both pins, as shipped from the factory. Controller Signal References” on page 73 for connector information.
b. HUMIDISTAT COMMON ISOLATION -: HMD_COM Jumper g. COMMUNICATION MODULE INTERFACE
The humidity (HUM) sensor commons are located on connector P298 and may This connection is used for either BACnet® or LonTalk® communication modules.
be isolated if they are powered remotely. Remove jumper. This jumper is located
to the right of P299 connector. This jumper would be removed only in unique h. DEMAND STATUS LEDS - Thermostat Input LED Indicators
situations where the device supplying the thermostat/humidistat signals to the M3 Indicates active state for G, W1, W2, Y1 and Y2 demands. Indicators are also
unit controller has its own power source and does not share a common reference available for occupied/unoccupied (OC) or global input (GLO). The indicators and
voltage with the M3 unit controller. Otherwise the jumper would remain installed their meanings are described in “Table 1. LED Operation Indicators”.
across both pins, as shipped from the factory. i. HEART BEAT LED INDICATORS
c. USB FLASH DRIVE INTERFACE USAGE
Some indicators on the circuit board are visible with the cover in place; others are
The M3 interface uses a USB A to B male cable for PC connection. This USB not. The indicators and their meanings are described in “Table 1. LED Operation
port is used for verifying service, downloading reports, transferring unit profiles Indicators”.
and performing firmware updates. On-site data collection requires use of a USB
flash drive. Data written to the drive includes date, time, serial number, catalog MODBUS CONNECTION (P358)
number, basic data, error code buffer, and unit configuration. This is a TIA-485 serial line over MODBUS (messaging structure) communication.
The is currently used only in the Energence Ultra-A Box models. This connection
d. S-BUS is used for communication between the M3 unit controller and inverter. See
This is the L-connection connection interface. This is a R485 network connection “Table 31. P358 (Ultra-A Box Only M3 Unit Controller)” on page 80 for pin-out
with other devices (NCP, comfort sensors, other RTU, etc.). information.
e. RJ-11 PHONE JACK: j. MODBUS LEDS
S-Bus connection is for factory tests. It is RS485 connection to the RJ-11 phone There is a transmit (TX) and receive (RX) activity indicated near the MODBUS
jack. Some DDC controllers may also be connected. connector.
Table 1. LED Operation Indicators
LED Status Indication Meaning
Green Slow Flash Normal Operation
Green Fast Flash Bootloader / firmware update mode
Heartbeat (HB) (D33)
No light Steady Off No voltage to M3 board or defective board
Green Steady On Unit in configuration / test mode (not in normal mode)

S-BUS / PC Connection (D70 and BUS (green) Flickering ON Network traffic present
D71) TX (yellow) Flickering ON Unit controller is transmitting

BACnet (option) - LEDs located on RX (green) Flickering ON Unit controller is receiving


module TX (yellow) Flickering ON Unit controller is transmitting

4
Table 1. LED Operation Indicators
LED Status Indication Meaning
RX (green) Flickering ON Unit controller is receiving
TX (yellow) Flickering ON Unit controller is transmitting
SERVICE (red) Flashing 1 sec. on; 1 sec. off Node is not configured; application loaded
LonTalk (option) - LEDs located on
module SERVICE (UNLIT) Steady off Node is completely configured
SERVICE (red) Constant on Node is configured; no application loaded
Quick flashes during
SERVICE (red) Messages being passed to M3; normal operation
initialization
G - Blower on (D17)
W1 - First-Stage Heating (D20)
W2 - Second -Stage Heating (D23)
Thermostat Input Yellow Indicates a thermostat demand Y1 - First-Stage Cooling (D26)
Y2 - Second-Stage Cooling (D29)
OCP - Occupied (D32)
GLO - Global input (D38)
MODBUS Two LEDs that indicate transmit (TX) and receive (RX) activity.
Thermostat LEDs indicate only with incoming thermostat connection via SmartWire™ connectors.
Slow Flash = 1 second on; 1 second off.
Fast Flash = ½ second on; ½ second off.
A “flickering” LED flashes significantly faster than a “fast flash“.
NOTE: LEDs are energized by 24VAC thermostat inputs.

4. System Status Screen NORMAL MODE


The display shows operating mode if in normal operation. Alarms will interrupt NETWORK MESSAGE FIRST TWO ALARMS THAT
ARE ACTIVE
the display. STATUS

Alarm messages will appear on the display and remain there until dismissed.
Dismissing an alarm is just clearing the alarm from using the entire screen to
display the condition(s). The alarm condition still exists and up to two alarm codes
COOLING
are displayed along the right side of the screen above the thermostat demand LON ON 74, 93
type status. To dismiss an alarm, press the BACK button. RAT: 76.0F Y1
DAT: 57.0F UNOCC

ZONE AND DISCHARGE THERMOSTAT


AIR TEMPERATURES OCCUPIED (OCC) OR
UNOCCUPIED (UNOCC) DEMAND TYPE

Figure 2. System Status Display

5
4.1. Network Types 4.4. Normal Mode and Status Messages
The second line on the left side (see “Figure 3. Alarm Code Readout Example”) The format of the message is mode and set point (see table 61).
is used for displaying network status. The status will indicate either ON or OFF
for the network employed. Table 3. Possible Mode and Status Messages
SCREEN NAME DESCRIPTION
Table 2. Network Types
COMP LOAD SHEDDING Unit is running at lower power capacity.
Screen Label Network Type
COOLING Cool demand present; unit is in mechanical cooling.
LON LonTalk
DEHUMIDIFICATION Unit is dehumidifying.
BACNET BACnet
FREE COOLING Cooling demand is present, no compressor cooling.
LCONN L-Connection
FRESH AIR COOLING Cool ventilation air to neutral value.
RTU Rooftop Unit stand-alone mode status indicator
FRESH AIR HEATING Heat ventilation air to neutral value.

4.2. Unit Operation HEATING Heat demand present; unit is heating.


CONTROLLER LOCKOUT User has disabled controller operation.
This section describes the display and control buttons, how to configure the unit, LOW AMBIENT LOCKOUT Outdoor air is too cold to allow compressors to run.
and how to read stored configuration data, status, and alarms.
MORNING WARMUP Outdoor air damper closed.
The M3 unit controller is an input and output junction point. If in the thermostat
mode, thermostat inputs at P297 result in an output to unit components. If the Unit is off due presence of alarm(s) that the system has
heartbeat LED is not flashing, see ”Table 1. LED Operation Indicators” on page OFF ON ALARM
determined will halt system operations.
4 for heartbeat operation. If the display shows an alarm. If the thermostat NOTE: Not all alarms will halt system operation. The first two
input indicating lights are not responding appropriately, check the thermostat or a active alarms are displayed on the main system status screen.
DDC control acting as thermostat inputs into P297. If the system has cleared the alarm there is usually a five minute
DELAY UP TO 5 MIN
Basic cooling and heating functions may be energized to test major unit delay before resuming system operations.
components by using the M3 unit controller testing function or by using jumper In certain models, the compressor turns on a few seconds after
wires on the Field Wiring Termination plug P297. DELAY UP TO 20 SEC
the outdoor fan is energized.
Compressor not allowed—free cooling. (During the first 30
4.3. Alarm Status Display minutes of the first cooling demand following a change from
PRE-COOL unoccupied to occupied, calls for mechanical [compressor]
Figure 33 shows how alarms are displayed. Alarming value may indicate the cooling are ignored if an economizer is installed and if outdoor
condition which triggered the alarm (temperature, voltage, pressure, time, etc.). air is suitable for free cooling.)
Unit has not been set up for operation. Must follow installation
PREINSTALL
menus.
Default start up delay before servicing demands. Go to M3 user
ALARM 173 START UP
2.4.2014 12: 02: 24 interface: SETUP > INSTALL
ALARMING VALUE = 0
AIR FLOW SWITCH CON SMOKE ALARM Smoke input detected.
TEST Network has unit in test mode.
BLOWER ON Indoor blower is on.
BLOWER ON - OAS Indoor blower is on and outdoor air is suitable.
Alarms are present - alarm code, alarming value, and
date / time stamp (hour, minute and seconds) of alarm NO DEMAND System not receiving a demand for cooling or heating.
event. NO DEMAND - OAS
System not receiving a demand for cooling or heating and
outdoor air is suitable.
While the alarm is displayed on the screen, press the help
COOL + MAX OPEN ECON Mechanical cooling is operating with maximum free cooling.
button for further details.
The down arrow on the screen indicates for information is COOL + MODULATE ECON Mechanical cooling is operating with variable free cooling.
available by scrolling down.

Figure 3. Alarm Code Readout Example


6
5. Firmware Update
The firmware on the M3 unit controller can be updated by inserting a USB thumb
drive containing the update.
NOTE: Flash drive media must be formatted using the either FAT or FAT32 file
systems.

5.1. Unit Controller USB Flash Drive Update Capability


Firmware updating is available using the USB port. To display the current firmware
M3XXXXXXXX.P2F/.P6F file goes here. (.P2F/.P6F) file
version:
name suffix is recommended to be in all CAPS
Go to DATA > FACTORY > SOFTWARE VERSION. but not mandatory. You can place both P2F and P6F
files in this folder.

5.2. Files Needed for Firmware Updating


Files needed to upgrade M3 unit controller from USB thumb drive: 5.4. Updating Firmware
M3XXXXXXXX.P2F/P6F a. After inserting the USB thumb drive:
(ALL UPPERCASE IS RECOMNMEND, BUT NOT MANDATORY)
Lennox recommends downloading and saving both .P2F and .P6F files for the Go to SERVICE > SOFTWARE UPDATE.
latest version onto the USB flash drive. The M3 will choose the appropriate file. b. Press the SELECT button, then use the adjust values (up/down) arrows to
DO NOT modify the file extension on a .P2F file to .P6F or vice-versa.
select a firmware version.
The xxxxxxxx are place holders for major and minor versions and build number
information in the actual file name, and varies from one version to the next. NOTE: If you get a message indicating “software update failed - sw update
file not found”, check to make sure the .P2F/.P6F file is located in the
5.3. Where to Place the .P2F/.P6F File on the USB Thumb Firmware > M3 folder.
Drive. NOTE: If you get the message “Not Applicable Equipment not Present”, may
indicate the Prodigy Unit Controller does not recognized the USB
a. Create folder name Firmware folder on the root directory of the USB thumb thumb drive inserted. Try a different thumb drive.
drive.
c. Press SAVE.
NOTE: Drive letter may differ from the one illustrated below. The following update sequence should occur:
b. Create a M3 folder under the Firmware folder. • SOFTWARE UPDATE STARTING
• SOFTWARE UPDATE ERASING FLASH
• SOFTWARE UPDATE PROGRAMMING FLASH

c. Place a copy of the .P2F/.P6F file into the M3 folder.

7
• SOFTWARE UPDATE PROGRAMMING FLASH PROGRESS xx% (xx% 8. Model Number and Configuration ID 1 and 2
indicates update percentage completed) This section addresses the requirement that specific configuration information
• SOFTWARE UPDATE RESETTING CONTROLLER. must be completed using the SETUP / INSTALL feature if a new unit controller
was being installed. Other requirements are the addition of accessories that were
d. After the unit controller resets, the first screen to appear will display the not factory-installed. Model number, configuration ID 1 and 2, catalog number,
following (xx.xx.xxxx indicates the software version number): serial number and RTU description are all key items required to be completed for
the system to operate correctly. Running the SETUP / INSTALL wizard allows the
PRODIGY 2.0 installer to verify that all fields have been completed as required.
M3 CONTROLLER
xx.xx.xxxx 8.1. Model
e. You may remove the USB thumb drive anytime after the reset is completed.
f. Firmware version can also be verify Model Number
Go to DATA > FACTORY > SOFTWARE VERSION. 1 2 3 4 5 6 7 8 9 10 11 12
NOTE: Firmware updates do not alter the unit controller configuration settings.
All settings will be retained after the firmware has been updated. Type [1, 2, 3] [12] Voltage
Electric = LCH or SCC
6. Saving and Loading User Profile Gas = LGH or SGC
See unit nameplate for
applicable electric voltage
When saving the user profile, all information concerning model number, designation.

configuration ID1 / ID2, parameters modified using the EDIT PARAMETER option
Tonnage [4, 5, 6]
and Test & Balance information are all stored to a non-volatile location in memory.
See unit nameplate for
The reference tasks are available from the M3 unit controller user interface: applicable tonnage [11] Design Sequence
designation.
a. To SAVE a user profile: 1 = First revision

Go to SERVICE > REPORT > SAVE USER PROFILE = YES [10] Factory Electric or Gas
b. To LOAD a user profile: Heat
See unit nameplate for applicable electric
Go to SERVICE > REPORT > LOAD USER PROFILE = YES or gas heat designation.

Efficiency [7]
7. Saving and Loading USB Profile High Efficiency = H
The USB Profile utility allows a copy of the profile to be save to a USB storage Standard Efficiency = S
device. Only EDIT PARAMETER changed settings and Test & Balance Ultra-High Efficiency = U
information is saved. The installer will need to configure the Model Number, and
Configurations ID 1 / ID 2 first before loading the saved USB profile. The USB Refrigerant [8]
Profile is typically used when replacing the M3 unit controller with a new one. HFC-410A = 4
The reference tasks are available from the M3 unit controller user interface:
a. To save a USB Profile: Blower Type [9] IMPORTANT: Always refer to the model
information listed on the unit nameplate when
Go to SERVICE > REPORT > USB PROFILE SAVE Belt Drive (1 speed) = B setting these options.

> enter a unique name for the profile and press SAVE. Direct Drive = D
Direct Drive ECM = E
b. To load a USB Profile: MSAV Belt Drive = M
NOTE: Options D, E, T and V
not available on SGC/SCC units.
Belt Drive (2 speed) = T
Go to SERVICE > REPORT > USB PROFILE LOAD
VAV Belt Drive = V
NOTE: Use the adjust and save values arrows to select highlight the desired
profile and press SAVE. Figure 4. Model Number

8
8.2. Configuration ID 1 8.3. Configuration ID 2
IMPORTANT: Always refer to the white sticker titled ORIGINAL FACTORY UNIT CONFIGURATION located inside the control box area.
CONFIGURATION ID 2
CONFIGURATION ID 1
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8
Air Flow Proving [1]
Switch (S52) [9] Electric Heat
*Humiditrol [1] [8] *Outdoor Air CFM Control Not Installed = N N = Not Installed
Not Installed = N N = Not applicable (for future use) Installed on M3 = C Y = Installed
Humiditrol Installed = H L = Outdoor Air Control Installed
with A24 Sensor set for low range.
Installed on DDC
Unconfigured = U Controller = D
M = Outdoor Air Control Installed
with A24 Sensor set for medium
Economizer [2]
range. Dirty Filter Switch (S27) [2] [8] *Load Shedding
Not Installed = N N = Not Installed
H = Outdoor Air Control Installed Not Installed = N
Motorized Outdoor Air with A24 Sensor set for high
Installed on M3 = C G = Global (P297 - pin 9)
Damper Only = M range.
Economizer - Temperature = T Installed on DDC Controller = D 2 = Installed on DI-2
3 = Installed on DI-3
Economizer Global = G Overflow Switch [3]
Economizer - Single
[7] *Advanced Air Flow (S149 / S179)
Enthalpy = S
Control System Not Installed = N
Economizer - Dual Enthalpy = D [7] *Zone Bypass Damper
N = Not Installed Installed on DI-2 = 2
Unconfigured = U N = Not Installed
S = Installed with Standard
Installed on DI-3 = 3 Y = Installed
Economizer

Power Exhaust [3] L = Installed with High Performance


Economizer
Not Installed = N Motor Overload [4] [6] *Ultra Violet Lamp
U = Unconfigured
Single-Stage = S Switch (S42)
N = Not Installed
Dual-Stage = D [6] *Blower Variable Not Installed = N
Y = Installed
*Variable Speed Drive =V
Frequency Drive Bypass Installed on DI-2 = 2
Unconfigured = U N = Not Installed
Installed on DI-3 = 3 [5] Phase / Voltage
A = Automatic Bypass Detection
Power Exhaust Control [4] M = Manual Bypass N = Not Installed
Not Installed = N U = Electronic Bypass Field
1 = Enabled Internal (Lennox)
Damper Position = A Un-configured * When Phase / Voltage detection monitoring is enabled on three-phase system and
*Pressure Switches = B
configured incorrectly will cause the system to go to demand hold and restart after 2 = *External (A42) Phase Detection
[5] Network Module 3 minutes. on DI-2
*A34 Pressure Sensor = C
N = Not Installed 3 = *External (A42) Phase Detection
NOTE: *Option not available on SCC/SGC rooftop units.
B = BACnet on DI-3
L = LonTalk (Lennox)

Figure 6. Configuration ID 2
NOTE: The M3 unit controller will display applicable alarm(s) if any positions is left unconfigured (U).

NOTE: *Option not available on SCC/SGC rooftop units.

Figure 5. Configuration ID 1

9
9. Menu Selection Overview

SELECT BACK
ALARMS, ZAT, DAT,
YES
SCROLL OCC OR UNOCC,
DEMAND STATUS

ALARMS
SHOW STATUS PRESENT?
NO
DATA ZAT, DAT, OCC
OR UNOCC,
DEMAND
SETUP STATUS

SERVICE

SETTINGS
HISTORY
TEST INSTALL

CONTROL

Use IN/OUTPUTS
REPLACE SCROLL NETWORK
arrows to INTEGRATION
RTU move
Use Use
OPTIONS
SCROLL SCROLL Use
FACTORY
arrows to arrows to SCROLL
move move TEST & arrows to
REPORT BALANCE move

INSTALL
NETWORK

SOFTWARE
UPDATE
GENERAL ADVANCED
STATUS

OFFLINE

RUNTIMES

10
10. Menu Navigation
The following tables indicate all levels of the menu interface. Many of these options have more levels which are described in the following sections that detail the
major categories of DATA, SETUP, SERVICE, and SETTINGS.
• Use the SELECT button to progress to the next menu level (i.e. level 1 to level 2).
• Use the SCROLL arrows ▲▼ to move (scroll) within a menu level.
• Use the BACK button to return to the previous menu level.
• Use the Adjust and set value arrows ▲▼ to change values of selected item.

10.1. Data

Table 4. Menu Interface (Level 1 - DATA)


NOTE: AVAILABLE MENU OPTIONS ARE DEPENDENT ON MODEL AND CONFIGURATION 1 AND 2 SETTINGS. USE THE ADJUST AND SET VALUES ARROWS TO SCROLL UP OR DOWN FOR
SELECTION OPTIONS.
Level 2 Level 3 Level 4 Level 5 Level 6
ALARMS
HISTORY CLEAR ALARM HISTORY = NO or YES
LAST SERVICE (time stamp of last service)
IN/OUTPUTS SENSORS LOCAL THERMOSTAT G: ON/OFF
W1: ON/OFF
W2: ON/OFF
Y1: ON/OFF
Y2: ON/OFF
BLOWER SPEED: X
OAT: xx F
RAT: xx F
DAT: xx F
ZAT (A2): xx F
C02: xx PPM
OAV: xx ft/min
BP: xx in h20
RH: xx %
IE
OE
GLO: ON/OFF
OCP: ON/OFF
SMOKE: ON/OFF
D12: ON/OFF
D13: ON/OFF
REHEAT D14: ON/OFF

11
Table 4. Menu Interface (Level 1 - DATA)
NOTE: AVAILABLE MENU OPTIONS ARE DEPENDENT ON MODEL AND CONFIGURATION 1 AND 2 SETTINGS. USE THE ADJUST AND SET VALUES ARROWS TO SCROLL UP OR DOWN FOR
SELECTION OPTIONS.
Level 2 Level 3 Level 4 Level 5 Level 6
SUCTION1: xx PSIG
SUCTION2: xx PSIG
C1 SUMP: xx F
C2 SUMP: xx F
C3 SUMP: xx F
C4 SUMP: xx F
DUCT PRESSURE: When a reading is available it will be displayed here. If
nothing is read a “-” will be displayed.
NETWORK THERMOSTAT G: ON/OFF
W1: ON/OFF
W2: ON/OFF
Y1: ON/OFF
Y2: ON/OFF
ZAT (A2): xx F
C02: xx PPM
RH: xx %
COMPRESSOR 1: ON/OFF
OUTPUTS
COMPRESSOR 1: ON/OFF
COMPRESSOR 3: ON/OFF
COMPRESSOR 4: ON/OFF
BLOWER: ON/OFF
EXHAUST: ON/OFF
FAN 1: ON/OFF
FAN 2: ON/OFF
FAN 3: ON/OFF
FAN 4: ON/OFF
FAN 5: ON/OFF
FAN 6: ON/OFF
HEAT 1: ON/OFF
HEAT 2: ON/OFF
HEAT 3: ON/OFF
HEAT 4: ON/OFF
REHEAT COIL 1: ON/OFF
REHEAT COIL 2: ON/OFF
SERVICE RELAY: ON/OFF

12
Table 4. Menu Interface (Level 1 - DATA)
NOTE: AVAILABLE MENU OPTIONS ARE DEPENDENT ON MODEL AND CONFIGURATION 1 AND 2 SETTINGS. USE THE ADJUST AND SET VALUES ARROWS TO SCROLL UP OR DOWN FOR
SELECTION OPTIONS.
Level 2 Level 3 Level 4 Level 5 Level 6
LCD HEATER: ON/OFF
CRANKCASE HEATER 1: ON/OFF
CRANKCASE HEATER 2: ON/OFF
CRANKCASE HEATER 3: ON/OFF
CRANKCASE HEATER 4: ON/OFF
MGV: “CLOSED” (NOTE: BLOWER SPEED IS SHOWN AS A PERCENTAGE ONLY ON VAV BLOWER CASE UNITS.)
FACTORY SOFTWARE VERSION
RTU DESCRIPTION
CATALOG NUMBER
MODEL NUMBER
SERIAL NUMBER
CONFIGURATION ID 1
CONFIGURATION ID 2
NETWORK BACNET MAC ADDRESS: XXX
BAUD RATE: XXXXX
DEVICE INSTANCE: X
LONTALK PROGRAM ID
NEURON ID
L-CONNECTION LCONN ADDRESS: X
ADVANCED STATUS CURRENT ALARMS ACTIVE ALARMS xxx
SETPOINTS OCC HEATt
UNOCC HEAT
OCC COOL
UNOCC COOL
APP MODE
BLOWER BLOWER STATUS BLOWER SPEED x%
SUPPLY TARGET x CFM
SUPPLY ACTUAL x CFM
DAMPER DAMPER STATUS TARGET: x%
ACTUAL x%
ACTUAL OA CFM
TARGET OA CFM
ECON DIFF PRESSURE
VAR SPEED COMPRESSOR COMPRESSOR SPEED TARGET: x%
ACTUAL: x%
13
Table 4. Menu Interface (Level 1 - DATA)
NOTE: AVAILABLE MENU OPTIONS ARE DEPENDENT ON MODEL AND CONFIGURATION 1 AND 2 SETTINGS. USE THE ADJUST AND SET VALUES ARROWS TO SCROLL UP OR DOWN FOR
SELECTION OPTIONS.
Level 2 Level 3 Level 4 Level 5 Level 6
EXHAUST EXHAUST STATUS EXHAUST: OFF or ON
EXHAUST1: OFF or ON
EXHAUST2: OFF or ON
(For more information concerning relationships PRESWITCH37: OFF or ON
between pressure switch, sensor and power
exhaust, refer to the Prodigy Application Guide). PRESWITCH39: OFF or ON
SPEED: 0%
BLDGP: -0.30 IN H20
RUNTIMES BELT x HRS
BLOWER x HRS
BLOWER x CYC
COOLING COMP 1: XX HRS - XX CYCLES
COMP 2: XX HRS - XX CYCLES
COMP 3: XX HRS - XX CYCLES
COMP 4: XX HRS - XX CYCLES
EXHAUST x HRS STAGE 1: XX HRS - XX CYCLES
STAGE 2: xx HRS - XX CYCLES
FANS FAN 1: xx HRS - CYCLES
FAN 2: xx HRS - CYCLES
FAN 3: xx HRS - CYCLES
FAN 4: xx HRS - CYCLES
FAN 5: xx HRS - CYCLES
FAN 6: xx HRS - CYCLES
FILTER x HRS FILTER x HRS
FREE COOL x HRS FREE COOL x HRS
FREE COOL x CYC FREE COOL x CYC
HEATING HEAT 1: xx HRS - XX CYCLES
HEAT 2: xx HRS - XX CYCLES
HEAT 3: xx HRS - XX CYCLES
HEAT 4: xx HRS - XX CYCLES
DEHUMID x HRS DEHUMID x HRS
DEHUMID x CRC DEHUMID x CRC
POWER ON x CYC POWER ON x CYC
POWER ON x HRS POWER ON x HRS
PREINSTALL x HRS PREINSTALL x HRS
UV LAMP xxx HRS UV LAMP xxx HRS

14
10.2. Setup

Table 5. Menu Interface (Level 1 - SETUP)


NOTE: AVAILABLE MENU OPTIONS ARE DEPENDENT ON MODEL AND CONFIGURATION 1 AND 2 SETTINGS. USE THE ADJUST AND SET VALUES ARROWS TO SCROLL UP OR DOWN FOR
SELECTION OPTIONS.
LEVEL 2 LEVEL 3 LEVEL 4 LEVEL 5 LEVEL 6 LEVEL 7
INSTALL LANGUAGE ENGLISH, ESPANOL, OR FRANCAIS
DATE/TIME DAY, MONTH, YEAR, HOURS, MINUTES, SECONDS
DISPLAY UNITS F/C FAHRENHEIT OR CELSIUS
MODEL NUMBER LOCATED ON UNIT NAMEPLATE.
SEE WHITE STICKER TITLED “ORIGINAL FACTORY UNIT CONFIGURATION” LOCATED ON THE RIGHT SIDE OF THE CONTROL BOX
CONFIGURATION ID 1
NEAR THE M3 CONTROLLER.
CONFIGURATION ID 2
CATALOG NUMBER LOCATED ON UNIT NAMEPLATE
SERIAL NUMBER LOCATED ON UNIT NAMEPLATE
RTU DESCRIPTION UP TO 18 ALPHA/NUMERIC CHARACTERS
DEHUMIDIFIER MODE
(OPTIONS ARE
DEPENDENT OF
CONFIGURATION).
FOR MORE INFORMATION
CONCERNING DACC BLOWER, OCCUPIED LOCAL SENSOR, NETWORK SENSOR DEHUMIDIFIER DEHUMID SETPOINT = X.XX %
AND DACH AND MGV,
REF TO THE PRODIGY
APPLICATION SECTION
ON MODULATING GAS
VALVE.
DEHUMIDIFIER DEHUMID DEADBAND = X.X %
REHEAT DI4
LOCAL SENSOR OR NETWORK
NO CONDITIONS DEHUMIDIFIER DEHUMID SETPOINT = X.XX %
SENSOR
DEHUMIDIFIER DEHUMID DEADBAND = X.X %
REHEAT DI4
LOCAL SENSOR OR NETWORK DISCHRG AIR
REPORT RH ONLY = NO
SENSOR CONTROL ENABLE
DISABLED
LOCAL SENSOR OR NETWORK
BLWR, OCC, PREV COOL DEHUMIDIFIER DEHUMID SETPOINT = X.XX %
SENSOR
DEHUMIDIFIER DEHUMID DEADBAND = X.X %
REHEAT DI4
LOCAL SENSOR, OR NETWORK
PREVIOUS COOLING DEHUMIDIFIER DEHUMID SETPOINT = X.XX %
SENSOR
DEHUMIDIFIER DEHUMID DEADBAND = X.X %
REHEAT DI4

15
Table 5. Menu Interface (Level 1 - SETUP)
NOTE: AVAILABLE MENU OPTIONS ARE DEPENDENT ON MODEL AND CONFIGURATION 1 AND 2 SETTINGS. USE THE ADJUST AND SET VALUES ARROWS TO SCROLL UP OR DOWN FOR
SELECTION OPTIONS.
LEVEL 2 LEVEL 3 LEVEL 4 LEVEL 5 LEVEL 6 LEVEL 7
DACC ENABLE ENABLED OR DISABLED
DACH ENABLE YES OR NO (NOTE: IF MGV IS NOT PRESENT, DACH IS NOT AN OPTION.)
DACH OCC SETPOINT 110 F (RANGE 80 F TO 140 F)
DACH UNOCC SETPOINT 95 F (RANGE 80 F TO 140 F)
SPMKT REHT W STAT
SPNJT REGT W SENSR
NETWORK NETWORK =
LCONN ADDRESS = X
INTEGRATION L-CONNECTION
CONTROL MODE = ROOM
SENSOR, MONITOR
NETWORK SENSOR CO2 = YES OR NO
ONLY OR NETWORK
THERMOSTAT
NETWORK SENSOR RELATIVE HUMIDITY = YES OR NO
NETWORK SENSOR TEMPERATURE = YES OR NO
ROOM SENSOR OCC BLOWER MODE= AUTO CYCLES OR ON-CONTINUOUS 1, 2 OR 3 *
BACKUP MODE = NONE, ROOM SENSOR, RETURN AIR BACKUP OR THERMOSTAT
BACKUP SETPOINTS OCCUPIED HEAT = XX.X F
BACKUP SETPOINTS UNOCCUPIED HEAT = XX.X F
BACKUP SETPOINTS OCCUPIED COOL = XX.X F
BACKUP SETPOINTS UNOCCUPIED COOL = XX.X F
OCC (OCCUPIED) BLOWER MODE DESCRIPTION:
AUTO CYCLE: BLOWER CYCLES WITH DEMAND
ON-CONTINUOUS 1: BLOWER IS ON WITH EITHER THE OCCUPANCY SENSOR OR OCCUPANCY SCHEDULER INDICATES OCCUPIED.
ON-CONTINUOUS 2: BLOWER IS ON ONLY WITH BOTH THE OCCUPANCY SENSOR AND OCCUPANCY SCHEDULER, BOTH INDICATES
OCCUPIED.
ON-CONTINUOUS 3: BLOWER IS ON ONLY WHEN BOTH THE OCCUPANCY SENSOR AND OCCUPANCY SCHEDULER INDICATES
OCCUPIED. IN ADDITION, BLOWER WILL BE ON A MINIMUM OF 25% OF THE TIME WHEN OCCUPANCY SCHEDULER INDICATES
OCCUPIED HOWEVER THE OCCUPANCY SENSOR INDICATES NOT OCCUPIED. THE 25% MINIMUM IS ACHIEVED BY TURNING
BLOWER ON FOR 30 MINUTES AND OFF FOR 90 MINUTES.
NETWORK = BACNET BACNET MAC ADDRESS = X
BACNET BAUD RATE = 9.6, 19.2, 38.4 OR 76.8 K
CONTROL MODE = ROOM
SENSOR, MONITOR
NETWORK SENSOR CO2 = YES OR NO
ONLY OR NETWORK
THERMOSTAT
NETWORK SENSOR RELATIVE HUMIDITY = YES OR NO
NETWORK SENSOR TEMPERATURE = YES OR NO
ROOM SENSOR OCC BLOWER MODE= AUTO CYCLES OR ON-CONTINUOUS 1, 2 OR 3 (SEE
DESCRIPTION ABOVE)

16
Table 5. Menu Interface (Level 1 - SETUP)
NOTE: AVAILABLE MENU OPTIONS ARE DEPENDENT ON MODEL AND CONFIGURATION 1 AND 2 SETTINGS. USE THE ADJUST AND SET VALUES ARROWS TO SCROLL UP OR DOWN FOR
SELECTION OPTIONS.
LEVEL 2 LEVEL 3 LEVEL 4 LEVEL 5 LEVEL 6 LEVEL 7
BACKUP MODE = NONE, ROOM SENSOR, RETURN AIR BACKUP OR THERMOSTAT
BACKUP SETPOINTS OCCUPIED HEAT = XX.X F
BACKUP SETPOINTS UNOCCUPIED HEAT = XX.X F
BACKUP SETPOINTS OCCUPIED COOL = XX.X F
BACKUP SETPOINTS UNOCCUPIED COOL = XX.X F
CONTROL MODE = ROOM
SENSOR, MONITOR
NETWORK = LONTALK NETWORK SENSOR CO2 = YES OR NO
ONLY OR NETWORK
THERMOSTAT
NETWORK SENSOR RELATIVE HUMIDITY = YES OR NO
NETWORK SENSOR TEMPERATURE = YES OR NO
ROOM SENSOR OCC BLOWER MODE= AUTO CYCLES OR ON-CONTINUOUS 1, 2 OR 3 (SEE
DESCRIPTION ABOVE)
BACKUP MODE = NONE, RETURN AIR BACKUP OR THERMOSTAT
BACKUP SETPOINTS OCCUPIED HEAT = XX.X F
BACKUP SETPOINTS UNOCCUPIED HEAT = XX.X F
BACKUP SETPOINTS OCCUPIED COOL = XX.X F
BACKUP SETPOINTS UNOCCUPIED COOL = XX.X F
NETWORK = RTU BACKUP MODE = NONE
SETPOINTS HEAT = XX.X F
STANDALONE OR RETURN AIR BACKUP

SETPOINTS COOL = XX.X F

TEST & BALANCE BLOWER BLOWER HEATING HIGH = XXXX CFM


BLOWER COOLING HIGH = XXXX CFM
BLOWER COOLING LOW = XXXX CFM
BLOWER VENTILATION = XXXX CFM
ON (TARGET XXXX CFM) ADJUST BLOWER RPM = XXXX RPM
HEATING HIGH = %
HEATING LOW = %
A BOX (NON-EP) - NOTE: Depending on configuration, HEATING LOW speed may be an option and is used for low heat.
HEATING, HIGH SPEED
AND LOW SPEED COOLING HIGH = %
COOLING LOW = %
ADJUST BLOWER % = xx

17
Table 5. Menu Interface (Level 1 - SETUP)
NOTE: AVAILABLE MENU OPTIONS ARE DEPENDENT ON MODEL AND CONFIGURATION 1 AND 2 SETTINGS. USE THE ADJUST AND SET VALUES ARROWS TO SCROLL UP OR DOWN FOR
SELECTION OPTIONS.
LEVEL 2 LEVEL 3 LEVEL 4 LEVEL 5 LEVEL 6 LEVEL 7
ADVANCED AIRFLOW
A BOX AND B BOX OR BLOWER CALIBRATION (HEATING, HIGH SPEED,
BIGGER LOW SPEED OR VENTILATION = CALIBRATION
TEST & BALANCE BLOWER HEATING, COOLING HIGH, DONE OR TURN BLOWER ON.
COOLING MED, COOLING
MED HIGH, COOLING MED IF TURN BLOWER ON IS SELECTED, BLOWER ON
LOW, COOLOW LOW and XXXXX > TURN BLOWER OFF= NO OR YES.
VENTILATION
STARTING BLOWER > BLOWER ON > CLOSING DAMPER > PROGRESS % WILL BE DISPLAYED. WILL
AUTO CALIBRATE =
RETURN TO AUTO CALIBRATE SCREEN AFTER REACHING 100%. PRESS THE ADJUST AND SET
START CALIBRATION OR
VALUE BUTTON FOR THE OPTION = CALIBRATION DONE. PRESS SAVE TO CONTINUE. RESULTS OF
CALIBRATION DONE
CALIBRATION ARE AVAILABLE IN SERVICE REPORT.

ENSURE CALIBRATION DONE OR TURN


BLOWER ON.

ZONE BOXES OPEN? =NO OR YES YES SELECTED TURN BLOWER ON = BLOWER ON = 51%
(RANGE 35 TO 100%)
STATIC PRES SP = 1.0 IN H20 (RANGE 0.1
TO 5.0)
=NO OR YES = IF YES, THEN PRESS
=NO OR YES = IF YES, PRESS SAVE.
SAVE
DAMPER FDBK CALIB > IS IS DMPR FULLY NOTE: Installer will need to visually inspect
DAMPER NOTE: Installer will need to visually
DAMPER CLOSED? OPEN?” the damper to ensure that it is
inspect the damper to ensure opened.
that it is closed.
MIN DAMPER POSITION >
ZONE BOXES OPEN = NO YES = BLOWER ON HIGH = 0% (RANGE 0 TO 100%)
OR YES (START BLOWER)
MIN DAMPER POSITION > BLOWER ON HIGH = XX %
MIN DAMPER POSITION > BLOWER ON LOW= XX %
ECONOMIZER
TEMP ECON TYPE =
NOTE: This option is dependant on configuration ID 1 setup.
TEMPERATURE OFFSET
OR TEMPERATURE SETPT
ECONOMIZER OAT SETPOINT = XX.X F.
ECONOMIZER ENTHALPY SETPOINT = XX MA
NOTE: These options are dependant on configuration ID 1 setup.
ECONOMIZER ENTHALPY OFFSET = XX MA
FREE COOLING SUPPLY AIR SETPOINT = XX.X F
DAMPER OUTDOOR AIRFLOW = XXX CFM

18
Table 5. Menu Interface (Level 1 - SETUP)
NOTE: AVAILABLE MENU OPTIONS ARE DEPENDENT ON MODEL AND CONFIGURATION 1 AND 2 SETTINGS. USE THE ADJUST AND SET VALUES ARROWS TO SCROLL UP OR DOWN FOR
SELECTION OPTIONS.
LEVEL 2 LEVEL 3 LEVEL 4 LEVEL 5 LEVEL 6 LEVEL 7
ADVANCED AIRFLOW
ALARMS = ENABLED OR
DISABLED (ONLY VISIBLE
ADV AIRFLOW ALARMS LO SPLY AIRFLOW ALM = XX%
IF CONFIGURATION ID
1, POSITION 2 IS SET
CORRECTLY).
ADV AIRFLOW ALARMS LO OD AIRFLOW ALM = XX%
ADV AIRFLOW ALARMS HI OD AIFLOW ALM = XX%
ADV AIRFLOW ALARMS ALM TRIGGER PERIOD = XXXX SEC
= NONE
VENTILATION OPTIONS = DEMAND CONTROL VENTILATION
= BUILDING PRESSURE CONTROL
IF DCV DEMAND CONTROL VENT > DAMPER START OPEN = XXX PPM
DEMAND CONTROL VENT > DAMPER FULL OPEN = XXXX.X PPM
DEMAND CONTROL VENT > DAMPER MAX OA CFM = X CFM
(ONLY VISIBLE IF CONFIGURATION ID 1, POSITION 2 IS SET CORRECTLY).
DEMAND CONTROL VENT > DAMPER MAX OPENING = XXX.X %.
IF BPC BUILDING PRESS CTROL > PRESSURE SETPOINT = X.X IN H20.
OUTDOOR AIR CONTROL
(ONLY VISIBLE IF
CONFIGURATION ID VELOCITY SETPOINT = XXX FT/MIN
1, POSITION 8 IS SET
CORRECTLY)
POWER EXHAUST ON BY ECON TRAVEL = XX.X %
POWER EXHAUST MODE = BLOWER ON, EXTERNAL ENABLE, OCCUPIED AND ALWAYS
EXHAUST PRESSURE SETPOINT = 0.05 IN H20 (RANGE -0.49 TO 0.50 IN H20)
FRESH AIR HEATING
FRESH AIR HEATING FAH SETPOINT = XX F
ENABLE FAH = NO OR YES
FRESH AIR COOLING
FRESH AIR COOLING AFC SETPOINT = XX F
ENABLE FAC = YES OR NO

19
10.3. Service

Table 6. Menu Interface (Level 1 - SERVICE)


NOTE: AVAILABLE MENU OPTIONS ARE DEPENDENT ON HARDWARE CONFIGURATION. USE THE ADJUST AND SET VALUES ARROWS TO SCROLL UP OR DOWN FOR SELECTION
OPTIONS.
USE THE ADJUST AND SET VALUES ARROWS TO
LEVEL 2 LEVEL 3 WHEN SELECTED (PRESS BACK TO RETURN TO THE PREVIOUS MENU)
SCROLL UP OR DOWN FOR SELECTION OPTIONS.
TEST COOL OPTIONS ARE COOL 1, COOL 2, COOL 3 AND COOL 4. COOL X ODN
RAT: XX.X F
DAT: XX.X F
(IF ADVANCED AIRFLOW IS ENABLED THEN ACTUAL CFM IS DISPLAYED OR NOT
APPLICABLE EQUIPMENT NOT PRESENT.
HEAT OPTIONS ARE HEAT 1, HEAT 2, HEAT 3 AND HEAT 4. HEAT X ON
RAT: XX.X F
DAT: XX.X F
NOTE: HEAT 3 and heat 4 are not supported for MGV. IF ADVANCED AIRFLOW IS ENABLED THEN ACTUAL CFM IS DISPLAYED OR NOT
APPLICABLE EQUIPMENT NOT PRESENT)
BLOWER BLOWER HI BLH ON/OFF SET POINT
BLOWER LOW BLL ON/OFF SET POINT
PROVING SWITCH PSW CLOSED/OPEN SET POINT
BLOWER FILTER SWITCH FSW CLOSED/OPEN SET POINT
RPM XX RPM FSW CLOSED/OPEN SET POINT
SPEED XX RPM TD: XX (IF COMPRESSOR IS TURNED ON)
ACTUAL: 0.1%.
DAMPER POSITION
NOTE: This function is only available if configuration ID 1, position 2 has been configured.
EXHAUST 1 OR 2 SET ON/OFF SETPOINT (EX1 OR EX2 ON/OFF ACTUAL)
FANS FAN 1 (OR FAN L) FN1 (OR FL) ON/OFF SETPOINT
FAN 2 (OR FAN H) FN2 (OR FH) ON/OFF SETPOINT
FAN 3 THROUGH 6. ON/OFF
WHEN SELECTING OPTION, RESPONSE WILL BE EITHER DEHUMIDIFIER X ON OR
DEHUMIDIFIER OPTIONS ARE HUM 1 AND HUM 2
NOT APPLICABLE EQUIPMENT NOT PRESENT.
OUTPUTS SERVICE RELAY SERVICE RELAY ON
FILTER RESET RUNTIME? = NO OR YES
BELT
(ONLY AVAILABLE RESET RUNTIME? = NO OR YES
BASED ON MODEL
NUMBER)
REPLACE UV LAMP RESET RUNTIME? = NO OR YES OR NOT APPLICABLE EQUIPMENT NOT PRESENT
FANS (1 THROUGH 6) RESET RUNTIME? = NO OR YES OR NOT APPLICABLE EQUIPMENT NOT PRESENT
BLOWER RESET RUNTIME? = NO OR YES
COMPRESSOR (1
RESET RUNTIME? = NO OR YES OR NOT APPLICABLE EQUIPMENT NOT PRESENT
THROUGH 4)

20
Table 6. Menu Interface (Level 1 - SERVICE)
NOTE: AVAILABLE MENU OPTIONS ARE DEPENDENT ON HARDWARE CONFIGURATION. USE THE ADJUST AND SET VALUES ARROWS TO SCROLL UP OR DOWN FOR SELECTION
OPTIONS.
USE THE ADJUST AND SET VALUES ARROWS TO
LEVEL 2 LEVEL 3 WHEN SELECTED (PRESS BACK TO RETURN TO THE PREVIOUS MENU)
SCROLL UP OR DOWN FOR SELECTION OPTIONS.

USB SERVICE USB SERVICE REPORT = DEFAULT NAME IS THE SERIAL NUMBER IF SET. OTHERWISE IT WILL BE 123456789. CAN BE RENAMED BY USER.
REPORT
REPORT MAXIMUM 18 CHARACTERS. WHEN COMPLETED A MESSAGE WILL APPEAR INDICATING “USB ACCESS COMPLETE)

START USB REPORT = SAF RPT (DEFAULT) AND CAN BE RENAMED BY USER.
USB ADV AIRFLOW USB ADVANCED AIRFLOW REPORT = START USB
MAXIMUM 18 CHARACTERS. WHEN COMPLETED A MESSAGE WILL APPEAR
RPT REPORT or USB REPORT DONE.
INDICATING “USB ACCESS COMPLETE)
SAVE USER PROFILE SAVE USER PROFILE = YES or NO
LOAD USER PROFILE LOAD USER PROFILE = YES or NO
USB PROFILE SAVE = 1234 UNLESS CATALOG NUMBER IS SET. DEFAULT IS CATALOG NUMBER. CAN BE RENAMED BY USER. MAXIMUM 18
USB PROFILE SAVE
CHARACTERS.
USB PROFILE LOAD = 1234XXXXXXXXXXX (USER
REPORT USB PROFILE LOAD ASSIGNED NAME AS SPECIFIED. TYPICALLY WILL LOAD PREVIOUSLY SAVED USB PROFILE.
CATALOG NUMBER.
LOAD FACTORY
LOAD FACTORY PROF = YES OR NO
PROF
LOG SERVICE EVENT LOG SERVICE EVENT = YES OR NO
SOFTWARE UPDATE (EITHER THE UPDATE WILL BE SUCCESSFUL OR THE FOLLOWING MESSAGES WILL APPEAR. SW UPDATE FAILED OR
SOFTWARE SW UPDATE FILE NOT FOUND.
SOFTWARE UPDATE
UPDATE NOTE: If a USB flash drive is not installed or the M3 unit controller cannot read the flash media, a message will appear “NOT APPLICABLE EQUIPMENT
NOT PRESENT.”
OFFLINE CLEAR DELAYS CLEAR DELAYS = YES OR NO.
RESET CONTROLLER = YES OR NO.
RESET CONTROLLER
NOTE: This reboots the M3 controller. No configuration settings are changed.
CONTROLLER
CONTROLLER LOCKOUT = YES OR NO.
LOCKOUT

21
10.4. Settings

Table 7. Menu Interface (Level 1 - SETTINGS)


NOTE: AVAILABLE MENU OPTIONS ARE DEPENDENT ON HARDWARE CONFIGURATION. USE THE ADJUST AND SET VALUES ARROWS TO SCROLL UP OR DOWN FOR SELECTION
OPTIONS.
LEVEL 2 LEVEL 3 LEVEL 4 LEVEL 5 LEVEL 6 LEVEL 7
CONTROL TYPE =
CONTROL NETWORK OR WIRED WIRED THERMOSTAT
THERMOSTAT

NETWORK > BACNET BACNET MAC ADDRESS = X

BACNET BAUD RATE = 9.6, 19.2, 38.4 OR 76.8 K


CONTROL MODE = ROOM SENSOR OR NETWORK THERMOSTAT
CONTROL MODE = MONITOR
NETWORK SENSOR C02 = YES OR NO
NETWORK SENSOR RELATIVE HUMIDITY = YES OR NO
NETWORK SENSOR TEMPERATURE = YES OR NO
ROOM SENSOR OCC BLOWER MODE = AUTO - CYCLES OR ON - CONTINUOUS 1,
CONTROL MODE
2, 3
= ROOM SENSOR
OR NETWORK BACKUP MODE = NONE, ROOM SENSOR, RETURN AIR BACKUP OR THERMOSTAT
THERMOSTAT
RAT OR ZONE BACKUP SETPOINTS OCCUPIED HEAT = XX.X F
BACKUP SETPOINTS UNOCCUPIED HEAT = XX.X F
BACKUP SETPOINTS OCCUPIED COOL = XX.X F
BACKUP SETPOINTS UNOCCUPIED COOL = XX.X F
NETWORK >
LCONN ADDRESS = X
L-CONNECTION
CONTROL MODE = MONITOR
CONTROL MODE
= ROOM SENSOR
NETWORK SENSOR C02 = YES OR NO
OR NETWORK
THERMOSTAT
NETWORK SENSOR RELATIVE HUMIDITY = YES OR NO
NETWORK SENSOR TEMPERATURE = YES OR NO
ROOM SENSOR OCC BLOWER MODE=ON-CONTINUOUS 1, 2, 3 OR AUTO CYCLES
BACKUP MODE = NONE, ROOM SENSOR, RETURN AIR BACKUP OR THERMOSTAT
RAT OR ROOM BACKUP SETPOINTS OCCUPIED HEAT = XX.X F
BACKUP SETPOINTS UNOCCUPIED HEAT = XX.X F
BACKUP SETPOINTS OCCUPIED COOL = XX.X F
BACKUP SETPOINTS UNOCCUPIED COOL = XX.X F
NETWORK > LONTALK CONTROL MODE = MONITOR

22
Table 7. Menu Interface (Level 1 - SETTINGS)
NOTE: AVAILABLE MENU OPTIONS ARE DEPENDENT ON HARDWARE CONFIGURATION. USE THE ADJUST AND SET VALUES ARROWS TO SCROLL UP OR DOWN FOR SELECTION
OPTIONS.
LEVEL 2 LEVEL 3 LEVEL 4 LEVEL 5 LEVEL 6 LEVEL 7
CONTROL MODE
= ROOM SENSOR
NETWORK SENSOR C02 = YES OR NO
OR NETWORK
THERMOSTAT
NETWORK SENSOR RELATIVE HUMIDITY = YES OR NO
NETWORK SENSOR TEMPERATURE = YES OR NO
ROOM SENSOR OCC BLOWER MODE=ON-CONTINUOUS 1, 2, 3 OR AUTO CYCLES
BACKUP MODE = NONE, ROOM SENSOR, RETURN AIR BACKUP OR THERMOSTAT
RAT OR ZONE BACKUP SETPOINTS OCCUPIED HEAT = XX.X F
BACKUP SETPOINTS UNOCCUPIED HEAT = XX.X F
BACKUP SETPOINTS OCCUPIED COOL = XX.X F
BACKUP SETPOINTS UNOCCUPIED COOL = XX.X F
RTU OPTION BLOWER SPEEDS BLOWER HEAT = XXXX CFM
BLOWER COOLING HIGH = XXXX CFM
BLOWER COOLING LOW = XXXX CFM
BLOWER HEATING HIGH = XXXX CFM
BLOWER VENTILATION = XXXX CFM
ON (TARGET XXXX CFM) ADJUST BLOWER RPM - XXXX RPM
HEATING HIGH = %
HEATING LOW = %
A BOX (NON-EP) - NOTE: Depending on configuration, HEATING LOW speed may be an option and is
HEATING, HIGH SPEED used for low heat.
AND LOW SPEED COOLING HIGH = %
COOLING LOW = %
ADJUST BLOWER % = xx
ADVANCED AIRFLOW
A BOX AND B BOX OR
BIGGER
BLOWER CALIBRATION (HEATING, HIGH SPEED, LOW SPEED OR VENTILATION =
HEATING, COOLING CALIBRATION DONE OR TURN BLOWER ON.
HIGH, COOLING MED,
IF TURN BLOWER ON IS SELECTED, BLOWER ON XXXXX > TURN BLOWER OFF=
COOLING MED HIGH,
NO OR YES.
COOLING MED LOW,
COOLOW LOW AND
VENTILATION
VFD BYPASS VFD BYPASS DISENGAGED ENGAGE? = NO OR YES

23
Table 7. Menu Interface (Level 1 - SETTINGS)
NOTE: AVAILABLE MENU OPTIONS ARE DEPENDENT ON HARDWARE CONFIGURATION. USE THE ADJUST AND SET VALUES ARROWS TO SCROLL UP OR DOWN FOR SELECTION
OPTIONS.
LEVEL 2 LEVEL 3 LEVEL 4 LEVEL 5 LEVEL 6 LEVEL 7
DAMPER ECONOMIZER ENTHALPY OFFSET = X MA
ECONOMIZER TEMP ECON TYPE = TEMPERATURE OFFSET OR TEMPERATURE SETPT
ECONOMIZER OAT SETPOINT = XX.X F
FREE COOLING SUPPLY AIR SETPOINT = XX F
OUTDOOR AIRFLOW = XXX CFM
ADVANCED AIRFLOW
ALARMS = ENABLED OR
DISABLED (ONLY VISIBLE
ADV AIRFLOW ALARMS LO SPLY AIRFLOW ALM = XX%
IF CONFIGURATION ID
1, POSITION 2 IS SET
CORRECTLY).
ADV AIRFLOW ALARMS LO OD AIRFLOW ALM = XX%
ADV AIRFLOW ALARMS HI OD AIFLOW ALM = XX%
ADV AIRFLOW ALARMS ALM TRIGGER PERIOD = XXXX SEC
MIN DAMPER POSITION BLOWER ON HIGH = X.X %
MIN DAMPER POSITION BLOWER ON LOW = X.X %
= NONE
VENTILATION OPTIONS = DEMAND CONTROL VENTILATION
= BUILDING PRESSURE CONTROL
IF DCV BUILDING PRESSURE CONTROL
DEMAND CONTROL VENT DAMPER START OPEN = XXXX.X PPM
DEMAND CONTROL VENT DAMPER FULL OPEN = XXXX.X PPM
DEMAND CONTROL VENT > DAMPER MAX OA CFM = X CFM
(ONLY VISIBLE IF CONFIGURATION ID 1, POSITION 2 IS SET CORRECTLY).
DEMAND CONTROL VENT DAMPER MAX OPENING = XXX.X%
IF BPC BUILDING PRESS CTRL > PRESSURE SETPOINT = X.X IN H20
OUTDOOR AIR CONTROL
(ONLY VISIBLE IF
CONFIGURATION ID VELOCITY SETPOINT = XXX FT/MIN
1, POSITION 8 IS SET
CORRECTLY)
POWER EXHAUST ON BY ECON TRAVEL = XX.X %
FRESH AIR HEATING
ENABLE FAH = YES OR FRESH AIR HEATING FAH SETPOINT = XX F
NO
FRESH AIR COOLING
ENABLE AFC = YES OR FRESH AIR COOLING AFC SETPOINT = XX F
NO

24
Table 7. Menu Interface (Level 1 - SETTINGS)
NOTE: AVAILABLE MENU OPTIONS ARE DEPENDENT ON HARDWARE CONFIGURATION. USE THE ADJUST AND SET VALUES ARROWS TO SCROLL UP OR DOWN FOR SELECTION
OPTIONS.
LEVEL 2 LEVEL 3 LEVEL 4 LEVEL 5 LEVEL 6 LEVEL 7
LOCAL SENSOR,
DEHUMIDIFIER MODE BLOWER OCCUPIED DEHUMIDIFIER DEHUMID SETPOINT = X.XX %
NETWORK SENSOR
DEHUMIDIFIER DEHUMID DEADBAND = X.X %
REHEAT DI4
LOCAL SENSOR,
NO CONDITION DEHUMIDIFIER DEHUMID SETPOINT = X.XX %
NETWORK SENSOR
DEHUMIDIFIER DEHUMID DEADBAND = X.X %
REHEAT DI4
REPORT RH ONLY LOCAL SENSOR OR NETWORK SENSOR
DISABLED
BLWR, OCC, LOCAL SENSOR,
DEHUMIDIFIER DEHUMID SETPOINT = X.XX %
PREV COOL NETWORK SENSOR
DEHUMIDIFIER DEHUMID DEADBAND = X.X %
REHEAT DI4
PREVIOUS LOCAL SENSOR,
DEHUMIDIFIER DEHUMID SETPOINT = X.XX %
COOLING NETWORK SENSOR
DEHUMIDIFIER DEHUMID DEADBAND = X.X %
REHEAT DI4
EDIT PARAMETER ENTER DATA ID
SEE TABLE 57 FOR SETUP PROMPTS FOR NEW SETUP. (THIS IS THE SAME AS SETUP > INSTALL DEHUMIDIFIER MODE PORTION OF
INSTALL NEW UNIT SETUP
THE WIZARD.)
CLEAR ALL CONFIG=YES OR NO. IF YES IS SELECTED. ARE YOU SURE?=YES OR NO. SEE TABLE 57 FOR SETUP PROMPTS FOR NEW
INSTALL NEW M3
M3 UNIT CONTROLLER.
GENERAL LANGUAGE ENGLISH, FRANCAIS OR ESPANOL
DAY, MONTH, YEAR HOURS, MINUTES AND SECONDS
DATE/TIME
NOTE: HOURS IN 24 HOUR CLOCK FORMAT (MILITARY)
DISPLAY UNITS F/C FAHRENHEIT OR CELSIUS
RTU DESCRIPTION ENTER A 18 POSITION ALPHA / NUMERIC NAME
CATALOG NUMBER LOCATED ON UNIT NAMEPLATE.
MODEL NUMBER
SERIAL NUMBER
CONFIGURATION ID 1 WHITE STICKER TITLED “ORIGINAL FACTORY UNIT CONFIGURATION” LOCATED ON THE RIGHT SIDE OF THE CONTROL BOX NEAR
CONFIGURATION ID 2 THE M3 CONTROLLER.

25
11. Thermal Protection Switches (S5, S7, S8, S31 and S180) 12. Blower Operation with Effective Occupancy
NOTE: Not all models use all of the reference switches. Verify with unit wiring This section describes how network occupancy signals are combined to produce
diagram to confirm switch(es) used. Also refer the unit installation effective occupancy.
instruction for switches used and operation. The blower runs to service heat and cool demands, regardless of the space
Thermal protection switches open on a temperature rise to de-energize the occupancy. However when there is no heating or cooling demand there are
corresponding compressor. Switches automatically reset when temperature options for how the blower should operate in conjunction with occupancy signals
drops. to keep the space ventilated, or the air stirred.
The corresponding compressor is locked out after three occurrences (default) a. California Energy Commission Title 24
of either high pressure or high temperature conditions during a demand cycle. The legacy option settings for OCC Blower Mode are AUTO CYCLES or ON-
The number of occurrences can be changed using for Parameter 98. Adjustable CONTINUOUS 1. These settings govern whether the blower runs continuously
range is 1 to 7 occurrences. when the space is considered occupied, or cycles on/off with the heating and
On certain compressors, these switches are in series with the high pressure cooling demand.
switches, and will cause a 300 second delay (default) which is set using Parameter To comply with the California Energy Commission Title 24 standard there are
110. This will also set off an alarm. Adjustable delay range is 64 to 1800 seconds. two additional values for OCC Blower Mode which are ON-CONTINUOUS 2
Go to SETTINGS > RTU OPTION > EDIT PARAMETER = 98 (MAX HP and ON-CONTINUOUS 3. See “Table 8. Blower Operation Description” for their
OCCURRENCES) descriptions.
Go to SETTINGS > RTU OPTION > EDIT PARAMETER = 110 (ERR TIME OFF b. LonTalk, BACnet and L Connection: These two new options are available
DELAY) when using these networks types that supplies a room occupancy signal (in
NOTE: Thermal protection switch alarms will not indicate an OFF ON ALARM addition to the scheduled occupancy).
state. NOTE: For L Connection the same two options are also available when using
an optional room occupancy sensor. If a room occupancy sensor is
11.1. Energence Ultra-High Efficiency Units (3- to 6-ton) not physically installed and configured for the network, then the only
options available for OCC Blower Mode are AUTO CYCLES or ON-
This model has a thermal protection switch connected to S7. When the compressor CONTINUOUS 1.
is de-energized due to an open thermal switch, alarm 192 is issued. When the
compressor is locked out after three occurrences, alarm 193 is issued. c. RTU Standalone: Since a room occupancy sensor cannot be used in this
configuration, then the only options for OCC Blower Mode are AUTO CYCLES
11.2. Tandem Compressors — Energence Ultra-High or ON-CONTINUOUS 1.
Efficiency Units (7-1/2 to 12-1/2-ton) d. Enabling Network Type
This model has two temperature switches (S5 and S8) in series with one pressure To enable the network module, go to SETUP > INSTALL and run the setup wizard.
switch (S4). If only one temperature switch is tripped, only the applicable When Configuration ID 1 appears on the screen, configure position 5 to one of
compressor will be de-energized. If pressure switch trips, both compressors are the applicable network types. N = Not Installed, B = BACnet and L = LonTalk.
de-energized. e. Menu Setup Procedure Method for OCC Blower Mode
These blower control options are handled by the OCC Blower Mode. These
11.3. Tandem Compressors — Energence Ultra-High setting and be changed using the following menu path:
Efficiency Units (15- and 20-ton) Go to SETUP > NETWORK INTEGRATION > NETWORK = “BACNET, LONTALK
or L CONNECTION” > (additional prompts concerning network configuration and
This model has two thermal protection switches (S5 and S8) in series with two sensor types will be asked) CONTROL MODE = ROOM SENSOR > ROOM
pressure switches (S4 and S28). If only one compressor shuts-off, this usually SENSOR OCC BLOWER MODE = “Table 8. Blower Operation Description”
indicates that the problem is related to a temperature switch. If a pressure switch
opens, both compressors in tandem will shut-off.

26
Table 8. Blower Operation Description
OCC Blower Mode Description
AUTO CYCLES Blower cycles on/off with demand. (Legacy usage.)
ON-CONTINUOUS 1 Blower runs when either the occupancy sensor or schedule, or both, indicates occupied. (Legacy usage.)
ON-CONTINUOUS 2 Blower runs when both the occupancy sensor and schedule indicate occupied.
ON-CONTINUOUS 3 The same as option 2, but blower runs for 30 minutes and is off for 90 minutes when schedule is occupied but the occupancy sensor is not occupied.

Table 9. BACnet Occupancy Objects


Input BACnet Value
0: space occupied
Occupancy Override
1: space unoccupied
Manual Control
2: refresh space occupied override timer
AO 103
3­255: auto; clear timer and return to scheduler
Occupancy Scheduler
0: space occupied
Schedule Control
1-­255: space unoccupied
AO 104
Occupancy Sensor 0: space occupied
Sensor Input 1: space unoccupied
AO 107 2­-255: auto; return to occupancy scheduler state
0: space occupied
Effective Effective Occupancy
1: space unoccupied
Occupancy AI 241
2: space occupied (timed override)

Table 10. LonTalk Occupancy Objects


Input BACnet Value
0: space occupied
nviOccManCmd 1: space unoccupied
Manual
Index = 11 2: refresh space occupied override timer
3­255: auto; clear timer and return to scheduler
nviOccSched1 0: space occupied
Schedule
Index = 10 1-­255: space unoccupied
0: space occupied
nviOccSensor
Sensor 1: space unoccupied
Index = 12
2­-255: auto; return to occupancy scheduler state
0: space occupied
Effective nvoEffectOccup
1: space unoccupied
Occupancy Index = 26
2: space occupied (timed override)

27
Table 11. Blower Operation Schedule
Manual Schedule Sensor Effective Blower Occupancy OCC Blower Mode Blower Operation
AUTO-CYCLES Cycles
ON-CONTINOUS 1 On
0, 2 n/a n/a OCCUPIED
ON-CONTINOUS 2 On
ON-CONTINOUS 3 On
AUTO-CYCLES
ON-CONTINOUS 1
1 n/a n/a UNOCCUPIED Cycles
ON-CONTINOUS 2
ON-CONTINOUS 3
AUTO-CYCLES Cycles
ON-CONTINOUS 1 On
3­-255 0 0, 2-255 OCCUPIED
ON-CONTINOUS 2 On
ON-CONTINOUS 3 On
AUTO-CYCLES Cycles
ON-CONTINOUS 1 On
3­-255 0 1 OCCUPIED
ON-CONTINOUS 2 Cycles
ON-CONTINOUS 3 Cycles w/Stir
AUTO-CYCLES
ON-CONTINOUS 1
3­-255 1-255 n/a UNOCCUPIED Cycles
ON-CONTINOUS 2
ON-CONTINOUS 3

28
13. Economizer • Option 1: Damper opens to its max­open position (Parameter 131 - FREE CL
The economizer, when configured, controls: MAX DAMPER) when any compressors start.
• Damper position, which determines how much outdoor air is used to meet NOTE: When using Option 1 and after the compressor is stopped, the M3 shall
free cooling or indoor air quality requirements, and resume damper modulation.
• Optional power exhaust fans. • Option 2: Is as follows:
On a cooling demand, outdoor air is used for free cooling instead of first-stage > Holds­off compressor on Y2 call until damper has modulated to maximum
compressor(s) when outdoor air is suitable. position (Parameter 131 - FREE CL MAX DAMPER) for three minutes.

13.1. Enabling Economizer and Settings > After three minutes, the compressor starts and the free cooling set point is
lowered to 45°F. Damper is not locked at maximum open while compres-
To enable the economizer if installed: sor is on, but modulates to maintain 45°F discharge air temperature.
Go to SETUP > INSTALL > When Y2 is satisfied, compressor goes off and free cooling set point is
See “Table 5. Menu Interface (Level 1 - SETUP)” on page 15 and go through restored to 55°F (Parameter 159 - FREE COOL SUPPLY SP).
the wizard. When reaching Configuration ID 1, position 2 will need to be set to the
applicable type of economizer. Valid types are: • Option 3: Same as Option 2, but with a 10 minute delay instead of a three
minute delay.
• M = Motorized Outdoor Air Damper Only
• T = Economizer - Temperature (Note: Used for both set point and offset 13.4. Free Cooling Compressor Lockout Mode and Low
temperature control.)
Ambient Set Point
• G = Economizer - Global
• S = Economizer - Single Enthalpy Go to SETTINGS > RTU OPTION > EDIT PARAMETER = 285
(FRCL COMP LCKOUT MD).
• D = Economizer - Dual Enthalpy
Default value is 2. Range is 0 to 2.
13.2. Damper Feedback Calibration • 0 = Disable Compressor Lockout
• 1 = Lockout Compressor if outdoor air is suitable regardless of outdoor air
Use the following procedure to perform a damper feedback calibration. temperature.
Go to SETUP > TEST & BALANCE > DAMPER > IS DAMPER CLOSED? • 2 = Lockout Compressor if outdoor air temperature is below Parameter 108
This drives the damper to the fully closed position. Visually inspect that the setting and Outdoor Air is Suitable (Default).
damper has stopped moving in the closed position, and answer YES to calibrate
damper closed position feedback value. Go to SETTINGS > RTU OPTION > EDIT PARAMETER = 108
Then the next screen will ask IS DMPR FULL OPEN? (FREE LO AMB LCKT SP).
This will drive the damper to fully open position. Visually inspect that the damper Default value is 55.0°F. Range is 45.0 to 80.0°F.
has stopped moving in the full open position, and answer YES to calibrate damper
full open position feedback value. 13.5. Outdoor Air Suitable for Free Cooling
13.3. Damper Operation During Free Cooling The M3 unit controller displays the outdoor air suitability information on the status
screen.
These are operating profile options for the economizer damper (Parameter 164 The appropriate sensors are provided when the economizer is factory-configured.
- ECONOMIZER PROFILE) during free cooling when any compressor is on and When the economizer is field-installed and configured, the single or dual enthalpy
can be selected as follows: modes require additional field-provided sensor(s).
• Option 0: Damper continues to modulate while compressors are on, but the
effect of mechanical cooling may force the damper closed to its minimum
position. After compressor starts, the free cooling set point is lowered to fixed
temperature setting of 45°F.
29
13.6. Enthalpy Set Point NOTE: When equipped with Motorized Outdoor damper Air Damper,
Prodigy 2.0 provides only Demand Control Ventilation. Free Cooling/
This setting pertains to the single enthalpy free cooling mode only. The M3 unit Economizer function is not available.
controller will enable free cooling when outdoor air enthalpy (A7) is less than the
enthalpy set point (Parameter 162 - ECON FREECL ENTH SP). Figure 6 shows
the approximate enthalpy sensor output at various temperatures and percentage 13.10. Economizer Checkout
of relative humidity.
The following checkout procedures are completed with unit energized. Confirm
proper operation of the heartbeat LED. Step 1 will determine whether the
100 economizer is allowing full damper travel. Use step 2 when the damper does not
90 respond to step 1.
80 Steps 3, 4, 5, and 6 checkout the operating modes; checkout only the mode that
applies to the unit being worked on.
70
60 CAUTION
50 Power exhaust fans will be functional. To prevent operation of power exhaust
40
fans, disconnect power to unit and then PED jack/plug P/J18.

30 Step 1. ECONOMIZER OUTPUT VOLTAGE


20
The M3 unit controller monitors P262 (DPOS) and operates as reference in
Section Damper Diagnostics in the Prodigy 2.0 (M3 unit controller) Application
10 Guide (Advance Features).
40°F 50°F 60°F 70°F 80°F 90°F 100°F
Go to SERVICE > TEST > DAMPER > POSITION > DAMPER POSITION ACTUAL: 0.0%
Figure 7. Enthalpy Sensor Output Current Honeywell C7400
a. The motor will slowly modulate to the closed position.
b. Change DAMPER POSITION ACTUAL to 100.0%.The motor will slowly
13.7. Free Cooling Damper Maximum Position modulate to the fully opened position.
Damper Maximum position for free cooling is by default set to 100%. To modify c. If the motor does not respond, go to step 2. If the motor does respond properly,
this settings, use the following path: go to the appropriate mode of operation checkout.
SETTINGS > RTU OPTION > EDIT PARAMETER - 131 (FREE CL MAX DAMPER) Step 2. OUTPUT VOLTAGE CHECK
Go to SERVICE > TEST > DAMPER > POSITION > DAMPER POSITION ACTUAL: 0.0%
13.8. Minimum Damper Position
a. Adjust the DAMPER POSITION ACTUAL to 0.0% position.
Use the following menu path to modified the minimum damper positions for both
high and low operations. b. Measure the voltage on P262 between pin 3 (VOT damper control) and pin
2 (GND) using pin 1 as common. Voltage should read approximately 2 VDC.
SETUP > TEST & BALANCE > DAMPER > MIN DAMPER POSITION BLOWER ON HIGH = .%
c. Adjust the DAMPER POSITION ACTUAL to 100.0% position.
SETUP > TEST & BALANCE > DAMPER > MIN DAMPER POSITION BLOWER ON LOW = .% NOTE: Allow approximately 90 seconds for actuator to react.
d. Measure the voltage between P262 between pin 3 (VOT damper control) and
13.9. Motorized Outdoor Air Damper pin 2 (GND) using pin 1 as common. Voltage should read approximately 10
volts DC. If not, check wiring and trouble shoot system.
Set damper position according to “Minimum Damper Position” section for
normal operation, make sure the motorized outdoor air damper is set correctly
in Configuration ID 1, position 2 needs to be set to M. The damper will open
to the specified position during the occupied time period and close during the
unoccupied time period.

30
Step 3. SINGLE ENTHALPY OPERATION (ODE) d. Disconnect A7 outdoor enthalpy sensor jack/plugs J/P104. Connect a 750
In the single enthalpy mode, dampers open for free cooling when the outdoor ohm resistor across J104-1 and J104-2.
enthalpy is less than the enthalpy set point (Parameter 162 - ECON FREECL
ENTH SP); dampers will try to modulate discharge air temperature (RT6) to Step 5. ALL TEMPERATURE MODES OF OPERATION
(Parameter 159 - FREE COOL SUPPLY SP) which has a default setting of 55.0°F In the Economizer – Temperature mode, the damper opens for free cooling when
(13°C). the outdoor air temperature is:
a. Go to SETUP > INSTALL > press SAVE until you get to the Configuration ID • Less than return air temperature by at least a difference of (Parameter 161 -
1, position 2 needs to be set to S for Economizer Single Enthalpy and press ECON FRCL TMP OFFST) if Temperature Offset mode is selected
SAVE.
• Less than (Parameter 160 - ECON FREECL TEMP SP)
b. To simulate low outdoor enthalpy. Disconnect A7 outdoor enthalpy sensor
jack/plugs J/P104. Connect a 750 ohm resistor across plug J104-1 and J104- In all modes, dampers will try to modulate discharge air temperature (RT6) to
(Parameter 159 - FREE COOL SUPPLY SP) which has a default setting of 55.0°F
2. J104 is located in the filter access area. (13°C).
c. Check all connections and wiring between J104 and the control. Refer to the “Displaying Sensor Inputs” section to read return air (RT16) and
outdoor air (RT17) temperatures. If outdoor air is not cooler than return air,
Step 4. DUAL ENTHALPY MODE OF OPERATION simulate a colder outdoor air temperature with a resistor. Select a resistor value
In dual enthalpy mode, dampers open for free cooling when the outdoor air that corresponds to a temperature:
enthalpy is lower than the return air enthalpy by difference value of (Parameter 163 a. Locate RT17 sensor in unit. Disconnect 1/4” quick connect terminals on wires
- ECN FRCL ENTH OFFST); dampers will modulate discharge air temperature leading from sensor.
(RT6) to (Parameter 159 - FREE COOL SUPPLY SP) which has a default setting
of 55.0°F (13°C). b. Jumper RT17 wires leading back to control with the appropriate resistor.
a. Go to SETUP > INSTALL > press SAVE until you get to the Configuration ID 1 c. Check all connections and wiring between RT17 and the M3 unit controller,
position 2 needs to be set to D for Economizer ­Dual Enthalpy and press SAVE and between RT16 and the M3 unit controller.
if performing an economizer field-install.
Table 12. TMP Mode Resistor Values
b. Use two resistors to simulate outdoor air enthalpy suitable.
Temp. °F Size Temp. °F Size Temp. °F Size Temp. °F Size
c. Disconnect A62 return air enthalpy sensor jack/plug J/P105. Place a 1500 (°C) Resistor (°C) Resistor (°C) Resistor (°C) Resistor
ohm resistor between J105-1 and J105-3. J/P105 is located in the filter access 30 (-1) 34,566 50 (10) 19,904 70 (21) 11,884 90 (32) 7,332
area. 40 ( 4) 26,106 60 (16) 15,313 80 (27) 9,298 100 (38) 5,826

DISCONNECT J/P104 DISCONNECT J/P105

Damper Travel: % of Maximum Open

PLACE JUMPER WIRE HERE


PLACE JUMPER WIRE HERE

READ
READ CURRENT
CURRENT HERE
HERE
- +
- + DC AMMETER
DC AMMETER
Measure A7 Current in Series Measure A62 Current in Series

Figure 8. Measure A7 and A62 Current in Series

31
Step 6. SGLOBAL MODULATING (GLO) MODE OF OPERATION If the economizer is operating in the free cooling mode and the indoor air quality
In the GLO (modulating) mode, dampers modulate open for free cooling when the control requires the damper to open further, the indoor air quality demand will
global input is energized; dampers will try to modulate discharge air temperature override the free cooling demand.
(RT6) to (Parameter 159 - FREE COOL SUPPLY SP) which has a default setting The IAQ function is not energized during the unoccupied or night time period.
of 55.0°F (13°C). NOTE: The IAQ sensor may also be used with systems containing a motorized
NOTE: The global input turns on the blower. outdoor air damper.
a. Set global mode using the Configuration ID 1, position 2, and set to character
G. 14.1. Default Operation
b. Connect a jumper between A55_P297-1 (24VAC) and A55_P297-9 (global). The M3 unit controller has a 0-10VDC indoor air quality input for a standard 0
The blower is energized and the damper will slowly open if discharge air - 2000ppm carbon dioxide sensor. The economizer starts opening at a carbon
temperature (RT6) is greater than (Parameter 159 - FREE COOL SUPPLY dioxide level of 700 ppm (default) (start open set point) and reaches full open at
SP) which has a default setting of 55.0°F (13°C). a carbon dioxide level of 1200ppm (default) (full open set point).
c. Disconnect 24VAC to A55_P297-9. The blower will turn off and the damper The damper opens to a default position of 50% (see Parameter 117). Determine
damper travel position using the following formula:
will close.
% Damper Travel = carbon dioxide ppm - Start Open ppm
d. If the damper does not actuate then check all connections and wiring between 5
P262A and B. Example: At a carbon dioxide level of 750ppm, the damper will be
approximately 50% open:
Step 7. ENTHALPY SENSOR OPERATION (A7 AND A62)
% Damper Travel = 750-500 = 50%
If enthalpy sensors are configured, current sensor reading by M3 controller can
be verified through the user interface: 5
a. Connect a direct current ammeter as shown in figure 4 to measure current Use the menu interface to read carbon dioxide ppm. DATA > IN/OUTPUTS >
output of A7 or A62. SENSORS > C02. Figure 5 shows default or proportional operation.

b. The reading will be between 4 and 20 ma. depending on outdoor temperature 14.2. Maximum and Minimum Demand Control Ventilation
and humidity. Refer to figure 3 to approximate reading. Damper Settings
Go to DATA > IN/OUTPUTS > SENSORS > LOCAL Maximum position is set using the following menu path:
(scroll down to IE: x.x mA and OE: x.x mA)
c. If the meter reads zero, check sensor wiring harness for continuity and/or Go to SETTINGS > RTU OPTIONS >DAMPER > DAMPER CONTROL VENTILATION
OPTIONS and select DEMAND CONTROL VENTILATION.
check polarity of sensor wiring.
Options are:
14. Demand Control Ventilation • DEMAND CONTROL VENT > DAMPER START OPEN = XXXX PPM
A field-provided and installed indoor air quality (IAQ) sensor can be used with • DEMAND CONTROL VENT > DAMPER FULL OPEN = XXXX PPM
the modulating economizer or OADM to control carbon dioxide levels in the
conditioned space. The carbon dioxide level in a space is an indicator of the • DEMAND CONTROL VENT > DAMPER MAX OA CFM = X CFM (only visible
number of people occupying a room. As the carbon dioxide level rises (indicating if configuration id 1, position 2 is set correctly).
the occupancy of a room has increased), dampers modulate open - regardless
of outdoor air suitability. Likewise, as the carbon dioxide level falls (indicating the • DEMAND CONTROL VENT > DAMPER MAX OPENING = XXX.X %.
occupancy has decreased), dampers modulate further closed.
Standard economizer installations have a minimum fresh air ventilation
requirement based on maximum room occupancy. With standard economizer
use, the amount of air required for maximum room occupancy is heated or cooled
with each heating or cooling cycle. IAQ installations use the maximum amount
of required ventilation air only with maximum room occupancy; less outdoor air
needs to be heated or cooled when fewer people are in the conditioned space.

32
14.4. Set Point Control Option
Low Temp. Operation High Temp. Operation
100 40°F Parameter 75°F Parameter 121 Set point control mode is commonly used in areas with high occupancy and
123 frequent change out such as classrooms or conference rooms.
Damper Travel:
% of Maximum
In applications requiring this on/off damper response to airborne dioxide levels,

(Parameter 117
66 30°F 85°F
set the start open (Parameter 118 - DCV DAMP START OPEN) set point higher
Open than the full open (Parameter 119 - DCV DAMP FULL OPEN) set point. The
dampers will drive to fully-open position immediately. Figure 6 shows the set point
33 20°F 95°F
Min. Position control option. Change Parameters 122 and 123 to set the minimum outdoor
10°F Parameter 122
temperature limits.
105°F Parameter 120
0
700 1000 Change Parameters 120 and 121 to set the maximum temperature limits.
Parameter 118 Parameter 119
CO2 (ppm)
IMPORTANT
Figure 9. Default Demand Control Ventilation (DCV) Operation Mixed air temperatures less than 45°F (7°C) on units with an aluminized heat
exchanger or less than 30°F (-1°C) on stainless steel heat exchangers will void
the manufacturer’s warranty.
14.3. Parameter Adjustments
Default indoor air quality economizer operation is based on common or average 100 Parameter 117
applications. Adjustments may be made to the indoor air quality Parameters to Max. Open
alter operation or meet required specifications. Use the user interface to change
Parameter 117 through 123.
Go to SETTINGS > RTU OPTIONS > EDIT PARAMETER
Select a demand control ventilation mode with Parameter 134. Modes 3 and 4 Close Open
will bring on the unit blower when demand control ventilation calls for maximum
damper open, and returns to auto-blower when demand control ventilation
damper returns to 0. The other modes only operate when the unit blower is on,
but will not bring it on themselves.
Some applications require a different carbon dioxide set point range than default Min. Position
settings. Damper start open (Parameter 118) and full open (Parameter 119) Parameter 119 Parameter 118
carbon dioxide set points may be adjusted from 0 to 2000 ppm. Use the following (full) (start)
formula to determine damper travel.
carbon dioxide (ppm)
NOTE: When changing carbon dioxide set point range, “start open” set point
should be less than “full-open” set point. Figure 10. Set point Control Indoor Air Quality Option
% Damper Travel = carbon dioxide ppm - Start Open ppm X Max Open (Parameter
117) Full Open - Start Open 14.5. Determining Indoor Air Quality Inputs
Example: An application requires the dampers open at 800 CO2 ppm and reach
full open at 1200. If the carbon dioxide level in the space reads 1000 ppm, Selection from the M3 unit controller menu display.
calculate the damper percent open as follows.
% Damper Travel = 1000 - 800 or 200 or .5 = 0.5 x 100 = 50% Go to DATA> IN/OUTPUTS > SENSORS
1200 - 800 400

33
14.6. BACNET
The configuration shown in figure 7 has terminations on the M3 unit controller BACnet modules at both ends and ONLY at both ends of the chain.
The configuration shown to the in figure 7 has a termination at the controller/router on one end and a termination at the M3 unit controller BACnet module on the other
end; terminations are ONLY at the ends of the chain.
Cable type - twisted pair with shield, 22 awg minimum, Belden #88761 or #8761 (Lennox 27M19, 94L63, 68M35).

ated) minated)
CONTROLLER/
ROUTER
(terminated) (not terminated) (not terminated) (not terminated) (terminated)
The configuration shown above has terminations on the
M3 unit controller BACnet modules at both ends and ONLY
at both ends of the chain.
The configuration shown to the right has a termination at minated)
the controller/router on one end and a termination at the
CONTROLLER/
ations are ONLY at the ends of the chain. ROUTER
Cable type - twisted pair with shield, 22 awg minimum, (terminated per mfg (not terminated) (terminated)
Belden #88761 or #8761 (Lennox 27M19, 94L63, 68M35). instructions)

Figure 11. Terminating Ends of a Daisy-Chained Network

14.7. L CONNECTION
The network control panel is an L Connection direct digital controller used on units which are not equipped with an M3 unit controller. The Building Controller (BC) is
used to control building functions such as lights and signs. Use L connection specific network cable and daisy chain as shown in the following figure. L Connection
daisy chains also need termination at the end nodes of the chain.
Cable type - twisted pair with shield, 22 awg minimum, Belden #88761 or #8761 (Lennox 27M19, 94L63, 68M35).
SYS BUS TERMINAL BLOCK SYS BUS TERMINAL BLOCK ON LENNOX
ON LENNOX CONTROLLERS CONTROLLERS IMC (M1-7, M1-8, NTC, BC S-BUS TERMINAL BLOCK ON LENNOX
IMC (M1-1 TO M1-6 L SERIES) AND ZONE CONTROLLERS) PRODIGY M2 OR M3 CONTROLLER
- G + - S + - S +

CONTINUE WIRING TYP.


TO LAST CONTROLLER
ON NETWORK
SHIELD SHIELD SHIELD
Cable type - twisted pair

um, Belden #88761 or


CONNECT + TERMINAL OF NCP TO + TERMINALS ON ALL CONTROLLERS. #8761 (Lennox 27M19,
94L63, 68M35).
1 CONNECT - TERMINAL OF NCP TO - TERMINALS ON ALL CONTROLLERS.
2 SHIELD
3 DO NOT CONNECT THE CABLE SHIELD TO THE ”G” TERMINAL ON M1-6 AND OLDER

Figure 12. L Connection® Network Daisy-Chain Communication Wiring


34
15. Abbreviations Table 13. Abbreviations
Table 13. Abbreviations Abbreviation Definition

Abbreviation Definition H1 1st stage heating

A55 M3 board. Main RTU control board H2 2nd stage heating

AI Analog input H3 3rd stage heating

AO Analog output H4 4th stage heating

BL Blower HP High pressure

C3 Add on board for third and forth compressor and second-stage heat (A178). HSP Heating setpoint

C1 1st stage cooling HT Heating

C2 2nd stage cooling IAQ Indoor air quality. Often synonymous with CO2 level in ppm

C3 3rd stage cooling IDE Indoor enthalpy. Depends on temperature and humidity

C4 4th stage cooling “w.c. Inches of water column

CAI Combustion air inducer LED Light emitting diode. An indicator light, found either as individual elements or
grouped together as segments to form characters
CAVB Constant air volume with bypass damper
LP Low pressure
COM Electrical common
LT Limit
CL Cooling
M3 M3 Unit Controller - main controller board (A55)
CP1 Compressor 1
MGV Modulating gas valve
CP2 Compressor 2
MSAV Multi Stage Air Volume
CP3 Compressor 3
OAC Outdoor air control
CP4 Compressor 4
OAS Outdoor air suitable for free cooling
CSP Cooling setpoint
OAT Outdoor air temperature
DAC Discharge (supply) air control
OCP Thermostat demand, occupied mode
DACC Discharge (supply) air control cooling
ODE Outdoor enthalpy. Depends on temperature and humidity
DACH Discharge (supply) air control heating
PID Proportional, integral and derivative based control loop
DAP Discharge (supply) air pressure
PPM Parts per million (mostly used for CO2 measurements)
DAT Discharge (supply) air temperature
RAP Return air pressure
DB Deadband
RAT Return air temperature
DCV Demand controlled ventilation
RH Relative humidity
DDC Direct digital control
RS Reset
DI Digital input
RTU Roof top unit
Diff Differential
RT6 Discharge air temperature sensor
DO Digital output
RT16 Return air temperature sensor
FAC Fresh air cooling control
RT17 Outdoor air temperature sensor
FAH Fresh air heating control
SMK Smoke detection mode (alarm)
FAT Fresh air tempering control. See FAC & FAH
SP Setpoint
FC Free cooling
Stg Stage
G Thermostat demand, blower
TB Terminal block
GLO Global mode or input (economizer)
UnOCP Unoccupied

35
Table 13. Abbreviations 17. USB Service Report Example
Abbreviation Definition =================================================== Cool High 1800 57
USB SERVICE REPORT Cool Low 1300 31
W1 Thermostat demand, heat stage 1 ===================================================
Service Date 04:03:2014
Heat
Ventilation
2000
1200
70
27
Service Time 19:26:35 Smoke 2000 70
W2 Thermostat demand, heat stage 2 Serial No. Economizer Differential Pressure(@ 2000 Supply
Software Version 08.00.0009 Airflow(cfm))
W3 Thermostat demand, heat stage 3 Hardware Version
Unit Number UNIT 1
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
Damper Position (%) Diff.Pressure(in.H20)
SBUS Address 2 −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
W4 Thermostat demand, heat stage 4 BACnet Address 2 0 0.39
Catalogue Number 50 0.23
VAC Alternating current voltage Model Number LGH060H4EH1Y 100 0.06
CONFIGURATION ID 1 NTNNNNLN Outside Airflow Targets

VAV Variable air volume. Accomplished with a variable frequency drive (VFD) CONFIGURATION ID 2 NNNNNNNNN
Status IDLE
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
Minimum Outside Air/Minimum DCV: 200 cfm
=================================================== Maximum DCV: 0 cfm
VDC Direct current voltage Runtime Data Minimum CO2: 700 ppm
Total Power On 23 HRS 8 CYCLES Maximum CO2: 1200 ppm
VFD Var. frequency drive. An AC inverter used to vary motor speed Before Install
Filter
0 HRS
12 HRS
−−−−−−−
−−−−−−−
===================================================
Alarm/Status Log
Belt 11 HRS −−−−−−− (143) 04:03:2014 19:26:13 RESET DAMPER PRESSURE
VT Ventilation Blower 12 HRS 50 CYCLES (141) 04:03:2014 19:26:13 RESET CFM TARGET TOO
Compressor 1 3 HRS 40 CYCLES HIGH
Y1 Thermostat demand, cooling stage one Compressor 2 4 HRS 27 CYCLES (143) 04:03:2014 19:06:19 SET DAMPER PRESSURE
Compressor 3 0 HRS 2 CYCLES (141) 04:03:2014 19:06:19 SET CFM TARGET TOO

Y2 Thermostat demand, cooling stage two


Compressor 4 0 HRS 3 CYCLES HIGH
Outdoor Fan 1 7 HRS 28 CYCLES ( 82) 04:03:2014 19:06:18 RESET CONTROLLER RESET
Outdoor Fan 2 2 HRS 22 CYCLES ( 82) 04:03:2014 19:06:18 SET CONTROLLER RESET
Y3 Thermostat demand, cooling stage three Outdoor Fan 3 0 HRS 2 CYCLES (143) 04:03:2014 18:59:41 SET DAMPER PRESSURE
Outdoor Fan 4 0 HRS 3 CYCLES (141) 04:03:2014 18:59:41 SET CFM TARGET TOO
Y4 Thermostat demand, cooling stage four Outdoor Fan 5
Outdoor Fan 6
0 HRS
0 HRS
3 CYCLES
3 CYCLES
HIGH
( 82) 04:03:2014 18:59:40 RESET CONTROLLER RESET
POWER EXHAUST 0 HRS 0 CYCLES ( 82) 04:03:2014 18:59:40 SET CONTROLLER RESET
ZAT Zone air temperature Heat Stage 1 0 HRS 1 CYCLES (143) 04:03:2014 18:35:19 SET DAMPER PRESSURE
Heat Stage 2 0 HRS 1 CYCLES (141) 04:03:2014 18:35:19 SET CFM TARGET TOO
Humiditrol 0 HRS 0 CYCLES HIGH
16. Parts and Kits Free Cooling
UV Lamp
0 HRS
0 HRS −−−−−−−
4 CYCLES (148) 04:03:2014 18:21:36 RESET SMARTAIRFLOW
CONFIG ERROR
=================================================== (170) 04:03:2014 18:21:36 RESET POWER EXHAUST

Table 14. Parts and Kits Available for M3 Unit Controller Sensor Data
OAT 66 degF
UNCONFIGURED
(165) 04:03:2014 18:21:36 RESET ECONOMIZER
RAT 72 degF UNCONFIGURED
Description Catalog Description Catalog Description Catalog DAT
ZAT
73 degF
78 degF
( 85) 04:03:2014 18:21:36 RESET INCORRECT
HUMIDITROL SETTINGS
number number number RH 50 % (132) 04:03:2014 18:21:24 RESET VFD BYPASS
CO2 460 ppm UNCONFIGURED
M3 Unit 14V60 USB service kit 59W52 SmartWire™ 59W57 ===================================================
SmartAirFlow System Data
(148) 04:03:2014 18:21:23
CONFIG ERROR
SET SMARTAIRFLOW

Controller tube Field Termination (132) 04:03:2014 18:21:23 SET VFD BYPASS

Replacement kit kit Calibrated On 04/03/2014 19:12:56 UNCONFIGURED


(170) 04:03:2014 18:21:23 SET POWER EXHAUST
Supply Airflow Calibration Table UNCONFIGURED
LCD Display 10X85 M3 unit controller 59W53 Lennox Prodigy 59W59 −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− (165) 04:03:2014 18:21:23 SET ECONOMIZER

Replacement Kit battery (10-pack) 2.0 USB Memory PWM(%) Speed(rpm) Airflow(cfm)
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
UNCONFIGURED
( 85) 04:03:2014 18:21:23 SET INCORRECT
Stick (5-pack) 20 480 1031 HUMIDITROL SETTINGS
30 570 1274 ( 82) 04:03:2014 18:20:31 RESET CONTROLLER RESET
M3 unit controller 10X86 BACnet 59W51 40
50
660
750
1493
1687
( 82) 04:03:2014 18:20:31 SET CONTROLLER RESET
( 82) 04:03:2014 18:16:32 RESET CONTROLLER RESET
cover Replacement kit 60 840 1857 ( 82) 04:03:2014 18:16:32 SET CONTROLLER RESET
70 930 2004 ( 82) 04:03:2014 18:14:10 RESET CONTROLLER RESET
80 1020 2126 ( 82) 04:03:2014 18:14:10 SET CONTROLLER RESET
90 1110 2223 ( 82) 04:03:2014 18:14:09 RESET CONTROLLER RESET
100 1200 2297 ( 82) 04:03:2014 18:14:09 SET CONTROLLER RESET

Supply Airflow Targets =====================================================


−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− END OF REPORT
Mode Desired Airflow(cfm) PWM(%)
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−

36
18. USB SmartAirflow Report 19. Alarms
===================================================== 0% 0.30 0 70
USB SMARTAIRFLOW REPORT
===================================================== 5%
2004
0.29 104 70 19.1. Phase - Voltage Detection
Service Date 04:03:2014 2004
Service Time
Serial No.
19:32:49 10%
2004
0.28 184 70
The M3 unit controller has the ability to detect that the rooftop unit power source
Software Version
Hardware Version
08.00.0009 15%
2004
0.27 261 70 has the correct frequency, phasing and voltage levels. When this feature is
Unit Number UNIT 1 20% 0.26 325 70 enabled, the detection of frequency and phasing is determined at power-on and
SBUS Address
BACnet Address
2
2 25%
2004
0.24 437 70
the voltage level is continuously monitored. If any of these is out of range, then
Catalogue Number 2004 an alarm is logged and the rooftop unit operation is locked out.
Model Number LGH060H4EH1Y 30% 0.23 561 70
CONFIGURATION ID 1 NTNNNNLN
CONFIGURATION ID 2 NNNNNNNNN
2004
=====================================================
a. Alarms Detected at Power-On Start up:
Status IDLE
=====================================================
END OF REPORT
• 121 - LINE FREQ DOES NOT MATCH UNIT CONFIG
Calibrated On 04/03/2014 19:12:56 • 126 - LINE PHASING DOES NOT MATCH UNIT CONFIG
b. Alarms - Continuously Monitoring
Supply Airflow Calibration Table
--------------------------------------
PWM(%) Speed(rpm) Airflow(cfm)
• 122 - 24VAC PRIMARY VOLTAGE LOW
--------------------------------------
20 480 1031 • 123 - 24VAC PRIMARY VOLTAGE HIGH
30 570 1274
40
50
660
750
1493
1687
• 134 - 24VAC SECONDARY VOLTAGE LOW
60 840 1857
70 930 2004 • 125 - 24VAC SECONDARY VOLTAGE HIGH
80 1020 2126
90
100
1110
1200
2223
2297
Alarms 122 through 125 are auto-resetting. The rooftop operation will be restored
five (5) minutes after the proper voltage levels are restored. Alarms 121 and 126
Supply Airflow Set Points
requires removing the power and correcting the issue before restoring the rooftop
-----------------------------------------------------
Desired Actual
operation.
Airflow(cfm)
Mode Airflow(cfm) PWM(%) (With Damper
The frequency (60 or 50 Hz) and the phasing (single or three-phase) of the power
Closed) Econ dP source is determined by the model number stored in the M3 unit controller. This
----------------------------------------------------- model number and enabling/disabling the Phase-Voltage Detection feature can
Cool Low
0.21
1300 31 1687 be modified through the M3 unit controller user interface. See the Installation and
Cool High 1800 57 1297 Setup Guide for instructions on how to configure the CONFIGURATION ID 2,
Heat
0.13
2000 70 1809
Position 5. Options are:
Ventilation
0.25
1200 27 2004 • N = NOT INSTALLED
0.30
Smoke
0.11
2000 70 1204 • 1 = ENABLED INTERNAL (LENNOX)
Outside Airflow Targets • 2 = EXTERNAL (A42) PHASE DETECTION ON DI-2
--------------------------------------------
Minimum Outside Air/Minimum DCV:
Maximum DCV:
200 cfm
0 cfm
• 3 = EXTERNAL (A42) PHASE DETECTION ON DI-3
Minimum CO2: 700 ppm
Maximum CO2: 1200 ppm When an event occurs, the M3 unit controller will display a code which corresponds
Ventilation Calibration(@ 2000 Supply
to control function. Error codes are stored and can be recalled later.
Airflow(cfm))
NOTE: Any references in the user interface referencing Advanced Airflow
-----------------------------------------------------
Damper Outdoor Supply actually indicates SmartAirflow®.
Supply
Position(%) Econ dP Airflow(cfm) PWM(%)
Airflow(cfm)

-----------------------------------------------------

37
19.2. Service Relays command. Other modes of operation may be selected and are described in the
Prodigy Application Guide (Advanced Features).
Selected alarms (marked with * in the following table result in the closure of NOTE: Any references in the user interface referencing Advance Airflow
the service relay contacts (DO1). The contacts remain closed until the Prodigy actually indicates SmartAirflow®.
resets, or alarm condition is cleared and alarm status is read via explicit S-BUS

19.3. M3 Unit Controller Alarm and Event Codes

Table 15. Prodigy 2.0 Alarm and Event Codes


SELECTED ALARMS (MARKED WITH * IN TABLE RESULT IN THE CLOSURE OF THE SERVICE RELAY CONTACTS (DO1).
ALARM
DISPLAY MESSAGE EVENT ACTION
CODE
Check power connections.
LOSS OF POWER DETECTION The M3 unit controller will set an alarm “Erratic Power” whenever service is turned off due to detection of power loss. User will be able to clear
1
(SINGLE PHASE UNITS) “Erratic Power” alarm via user interface. The M3 unit controller will clear “Power Erratic” after the Compressor Min OFF Delay has expired. If
compressor demand is still present the M3 unit controller will restart compressor(s) after the Compressor Min OFF Delay has expired.
2 - 3 RESERVED
A173 input is sensed as closed. Will automatically clears once input is detected open. For smoke mode, check for source of smoke. While
4* SMOKE DETECTOR INPUT (A173)
Smoke Alarm is active, the M3 unit controller will not service any cooling, heating or ventilation demands.
Unit off. Air flow switch is normally closed. Monitoring starts 16 seconds after blower is started. if air flow switch is detected open after 16
5* BLOWER S52 second delay period, all compressors are de-energized, gas valves closed, electric heat turned off, economizer damper closed, and blower is
stopped. Alarm will automatically clear once the error timed off delay has expired and system will resume. Check blower operation.
6* DIRTY FILTER SWITCH S27 Dirty filter switch is detected as closed and will automatically clear once switch is detected open. Replace filter or check filter switch S27.
7 RESERVED
Lockout is active with multiple alarm code 5 detected. Alarm can be manually cleared through the user interface. Check blower operation.
8* STRIKE 3 ON BLOWER S52
Once problem is corrected, lockout alarm can be cleared by resetting the M3 unit controller.
9 - 11 RESERVED
Compressor is off. Check charge, fans and coil.
NOTE: On Energence Ultra-High Efficiency units - if only alarm 12 is present then issue could be high temperature S5 switch. If alarm 12 is
COMP 1 HIGH PRESS S4 OR HI TEMP accompanied with alarm 14 then most likely it is the high pressure S4 switch.
12
S5
The unit controller will clear high pressure switch alarm when corresponding high pressure switch is detected as closed. Compressor will not
restart until corresponding high pressure switch is closed and Minimum Off Delay (cooling or heating) has expired.
• Compressor is lockout. Check charge, fans and coil. Use service menu to clear lockouts.
• User will be able to clear high pressure switch compressor lockout and alarm via user interface. High pressure switch compressor
STRIKE 3 ON COMP 1 HIGH PRESS S4 lockout and alarm will be cleared after the M3 unit controller reset.
13*
OR HI TEMP S5
• High pressure switch compressor lockout and alarm will be cleared on termination of cooling demand.
• Default is 3 occurrences and can be set between 1 and 7 occurrences.
Compress is off. Check charge, fans and coil.
NOTE: On Energence Ultra-High efficiency units tandem alarms (14) compressor 2 high temperature S8 switch. If accompanied with alarm 15
14 COMP 2 HIGH PRESS S7 then most likely the S4 high pressure switch is the issue.

The M3 unit controller will clear high pressure switch alarm when corresponding high pressure switch is detected as closed. Compressor will
not be restarted until corresponding high pressure switch is closed and Minimum Off Delay (cooling or heating) has expired.

38
Table 15. Prodigy 2.0 Alarm and Event Codes
SELECTED ALARMS (MARKED WITH * IN TABLE RESULT IN THE CLOSURE OF THE SERVICE RELAY CONTACTS (DO1).
ALARM
DISPLAY MESSAGE EVENT ACTION
CODE
• Compressor lockout. Check charge, fans and coil. Use service menu to clear lockouts.
• User will be able to clear high pressure switch compressor lockout and alarm via user interface. High pressure switch compressor
STRIKE 3 ON COMP 2 HIGH PRESS S5 lockout and alarm will be cleared after the M3 unit controller reset.
15*
OR S7
• High pressure switch compressor lockout and alarm will be cleared on removal of cooling demand.
• Default is 3 occurrences and can be set between 1 and 7 occurrences.
• Compressor is off. Check charge, fans and coil.
16 COMP 3 HIGH PRESS S28 • The M3 unit controller will clear high pressure switch alarm when corresponding high pressure switch is detected as closed. Compressor
will not be restarted until corresponding high pressure switch is closed and Minimum Off Delay (cooling or heating) has expired.
• Compressor lockout. Check charge, fans and coil. Use service menu to clear lockouts.
• User will be able to clear high pressure switch compressor lockout and alarm through the user interface. High pressure switch
STRIKE 3 ON COMP 3 HIGH PRESS
17* compressor lockout and alarm will be cleared after the M3 unit controller reset.
S28
• High pressure switch compressor lockout and alarm is cleared on removal of cooling demand. Default is 3 occurrences and can be set
between 1 and 7 occurrences.
• Compressor lockout. Check charge, fans and coil.
18 COMP 4 HIGH PRESS S96 • The M3 unit controller will clear high pressure switch alarm when corresponding high pressure switch is detected as closed. Compressor
will not be restarted until corresponding high pressure switch is closed and Minimum Off Delay (cooling or heating) has expired.
• Compressor lockout. Check charge, fans and coil. Use service menu to clear lockouts.
• User will be able to clear high pressure switch compressor lockout and alarm via user interface. High pressure switch compressor
STRIKE 3 ON COMP 4 HIGH PRESS
19* lockout and alarm will be cleared after the M3 unit controller reset.
S96
• High pressure switch compressor lockout and alarm is cleared on removal of cooling demand. Default is 3 occurrences and can be set
between 1 and 7 occurrences.
NOTE: EVENTS 12­19 COULD ALSO BE CAUSED BY A HIGH TEMPERATURE CONDITION ON SOME COMPRESSORS EQUIPPED WITH A HIGH TEMPERATURE SHUTDOWN.
20 UNIT SHUTDOWN A42 Phase monitor.
21 RESERVED
22 COMP 1 LOW PRESS S87 Compressor is off. Check charge, fans and coil. Use service menu to clear lockouts.
• Compressor is off. Check charge, fans and coil. Use service menu to clear lockouts.
23* STRIKE 3 ON COMP 1 S87
• Number of occurrences is set using Parameter 99 (max lo occurrences). Default is 3 occurrences.
24 COMP 2 LOW PRESS S88 Compressor is off. Check charge, fans and coil.
• Compressor is off. Check charge, fans and coil. Use service menu to clear lockouts.
25* STRIKE 3 ON COMP 2 S88
• Number of occurrences is set using Parameter 99 (max lo occurrences). Default is 3 occurrences.
26 COMP 3 LOW PRESS S98 Compressor if off. Check charge, fans and coil.
• Compressor is off. Check charge, fans and coil. Use service menu to clear lockouts.
27* STRIKE 3 ON COMP 3 S98
• Number of occurrences is set using Parameter 99 (max lo occurrences). Default is 3 occurrences.
28 COMP 4 LOW PRESS S97 Compressor if off. Check charge, fans and coil.
• Compressor is off. Check charge, fans and coil. Use service menu to clear lockouts.
29* STRIKE 3 ON COMP 4 S97
• Number of occurrences is set using Parameter 99 (max lo occurrences). Default is 3 occurrences.

39
Table 15. Prodigy 2.0 Alarm and Event Codes
SELECTED ALARMS (MARKED WITH * IN TABLE RESULT IN THE CLOSURE OF THE SERVICE RELAY CONTACTS (DO1).
ALARM
DISPLAY MESSAGE EVENT ACTION
CODE
• Check for block drain, condensate lines and drain pan overflow switch.
DRAIN PLAN OVERLFOW SHUTDOWN • Alarm set if overflow switch is detected opened and compressor will be locked out. System will automatically clear alarm once switch
30*
(S149) is detected closed. System will resume operation (compressor lockout), after the Error Timed OFF Delay has expired following the
Overflow switch alarm clear.
31 RESERVED
32 COMP 1 FRZSTAT OPEN S49 Compressor is off. Check freezestat, air flow, charge, coil, air filter and outside air temperature.
• Compressor is locked out. Check freezestat, air flow, charge, coil, air filter and outside air temperature.
33* STRIKE 3 COMP 1 FRZSTAT OPEN S49
• Number of occurrences is set using Parameter 81 (max freeze sat occ). Default is 3 occurrences.
34 COMP 2 FRZSTAT OPEN S50 • Compressor is locked out. Check freezestat, air flow, charge, coil, air filter and outside air temperature.
• Compressor is locked out. Check freezestat, air flow, charge, coil, air filter and outside air temperature.
35* STRIKE 3 COMP 2 FRZSTAT OPEN S50
• Number of occurrences is set using Parameter 81 (max freeze sat occ). Default is 3 occurrences.
36 COMP 3 FRZSTAT OPEN S53 • Compressor is locked out. Check freezestat, air flow, charge, coil, air filter and outside air temperature.
• Compressor is locked out. Check freezestat, air flow, charge, coil, air filter and outside air temperature.
37* STRIKE 3 COMP 3 FRZSTAT OPEN S53
• Number of occurrences is set using Parameter 81 (max freeze sat occ). Default is 3 occurrences.
38 COMP 4 FRZSTAT OPEN S95 • Compressor is locked out. Check freezestat, air flow, charge, coil, air filter and outside air temperature.
• Compressor is locked out. Check freezestat, air flow, charge, coil, air filter and outside air temperature.
39* STRIKE 3 COMP 4 FRZSTAT OPEN S95
• Number of occurrences is set using Parameter 81 (max freeze sat occ). Default is 3 occurrences.
40 RETURN AIR OVER HEAT LIMIT RT16 Heat is above set point. Check space conditions and sensors.
RETURN AIR UNDER COOL LIMIT
41 Cool is below set point. Check space conditions and sensors.
RT16
• System will set an alarm if S42 witch is detected as open. System will automatically clear alarm once S42 switch is detected closed.
BLOWER MOTOR OVERLOAD (S42 OR System will resume operation (servicing the demands), after the Error Timed OFF Delay has expired following S42 or S135 clear.
42*
S135) SHUTDOWN
• Check external motor overloads.
43 RESERVED
44* GAS VALVE ON NO DEMAND GV1 Unit is off. Gas valve 1 has power, but no demand. Check gas valve and wiring.
45* GAS VALVE ON NO DEMAND GV2 Unit is off. Gas valve 2 has power, but no demand. Check gas valve and wiring.
46 - 48 RESERVED
Third and fourth compressors are off. Alarm automatically clears once 24VAC is present. The M3 unit controller will resume operation once
49 No 24VAC ON A178 (C3) CONTROL
the ERROR TIME OFF DELAY is completed. Parameter 110 is used to set the reference delay. Factory delay default is 300 seconds.
50 PRIMARY HEAT 1 LIMIT OPEN S10 Heat section 1 primary gas heat limit switch is open. Check air flow, air filter, limit switch and wiring.
STRIKE 3 PRIMARY HEAT 1 LIMIT
51* Heat section 1 primary gas heat limit switch is open. Check air flow, air filter, limit switch and wiring. Number of occurrences is reached.
OPEN S10
52 SECONDARY HEAT 1 LIMIT OPEN S21 Heat section 1 secondary gas heat limit switch is open. Check air flow, air filter, limit switch and wiring.
STRIKE 3 SECONDARY HEAT 1 LIMIT
53* Heat section 1 secondary gas heat limit switch is open. Check air flow, air filter, limit switch and wiring. Number of occurrences is reached.
OPEN S21
54 HEAT 1 S15 LIMIT OPEN Heat section 1 primary electric heat limit switch is open. Check air flow, air filter, limit switch and wiring.
55* ROLL OUT OPEN Heat section 1 flame roll out burner 1 switch is open. Check gas roll out switch S47.

40
Table 15. Prodigy 2.0 Alarm and Event Codes
SELECTED ALARMS (MARKED WITH * IN TABLE RESULT IN THE CLOSURE OF THE SERVICE RELAY CONTACTS (DO1).
ALARM
DISPLAY MESSAGE EVENT ACTION
CODE
56 HEAT 1 CAI SWITCH S18 Check heat section 1 combustion air motor and proof switch.
57* STRIKE 3 HEAT 1 CAI SWITCH S18 Check heat section 1 combustion air motor and proof switch. Number of occurrences is reached.
58 HEAT 1 NO PROOF GAS VALVE GV1 Check heat section 1 ignition control, flame proof, gas valve 1 and gas supply.
59* STRIKE 3 NO PROOF GAS VALVE GV1 Check heat section 1 ignition control, flame proof, gas valve 1 and gas supply. Number of occurrences is reached.
60 PRIMARY HEAT 2 LIMIT OPEN S99 Check heat section 2 primary burner limit switch to see if it is open. Check air flow, limit switch and wiring.
STRIKE 3 PRIMARY HEAT 2 LIMIT
61* Check heat section 2 primary burner limit switch to see if it is open. Check air flow, limit switch and wiring. Number of occurrences is reached.
OPEN S99
62 HEAT 2 LIMIT OPEN S100 Heat section 2 secondary heat limit switch is open. Check air flow, limit switch and wiring.

63* STRIKE 3 HEAT 2 LIMIT OPEN S100 Heat section 2 secondary heat limit switch is open. Check air flow, limit switch and wiring. Number of occurrences is reached.

64 RESERVED
65* HEAT 2 ROLLOUT OPEN S69 Check roll out sensor and gas supply.
66 HEAT 2 CAI SWITCH S45 Check heat section 2 combustion air motor and proof switch.
67* STRIKE 3 HEAT 2 CAI SWITCH S45 Check heat section 2 combustion air motor and proof switch. Number of occurrences is reached.
68 HEAT 2 NO PROOF GAS VALVE GV2 Check heat section 2 ignition control, flame roof, gas valve 2 and gas supply.
69* STRIKE 3 NO PROOF GAS VALVE GV2 Check heat section 2 ignition control, flame roof, gas valve 2 and gas supply. Number of occurrences is reached.
70 - 72 RESERVED
73 NETWORK SENSOR ERROR Check with integrator for refresh rate, network status lights and wiring.
• If measurement is out of specified range (including open/short detection) the system will ignore the Zone Temperature Sensor readings
and set the alarm.
• If measurement of Zone Temperature Sensor is out of specified range (including open/short detection) the system will change operating
74* ZONE (ROOM) SENSOR A2 mode to the specified Backup mode (None, Local Thermistor or Return Air temp).
• The system will clear the alarm, if zone temperature sensor measurement is detected in specified operating range and return the system
to monitoring the A2 sensor as the primary sensor input.

Check zone (room) sensor and wiring


• If measurement of the outdoor temperature sensor is out of specified range (including open / short detection, the alarm will be activated.
OUTDOOR TEMPERATURE SENSOR Alarm will automatically clear once in range condition is detected.
75*
(RT17)
• Check sensor and wiring.
• If measurement is below specified range ( <5 % RH) the system will ignore the Relative Humidity readings. If measurement is above the
specified range( >100% RH) the system will limit the value to 100%.
• If measurement of Relative Humidity Sensor is below specified range while the dehumidification mode using RH sensor is enabled, the
76* HUMIDITY SENSOR A91
system will set an alarm. The system will clear the alarm if Relative Humidity sensor measurement is detected in specified operating
range OR dehumidification mode using RH sensor is disabled.
• Check sensor and wiring.
• If measurement of the discharge air temperature sensor is out of specified range (including open / short detection, the alarm will be
77* DISCHARGE AIR TEMP SENSOR RT6 activated. Alarm will automatically clear once in range condition is detected.
• Check sensor and wiring.

41
Table 15. Prodigy 2.0 Alarm and Event Codes
SELECTED ALARMS (MARKED WITH * IN TABLE RESULT IN THE CLOSURE OF THE SERVICE RELAY CONTACTS (DO1).
ALARM
DISPLAY MESSAGE EVENT ACTION
CODE
• If measurement of the return air temperature sensor is out of specified range (including open / short detection, the alarm will be
78* RETURN AIR TEMP SENSOR (RT16) activated. Alarm will automatically clear once in range condition is detected.
• Check sensor and wiring.
Add-on board problem, reset M3 unit controller to clear. When the communication alarm 80 persists for more than 30 seconds even after
79* ADD­ON BOARD PROBLEM
several retries for establishing the communication this Alarm is logged. Alarm can only be cleared by M3 Unit controller reset.
ADD­ON BOARD COMMUNICATION When the M3 unit controller is not able to communicate with any attached add-on boards (C3 and GP3) this alarm code is logged. The M3
80
PROBLEM unit controller will retry to establish the communication once every 5 second. Alarm is automatically cleared once communication is restored.
Check reheat settings. Alarm 81 is raised under these two conditions:
81 REHEAT SETUP ERROR 1. If the user sets up the unit to use supermarket reheat on a non-­gas unit.
2. If the user sets up the unit to use Humiditrol reheat but the heater type is heat pump
82 CONTROLLER RESET If set when M3 unit controller powers up. Will Indicated reason for reset if known.
• Check system configuration (model number, Configuration ID 1 and ID 2. If a model number is used that requires a daughter card, the
83* INCORRECT SETTINGS M3 unit controller will attempt to detect the presences of the add-on board if not detected, this alarm will be set.
• This hardware configuration alarm can be only cleared by resetting or power cycling the M3 unit controller.
84 RESERVED
Check Humiditrol settings. Check Configuration ID 1, position 1 and verify that the position is not set to U. Should be set to either N (not
85 INCORRECT HUMIDITROL SETTINGS
installed) or H (Humiditrol). Alarm will automatically clear once correct option is set.
Check thermostat inputs for simultaneous heat and cooling wiring. Once condition is corrected, unit controller will resume operation after error
86* CONFLICTING THERMOSTAT INPUT
time off day has expired.
87 -90 RESERVED
• If Enthalpy Sensor failure is detected, the system will disable ‘Free Cooling’ operation.

NOTE: Valid Outdoor Enthalpy Sensor reading is required for both ‘ODE’ (Outdoor Enthalpy) and ‘ODE differential’ (Outdoor differential). Valid
91* OUTDOOR ENTH SENSOR A7 Indoor Enthalpy Sensor reading is required for ‘ODE differential’ (Outdoor differential).
• Check economizer Parameters 160 and 161. Also check enthalpy Parameters 162 and 163.
• Check sensor and wiring.
If Enthalpy Sensor failure is detected, the system will disable ‘Free Cooling’ operation.
NOTE: Valid Outdoor Enthalpy Sensor reading is required for both ‘ODE’ (Outdoor Enthalpy) and ‘ODE differential’ (Outdoor differential). Valid
92* INDOOR ENTH SENSOR A62 Indoor Enthalpy Sensor reading is required for ‘ODE differential’ (Outdoor differential).

Check wiring and test A62 sensor using specified method in M3 application guide, section titled economizer checkout.
• Check communication loss with network sensor or if M3 unit controller If NETWORK INTEGRATION is set to RTU STANDALONE
MODE and backup sensor is set to RETURN AIR BACKUP.
• While running in backup mode the unit controller will set this alarm. The unit controller will return from Backup mode to Primary (Main)
93* BACKUP MODE
mode on a reset or after the Primary mode (room Sensor is not in error or OR network communication is re-established and available for
300 seconds.
• Backup mode alarm will be cleared on the reset OR after the unit controller has returned to primary (main) system mode.
94* BAD ZONE SENSOR SET POINT Ensure that the heating and cooling set points honor the auto-changeover deadband.
95 - 98 RESERVED
Check sensor and wiring. This alarm activates when the A24 sensor input signal is continuously above 25% of sensor measuring range for
99* OUTDOOR ECON SENSOR A24 more than five minutes with blower stopped. The M3 unit controller will disable the Outdoor Air CFM control. The alarm automatically clears
when the sensor reading is below 10% sensor measuring range for one minute.
42
Table 15. Prodigy 2.0 Alarm and Event Codes
SELECTED ALARMS (MARKED WITH * IN TABLE RESULT IN THE CLOSURE OF THE SERVICE RELAY CONTACTS (DO1).
ALARM
DISPLAY MESSAGE EVENT ACTION
CODE
100* AIR VOL CONTROL SETUP ERROR Check for proper installation of GP board and settings.
101* MGV CONTROL SETUP ERROR Check for proper installation of GP board and settings.
102* GP CONTROL SETUP ERROR Check for proper installation of GP board and settings.
103* ADVANCED CONTROL SETUP ERROR Check M3 unit controller Configuration ID 1 settings.
104 - 105 RESERVED
106* BUILDING PRESS SENSOR A34 Check sensor and wiring.
Check sensor and wiring.
The unit controller will set Supply Air Static Pressure Sensor (A30) error status if:
• Input signal is above 4.9” wc for more than 30 seconds.
107* DUCT SUPPLY PRESS SENSOR A30 OR
• Input signal is below 0.1”wc 20 seconds after the blower has started with setting at or above Blower Output ­Static Duct Alarm Check.

The M3 unit controller will clear the Supply Air Static Pressure Sensor (A30) error status and alarm after the expiration of Error Time OFF
delay.
• Check sensor and wiring.
• The M3 unit controller will shutdown operation for Error Off time (Parameter 110) if supply air static pressure exceeds supply static
DUCT SUPPLY HIGH PRESS SENSOR
108 shutdown setpoint for 20 seconds (default) Parameter 42.
A30
• The M3 unit controller will clear High Supply Static (Duct) Pressure after Error Off Time has expired and static duct pressure is below
Supply Static Set Point Shutdown.
• Check sensor and wiring.
• Prodigy controller shall “lock­out” a unit operation after the Max Static Duct Pressure Occurrences have occurred of Supply Static
STRIKE 3 DUCT SUPPLY PRESS Pressure Sensor Error (alarm 107) and/or High Supply Static (Duct) Pressure (alarm 108).
109*
SENSOR A30 • User shall be able to clear supply static pressure lockout and alarm via User Interface. Supply Static Pressure lockout and alarm shall
be cleared after the Prodigy controller reset.
• The number of strikes is three by default. this can be changed using Parameter 43. Optional occurrence setting is 1 to 7.
110 WAITING ON NETWORK DATA Check network or comfort sensor and wiring.
111 PROFILE ERROR Configuration profile unrecoverable. Settings may have changed.
112 - 120 RESERVED
Power­source line frequency is determined by the entered model number. This alarm is enabled by the Phase­Voltage Detection feature. The
LINE FREQ DOES NOT MATCH UNIT
121* M3 unit controller does not have an automatic clearing method, unit power cycle or reset will be required to re-evaluate the phase sequence
CONFIG
again.
• Low output voltage on T1 transformer. alarm set when 24VAC voltage low if calculated RMS voltage is below low voltage alarm
threshold for more than two seconds. System will stop unit operations (cooling, heating and ventilation). Low voltage threshold is 18VAC.
122* 24VAC PRIMARY VOLTAGE LOW • The M3 unit controller will clear alarm 24VAC Voltage Low if calculated RMS voltage is above Low Voltage Alarm Threshold + 1 VAC
for more than two seconds. After the low 24VAC alarm has been cleared, the M3 unit controller will ignore all service demands until the
Error Time Off Delay has expired.
• High output voltage on T1 transformer. alarm set when 24VAC voltage high if calculated RMS voltage is below low voltage alarm
threshold for more than two seconds. System will stop unit operations (cooling, heating and ventilation). Low voltage threshold is 30VAC.
123* 24VAC PRIMARY VOLTAGE HIGH • The M3 unit controller will clear alarm 24VAC Voltage high if calculated RMS voltage is above High Voltage Alarm Threshold + 1 VAC for
more than two seconds. After the HIGH 24VAC alarm has been cleared, the M3 unit controller will ignore all service demands until the
Error Time Off Delay has expired.

43
Table 15. Prodigy 2.0 Alarm and Event Codes
SELECTED ALARMS (MARKED WITH * IN TABLE RESULT IN THE CLOSURE OF THE SERVICE RELAY CONTACTS (DO1).
ALARM
DISPLAY MESSAGE EVENT ACTION
CODE
• Low output voltage on T1 transformer. alarm set when 24VAC voltage low if calculated RMS voltage is below low voltage alarm
threshold for more than two seconds. System will stop unit operations (cooling, heating and ventilation). Low voltage threshold is 18VAC.
124* 24VAC SECONDARY VOLTAGE LOW • The M3 unit controller will clear alarm 24VAC Voltage Low if calculated RMS voltage is above Low Voltage Alarm Threshold + 1 VAC
for more than two seconds. After the low 24VAC alarm has been cleared, the M3 unit controller will ignore all service demands until the
Error Time Off Delay has expired.
• High output voltage on T1 transformer. alarm set when 24VAC voltage high if calculated RMS voltage is below low voltage alarm
threshold for more than two seconds. System will stop unit operations (cooling, heating and ventilation). Low voltage threshold is 30VAC.
125* 24VAC SECONDARY VOLTAGE HIGH • The M3 unit controller will clear alarm 24VAC Voltage HIGH if calculated RMS voltage is above high voltage alarm Threshold + 1 VAC
for more than two seconds. After the high 24VAC alarm has been cleared the M3 unit controller will ignore all service demands until the
Error Time Off Delay has expired.
LINE PHASING DOES NOT MATCH During power up or reset of unit, Mismatch on single or 3­phase power, or reverse rotation on 3­phase detected. This alarm is enabled by the
126*
UNIT CONFIG Phase ­Voltage Detection feature.
127 - 128 RESERVED
129* VFD SHUTDOWN VFD fault detected. Check belt and for blower overload. Fix source of fault and reset M3 unit controller.
130 VFD BYPASS ENGAGED VFD bypass mode. Mode is engaged. Blower may or may not be disengage.
131 RESERVED
132 VFD BYPASS NOT CONFIGURED VFD bypass mode has not been selected. Unit operates as if bypass is not installed.
133 RESERVED
ADVANCED AIRFLOW LOW SUPPLY Advanced Airflow enabled RTU ­ indicates airflow target cannot be achieved. Check cause of airflow reduction such as dirty filter, changes in
134
CFM duct work, etc
135* ADVANCED AIRFLOW NO AIRFLOW Blower RPM is too low as indicates by blower status. This means that the blower is not working. Repair blower and reset M3 unit controller.
ADVANCED AIRFLOW OUTSIDE AIR
136* Outdoor air damper stuck or actuator problem.
DAMPER/ECON MECHANICAL FAULT
ADVANCED AIRFLOW LOW OUTDOOR
137 Outdoor airflow is too low so the building is not getting the designed outdoor airflow based on IAQ.
AIRFLOW
138 RESERVED
ADVANCED AIRFLOW OUTDOOR
139 Ventilation CFM is too high so the RTU is wasting energy.
AIRFLOW TOO HIGH
ADVANCED AIRFLOW CFM
140
UNATTAINABLE ­TARGET TOO LOW
Verify the MSAV blower settings and set the CM targets below set CFM. The alarm value will be displayed on the M3 unit controller screen.
ADVANCED AIRFLOW CFM
141
UNATTAINABLE ­TARGET TOO HIGH
142 RESERVED
ADVANCED AIRFLOW DAMPER
143* Outdoor air differential pressure sensor value not in valid range. Might be tubing problem or high return duct resistance.
PRESSURE ERROR.
144 - 145 RESERVED
146 SERVICE LOGGED Service event logged.
147* OA DAMPER ERROR During free cooling damper is not modulating.
148* ADVANCED AIRFLOW CONFIG ERROR Economizer should be installed and blower should be ECM type.

44
Table 15. Prodigy 2.0 Alarm and Event Codes
SELECTED ALARMS (MARKED WITH * IN TABLE RESULT IN THE CLOSURE OF THE SERVICE RELAY CONTACTS (DO1).
ALARM
DISPLAY MESSAGE EVENT ACTION
CODE
OUTDOOR AIR DIFF PRESSURE
149* Check outdoor air damper differential pressure sensor and wiring.
SENSOR ERROR
NOT ECONOMIZING WHEN OUTDOOR
150* May be due to the damper motor being unplugged or disconnected.
AIR IS SUITABLE
ECONOMIZING WHEN OUTDOOR AIR
151* This may be due to damper motor being blocked or stuck open and therefore not closing.
IS NOT SUITABLE
152 - 164 RESERVED
165 ECONOMIZER NOT CONFIGURED Configuration ID 1, position 2 is set to U. Select applicable option using setup/install wizard.
CAI PRESSURE SWITCH STUCK This alarm will occur when the combustion air pressure switch (S18) is detected as closed immediately after the furnace demand relay is
166
CLOSED ­GV1 energized and before the combustion air blower is energized. Gas valve 1.
CAI PRESSURE SWITCH STUCK This alarm will occur when the combustion air pressure switch (S45) is detected as closed immediately after the furnace demand relay is
167
CLOSED ­GV2 energized and before the combustion air blower is energized. Gas valve 2.
COMBUSTION AIR SW NOT OPEN
168*
LOCKOUT ­GV1 System locked out due to S45 switch closed and a specific number occurrences detected based on Parameter 72 (max cai no prf occ) setting
COMBUSTION AIR SW NOT OPEN during a single cycle.
169*
LOCKOUT ­GV2
170 POWER EXHAUST NOT CONFIGURED Configuration ID 1, position 3 is set as U (unconfigured).
POWER EXHAUST CONFIGURATION
171 Configuration ID 1, position 4 is set correctly. if position 3 is configured then position 4 must be also.
ERROR
172 RESERVED
173 AIR FLOW SWITCH CONFIG ERROR Verify that Configuration ID 2, position 1 is set correctly.
ZONE (ROOM) BYPASS DAMPER Room bypass damper operation is only compatible with cab blowers. Prodigy will only allow zone bypass unit operation if configuration ID1 is
174
CONFIGURATION ERROR set to installed for units with B or T type blowers. Alarm will automatically clear when configuration conflict is corrected.
INVALID LOAD SHEDDING INPUT Alarm will occur if load shedding input is shared with other optional devices or inputs, for example - global, blower overload, drain pan
175
CONFIGURATION overflow, etc.
SBUS RECEIVED AN OBSOLETE M3 This alarm occurs when a SBUS main device sends a M2 style command to the M3 unit controller. The alarm is immediately cleared and a
176
COMMAND history of the event is stored.
177 MODEL NUMBER NOT DEFINED Missing model configuration data. Run setup > install and complete model number information.
178 - 181 RESERVED
• Prodigy provides 0-5VDC analog input for the suction pressure sensor. Sensor output is connected to P333, pin 1. Valid suction
pressure range is 0 to 300 psig.
• If Suction Pressure Sensor is detected on Energence Ultra-high efficiency unit falls below the 30 psig then Prodigy will assume that
the Pressure Sensor sensor is faulty and ignore Pressure Sensor readings. Alarm will automatically clear once input is within normal
ULTRA: SUCTION PRESSURE operating range.
182
SENSOR ERROR
• The alarming value indicates which suction pressure sensor failed.

0 - Tandem 1 Suction Pressure Sensor Failure


1 - Tandem 2 Suction Pressure Sensor Failure

45
Table 15. Prodigy 2.0 Alarm and Event Codes
SELECTED ALARMS (MARKED WITH * IN TABLE RESULT IN THE CLOSURE OF THE SERVICE RELAY CONTACTS (DO1).
ALARM
DISPLAY MESSAGE EVENT ACTION
CODE
ULTRA: COMPRESSOR 1 SUMP • Alarm will occur when an open or short condition is detected. Alarm will also occur when unit controller via the temperature sensor
183
TEMPERATURE SENSOR ERROR detects an out of range. Valid range is ­30°F to 150°F. Possible causes are faulty temperature sensor / circuit or improper installation.
• The alarming value indicates which Compressor Sump Temp sensor failed.
ULTRA: COMPRESSOR 2 SUMP
184 0 - Tandem 1 Compressor 2 Sump Temp Sensor Failure
TEMPERATURE SENSOR ERROR
1 - Tandem 2 Compressor 2 Sump Temp Sensor Failure
185 ENGINEERING USE ONLY.
In systems with EBM blower, prodigy shall start monitoring the motor alarm output (normally closed relay contact) ten seconds after blower
command is sent. The M3 unit controller will stop unit operation if fault conditions (relay contact open ­logic input high) are detected.
186* BLOWER MOTOR FAULT
NOTE: Motor alarm is wired to P259­7; shared with VFD alarm and ECM blower rpm inputs. Alarm will clear when in­range temperature is
detected.
• Alarming Value = Inverter error code
• Possible alarming values for Prodigy Alarm 187 are:
> 12 - High Comp Current
> 13 - High Heat sink temperature
187 INVERTER LOW LEVEL ALARM
> 14 - High PFC input current
• If the alarm continues after outdoor conditions have moderated, check the fan, charge and coil. Alarm 187 will automatically clear when
minimum off time expires.
• Refer to trouble shooting guide in service manual for more information.
NOTE: The inverter will automatically slow the compressor speed due to any of the above conditions and the condition drops below the time-based dependence of the system’s output
on present and past inputs.
• Alarming Value = Inverter error code
• Possible alarming values for Prodigy Alarm 188 are:
> 21 - Peak DC current
> 22 - Maximum current reached lockout
> 23 - DC Link low voltage
> 26 - Locked Rotor
> 28 - DC Link high voltage
188 INVERTER HIGH LEVEL ALARM
> 29 - Compressor over current
> 61 - Low outdoor ambient inverter lockout
> 62 - High Heat Sink Temperature lockout
> 75 - Low Input Voltage
• No action required. Compressor stops for the duration of the minimum run time. Unit shuts down after ten occurrences in one hour and
Alarm 189 is initiated. Alarm 188 will automatically clear when inverter error clears.
• Refer to trouble shooting guide in service manual for more information.
• Alarming Value = Inverter error code
• Possible alarming values for Prodigy Alarm 189 are 21, 22, 23, 26, 28, 29, 61, 62 and 75.
189 INVERTER FATAL ALARM
• Alarm 189 will clear upon manual reset.
• Refer to trouble shooting guide in service manual for more information.

46
Table 15. Prodigy 2.0 Alarm and Event Codes
SELECTED ALARMS (MARKED WITH * IN TABLE RESULT IN THE CLOSURE OF THE SERVICE RELAY CONTACTS (DO1).
ALARM
DISPLAY MESSAGE EVENT ACTION
CODE
Unable to communicate with inverter. Prodigy will disable compressor operation. Replace communication cable between inverter and M3 unit
190 INVERTER COMMUNICATION ERROR
controller. If alarm continues, replace M3 unit controller or inverter.
191 INVERTER VOLTAGE MISMATCH Prodigy will disable compressor operation. Replace with correct inverter part.
Check temperature trip switch. Compressor is off. Also check charge, fans and coil. The unit controller will clear the temperature trip alarm
192 TEMP SWITCH TRIP when corresponding compressor top cap temperature trip switch is detected as closed. Compressor will not restart until the corresponding
temperature trip switch is closed and the minimum off delay has expired.
Prodigy will disable compressor operation (lockout). Check switch, charge, fans and coil. Default is three occurrences. Alarm will be
193 STRIKE 3 TEMP TRIP
automatically cleared after removal of cooling demand.

47
20. M3 Unit Parameters
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No
ENGLISH,
Select desired language for user interface. Options are English, French and
2 LANGUAGE LANGUAGE SPANISH OR Option
Spanish.
FRENCH
Power and Damper Parameters
If applicable Applicable to Energence Standard Efficiency 3- to 6-ton units only.
to specific • 16 = Runs the blower in high speed when occupied and there is not other
VAV CONTROL Variable Air Volume Control unit, see unit active demand (room sensor mode only)
5 0 511 Option
MODE Mode Parameter
label for default • 32 = Runs the blower in high speed when G is active and there is no other
setting active demand (thermostat mode only)

Check unit
label as
BLOWER Parameters • Applicable to Energence High Efficiency 3- to 5-ton units.
6 Blower Smoke Output 20 100 %
SMOKE OUTPUT may be • Blower staged percentage output during smoke detection.
configured to
order.

BLOWER HEAT Depends on • Applicable to Energence High Efficiency 3- to 5-ton units only.
7 Blower Heat Output 20 100 %
OUTPUT equipment • Blower staged percentage output high speed; used for high heating speed.
• Applicable to Energence High Efficiency 3- to 5-ton units only.
BLOWER LO CL Depends on
8 Blower Cool Output 20 100 % • Blower staged percentage output low speed; used for low cooling or
OUTPUT equipment
ventilation.
Minimum Damper Position • Minimum damper position during low speed blower operation.
MIN DAMPER
9 During High Speed Blower 0 0 100 %
LOW BLWR • Use Parameter 132 during high speed blower operation
Operation
• Applicable to Energence Standard Efficiency 3- to 6-ton units only.
FREE CL STG Free Cooling Blower Stage
10 0 300 1800 Sec • Free cooling blower stage-up delay. Blower runs low speed during delay, and
UP DLY Up Delay
then shifts to high speed.
ENBL FIELD Enabled Field Status 0 = OFF
11 Option Enabled Field Status Report
STAT RPT Report 1 = ON
Check unit Multi-Stage Air Volume Smoke Detection Mode (Alarm)
Multi-Stage Air Volume Parameter NOTE: In order for the SMOKE CFM change to take affect, go the SETUP > TEST
12 MSAV SMK CFM Smoke Detection Mode 450 label as default 14400 CFM & BALANCE > BLOWER and run the wizard. Performing this task will
(Alarm) may be altered recalculate the output to the desired CFM. No adjustments are required
at factory test. during this procedure.
Check unit
Maximum Cubic Feet Per Parameter
19 MAX CFM RPM Minute Revolutions Per 445 label as default 1780 RPM Maximum Cubic Feet Per Minute Revolutions Per Minute
Minute may be altered
at factory test.
Minimum Output Cooling
MIN OUPT CL VT
27 Vent Smoke Detection 30 50 100 % Minimum Output Cooling Vent Smoke Detection Mode (Alarm)
SMK
Mode (Alarm)

48
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No
MIN OUTPUT
28 Minimum Output Heat 30 50 100 % Minimum Output Heat
HEAT
Check unit
Parameter
MIN DAMPER
29 Minimum Damper Blower 0 label as default 101 % Setting this Parameter to 101.0% will disable this feature.
BLOWER
may be altered
at factory test.
PWREXH STG2 Power Exhaust Stage 2
30 0 70 100 % Power Exhaust Stage 2 Minimum Blower
MIN BLR Minimum Blower
Supply Proportional Base
Control Loop for Variable
SUPPLY PID P Variable Air Volume or Constant Air Volume with Bypass Damper supply PID
31 Air Volume or Constant 0 17 127 Counts
CONST Proportional constant.
Air Volume with Bypass
Damper
Supply Integral Base
Control Loop for Variable
SUPPLY PID I Variable Air Volume or Constant Air Volume with Bypass Damper supply PID
32 Air Volume or Constant 0 12 127 Counts
CONST Integral constant.
Air Volume with Bypass
Damper
Supply Derivative Base
Control Loop for Variable
SUPPLY PID D Variable Air Volume or Constant Air Volume with Bypass Damper supply PID
33 Air Volume or Constant 0 0 127 Counts
CONST derivative constant.
Air Volume with Bypass
Damper
Constant Air Volume with
BLR STC PRESS Bypass Damper Static Constant air volume with bypass damper static pressure set point during smoke
34 0 1 5 w.c.
SMK SP Pressure Set Point During alarm.
Smoke Alarm
Constant Air Volume with
BLR STC PRES Bypass Damper Static
35 0 1 5 w.c. Constant air volume with bypass damper static pressure set point for ventilation.
VT SP Pressure Set Point for
Ventilation
Constant Air Volume with
BLR STC PRES Bypass Damper Static
36 0 1 5 w.c. Constant air volume with bypass damper static pressure set point for heating
HT SP Pressure Set Point for
Heating
Constant Air Volume with
BLR STC PRES Bypass Damper Static
37 0 1 5 w.c. Constant air volume with bypass damper static pressure set point for cooling
CL SP Pressure Set Point for
Cooling
Constant Air Volume with
• Constant air volume with bypass damper minimum output for cooling,
Bypass Damper Minimum
ventilation and during smoke alarms. This sets the minimum air delivered.
MIN OUTPT CL Output Percentage
38 20 20 100 %
VT SMK Set Point for Cooling, • Bypass damper motor is set to 10 to 2 volts with 10 volts being closed.
Ventilation and Smoke
• 20% setting = 2 volts or damper completely opened.
Alarms

49
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No
• Constant air volume with bypass damper minimum output for heating.
Constant Air Volume with
MIN OUTPUT Bypass Damper Minimum • This sets the minimum air delivered.
39 20 20 100 %
HEAT Output Percentage Set • Bypass damper motor is set to 10 to 2 volts with 10 volts being closed.
Point for Heating
• 20% setting = 2 volts or damper completely opened.
• Constant air volume with bypass damper maximum output.
Constant Air Volume with
BLOWER MAX Bypass Damper Maximum • This sets the maximum air delivered.
40 40 100 100 %
OUTPUT Output Percentage Set • Bypass damper motor is set to 10 to 2 volts with 10 volts being closed.
Point
• 100% setting = 10 volts or damper completely closed.
Constant Air Volume with
SUPPLY Bypass Damper Manual Constant air volume with bypass damper manual reset value output. This is the
41 20 52 100 %
MANUAL RESET Reset Value Output output when unit is off.
Percentage Set Point
STATIC Air Supply Static Shutdown Supply static shutdown set point. Unit will shutdown for Parameter 110 minutes if
42 0 2 5 w.c.
SHUTDOWN SP Set Point duct pressure exceeds this value for 20 seconds.
• The number of occurrences before permanent lockout. Counter resets when
STATIC Static Pressure Lockout M3 resets.
43 1 3 7 Counts
LOCKOUT CNT Counter Set Point
• Refer to Parameter 226 to either enable or disable this feature.
• Supply Static Pressure Sensor (A30) connected at (A133_P195_6) (TB18_6)
Supply Static Sensor (A30) alarm threshold.
STATIC LO
44 Low Alarm Percentage Set 30 40 100 %
ALARM CHK • Blower percent speed before checking sensor after a 20 second delay.
Point
• A value of 30% disables the low threshold or “open” alarm trap.
Electric Heating Parameters
HT ELEC Electric Heat Warm-up Time Warm-up time delay. The time that the economizer is forced closed during warm-
58 0 60 136 Minutes
WARMUP DLAY Delay for Economizer up (first occupied + heat demand)
HT ELEC BL OFF Electric Heat Blower Off System
60 0 300 Seconds The time the blower stays on after the heating demand is lost.
DLAY Delay Set Point. Dependent
Service output activation. Maximum Primary and Secondary Limit occurrences
HT ELEC MAX LT Electric Heat Maximum stored before service relay is energized.
61 1 3 15 Counts
OCC Primary and Secondary
NOTE: Heating stage is not locked out.
HT ELEC STAGE Electric Heat Time Delay
62 12 12 60 Seconds Time delay between heat stages.
DELAY Between Heat Stages

Electric Heat Maximum • Stage up timer. The maximum time that lower stage runs before calling next
HT ELEC STG heat stage. Used in room sensor applications.
63 Lower Stage Run Time in 0 912 3600 Seconds
UP TMR
Room Sensor Applications • Disabled if set to 0.
Electric Heat Time Delay for
HT ELEC STG Lower Stage Termination • Time delay before a lower stage turns off following a higher stage termination.
64 0 0 3600 Seconds
DWN TMR Following Higher Stage • Used in room sensor applications.
Termination

50
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No
Gas Heating Parameters
Gas Time Delay for
HT GAS Warm-up time delay. The time that the economizer is forced closed during warm-
65 Economizer Being Closed 0 60 136 Minutes
WARMUP DELAY up (first occupied + heat demand) .
During Warm-up
HT GAS BLR ON Gas Blower On Delay After System
66 8 60 Seconds The time before the blower turns on after a heating demand.
DELAY Heating Demand Dependent
Gas Blower Off Delay
HT GAS BLR System
67 After Heading Demand 80 300 Seconds The time the blower stays on after the heating demand is terminated.
OFF DLAY Dependent
Termination
HT GAS HI FIRE Gas Minimum Low Fire
69 30 100 300 Seconds The minimum low fire time before high fire is allowed.
DLAY Time Prior to High Fire
HT GAS OFF
70 Heating Off Delay Timer 30 100 300 Seconds Heating off delay.
DELAY
Maximum Combustion
MAX CAI PRF Air Inducer Proof Switch Service relay activation. Maximum combustion air Inducer proof switch
71 1 3 5 Occurrences
SW OCC Occurrence Setting Prior To occurrences stored before service output is energized.
Service Output Energized.
Maximum Combustion After the initial maximum combustion air Inducer proof switch closure, the
MAX CAI NO
72 Air Inducer Proof Switch 1 3 15 Occurrences system will continue to monitor the pressure switch and set alarm if three open
PRF OCC
Occurrences occurrences are detected
Maximum Gas Valve Sense Service output activation. Maximum gas valve sense occurrences stored before
MAX GV SENSE service output is energized.
73 Occurrences Stored Prior to 1 3 5 Occurrences
OCC
Service Output Is Energized NOTE: Heating stage is not locked out.
• Stage-up timer. The maximum time that lower stage runs before calling next
HT GAS STG UP heat stage. Used in room sensor applications.
74 Gas Stage Up Timer 0 912 3600 Seconds
TMR
• Disabled if set to 0.

HT GAS STG • Time delay before a lower stage turns off following a higher stage termination.
75 Gas Stage Down Timer 0 0 3600 Seconds
DWN TMR • Used in room sensor applications.

51
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No
Block 4 Cooling Parameters
• Cool down time delay. Time that Y2 is ignored during cool down period (when
COOL DOWN first occupied + cool demand)
78 Cool Down Time Delay 0 30 136 Minutes
DELAY • This delay is only used if an economizer is used and the outdoor air is
suitable.
See section
COOL BLR ON Cooling Blower On Time
79 0 3.3.9. on page 60 Seconds The time before the blower turns on after a cooling demand.
DELAY Delay
20 for defaults.
See section
COOL BLR OFF Cooling Blower Off Time 3.3.10. on
80 0 240 Seconds The time the blower stays on after the cooling demand is lost.
DELAY Delay page 20 for
defaults.
Service output activation and compressor lockout. Maximum freeze thermostat
MAX FREEZE Maximum Freeze
81 1 3 3 Occurrences occurrences are stored before service relay is energized and compressor is
STAT OCC Thermostat Occurrence
locked-out.
COND FAN Condenser Fan Restart Low ambient anti-windmilling condenser fan delay. The time period that the last
82 0 6 16 Seconds
RESTRT DLY Time Delay operating fan is turned off before starting the next fan.

Low Ambient Outdoor Air • Low ambient outdoor air limit temp. 1. Parameters 83 and 84 are used to
83 LAC SP TEMP 1 Limit Temperature 1 Set 10 40 60 ºF shed fans.
Point • Temperature setting must be less than or equal to Parameter 84.

Low Ambient Outdoor Air • Low ambient outdoor air limit temp. 2. Parameters 83 and 84 are used to
84 LAC SP TEMP 2 Limit Temperature 2 Set 10 55 60 ºF shed fans.
Point • Temperature setting must be greater than or equal to Parameter 83.
Check unit
Parameter • Low ambient lockout for compressor 1.
COMP1 LO TMP Low Ambient Temperature
85 -31 label as default 80 ºF • A value of (-31°F) will disable low ambient lockout function.
LCKOUT Lockout for Compressor 1
may be altered • Temperature setting must be less than or equal to Parameter 86.
at factory test.
Check unit • Low ambient lockout for compressor 2.
Parameter
COMP2 LO TMP Low Ambient Temperature • A value of (-31ºF) will disable low ambient lockout function.
86 -31 label as default 80 ºF
LCKOUT Lockout for Compressor 2
may be altered • Temperature setting must be greater than or equal to Parameter 85 and less
at factory test. than or equal to Parameter 87.
Check unit • Low ambient lockout for compressor 3.
Parameter
COMP3 LO TMP Low Ambient Temperature • A value of (-31ºF) will disable low ambient lockout function.
87 -31 label as default 80 ºF
LCKOUT Lockout for Compressor 3
may be altered • Temperature setting must be greater than or equal to Parameter 86 and less
at factory test. than or equal to Parameter 88.
Check unit
Parameter • Low ambient lockout for compressor 4.
COMP4 LO TMP Low Ambient Temperature
88 -31 label as default 80 ºF • A value of (-31ºF) will disable low ambient lockout function.
LCKOUT Lockout for Compressor 4
may be altered • Temperature setting must be greater than or equal to Parameter 87.
at factory test.

52
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No
COMP MIN OFF Compressor Minimum Off
89 60 300 510 Seconds Compressor minimum off delay.
DELAY Delay
COMP MIN RUN Compressor Minimum Run
91 60 240 510 Seconds Compressor minimum run time.
TIME Time
MAX HP Maximum High Pressure Maximum High Pressure occurrences that are stored before control locks off
98 1 3 7 Occurrences
OCCURRENCES Occurrences compressor stage and energizes the service output.
MAX LP Maximum Low Pressure Maximum Low Pressure occurrences that are stored before control locks off
99 1 3 7 Occurrences
OCCURRENCES Occurrences compressor stage and energizes the service relay.
LP SW IGNORE Low Pressure Switch Ignore
100 0 120 600 Seconds Low Pressure Switch Ignore Time
TIME Time
• Stage 2 stage up timer. The maximum time that cooling stage 1 runs before
Maximum Stage 1 Cooling calling cooling stage 2.
CL STG 2
101 Time Before Call for Stage 0 912 3600 Seconds
STGUP TIME • Used in room sensor applications.
2 Cooling
• Disabled if set to 0.
• Stage 3 stage up timer. The maximum time that cooling stage 2 runs before
Maximum Stage 2 Cooling calling cooling stage 3.
CL STG 3
102 Time Before Call for Stage 0 912 3600 Seconds
STGUP TIME • Used in room sensor applications.
3 Cooling
• Disabled if set to 0.
• Stage 4 stage up timer. The maximum time that cooling stage 3 runs before
Maximum Stage 3 Cooling calling cooling stage 4.
CL STG 4
103 Time Before Call for Stage 0 912 3600 Seconds
STGUP TIME • Used in room sensor applications.
4 Cooling
• Disabled if set to 0

CL STAGE • Time delay before a lower stage turns off following a higher stage termination.
104 Cooling Stage Down Time 0 912 3600 Seconds
DOWN TIME • Used in room sensor applications.
Dehumidification Mode
• 0 = No reheat.
• 1 = Supermarket reheat using De-Humidistat (wired thermostat mode only)
0 - No • 2 = Supermarket reheat using relative humidity sensor.
Humiditrol is
installed • 3 = Humiditrol reheat. Conditions: Blower must be energized, Must be
occupied, At least one previous cooling demand.
105 DEHUMID MODE Dehumidification Mode 0 6 - All Others 7 Option
• 4 = Relative Humidity measurement / display. No Supermarket or Humiditrol
(Check Unit reheat.
Parameter
Label) • 5 = Humiditrol reheat. Conditions: At least one previous cooling demand.
• 6 = Humiditrol reheat. Conditions: Blower must be energized, Must be
occupied.
• 7 = Humiditrol reheat. Conditions: None

53
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No
• Percent relative humidity where supermarket or Humiditrol reheat demand is
Check unit energized. Used of dehumid mode option 2, 3, 5, 6 or 7. Dehumidification is
Parameter de-energized at set point – dead-band (Parameter 107)).
DEHUMID
106 Dehumidification Set Point 0 label as default 99 % RH
SETPOINT • Digital Input 4 only. Energized input signal calls for dehumidification demand.
may be altered
at factory test. L Connection Network Relative Humidity set point will override this set point.
(Such as from NCP).
Used of dehumidification Parameter 105, option 2, 3, 5, 6 or 7. Dehumidification is:
DEHUMID Dehumidification Dead • ON when relative humidity is equal to or greater than Parameter 106.
107 1 3 10 % RH
DEADBAND Band (neutral zone) • OFF when Relative Humidity is less than Parameter 106 minus Parameter
107.
FREE LO AMB Free Cooling Low Ambient When outdoor air is suitable for free cooling and an economizer is present, the
108 45 55 80 °F
LCKT SP Lockout Set Point compressor will not run when ambient is below this value.
Smoke alarm control options.
• 0 = Blower off, exhaust fan off and fresh air damper closed.
• 2 = Blower off, exhaust fan on and fresh air damper closed.
SMOKE ALARM
109 Smoke Alarm Control 0 0 13 Option
CONTROL • 9 = Blower on, exhaust fan off and fresh air damper opened.
• 10 = Blower on, exhaust fan on and fresh air damper closed.
• 11 = Blower on, exhaust fan on and fresh air damper opened.
ERR TIME OFF
110 Error Time Off Delay 64 300 1800 Seconds Off time delay if a “no-run” error occurs.
DELAY
Cooling staging options:
• 0 = No cooling operation
• 1 = Wired thermostat operation, Two cooling stages and units with
Economizers
> Y1 = Free Cooling,
> Y2 = Adds all mechanical stages.
• 2 = Wired thermostat operation. Two cooling stages and Units with
Check unit Economizers
Parameter
COOL STAGING > Y1 - Free Cooling
111 Cooling Staging Option 0 label as default 4 Option
OPTION > Y2 - adds first stage of mechanical.
may be altered
at factory test. • 3 = Wired thermostat operation. Three cooling stages.
> Y1 only - first stage,
> Y2 only - second stage,
> Y1+Y2 - third stage.

NOTE: Units with Economizers Y2 only adds first stage of mechanical, Y1+Y2
adds first and second stage of mechanical.
• 4 = Discharge air control. Up to four stages.

54
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No
Block 5 Miscellaneous Parameters
Heating staging options:
• 0 = No heating operation.
HEAT STAGING
112 Heating Staging Option 0 2 2 Option
OPTION • 1 = Discharge air control with up to four stages.
• 2 = Thermostat operation.
• Enables return air temperature limit option.
EN RET AIR TMP Enable Return Air
113 0 0 1 Option • Return air limits may be used for limiting zone temperatures. Continuous fan
LMT Temperature Limit
operation recommended.
• Return air limit for cooling. If the return air cooling limit is exceeded, the
COOL RET AIR cooling demands are interrupted.
114 Cooling Return Air Limit 60 65 80 °F
LIMIT
• Parameter 113 must be set to 1 to enable.
• Return air limit for heating. If the return air heating limit is exceeded, the
HEAT RET AIR heating demands are interrupted.
115 Heating Return Air Limit 60 85 100 °F
LIMIT
• Parameter 113 must be set to 1 to enable.
DCV MAX Demand Control Ventilation
117 0 50 100 % Maximum allowed demand control ventilation damper open position.
DAMPER OPEN Maximum Damper Open

DCV DAMP Demand Control Ventilation • Damper “start open” CO2 set point for Demand Control Ventilation.
118 0 700 2000 PPM
START OPEN Damper Start Open • Level where fresh air damper begins to open.
Demand Control Ventilation • Damper “full open” CO2 set point for Demand Control Ventilation.
DCV DAMP FULL
119 Maximum Damper Full 0 1200 2000 PPM
OPEN • Level where fresh air damper is opened to maximum.
Open Set Point
Demand Control Ventilation
DCV HI TMP OV Outdoor Air Control Hi
120 -31 105 132 °F High outdoor air temp. where fresh air damper is closed to minimum position.
FL CL Temperature Override Full
Closed
Demand Control Ventilation
DCV HI TMP OV Outdoor Air Control Hi
121 -31 75 132 °F High outdoor air temperature where fresh air damper begins to close.
ST CL Temperature Override Start
Closing
Demand Control Ventilation
DCV LO TMP OV Outdoor Air Control Low
122 -31 10 132 °F Low outdoor air temperature where fresh air damper is closed to minimum position
FL CL Temperature Override Full
Closed
Demand Control Ventilation
DCV LO TMP OV Outdoor Air Control Low
123 -31 40 132 °F Low outdoor air temp. where fresh air damper begins to close.
ST CL Temperature Override Start
Closing
OAC MANUAL Outdoor Air Control Manual
127 0 50 100 % Manual reset value.
RESET Reset
OAC PID P Outdoor Air Control PID P
128 0 2 127 Counts Outdoor Air Control PID P Constant
CONSTANT Constant
OAC PID I Outdoor Air Control PID I
129 0 30 127 Counts Outdoor Air Control PID I Constant
CONSTANT Constant
55
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No
OAC PID D Outdoor Air Control PID D
130 0 0 127 Counts Outdoor Air Control PID D Constant
CONSTANT Constant
FREE CL MAX Free Cooling Maximum
131 0 100 100 % The maximum allowed fresh air damper opening for free cooling.
DAMPER Damper
MIN DAMPER
132 Minimum Damper Position 0 0 100 % Minimum fresh air damper position during occupied operation.
POSITION
• Suspends all unit operation room sensor and Constant Air Volume with
bypass damper applications.
ZONE SENS Room Sensor Start-up • Suspends Fresh Air Heat Control-Reheat, Fresh Air Cooling Control, Fresh
133 2 2 30 Minutes
STRTUP DLY Delay Air Heat Control options and all GP outputs.
• May be used to stagger unit start-ups. Does NOT delay demands in
thermostat mode.
Options are:
• 0 = Ventilation is disabled.
• 1 = Demand control ventilation with outdoor temperature limit and blower on.
(Default)
• 2 = Demand control ventilation without Outdoor Temperature Limit and Blower
ON.
IAQ INPUT Indoor Air Quality Input • 3 = Demand control ventilation with Outdoor Temperature Limit and Blower
134 0 1 7 Option
MODE Mode AUTO / ON.
• 4 = Demand control ventilation without Outdoor temperature Limit and no
blower AUTO / ON.
• 5 = Outdoor air control with outdoor temperature limit.
• 6 = Outdoor air control without outdoor temperature limit
• 7 = Building pressure control
System 1 Parameters
Check unit • Backup occupied heating set point.
Parameter • Used if the communications link is lost for 5 minutes between the M3 and
137 OCC HEAT STPT Occupied Heating Set Point 40 label as default 95 °F NCP. Used only with room sensor applications.
may be altered • Set point temperature must be less than or equal to (Parameter 139 minus
at factory test. Parameter 152).
• Backup unoccupied heating set point. Used if the communications link is lost
for 5 minutes between the M3 and NCP.
UNOCC HEAT Unoccupied Heating Set
138 40 60 95 °F • Used only in room sensor applications.
STPT Point
• Set point temperature must be less than or equal to (Parameter 140 minus
Parameter 152).
• Backup occupied cooling set point.
• Used if the communications link is lost for 5 minutes between the M3 and
OCC COOL
139 Occupied Cooling Set Point 40 75 95 °F NCP. Used only in room sensor applications.
STPT
• Set point temperature must be greater than or equal to Parameter 137 plus
Parameter 152).

56
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No
• Backup unoccupied cooling set point.
• Used if the communications link is lost for 5 minutes between the M3 unit
UNOCC COOL Unoccupied Cooling Set
140 40 85 95 °F controller and network control panel. Used only in room sensor applications.
STPT Point
• Set point temperature must be greater than or equal to Parameter 138 plus
Parameter 152).

AFTERHOUR After Hours Override Time • After hours override timer.


141 0 60 480 Minutes
OVRRD DLY Delay • Only used on room sensor applications without a network control panel.
• Heating dead-band. Used only with M3 unit controller room sensor
HEAT STAGE applications.
142 Heat Stage Deadband 1 1 3.75 °F
DEADBAND • Dead band must be less than or equal to Parameter 152 minus Parameter
143.
• Cooling dead-band. Used only with room sensor applications.
COOL STAGE
143 Cool Stage Deadband 1 1 3.75 °F • Dead band must be less than or equal to Parameter 152 minus Parameter
DEADBAND
142.

COOL STAGE1 • Cooling stage 1 differential. Used only with room sensor applications.
144 Cooling Stage 1 Differential 0 0.5 3 °F
DIFFER • Differential temperature must be less than or equal to Parameter 145.
• Cooling stage 2 differential. Used only with room sensor applications.
COOL STAGE2
145 Cooling Stage 2 Differential 0 1 3 °F • Differential temperature must be greater than or equal to Parameter 144 and
DIFFER
less than or equal to Parameter 146.
• Cooling stage 3 differential. Used only with room sensor applications.
COOL STAGE3
146 Cooling Stage 3 Differential 0 1.5 3 °F • Differential temperature must be greater than or equal to Parameter 145 and
DIFFER
less than or equal to Parameter 147.

COOL STAGE4 • Cooling stage 4 differential. Used only with room sensor applications.
147 Cooling Stage 4 Differential 0 2 3 °F
DIFFER • Differential temperature must be greater than or equal to Parameter 146.

HEAT STAGE1 • Heating stage 1 differential. Used only with room sensor applications.
148 Heating Stage 1 Differential 0 0.5 3 °F
DIFFER • Differential temperature must be less than or equal to Parameter 149.

HEAT STAGE2 • Heating stage 2 differential. Used only with room sensor applications.
149 Heating Stage 2 Differential 0 1 3 °F
DIFFER • Differential temperature must be greater or equal to Parameter 148.
• Heating stage 3 differential temperature. Used only with room sensor
HEAT STAGE3 applications.
150 Heating Stage 3 Differential 0 1.5 3 °F
DIFFER
• Differential temperature must be greater than or equal to Parameter 149.
• Heating stage 4 differential temperature. Used only with room sensor
HEAT STAGE4 applications.
151 Heating Stage 4 Differential 0 2 3 °F
DIFFER
• Differential temperature must greater than or equal to Parameter 150.
• Minimum auto changeover dead-band temperature. Dead band must be
AUTO CHGOVR Automatic Changeover greater than or equal to Parameter 142 plus Parameter 143.
152 2 3 10 °F
DEADBND Deadband
• Used in room sensor applications.

57
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No
Check unit
Parameter
AUTO CHGOVR Automatic Changeover
153 1 label as default 15 Minutes Auto changeover time delay. Delay between heating and cooling modes.
DELAY Delay
may be altered
at factory test.
Blower control option for room sensor applications during occupied periods.
• Auto Cycle: Blower cycles with demand
• On-Continuous 1: blower is on with either the occupancy sensor or
occupancy schedule indicates occupied.
OCC BLOWER AUTO- • On-Continuous 2: Blower is on only when both the occupancy sensor and
154 Occupied Blower Mode Option occupancy scheduler indicates occupied.
MODE CYCLES
• On-Continuous 3: lower is on only when both the occupancy sensor and
occupancy scheduler indicates occupied. in addition, blower will be on a
minimum of 25% of the time when occupancy scheduler indicates occupied
by the occupancy sensor indicates not occupied. The 25% minimum is
achieved by turning blower on for 30 minutes and off for 90 minutes.

FREECOOL Free Cooling Lockout Set • Locks out free cooling when outdoor temperature is below the set value.
155 30 30 60 °F
LOCKOUT SP Point • Setting value to 29°F disables free cooling lockout.
FRESH AIR See 507242-XX, Prodigy Application Guide for further details and to change the fresh air heat (FAH) set point. Modify the set point only using the method described in
156
HEAT SP the reference section.
FAH STAGE Fresh Air Heating Stage
157 3 10 15 °F Fresh Air Heating stage dead-band.
DEADBAND Deadband
FAH MIN CYCLE Fresh Air Heating Minimum
158 120 480 1800 Seconds Fresh Air heating minimum cycle time.
TIME Cycle Time
Economizer modulates dampers to maintain supply air temperature (RT6) at this
FREE COOL Free Cooling Supply Set
159 45 55 65 °F set point during free cooling. DACC reset applies. See Parameter 207 - Parameter
SUPPLY SP Point
201
Outdoor Air Temperature is less than Parameter Set Point between 41-75°F,
ECON FREECL Economizer Free Cooling
160 40 60 75 °F or when Outdoor Air temperature is less than Return Air Temperature between
TEMP SP Temperature Set Point
0-40°F.
ECON FRCL Economizer Free Cooling
161 0 10 40 °F Economizer Free Cooling Temperature Offset
TMP OFFSET Temperature Offset
ECON FREECL Economizer Free Cooling
162 10 12 19 mA Economizer Free Cooling Enthalpy Set Point
ENTH SP Enthalpy Set Point
ECN FRCL ENTH Economizer Free Cooling
163 1 1 5 mA Economizer Free Cooling Enthalpy Offset
OFFST Enthalpy Offset

58
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No
These are the operating profile options for the economizer damper during free
cooling when any compressor is on and can be selected as follows:
• Option 0: Damper continues to modulate while compressors are on, but the
effect of mechanical cooling may force the damper closed to its minimum
position. After compressor starts, the free cooling setpoint is lowered to a
fixed temperature of 45°F.
• Option 1: Damper opens to its max­open position (Parameter 131 - FREE CL
MAX DAMPER) when any compressors start.

NOTE: When using Option 1 and after the compressor is stopped, the M3 will
resume damper modulation.
• Option 2: Damper continues to modulate while compressors are on, but the
ECONOMIZER effect of mechanical cooling may force the damper closed to its minimum
164 Economizer Profile 0 2 3 Option
PROFILE position. This is the factory default setting.
> Holds ­off compressor on Y2 call until damper has modulated to
maximum position (Parameter 131 - FREE CL MAX DAMPER) for three
minutes.
> After three minutes, compressor starts and the free cooling setpoint
is lowered to 45°F. Damper is not locked at maximum open while
compressor is on, but modulates to maintain 45°F discharge air
temperature.
> When Y2 is satisfied, compressor goes off and free cooling setpoint is
restored to 55°F (Parameter 159 - FREE COOL SUPPLY SP).
• Option 3: Same as Option 2, but with a 10 minute delay instead of a three
minute delay.
System 2 Parameters
FAH STAGE Fresh Air Heating Stage • Fresh Air Heating stage differential.
165 0 2 20 °F
DIFFER Differential • 0 value for first stage heating only for Fresh Air Heating.
Fresh Air Heating Control
FAH REHEAT Outdoor air temperature set point that enables fresh air heating for reheat demand
166 Reheat Outdoor Air 20 45 60 °F
OAT SP and opens damper to Parameter 167 when outdoor air is less than set point.
Temperature Set Point
FAH REHEAT Fresh Air Heating Control
167 5 40 100 % Fresh air damper position during Fresh Air Heating reheat operation.
DAMPER Reheat Damper Position
Fresh Air Heat Control Set
168 FAH REHEAT SP 40 40 70 °F Fresh Air Heating Reheat set point.
Point
Fresh Air Tempering
FAT AUTO Fresh Air Heating Control or Fresh Air Cooling Control air Tempering auto-
169 Automatic Changeover 15 30 120 Minutes
CHGOVR DLY changeover delay.
Delay
FRESH AIR See 507242-01, Prodigy Application Guide for further details and to change the fresh air cool (FAC) set point. Modify the set point only using the method described in
170
COOL SP the reference section.
FAC STAGE Fresh Air Cooling Control
171 3 10 15 °F Fresh Air Cooling stage dead-band.
DEADBAND Deadband
FAC MIN CYCLE Fresh Air Cooling Control
172 120 480 1800 Seconds Fresh Air Cooling minimum cycle time.
TIME Cycle Time

59
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No

FAC STAGE Fresh Air Cooling Control • Fresh Air Cooling stage differential between stages.
173 0 2 20 °F
DIFFER Stage Differential • Set to 0 for first stage cooling only for Fresh Air Cooling.
DACH OCC Discharge Air Control
174 60 110 140 °F Discharge Air Control Heating set point during occupied period.
SETPOINT Heating Occupied Set Point
Discharge Air Control
DACH UNOCC
175 Heating Unoccupied Set 60 95 140 °F Discharge Air Control Heating set point during unoccupied period.
SETPOINT
Point
DACH STAGE Discharge Air Control
176 5 5 20 °F Discharge Air Control Heating dead-band.
DEADBAND Heating Stage Deadband
Discharge Air Control
DACH FAH STG
177 Heating Stage-Up Time 0 180 900 Seconds Discharge Air Control Heating and Fresh Air Heating stage-up time delay.
UP TMR
Delay
Discharge Air Control
DACH FAH STG Heating and Fresh Air
178 0 120 600 Seconds Discharge Air Control Heating and Fresh Air Heating stage-down time delay.
DN TMR Heating Control Stage-
Down Time Delay
DACH STAGE Discharge Air Control
179 2 2 20 °F Discharge Air Control Heating stage differential
DIFFER Heating Stage Differential
DACC OCC Discharge Air Control
180 40 55 80 °F Discharge Air Control Cooling set point during occupied period.
SETPOINT Cooling Occupied Set Point
Discharge Air Control
DACC UNOCC
181 Cooling Unoccupied Set 40 65 100 °F Discharge Air Control Cooling set point during unoccupied period.
SETPOINT
Point
Discharge Air Control
DACC STAGE
182 Cooling Deadband Set 5 5 20 °F Discharge Air Control Cooling stage dead-band.
DEADBAND
Point
Discharge Air Control
DACC FAC STG
183 Cooling and Fresh Air 0 180 900 Seconds Discharge Air Control Cooling and Fresh Air Cooling stage-up delay.
UP TMR
Cooling Stage-Up Delay
Discharge Air Control
DACC FAC STG Cooling and Fresh Air
184 0 120 600 Seconds Discharge Air Control Cooling and Fresh Air Cooling stage-down time delay.
DN TMR Cooling Stage-Down Time
Delay
DACC STAGE Discharge Air Cooling
185 2 2 20 °F Discharge Air Cooling stage differential.
DIFFER Stage Differential

60
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No
A55 Service Output Control Mode = X + 32*Y + 16*Z
Input source = X:
• 0 = None
• 1 = Compressor 1 duty cycle. (Compressor crankcase heater function.)
> On when outdoor air temperature is less than or equal to Parameter 189
and greater than or equal to Parameter 192 seconds have passed with
compressor 1 off.
> Off when Outdoor Air temperature is greater than Parameter 189 plus
3°F (fixed dead-band) or is less than Parameter 192 seconds have
passed with compressor 1 off
• 2 = On when occupied.
• 3 = On when blower on,
• 4 = On when heating demand.
• 5 = On when cooling demand.
SRV OUTPT Service Output Control • 6 = On when heating or cooling demand.
186 0 0 127 Option
CTRL MODE Mode
• 7 = System Relative Humidity (A55_P298_5 RH)
• 8 = System Indoor Air Quality. (A55_P298_3 IAQ)
• 9 = System Outdoor Air Temperature (A55_P267_1/2 OAT)
• 10 = Energy Recovery System
• 11 = SCR Option for Electric Heat

Algorithm Y for input sources 7 - 9:


• 0 = Hysteresis loop (see sections 14.2 - 14.4)
• 1 = Window - On when input is in range; (see sections 14.2 - 14.4)
• 2 = Delayed-on. (see sections 14.2 - 14.4)
• 3 = Delayed-off. (see sections 14.2 - 14.4)

Inversion Z:
• 0- Output not inverted.
• 1- Output inverted.
SRV OUTPT SP Service Output Set Point for
187 0 996 2000 ppm A55 service relay output set point.
C02 Carbon Dioxide
SRV OUTPT SP Service Output Set Point for
188 0 100 100 % Service Output Set Point for Relative Humidity
RH Relative Humidity
SRV OUTPT SP Service Output Set Point
189 -31 51 132 °F Service Output Set Point Temperature
TEMP Temperature
SRV OUTPT DB Service Output Deadband
190 16 102 2000 ppm A55 service relay output dead-band or delay.
C02 for Carbon Dioxide
SRV OUTPT DB Service Output Deadband
191 2 13 100 % Service Output Deadband for Relative Humidity
RH for Relative Humidity
SRV OUTPT DB Service Output Deadband
192 1 8 162 °F Service Output Deadband for Temperature
TEMP for Temperature

61
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No
SRV OUTPT
193 Service Output Delay 64 416 8160 Seconds Service Output Delay
DELAY
Number of compressors to be turned off when load shedding is active.
LOAD SHED Number of compressors to Applicable to Energence Standard Efficiency 3- to 6-ton units only. 2-stage
194 0 0 4 Option
NUM COMP shed during load shedding compressor, a value of one shuts off 2nd stage only and a value of 2 turns
compressor completely off.
BACnet MAC Address. A value of 0-128 sets the BACnet MAC address to that
196 MAC ADDRESS MAC Address 0 128 128 Address
value.
9.6K
19.2K
197 BAUD RATE Baud Rate Option Baud rate setting.
38.4K
76.8K
System 3 Parameters
Discharge Air Control • Discharge Air Control Cooling outdoor temperature ambient cooling
DACC OAT RS Cooling Outdoor Air adjustment reset band.
201 0 0 30 °F
ADJ BND Temperature Adjustment
Band • Also used to reset free cooling set point (Parameter 159).

Discharge Air Control


DACC OAT RS Cooling Outdoor Air • Discharge Air Control Cooling outdoor air temperature cooling reset set point.
202 40 80 100 °F
ADJ SP Temperature Cooling Reset • Also used to reset free cooling set point (Parameter 159).
Set Point
Discharge Air Control • Discharge Air Control Cooling outdoor ambient temperature cooling
DACC OAT RS Cooling Outdoor Ambient proportional band.
203 1 20 60 °F
PRP BND Air Temperature Cooling
Proportional Band • Also used to reset free cooling set point (Parameter 159).

Discharge Air Control • Discharge Air Control Cooling return air reset adjustment band. 0 disables
DACC RAT RS return air cooling reset.
204 Cooling Return Air Reset 0 0 30 °F
ADJ BND
Adjustment Band • Also used to reset free cooling set point (Parameter 159).
Discharge Air Control • Discharge Air Control Cooling return air reset set point.
DACC RAT RS
205 Return Air Reset 50 70 80 °F
ADJ SP • Also used to reset free cooling set point (Parameter 159).
Adjustment Set Point
Discharge Air Control • Discharge Air Control Cooling return air reset proportional band.
DACC RAT RS
206 Cooling Return Air Reset 1 10 30 °F
PRP BND • Also used to reset free cooling set point (Parameter 159).
Proportional Band
• Discharge Air Control Cooling total reset limit. This limits the total DACC reset
Discharge Air Control allowed.
207 DACC RS LIMIT 5 10 20 °F
Cooling Reset Limit
• Also used to reset free cooling set point (Parameter 159).
Discharge Air Control
DACH OAT RS Heating Outdoor Air
208 0 0 30 °F Discharge Air Control Heating outdoor temperature reset adjustment band.
ADJ BND Temperature Reset
Adjustment Band
Discharge Air Control
DACH OAT RS
209 Heating Reset Adjustment -31 40 60 °F Discharge Air Control Heating outdoor temperature reset set point.
ADJ SP
Set Point
62
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No
Discharge Air Control
DACH OAT RS Heating Outdoor Air
210 1 20 60 °F Discharge Air Control Heating temperature reset proportional band.
PRP BND Temperature Reset
Proportional Band
Discharge Air Control
DACH RAT RS Heating Return Air
211 0 0 30 °F Discharge Air Control Heating return reset adjustment band.
ADJ BND Temperature Adjustment
Band
Discharge Air Control
DACH RAT RS
212 heating Return Air Heating 50 70 80 °F Discharge Air Control Heating return air heating reset set point.
ADJ SP
Reset Set Point
Discharge Air Control
DACH RAT RS
213 Heating Return Air Heading 1 10 30 °F Discharge Air Control Heating return air heating reset proportional band.
PRP BND
Reset Proportional Band
Discharge Air Control
214 DACH RS LIMIT Heating Return Air Heating 5 10 20 °F Discharge Air Control Heating reset limit. This limits the total DACH reset allowed.
Reset Limit
EXH FN STG1 Exhaust Fan Stage 1
215 0 50 100 % Exhaust fan stage 1 damper set point.
DAMP SP Damper Set Point
Check unit
Parameter
EXH FN STG1 Exhaust Fan Stage 1
216 0 label as default 100 % Exhaust Fan Stage 1 Damper Deadband
DAMP DB Damper Deadband
may be altered
at factory test.
EXH FN STG1
PRES SP Stage 1 set point Exhaust Fan Stage 1 Pressure Set Point.
217 or or -0.5 0.05 0.5 in w.c. or
VFD PE PRES VFD PE set point VFD Power Exhaust Building Pressure Set Point.
SP
EXH FN STG1
218 Stage 1 deadband 0 0.02 1 in w.c. Exhaust Fan Stage 1 Pressure Deadband.
PRES DB
EXH FN STG2 Exhaust Fan Stage 2
219 0 75 100 % Exhaust Fan Stage 2 Damper Set Point
DAMP SP Damper Set Point
EXH FN STG2 Exhaust Fan Stage 2
220 0 10 100 % Exhaust Fan Stage 2 Damper Deadband
DAMP DB Damper Deadband
EXH FN STG2
221 Stage 2 setpoint -0.5 0.10 0.5 in w.c. Exhaust Fan Stage 2 Pressure Set Point
PRES SP
EXH FN STG2
222 Stage 2 deadband 0 0.05 1 in w.c. Exhaust Fan Stage 2 Pressure Deadband.
PRES DB
EXH FAN STGUP Exhaust Fan Stage Up
223 0 100 300 Seconds Exhaust Fan Stage Up Delay
DELAY Delay
EXH FAN Exhaust Fan Stage Down
224 0 100 200 Seconds Stage 1 off-delay. (Only used for 2 stage operation)
STGDWN DLAY Delay

63
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No
• Applicable to Energence Standard Efficiency 3- to 6-ton units only.
CL LO CFM Advanced Airflow Low
228 -1200 0 1200 Count • If the absolute value of this Parameter is greater than Parameter 17. then this
CALIB Speed Calibration
is not considered in target calculation.
• Applicable to Energence Standard Efficiency 3- to 6-ton units only.
Advanced Airflow Hi Speed
229 CL HI SPD CALIB -1200 0 1200 Count • If the absolute value of this Parameter is greater than Parameter 14. then this
Calibration
is not considered in target calculation
CL MED LO SPD Advanced Airflow Medium
230 -1200 0 1200 Count Applicable to Energence Standard Efficiency 3- to 6-ton units only.
CALIB Speed Calibration
CL MED HI SPD Advanced Airflow Medium
231 -1200 0 1200 Count Applicable to Energence Standard Efficiency 3- to 6-ton units only.
CALIB High Speed Calibration
HEAT CFM Advanced Airflow Heat
232 -1200 0 1200 Count Applicable to Energence Standard Efficiency 3- to 6-ton units only.
CALIB CFM Calibration
Advanced Airflow Vent CFM
233 VENT CFM CALB -1200 0 1200 Count Applicable to Energence Standard Efficiency 3- to 6-ton units only.
Calibration
Advanced Airflow Low
LO SP CFM
234 Speed CFM Alarm Set 15 25 100 % Applicable to Energence Standard Efficiency 3- to 6-ton units only.
ALARM SP
Point
Advanced Airflow Low
LO SP CFM
235 Speed CFM Alarm 0 1800 3600 Seconds Applicable to Energence Standard Efficiency 3- to 6-ton units only.
ALARM EU
Evaluation
NO AIRFLOW Advanced Airflow No Airflow
236 0 20 300 Count Applicable to Energence Standard Efficiency 3- to 6-ton units only.
ALARM EU Alarm Evaluation
OUTDOOR AIR
237 Outdoor Air Target 0 0 750 CFM Applicable to Energence Standard Efficiency 3- to 6-ton units only.
TARGET
OUTDOOR CFM Advanced Airflow Outdoor
238 -600 0 600 Count Applicable to Energence Standard Efficiency 3- to 6-ton units only.
CALIB CFM Calibration
LO OD CFM Advanced Airflow Outdoor
239 15 25 100 % Applicable to Energence Standard Efficiency 3- to 6-ton units only.
ALARM SP CFM Alarm Set Point
Advanced Air Flow High
HI OD CFM
240 Outdoor CFM Alarm Set 15 25 100 % Applicable to Energence Standard Efficiency 3- to 6-ton units only.
ALARM SP
Point
600 (3-ton
Unit)
Advanced Airflow Maximum
MAX OD CFM 800 (4-ton
241 Outdoor CFM Demand 0 2400 CFM Applicable to Energence Standard Efficiency 3- to 6-ton units only.
DCV SP Unit)
Control Ventilation Set Point
1000 (5-ton
Unit)
Advanced Air Flow Low
LO OD CFM
243 Outdoor CFM Alarm 0 1800 3600 Seconds Applicable to Energence Standard Efficiency 3- to 6-ton units only.
ALARM EU
Evaluation
Advanced Air Flow High
HI OD CFM
244 Outdoor CFM Alarm 0 1800 3600 Seconds Applicable to Energence Standard Efficiency 3- to 6-ton units only.
ALARM EU
Evaluation

64
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No
Advanced Airflow Outdoor
OD DP ERR
245 Air Damper Error Alarm 0 1800 3600 Seconds Applicable to Energence Standard Efficiency 3- to 6-ton units only.
ALARM EU
Evaluation
Advanced Airflow Altitude
246 ALTITUDE STPT 0 650 25000 Feet Applicable to Energence Standard Efficiency 3- to 6-ton units only.
Set Point
BLR CALIB Blower Calibration Ramp
247 4 10 40 % Applicable to Energence Standard Efficiency 3- to 6-ton units only.
RAMP RATE Rate
FAHRENHEIT
DISPLAY UNITS Display Unit (Fahrenheit or or
258 Option Temperature unit of measurement.
F/C Celsius)
CELSIUS
• 0 = Disable Free Cooling Low Ambient Compressor Lockout (default).
FRCL COMP Free Cooling Compressor • 1 = Lockout Compressor whenever the outdoor air is suitable regardless of
285 0 2 2 Option
LCKOUT MD Lockout Mode outdoor air temperature.
• 2 = Enable Free Cooling Low Ambient Compressor Lockout.
NOTE: Options for Parameter 287 are not accessible via the M3 unit controller user interface. Options can be set using the Lennox UC
software.

Here is an example of the selection options for Algorithms Enable via the Lennox UC Software:
Set Bit Description
0x00000002 Enable Fresh Air Heating (ALGO_FAH)
0x00000004 Enable Fresh Air Cooling (ALGO_FAC)
0x00000008 Enable DACC Return Air Reset (ALGO_DACC_RAT_RESET)
ALGORITHMS
287 Algorithms Enabled 0x00000010 Enable DACC Outdoor Air Reset (ALGO_DACC_OAT_RESET)
ENABLED
0x00000020 Enable DACH Return Air Reset (ALGO_DACH_RAT_RESET)
0x00000040 Enable DACH Outdoor Air Reset (ALGO_DACH_OAT_RESET)
0x00000080 Enable Supply Static Pressure Sensor Alarm (ALGO_LO_STATIC_PRESSURE_ALARM)
0x00000100 Enable Low Outdoor Temp override of DCV/OAC operation (ALGO_LO_OAT_DCV_OAC_OVERRIDE)
0x00000200 Enable High Outdoor Temp override of DCV/OAC operation (ALGO_HI_OAT_DCV_OAC_OVERRIDE)
0x00000800 Enable Free Cooling Blower Stage Up
.
LON
Heartbeat configuration proprieties define how often a network variable update is
305 HEARTBEAT LonTalk Heartbeat Time 0 100 10,000 Seconds
transmitted from a sending node.
TIME
• 0 = Disabled
FAH REHEAT • 1 = Allowed, must be occupied
313 Fresh Air Reheat Mode 0 0 3 Option
MODE • 2 = Allowed, blower must be energized and in occupied mode.
• 3 = Allow. No conditions apply.
The M3 unit controller will ensure that active VFD drive output is equal or greater
MSAV MIN VFD MSAV Minimum VFD Drive
314 10 33 50 % than Minimum VFD drive output. If conversion from CFM setting to VFD drive
DR OUT Output
yields lower value. The system will use Minimum VFD drive output instead output.
OUT AIR UNIT This Parameter is applicable in Zone Sensor mode (i.e. not applicable for local/
317 Outdoor Air Unit Options 0 0 2 Option
OPTNS remote thermostat mode).

65
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No
ENTH HIGH TMP Enthalpy High Temperature When in Enthalpy mode, the outdoor air suitability (OAS) will be set only if the
321 45 75 85 °F
LIMT Limit outdoor air temperature is lesser than this Parameter set point.
ZON SNSR CAL Zone Sensor Calibration This setting is applicable to local temperature sensor only.
323 -5 0 5 °F
OFFSET Offset NOTE: Parameter 323 is only available in firmware version 8.01 or later.
BPC MANUAL Building Pressure Control Manual reset value. This Parameter defines the default outdoor air damper
327 0 50 100 %
RESET Manual Reset position
BPC PID P Building Pressure Control
328 0 100 127 Count BPC PID Proportional Constant
CONST PID P Constant
BPC PID I Building Pressure Control
329 0 30 127 Count BPC PID Integral Constant
CONST PID I Constant
• 1 - Occupied - PID set point A; Unoccupied - PID set point B
• 2 - Occupied - PID set point A; Unoccupied -Staged output B
• 3 - Occupied - Staged output A; Unoccupied - PID set point B
• 4 - Occupied - Staged output A; Unoccupied - Staged output B
• 5 - Blower On - PID set point A; Blower Off - PID set point B
• 6 - Blower On - PID set point A; Blower Off - Staged output B
• 7 - Blower On - Staged output A; Blower Off - PID set point B
Mode
330 GP A02 MODE General Purpose A02 Mode 0 0 12 • 8 - Blower On - Staged output A; Blower Off - Staged output B
Selection
• 9 - DI2 on - PID set point B (1); DI3 on - PID set point A (2); Otherwise off.
• 10 - DI2 on - PID set point B (1); DI3 on - Staged Output A (2); Otherwise off.
• 11 - DI2 on - PID set point B (1); DI3 on - Staged Output A (2); Otherwise
off.
• 12 - Reserved
• (1) -DI3 (on M3) doesn’t matter
• (2) -DI2 (on M3) is off
General Purpose A02 Set
331 GP A02 SP A 0 0 100 % Analog output channel 2, set point A.
Point A
General Purpose A02 Set
332 GP A02 SP B 0 0 100 % Analog output channel 2, set point B.
Point B
General Purpose A02
333 GP A02 STG A 0 0 100 % Analog output channel 2, stage A
Stage A
General Purpose A02
334 GP A02 STG B 0 0 100 % Analog output channel 2, stage B
Stage B

General Purpose A02 • 0 = PWM


335 GP A02 OUTPUT 0 0 1 Selection
Output • 1 = 0-10 VDC
General Purpose A02
GP A02 PWM
336 Pulse-Width Modulation 50 200 2000 Hz Analog output PWM frequency.
FREQ
Frequency

66
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No
General Purpose A02
337 GP A02 KP Proportional Constant for 0 0 100 Count Analog output channel 2 PID loop proportional constant.
PID
General Purpose A02
338 GP A02 KI 0 0 100 Count Analog output channel 2 PID loop integral constant.
Integral Constant for PID
GP A02 MIN General Purpose A02
340 0 0 100 % Analog output channel 2 minimum output.
OUPUT Minimum Output
GP A02 MAX General Purpose A02
341 0 100 100 % Analog output channel 2 maximum output.
OUPUT Maximum Output
Source/feedback for the PID loop.
• 1 = Analog input 1 on GP3 A02
General Purpose A02
342 GP A02 SOURCE 1 1 3 Selection
Source • 2 = Analog input 2 on GP3 A02
• 3 = Analog input 3 on GP3 A02
GP A02 CYCL General Purpose A02 Cycle
343 0 1 180 Seconds Frequency of execution of PID loop.
INTRVL Interval
• 1 - Occupied - PID set point A; Unoccupied - PID set point B
• 2 - Occupied - PID set point A; Unoccupied -Staged output B
• 3 - Occupied - Staged output A; Unoccupied - PID set point B
• 4 - Occupied - Staged output A; Unoccupied - Staged output B
• 5 - Blower On - PID set point A; Blower Off - PID set point B
• 6 - Blower On - PID set point A; Blower Off - Staged output B
Mode • 7 - Blower On - Staged output A; Blower Off - PID set point B
344 GP A03 MODE General Purpose A03 Mode 0 0 11
Selection • 8 - Blower On - Staged output A; Blower Off - Staged output B
• 9 - DI2 on - PID set point B (1); DI3 on - PID set point A (2); Otherwise off.
• 10 - DI2 on - PID set point B (1); DI3 on - Staged Output A (2); Otherwise off.
• 11 - DI2 on - PID set point B (1); DI3 on - Staged Output A (2); Otherwise off.
• 12 - Reserved
• (1) -DI3 (on M3) doesn’t matter
• (2) -DI2 (on M3) is off
General Purpose A03 Set
345 GP A03 SP A 0 0 100 % Analog output channel 3, set point A.
Point A
General Purpose A03 Set
346 GP A03 SP B 0 0 100 % Analog output channel 3, set point B.
Point B
General Purpose A03
347 GP A03 STG A 0 0 100 % Analog output channel 3, stage A
Stage A
General Purpose A02
348 GP A03 STG B 0 0 100 % Analog output channel 3, stage B
Stage B

General Purpose A03 • 0 = PWM


349 GP A03 OUTPUT 0 0 1 Selection
Output • 1 = 0-10 VDC

67
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No
General Purpose A03
GP A03 PWM
350 Pulse-Width Modulation 50 200 2000 Hz Frequency of execution of PID loop.
FREQ
Frequency
General Purpose A03
351 GP A03 KP 0 0 100 Count Analog output channel 3 PID loop proportional constant.
Proportional Constant
General Purpose A03
352 GP A03 KI 0 0 100 Count Analog output channel 3 PID loop integral constant.
Integral Constant
GP A03 MIN General Purpose A03
354 0 0 100 % Analog output channel 3 minimum output.
OUPUT Minimum Output
GP A03 MAX General Purpose A03
355 0 100 100 % Analog output channel 3 Maximum output.
OUPUT Maximum Output
Source/feedback for the PID loop.
• 1 = Analog input 1 on GP3 A03
General Purpose A03
356 GP A03 SOURCE 1 1 3 SOURCE
Source • 2 = Analog input 2 on GP3 A03
• 3 = Analog input 3 on GP3 A03
GP A03 CYCL General Purpose A03 Cycle
357 0 1 180 Seconds Frequency of execution of PID loop.
INTRVL Interval

68
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No
GP3 Digital Out Control Mode = X + 32*Y + 16*Z
Input Sources X:
• 0 = None.
• 1 = Compressor 1 duty cycle. (Compressor crankcase heater function)
> On when outdoor air temperature is > = Parameter 364 seconds have
passed with compressor 1 off.
> Off when outdoor air temperature > Parameter 362 + 3°F (fixed dead-
band) or compressor 1 is turned on.
• 2 = On when Occupied
• 3 = On when blower on.
• 4 = On when heating demand
• 5 = On when cooling demand
358 GP D01 MODE General Purpose D01 Mode 0 0 127 Input Source • 6 = On when heating or cooling demand
• 7 = System RH (use Parameter 361)
• 8 = System IAQ (use Parameter 360)
• 9 = System OAT (use Parameter 362)
• 10 = On based on GP3 Temperature Sensor 1 (use Parameter 362)
• 11 = On based on GP3 Temperature Sensor 2 (use Parameter 362)
• 12 = On based on GP3 AI1 (use Parameter 359)
• 13 = On based on GP3 AI2 (use Parameter 359)
• 14 = On based on GP3 AO1 (use Parameter 359)
• 15 = On based on GP3 AO2 (use Parameter 359)
• Algorithm Y for Input Sources 7-15 (see 507242-01, Prodigy Application
Guide for further details).
GP D01 SP General Purpose D01 Set
359 0 0 10 Volts General Purpose D01 Digital output control mode set point.
VOLTS Points Volts
General Purpose D01 Set
360 GP D01 SP PPM 21 996 1996 PPM General Purpose D01 Digital output control mode set point.
Point Parts Per Million
GP D01 SP General Purpose D01 Set
361 0 0 100 % General Purpose D01 Digital output control mode set point.
PERCENT Point Percentage
GP DO1 SP General Purpose D01 Set
362 -31 0 132 °F General Purpose D01 Digital output control mode set point.
DEGREES Point Degree
General Purpose D01 Digital output control mode set point.
GP D01 DB General Purpose D01 Dead
363 0 0 100 % EXAMPLE: If this Parameter is set to 10%, then the dead-band in Fahrenheit
PERCENT Band Percentage
would be (DO Temperature Set Point * 10 /100).
GP D01 TIME General Purpose D01 Time
364 1 416 8160 Seconds For delay on or delay off.
DELAY Delay

69
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No
GP3 Digital Out Control Mode = X + 32*Y + 16*Z
Input Sources X:
• 0 = None.
• 1 = Compressor 1 duty cycle. (Compressor crankcase heater function)
> On when outdoor air temperature is < = Parameter 369 and > = P 371
seconds have passed with compressor 1 off.
> Off when outdoor air temperature > Parameter 369 + 3°F (fixed dead-
band) or compressor 1 is turned on.
• 2 = On when Occupied
• 3 = On when blower on.
• 4 = On when heating demand
• 5 = On when cooling demand
Mode
365 GP D02 MODE General Purpose D02 Mode 0 0 127 • 6 = On when heating or cooling demand
Selection
• 7 = System RH (use Parameter 368)
• 8 = System IAQ (use Parameter 367)
• 9 = System OAT (use Parameter 369)
• 10 = On based on GP3 Temperature Sensor 1 (use Parameter 369)
• 11 = On based on GP3 Temperature Sensor 2 (use Parameter 369)
• 12 = On based on GP3 AI1 (use Parameter 366)
• 13 = On based on GP3 AI2 (use Parameter 366)
• 14 = On based on GP3 AO1 (use Parameter 366)
• 15 = On based on GP3 AO2 (use Parameter 366)
• Algorithm Y for Input Sources 7-15 (see 507242-01, Prodigy Application
Guide for further details).
GP D02 SP General Purpose D02 Set
366 0 0 10 Volts General Purpose D02 Digital output control mode set point.
VOLTS Point Volts
General Purpose D02 Set
367 GP D02 SP PPM 21 996 1996 PPM General Purpose D02 Digital output control mode set point.
Point Parts Per Million
GP D02 SP General Purpose D02 Set
368 0 0 100 % General Purpose D02 Digital output control mode set point.
PERCENT Point Percentage
GP D02 SP General Purpose D02 Set
369 -31 0 132 °F General Purpose D02 Digital output control mode set point.
DEGREES Point Degree
GP D02 DB General Purpose D02 Dead
370 0 0 100 % General Purpose D02 Digital output control mode set point.
PERCENT Band Percentage
GP2 DO2 TIME General Purpose D02 Time
371 1 416 8160 Seconds General Purpose D02 Digital output control mode set point.
DELAY Delay
DISCHARGE AIR Discharge Air Cooling Set Set point used by the compressor / DAT PI in room sensor mode to determine the
375 45 55 65 °F
CL SP Point compressor speed.
BLOWER LO HT Depends on Applicable to Energence High Efficiency 3- to 5-ton units only. ·Blower staged
382 Blower Low Heat Output 20 100 %
OUTPUT equipment percentage output low speed; used for low heating for certain P volt models

70
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No
This will allow the CS8500
BACNET & CS to act as a sub to the M3 • 0 = Disabled (default) (Required setting for connection with ICON system.
385 0 0 1 Option
COEXIST Unit Controller and connect • 1 = Enabled (BACNET & CS8500 can co-exist.
via BACNET.
VAV supply static pressure
VAV SMK PRESS
386 set point during smoke 0 1 5 in w.c.
SP
operation
VAV VT PRESS VAV supply static pressure
387 0 1 5 in w.c.
SP set point during ventilation
VAV HT PRESS VAV supply static pressure
388 0 1 5 in w.c.
SP set point during heating
VAV CL PRESS VAV supply static pressure
389 0 1 5 in w.c.
SP set point during cooling
VAV MAX
390 VAV PID loop max speed 40 100 100 %
OUTPUT
VAV VAV PID loop manual reset
391 0 60 100 %
MANUALRESET value.
"MGV start up delay is
based on the setting. For
MGV STARTUP
392 example the default startup 4 16 300 Seconds
DELAY
delay is 16 seconds after
moving to high fire."
393 MGV MAX MGV PID loop min speed 60 80 100 %
394 MGV MIN MGV PID loop max speed 0 20 100 %
MGV PID MGV PID loop manual reset
395 0 50 100 %
MANUAL RST value.
MGV PID P MGV PID loop proportional
396 0 40 127 Counts
CONST constant
MGV PID I MGV PID loop integral
397 0 64 127 Counts
CONST constant
MGV PID D MGV PID loop derivative
398 0 0 127 Counts
CONST constant
Shift to high speed CAB
399 MGV SP HI CAB when MGV output rises 0 65 100 %
above this value.
Deadband for shifting down
400 MGV DB HI CAB 2 17 100 %
to low speed CAB
Exhaust Fan Enable Options:
• Blower On
POWER • Always
401 Power Exhaust Mode N/A Blower On N/A Options
EXHAUST MODE
• Occupied
• External Enable

71
Table 16. M3 Unit Parameters
Control Control Value
Parameter Short
Parameter Screen Name Units Description
Description Min. Default Max.
No

EXH FN LOW • 0 = Disabled


402 Low Speed Cycling. 0 1 Options
SPD CYCL • 1 - Enables Low Speed Cycling.
Speed for stage 1 when
EXH FN STG1 using a VFD for controlling
403 0 50 100 %
SPEED exhaust fan in staged
mode.
Speed for stage 2 when
EXH FN STG2 using a VFD for controlling
404 0 100 100 %
SPEED exhaust fan in staged
mode.
EXH FN SMK Exhaust Fan set point for
405 -0.50 -0.50 0.50 in w.c.
PRES SP PID control
EXH FN MIN Exhaust Fan PID loop min
406 0 50 100 %
SPEED speed
EXH FN MAX Exhaust Fan PID loop max
407 0 100 100 %
SPEED speed
EXH FN Exhaust Fan PID loop
408 0 100 100 %
MANUAL RESET manual reset value.
EXH FN P Exhaust Fan PID loop
409 0 20 127 Counts
CONTSTANT proportional constant
EXH FN I Exhaust Fan PID loop
410 0 64 127 Counts
CONSTANT integral constant
EXG FN D Exhaust Fan PID loop
411 0 0 127 Counts
CONSTANT derivative constant
This Parameter is applicable to ‘T’ type Blower only.
• 0 - Auto
EN FIXED BLWR
412 Enable Fixed Blower Speed 0 0 2 Options
SPD • 1 - Always run the blower at low speed
• 2 - Always run the blower at high speed
HI CL REHEAT
414 High Cool Reheat Time Out 0 0 30 Sec Reheat run-time on call for high cooling.
TMOUT
Damper overshoot percentage when moving to a more closed position. The
DAMP BKLASH Damper Backlash
415 0 25 40 % damper will move this percentage beyond the target position, then reverse and
ADJ Adjustment
move to the final target position.
BLOWER COOL Depends on Applicable to Energence High Efficiency 3- to 5-ton units only. Blower staged
416 Blower Cooling High 20 100 %
OUTPUT equipment percentage output high speed; used for high cooling or ventilation,

72
21. M3 Unit Controller Signal References
24VAC 24 VAC COM
S - BUS P297 P298 P299
- S + 3 3
S2
3 2 6 2 2 2 3 3 3 2 2 3

MS 9413-03-401 MS 9413-10-407 MS 9413-10-408 MS 9413-10-409

Figure 13. M3 Unit Controller Signal Reference Guide

73
22. M3 Unit Controller Connections Diagram

MSLO 9407-012-030-605 MSLO 9407-S08-003-605 MSLO 9407-S08-000-960 MSLO 9407-S12-000-960 MSLO 9407-006-061-314 MSLO 9407-008-078-715

1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 1 2 3 4 5 6 7 8

A B C A B C A B C A B C D E A B A B C

P264 - BLOWER DECK P265 - CONTACTORS/ RELAYS P266 - HEATING CONTROL P267 - OUT FAN AREA
& DAMPER P SENSOR

MSLO 9407-S04-000-960
1
T1-24V
PLUG # P264 BLOWER DECK AREA 7 GND GROUND GND
8

Pin # Label Description Type 1 RT6 DISCHARGE AIR TEMP 8 5VDC 5 VDC SUPPLY 5VDC 2
PLUG # P259 BLOWER ECM MOTOR RES 0-5 VDC
7

2 GND DIGITAL GROUND PLUG # P268 POWER


P259 - BLOWER ECM MOTOR

1 ODF/PWM 1 OUTDOOR FAN PWM1 PWM


B

3 S49 FREEZESTAT 1 (NC) SW 5VDC 1 T1-1 24VAC POWER TRANSFORMER 1 24 VAC 3


6

2 ODF/PWM 2 OUTDOOR FAN PWM2 PWM 4 VSS 5VDC 5 VDC 2


MSLO 9407-008-026-960

T1-COM 24VAC COMMON TRANSFORMER 1 24 VAC COM


3 GND DIGITAL GROUND GND 5 S50 FREEZESTAT 2 (NC) SW 5VDC 3 T18-1 24VAC POWER TRANSFORMER 1 24 VAC 4
5

4 IDB/PWM/VO A-BOX: INDOOR BLOWER PWM PWM 4 T18-COM 24VAC COMMON TRANSFORMER 1 24 VAC COM
6 S52 AIR FLOW SWITCH (NO) SW 5VDC
* MSAV/VAV: VFD VOLT OUT 0-10 V OUT PLUG # P269 REHEAT - HUMIDITROL; ULTRA - TXV
4

7 VSS 5VDC 5 VDC


1

MSLO 9407-005-017-960
* EBM ULTRA: VOLT OUT 0-10 V OUT 8 S27 DIRTY FILTER SWITCH (NO) SW 5VDC T43 24 VAC POWER 24VAC
T43
3

ZONE: DAMPER ACTUATOR (CAV) 2 T43 24 VAC COMMON 24 VAC COM 1


* 0-10 VAC PLUG # P265 CONTACTORS/ RELAYS
A

5 MSAV RELAY 3 L14 REHEAT SOLENOID 1; ULTRA TXV 1 24VAC DO


COM 2
1 COM 24VAC COMMON 24 VAC COM
2

* A-BOX: 2ND STAGE COMPRESSOR 1 24VAC DO 4 L30 REHEAT SOLENOID 2; ULTRA TXV 2 24VAC DO
2 K1 CONTACTOR COMPRESSOR 1 24VAC DO 3
* MSAV/VAV: EXHAUST 2ND BYPASS 24VAC DO 5 RSV RESERVED 24VAC DI
3
1

K2 CONTACTOR COMPRESSOR 2 24VAC DO


6 GND DIGITAL GROUND GND PLUG # P333 ULTRA - SENSORS 4
4 K3 CONTACTOR BLOWER 24VAC DO
7 IDB A-BOX: IDB FEEDBACK 5VDC 1 A185 TRANSDUCER TANDEM COMPRESSOR 0-5 VDC
* A-BOX: INDOOR BLOWER LOW 24VAC DO 5
*
MSAV/VAV/ULTRA B-C ALARM CONTACT (MUST BE
5VDC 5 COM 24VAC COMMON 24 VAC COM 2 5VDC 5VDC SUPPLY 5VDC OPEN
WIRED TO GND)
6 K10 RELAY OUTDOOR FAN 1 24VAC DO 3 GND DIGITAL GROUND
8 V BIAS V BIAS 18VDC RES 0-5 VDC
* RELAY K191 ULTRA: CRANKCASE HTR 24VAC DO 4 RT37 SENSOR THERMISTOR 1, COMPRESSOR 1
PLUG # P262 ECONOMIZER CONTROL PLUG # P271 HEATING 1 SAFETY
7 K68 RELAY OUTDOOR FAN 2 24VAC DO
1 T1 24VAC POWER 24VAC * A-BOX; INDOOR BLOWER HIGH 24VAC DO 1 S10-C PRIMARY LIMIT BURNER 1 C
2 GND DIGITAL GROUND 24 VAC COM * RELAY K196 ULTRA: CRANKCASE HTR 24VAC DO 2 S10-NC PRIMARY LIMIT BURNER 1 NC SW 24 VAC
3 VOT DAMPER CONTROL 2-10 VDC DO 8 COM 24 VAC COMMON COM 3 S10-NO PRIMARY LIMIT BURNER 1 NO
4 DPOS DAMPER POSITION FEEDBACK 2-10 VDC DI 9 K13 RELAY COMBUSTION AIR BLOWER 1 24VAC DO 4 S21-C SECONDARY LIMIT BURNER 1 C
5 GND DIGITAL GROUND SW 24VAC
RES 0-5 VDC
10 OPEN 5 S21-NC SECONDARY LIMIT BURNER 1 NC
6 RT16 + RETURN AIR TEMP 11 COM 24 VAC COMMON COM 6 S47 ROLL OUT SWITCH BURNER 1
7 A7 S OUTDOOR ENTHALPY SENSOR 4- 20 mA AI 12 K65 RELAY EXHAUST FAN 24VAC DO SW 24VAC
7 S47 ROLL OUT SWITCH BURNER 1
8 18 VDC 18 VOLTS DC POWER 18VDC PLUG # P266 HEATING CONTROL & DAMPER P SENSOR 8 S18 CAB PROOF SWITCH 1
9 A62 S INDOOR ENTHALPY SENSOR 4- 20 mA AI SW 24VAC
1 COM 24VAC COMMON 24 VAC COM 9 S18 CAB PROOF SWITCH 1
10 A173 SMOKE DETECTOR 24 V DI 2 A3, K15 HEAT 1 , ELECTRIC HEAT 1 24VAC DO 10 GV1 GAS VALVE SENSE 1 24VAC DI
11 T1 SMOKE DETECTOR 24 VAC 24 VAC 3 W2, K16 HEAT 2, ELECTRIC HEAT 2 24VAC DO
12 COM SMOKE DETECTOR 24 COMMON POWER 4 DDPS DAMPER DIFFER. PRESSURE SENSOR 0-5 VDC
PLUG # P263 HIGH AND LOW PRESSURE 5 GND GROUND GND

1 RT38 SENSOR THERMISTOR 2, COMPRESSOR 2 6 5VDC 5VDC SUPPLY 5VDC MSLO 9407-004-029-960 MSLO 9407-S10-000-960

(ULTRA JPRESSURE.
RES 0-5 VDC PLUG # P267 OUTDOOR FAN AREA
2 GND GROUND

(ULTRA TEMP.
1 RT17 OUTDOOR AIR TEMP 1 2 3 4 1 2 3 4 5 6 7 8 9 10
3 S4 HIGH PRESSURE COMPRESSOR 1 SW 24VAC RES 0-5 VDC
A B

SENSOR 1
2 GND DIGITAL GROUND
4 T1 24VAC POWER 24 VAC
3 S11 LOW PRESSURE FAN 1 SW 24VAC A B

SENSOR 1
5 S87 LOW PRESSURE COMPRESSOR 1 NC SW 24VAC
4 R 24VAC 24VAC DO
6 S7 HIGH PRESSURE COMPRESSOR 2 SW 24VAC
5 S84 LOW PRESSURE FAN 2 SW 24VAC
7 T1 24VAC POWER 24 VAC
8 S88 LOW PRESSURE COMPRESSOR 2 SW 24VAC
6 A30 STATIC DUCT PRESSURE 10VDC

P333 - ULTRA SENSORS

IAQ+IAQ - HUM TMP DO1 DO2 DI1 R DI2 R DI3 R DI4 C

S - BUS P297 P298 P299


- S +
S2 S1
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
M3 UNIT CONNECTIONS DIAGRAM
3 A B C A B C E A B C D
T-STAT HUMIDISTAT
COMMON DATE: 02/19 REV: 0
COMMON
SUPERSEDES FORM NO.
MSLO 9406-003-00C-121 MSLO 9408-010-576-960 MSLO 9408-S10-000-960 MSLO 9408-010-075-960 538033-01

Figure 14. M3 Unit Connections Diagram


74
23. M3 Unit Controller (A55)
Table 17. P259 Variable Blower and Fan Control
Pin # Label Description Type
1 ODF / PWM 1 OUTDOOR FAN PWM1 PWM
2 ODF / PWM 2 OUTDOOR FAN PWM2 PWM
3 GND DIGITIAL GROUND GND
4 IDB / PWM / VO ENERGENCE STANDARD EFFICIENCY 3 TO 6-TON UNIT INDOOR BLOWER PWM PWM
* MSAV / VAV: VFD VOLT OUT 0-10 VAC OUT
* ALL ENERGENCE ULTRA-HIGH EFFICIENCY UNITS EBM: VOLT OUT 0-10 VAC OUT
* ZONE: DAMPER ACUATOR (CAV) 0-10 VAC
5 MSAV RELAY
* ENERGENCE STANDARD EFFICIENCY 3 TO 6-TON UNIT: 2ND STAGE COMPRESSOR 1 24VAC DO
* MSAV w/AUTO BYPASS; 2ND STAGE EXHAUST 24VAC DO
6 GND DIGITAL GROUND GND
7 IDB ENERGENCE STANDARD EFFICIENCY 3 TO 6-TON UNIT: IDB FEEDBACK 5VDC
MSAV / VAV / ENERGENCE ULTRA-HIGH EFFICIENCY 7-1/2 TO 20-TON UNITS ALARM CONTACT
* 5VDC
(MUST BE WIRED TO GND)
8 V BIAS V-BIAS 18VDC

Table 18. P262 Economizer Control


Pin # Label Description Type
1 T1 24VAC POWER 24VAC
2 GND DIGITAL GROUND 24VAC COM
3 VOT DAMPER CONTROL 2-10VDC DO
4 DPOS DAMPER POSITION FEEDBACK 2-10VDC DI
5 GND DIGITAL GROUND RES 0-5VDC
6 RT16 + RETURN AIR TEMP
7 A7 S OUTDOOR ENTHALPY SENSOR 4-20 mA AI
8 18VDC 18VDC POWER 18VDC
9 A62 S INDOOR ENTHALPY SENSOR 4-20 mA AI
10 A173 SMOKE DETECTOR 24VAC DI
11 T1 SMOKE DETECTOR 24VAC
24VAC POWER
12 COM SMOKE DETECTOR 24VAC COMMON

75
Table 19. P263 High and Low Pressure
Pin # Label Description Type
1 UTS2 ULTRA SUMP TEMP COMPRESSOR 2
RES 0-5VDC
2 GND GROUND
3 S4 HIGH PRESSURE COMPRESSOR 1 SW 24VAC
4 T1 24VAC POWER 24VAC
5 S87 LOW PRESSURE COMPRESSOR 1 NC SW 24VAC
6 S7 HIGH PRESSURE COMPRESSOR 2 SW 24VAC
7 T1 24VAC POWER 24VAC
8 S88 LOW PRESSURE COMPRESSOR 2 SW 24VAC

Table 20. P264 Blower Deck Area


Pin # Label Description Type
1 RT6 DISCHARGE AIR TEMP
RES 0-5VDC
2 GND DIGITAL GROUND
3 S49 FREEZESTAT 1 (NC) SW 5VDC
4 VSS 5VDC 5VDC
5 S50 FREEZESTAT 2 (NC) SW 5VDC
6 S52 AIR FLOW SWITCH (NO) SW 5VDC
7 VSS 5VDC 5VDC
8 S27 DIRTY FILTER SWITCH (NO) SW 5VDC

76
Table 21. P265 Contactors / Relays
Pin # Label Description Type
1 COM 24VAC COMMON 24VAC COM
2 K1 CONTACTOR COMPRESSOR 1 24VAC DO
3 K2 CONTACTOR COMPRESSOR 2 24VAC DO
4 K3 CONTACTOR BLOWER 24VAC DO
* ENERGENCE STANDARD EFFICIENCY 3 TO 6-TON UNITS INDOOR BLOWER LOW 24VAC DO
5 COM 24VAC COMMON 24VAC COM
6 K10 RELAY OUTDOOR FAN 1 24VAC DO
* RELAY K191 ULTRA: CRANKCASE HEATER 24VAC DO
7 K68 RELAY OUTDOOR FAN 2 24VAC DO
* A-BOX: INDOOR BLOWER HIGH 24VAC DO
* RELAY K196 ULTRA: CRANKCASE HEATER 24VAC DO
8 COM 24VAC COMMON 24VAC COM
9 K13 RELAY COMBUSTION AIR BLOWER 1 24VAC DO
10 COM 24VAC COMMON 24VAC COM
11 K85 RELAY EXHAUST FAN 24VAC DO

Table 22. P266 Heating Control and Damper ΔP Sensor


Pin # Label Description Type
1 COM 24VAC COMM 24VAC COM
2 A3, K15 HEAT 1, ELECTRIC HEAT 1 24VAC DO
3 W2, K16 HEAT 2, ELECTRIC HEAT 2 24VAC DO
4 DDPS DAMPER DIFFER. PRESSURE SENSOR 0-5VDC
5 GND GROUND GND
6 5VDC 5VDC SUPPLY 5VDC

Table 23. P267 Outdoor Fan Area


Pin # Label Description Type
1 RT17 OUTDOOR AIR TEMP
RES 0-5VDC
2 GND DIGITAL GROUND
3 S11 LOW PRESSURE FAN 1 SW 24VAC
4 R 24VAC 24VAC DO
5 S84 LOW PRESSURE FAN 2 SW 24VAC
6 A30 STATIC DUCT PRESSURE 10VDC
7 GND GROUND GND
8 5VDC 5VDC SUPPLY 5VDC

77
Table 24. P268 Power
Pin # Label Description Type
1 T1-1 24VAC POWER TRANSFORMER 1 24VAC
2 T1-COM 24VAC COMMON TRANSFORMER 1 24VAC COM
3 T18-1 24VAC POWER TRANSFORMER 1 24VAC
4 T18-COM 24VAC COMMON TRANSFORMER 1 24VAC COM

Table 25. P269 Reheat - Humiditrol: Ultra - TXV


Pin # Label Description Type
1 T43 24VAC POWER 24VAC
2 T43 24VAC COMMON 24VAC COM
3 L14 REHEAT SOLENOID 1: ULTRA TXV 1 24VAC DO
L30*
4 ENERGENCE B 12.5T 2-SPEED REHEAT SOLENOID 2: ULTRA TXV 2 24VAC DO
OD FAN RELAYS - K251/K252
5 RSV RESERVED 24VAC DI

Table 26. P271 Heating 1 Safety


Pin # Label Description Type
1 S10-C PRIMARY LIMIT BURNER 1C
2 S10-NC PRIMARY LIMIT BURNER 1 NC SW 24VAC
3 S10-NO PRIMARY
4 S21-C SECONDARY LIMIT BURNER 1C
SW 24VAC
5 S21-NC SECONDARY LIMIT BURNER 1 NC
6 S47 ROLL OUT SWITCH BURNER 1
SW 24VAC
7 S47 ROLL OUT SWITCH BURNER 1
8 S18 CAB PROOF SWITCH 1
SW 24VAC
9 S18 CAB PROOF SWITCH 1
10 GV1 GAS VALVE SENSE 1 24VAC

78
Table 27. P297 Thermostat
Pin # Label Description Type
1 R TRANSFORMER 1 24VAC POWER 24VAC
2 C TRANSFORMER 1 24V COMMON 24VAC COMM
3 G BLOWER SIGNAL 24VAC DI
4 W1 1ST STAGE HEATING 24VAC DI
5 W2 2ND STAGE HEATING 24VAC DI
6 Y1 1ST STAGE COOLING 24VAC DI
7 Y2 2ND STAGE COOLING 24VAC DI
8 OCP OCCUPIED SIGNAL 24VAC DI
9 GLO GLOBAL CONTROL INPUT 24VAC DI
10 RSV RESERVED NA

Table 28. P298 IAQ Interface


Pin # Label Description Type
1 R TRANSFORMER 1 24VAC POWER 24VAC
2 C TRANSFORMER 1 24V COMMON 24VAC COMM
3 IAQ+ INDOOR AIR QUALITY 0-10VDC AI
4 GND INDOOR AIR QUALITY 0-10VDC AI
5 HUM RH SENSOR 0-10VDC AI
6 GND DIGITAL GROUND GND
7 TMP ROOM SENSOR THERMISTOR
8 DO1 SERVICE RELAY OUTPUT 24VAC DO
9 GND 24 VAC COMMON 24VAC COMM
10 DO2 EXHAUST FAN 24VAC DO

79
Table 29. P299 Safety
Pin # Label Description Type
1 DI1 SMOKE DETECTOR (NO) 24VAC DI
2 R TRANSFORMER 1 24VAC POWER 24VAC
3 C TRANSFORMER 1 24V COMMON 24VAC COMM
4 DI2 DIGITAL INPUT 2 FORMER (S42 & S135) 24VAC DI
5 R TRANSFORMER 1 24VAC POWER 24VAC
6 DI3 DIGITAL INPUT 3 FORMER (S149 & A42 FOR A BOX) 24VAC DI
7 R TRANSFORMER 1 24VAC POWER 24VAC
8 DI4 DIGITAL INPUT 4 FORMER (HUMIDITROL INPUT) 24VAC DI
9 C TRANSFORMER 1 24V COMMON 24VAC COMM
10 RSV RESERVED NA

Table 30. P333 Ultra - Sensors


Pin # Label Description Type
1 UPS1 SUCTION PRESSURE 0-5VDC
2 5VDC 5VDC SUPPLY 5VDC
3 GND DIGITAL GROUND
RES 0-5VDC
4 UTS1 SUMP TEMP COMPRESSOR 1

Table 31. P358 (Ultra-A Box Only M3 Unit Controller)


Pin # Label Wire Color
1 RS485_A RED
2 RS485_B YELLOW
3 NOT USED

4 GND BLACK

80
23.1. GP3 Control (A187)

Table 32. P348


Pin # Description Type
1 5VDC SUPPLY (10MA MAX) 5VDC
2 ANALOG/PWM OUTPUT 4 AO: 0-10VDC; PWM: 0-15V
* ULTRA C: PWM FAN B23/B24 PWM: 0-15V
3 ANALOG/PWM OUTPUT 2 AO: 0-10VDC; PWM: 0-15V
4 ANALOG/PWM OUTPUT 3 AO: 0-10VDC; PWM: 0-15V
* ULTRA C: PWM FAN B22 PWM: 0-15V
5 ANALOG/PWM OUTPUT 1 AO: 0-10VDC; PWM: 0-10V
6 RELAY 1 - NORMALLY OPEN RELAY (DRY) CONTACT
7 RELAY 1 - COM RELAY (DRY) CONTACT
8 RELAY 2 - COM RELAY (DRY) CONTACT
9 RELAY 2 - NORMALLY OPEN RELAY (DRY) CONTACT
10 DIGITAL INPUT 3 24V DI
11 DIGITAL INPUT 4 24V DI
12 DIGITAL INPUT 2 24V DI
13 THERMISTOR INPUT 2 (10K@25C)
RES 0 - 3.3 VDC
* ULTRA C: SENSOR THERMISTOR COMPRESSOR 4
14 ANALOG INPUT 1 0-10VDC
* ULTRA C: TRANSDUCER TANDEM COMP B 0-5VDC
15 ANALOG INPUT 2 0-10VDC
16 THERMISTOR INPUT 1 (10K@25C)
RES 0 - 3.3 VDC
* ULTRA C: SENSOR THERMISTOR COMPRESSOR 3
17 ANALOG INPUT 3 (0-10VDC) 0-10VDC
18 GROUND GND
19 GROUND GND
20 GROUND GND
21 GROUND GND
22 COM COM
23 COM COM
24 DIGITAL INPUT 1 24V DI

81
23.2. C3 Control (A178)

Table 33. P118


Pin # Label Description Type
1 24VAC 24VAC SUPPLY (FOR RELAY OUTPUTS) 24VAC
2 COM 24VAC COM 24VAC COM
3 OPEN (NOT USED)
4 OPEN (NOT USED)
5 FAN3 RELAY OUTDOOR FAN 3 24VAC DO
* ULTRA C: RELAY K233 CRANKCASE HEATER COMP 3
6 OPEN (NOT USED)
7 OPEN (NOT USED)
8 FAN4 RELAY OUTDOOR FAN 4 24VAC DO
* ULTRA C: RELAY K234 CRANKCASE HEATER COMP 4
9 FAN5 RELAY OUTDOOR FAN 5 24VAC DO
10 FAN6 RELAY OUTDOOR FAN 6 24VAC DO
11 CMP3 CONTACTOR COMPRESSOR 3 24VAC DO
12 CMP4 CONTACTOR COMPRESSOR 4 24VAC DO

Table 34. P119


Pin # Label Description Type
1
HPSW3 HIGH PRESSURE SWITCH COMPRESSOR 3 SW 24VAC
2
3
HPSW4 HIGH PRESSURE SWITCH COMPRESSOR 4 SW 24VAC
4
5
FRZST3 FREEZESTAT COMPRESSOR 3 SW 5VDC
6
7
LPSW3 LOW PRESSURE SWITCH COMPRESSOR 3 SW 24VAC
8
9
FRZST4 FREEZESTAT COMPRESSOR 4 SW 5VDC
10
11
LPSW4 LOW PRESSURE SWITCH COMPRESSOR 3 SW 24VAC
12
13 OPEN (NOT USED)
14 OPEN (NOT USED)
15 OPEN (NOT USED)
16 OPEN (NOT USED)

82
Table 35. P272
Pin # Label Description Type
1 PRIMARY LIMIT BURNER 2 C SW 24VAC
2 PRIMARY LIMIT PRIMARY LIMIT BURNER 2 NC
3 PRIMARY LIMIT BURNER 2 NO
4 SECONDARY LIMIT BURNER 2 C SW 24VAC
SECONDARY
5 SECONDARY LIMIT BURNER 2 NC
6
ROLLOUT SWITCH BURNER 2 SW 24VAC
7
GAS2 SAFETY
8
SWITCHES CAB PROOF SWITCH 2 SW 24VAC
9
10 GAS VALVE SENSE 2 24VAC DI

Table 36. P332


Pin # Label Description Type
1 COM 24VAC COM 24VAC COM
2 A12 K17 HEAT 3, ELECTRIC HEAT 3 24VAC DO
3 W2 K18 HEAT 4, ELECTRIC HEAT 4 24VAC DO
4 CAB2 RELAY COMBUSTION AIR BLOWER 2 24VAC DO

83
24. Quick Start Guide

CAUTION
Check rooftop unit electrical power for proper voltage and phasing. Check gas train components.

a. Turn on unit and dismiss alarm messages as necessary.


b. Follow SETUP > INSTALL menu to properly configure unit
c. Be sure unit is in normal operating mode as seen in display (COOLING, HEATING, IDLE, etc).
d. To verify operation use SERVICE > TEST menu.
Control Mode Menu Setup Needed Tips
THERMOSTAT (Factory set for 2-stage thermostat) Check LEDs for signals.
• Setup information to be verified with integrator.
• Follow wiring instructions including network termination
BACnet SETUP > NETWORK INTEGRATION > NETWORK TYPE = BACNET
• Remember to set MAC address 0-127
• Expert level BACnet service manual available.
• Setup information to be verified with integrator.
• Follow wiring instructions including network termination
LonTalk SETUP > NETWORK INTEGRATION > NETWORK TYPE = LONTALK
• XIF file available. Neuron ID on sticker.
• Expert level LonTalk service manual available.
• Follow wiring instructions including network termination
L Connection SETUP > NETWORK INTEGRATION > NETWORK TYPE = L-CONNECTION • Comfort Sensors are 24 VAC polarity sensitive.
• All network devices need to be correctly addressed
• Verify damper minimum positions
Damper SETUP > TEST & BALANCE > DAMPER
• Refer to Economizer section of manual for more detail
• Give unit time to start-up.
Local Mode SETUP > NETWORK INTEGRATION > NETWORK TYPE = RTU STANDALONE
• Humidity control requires sensor or error code 7649
• Three possible connections, LOCAL SENSOR, NETWORK
Dehumidifier Dehumidifier setup will be done during the SETUP >INSTALL wizard. It’s the last part of that wizard. SENSOR and REHEAT DI4.
• Analog sensor wiring is polarity sensitive
Change motor torque; see • Final motor CFM should be set by Test and Balance technician
Blower
SETUP > TEST & BALANCE > BLOWER • Blower charts are located in the unit installation instruction.

84
25. Wiring Diagrams
24 V POWER


-&
3
7207+(50267$7,13876
5 -$ 3
725 $
5 
& 
 & 
*   % 
72* * 
. $
W1 6 -    
-$
B  W1  : 3
 

.


W2
 W2 

$
W2
72<  


$ Y1 

-
3
$// 27+(5 7+(50267$7
% Y1 
 

- 
Y2 6,*1$/6 5(0$,1 &211(&7('
$66+2:1217+(5,*+7  Y2 

3
2&3 


$
2&3
TO PROVIDE SUPERMARKET REHEAT SCHEME &
USE S86 DEHUMIDISTAT AND K55. 

$ 
$ -$ -$
 3
<  5
 

-
3

3
-
-$

-
$ <   &
.  

.
% %
<    
   $,
%
  

$

&
TO PROVIDE THREE 92  +80 
COMPRESSOR STAGES.

REQUIRES 3 HEAT, 3 $ $ 
COOL THERMOSTAT -$ 703

-


3

3
-

AND K27 RELAY. (;&  '
9,1 

-%


3
'2
*1'  - 3
% *1'  & -$ 0
6,*    57
 ',
  '2
-$ 3  
 ', 57
 5

-$
$

3
-$ 
  5 - 3 57
 
   &
6 6 %
%
 ',  


  5
. -&

&
&
 ',  6
 7
  5 $

9$&

.
6 6 ' 
 ',

 %
 & 
TO PROVIDE COMPRESSOR
 6 SHUT OFF, 120 VAC
P304 PROVIDED BY GENERATOR
24 V COMMON

FOR MOTORS WITH S42 EXTERNAL OVERLOAD LESS



INVERTER, SEE INVERTER WITH BY PASS FOR S42 HOOK UP
DESCRIPTION P253 PLUG, SMOKE DETECTOR TWO
PLUG, MODULE, CONTROL SMOKE USE S86 DEHUMIDISTAT AND K55 FOR OPTIONAL
KEY COMPONENT
P255 DETECTION  SUPERMARKET REHEAT SCHEME, PRODIGY PARAMETERS NEED
A2 SENSOR, ELECTRONIC THERMOSTAT
PLUG, ECONOMIZER TO BE MODIFIED UNDER THE SETTINGS MENU OR VIA UC
$ &21752/287'225$,5&)0)/2: P262
SOFTWARE FOR SIMULTANEOUS HEATING AND COOLING.
P264 PLUG, BLOWER DECK
$ ',))(5(17,$/35(6685(75$16'8&(5
P297 PLUG, THERMOSTAT - DDC INTERFACE  REMOTE LOCATION OF RT6
A55 CONTROL BOARD, MAIN
SENSOR, CO2 (IAQ) OPTIONAL P298 PLUG, IAQ INTERFACE
A63 P298-8 (DO-1) IS SERVICE RELAY OUTPUT (24VAC)
P299 PLUG, SAFETY INTERFACE 
A91 SENSOR, HUMIDITY IF USED CONNECT TO AN INDICATOR LIGHT
SENSOR ONE, SMOKE, RETURN AIR P304 PLUG, SYS BUS
A171 THERMOSTAT HOOKUP FOR PROGRAMMABLE CONFIGURATION
SENSOR TWO, SMOKE, SUPPLY AIR RT6 SENSOR, SUPPLY AIR TEMP 
A172 OF THE BOARD (A55).
MODULE, CONTROL SMOKE DETECTION RT16 SENSOR, RETURN AIR TEMP
A173
JACK, AIR FLOW CONTROL S27 SWITCH, FILTER PRODIGY SETTINGS MUST BE MODIFIED WHEN K222, S42,
J26 
JACK, RT16 RETURN AIR SENSOR S52 SWITCH, AIRFLOW S52, S149 OR S179 ARE INSTALLED
J99
J100 JACK, RT6 SUPPLY AIR SENSOR S42 SWITCH, OVERLOAD RELAY BLOWER MOTOR
 CONNECT A172 SENSOR TO J261 ON SUPPLY AIR SMOKE
J250 JACK, SMOKE DETECTOR ONE S86 SWITCH, DEHUMIDISTAT
DETECTOR ONLY
J251 JACK, SMOKE DETECTOR ONE S135 OVERLOAD, BLOWER MOTOR SUPPLY
J252 JACK, SMOKE DETECTOR TWO S149 SWITCH, OVERFLOW ONE  S179, OVERFLOW SWITCH USED ON LGH/LCH 420-600 UNITS
J253 JACK, SMOKE DETECTOR TWO 6 SWITCH, OVERFLOW TWO ONLY
JACK, MODULE, CONTROL SMOKE T8 TRANSFORMER, 120 V GENERATOR POWERED  A63, A34 & A24 ARE MUTUALLY EXCLUSIVE
J255 DETECTION
J261 JACK, SUPPLY SMOKE DETECTOR JUMPER
 FACTORY INSTALLED OPTION FOR LGH/LCH 242-600 UNITS
J262 JACK, ECONOMIZER ONLY
J264 JACK, BLOWER DECK
J297 JACK, THERMOSTAT - DDC INTERFACE
J298 JACK, IAQ INTERFACE
J299 JACK, SAFETY INTERFACE
K27, -1 RELAY, TRANSFER
K55,-1 RELAY, BLOWER
K222,
-1 RELAY, COMPRESSOR LOCKOUT
P26 PLUG, AIR FLOW CONTROL ACCESSORIES
P99 PLUG, RT16 RETURN AIR SENSOR
P100 PLUG, RT6 SUPPLY AIR SENSOR
P250 PLUG, SMOKE DETECTOR ONE
P251 PLUG, SMOKE DETECTOR ONE
P252 PLUG, SMOKE DETECTOR TWO REV. 3

Figure 15. Wiring Diagram


85
24 V POWER

-&
3
72$7+(50267$7,13876
5 -$ 3
725 5  $
& 
 & 
*   % 
72* * 
.
W1 6 -    
B  W1  : 3

.
W2
 W2 

$
W2
72<
$ Y1 

-
3
$// 27+(5 7+(50267$7  Y1 
Y2 6,*1$/6 5(0$,1 &211(&7('
$66+2:1217+(5,*+7 Y2 
2&3


$
2&3
TO PROVIDE SUPERMARKET REHEAT SCHEME &
USE S86 DEHUMIDISTAT AND K55. 


$ -$
 3
<  5

-
3

3
-
-$

-
$ <   &
.

.
%
<    
 $,
%
 

$

&
TO PROVIDE THREE 92  +80 
COMPRESSOR STAGES.

REQUIRES 3 HEAT, 3 $ 
COOL THERMOSTAT 703

-


3

3
-

AND K27 RELAY. '
9,1 

-%


3
'2
- 3
*1'  & -$ 0
  57
&  ',
 '2

)$
-$ 3  
 ', 57
12  5

-$
3
-$ 
  5 - 3 57
 
   &
6 %
$ %  
  ',

  5
. -&

&
&
   ',  6  7

  5 $

9$&

.
6 ' 
 ',
 
%
 & 
TO PROVIDE COMPRESSOR
 6 SHUT OFF, 120 VAC
P304 PROVIDED BY GENERATOR
24 V COMMON

FOR MOTORS WITH S42 EXTERNAL OVERLOAD LESS



INVERTER, SEE INVERTER WITH BY PASS FOR S42 HOOK UP
DESCRIPTION PLUG, MODULE, CONTROL SMOKE
P255 DETECTION USE S86 DEHUMIDISTAT AND K55 FOR OPTIONAL
KEY COMPONENT
P262 PLUG, ECONOMIZER  SUPERMARKET REHEAT SCHEME, A55 PARAMETERS NEED TO
A2 SENSOR, ELECTRONIC THERMOSTAT
PLUG, BLOWER DECK BE MODIFIED UNDER THE SETTINGS MENU OR VIA UC
A55 PANEL, MAIN P264
SOFTWARE FOR SIMULTANEOUS HEATING AND COOLING.
SENSOR, CO2 (IAQ) OPTIONAL P297 PLUG, THERMOSTAT - DDC INTERFACE
A63
P298 PLUG, IAQ INTERFACE  REMOTE LOCATION OF RT6
A91 SENSOR, HUMIDITY
SENSOR ONE, SMOKE, RETURN AIR P299 PLUG, SAFETY INTERFACE
A171 P298-8 (DO-1) IS SERVICE RELAY OUTPUT (24VAC)
P304 PLUG, SYS BUS 
A172 SENSOR TWO, SMOKE, SUPPLY AIR IF USED CONNECT TO AN INDICATOR LIGHT
MODULE, CONTROL SMOKE DETECTION RT6 SENSOR, SUPPLY AIR TEMP
A173 THERMOSTAT HOOKUP FOR PROGRAMMABLE CONFIGURATION
JACK, RT16 RETURN AIR SENSOR RT16 SENSOR, RETURN AIR TEMP 
J99 OF THE A55 BOARD
JACK, RT6 SUPPLY AIR SENSOR S27 SWITCH, FILTER
J100
JACK, SMOKE DETECTOR ONE S52 SWITCH, AIRFLOW A55 SETTINGS MUST BE MODIFIED WHEN K222, S42, S52,
J250 
JACK, SMOKE DETECTOR ONE SWITCH, OVERLOAD RELAY BLOWER MOTOR S149 OR S179 ARE INSTALLED
J251 S42
J252 JACK, SMOKE DETECTOR TWO S86 SWITCH, DEHUMIDISTAT
 CONNECT A172 SENSOR TO J261 ON SUPPLY AIR SMOKE
J253 JACK, SMOKE DETECTOR TWO S149 SWITCH, OVERFLOW ONE
DETECTOR ONLY
JACK, MODULE, CONTROL SMOKE T8 TRANSFORMER, 120 V GENERATOR POWERED
J255 DETECTION
J261 JACK, SUPPLY SMOKE DETECTOR JUMPER
J262 JACK, ECONOMIZER
J264 JACK, BLOWER DECK
J297 JACK, THERMOSTAT - DDC INTERFACE
J298 JACK, IAQ INTERFACE
J299 JACK, SAFETY INTERFACE
K27, -1 RELAY, TRANSFER
K55,-1 RELAY, BLOWER WIRING DIAGRAM 04/18
K222,
-1 RELAY, COMPRESSOR LOCKOUT
P99 PLUG, RT16 RETURN AIR SENSOR
P100 PLUG, RT6 SUPPLY AIR SENSOR
P250 PLUG, SMOKE DETECTOR ONE ACCESSORIES
P251 PLUG, SMOKE DETECTOR ONE ELECTRONIC OR ELECTROMECHANICAL
P252 PLUG, SMOKE DETECTOR TWO THERMOSTAT FOR STRATEGOS
P253 PLUG, SMOKE DETECTOR TWO
SECTION C REV. 0
Supersedes New Form No.
537108-01 537985-01

Figure 16. Wiring Diagram

86
26. Prodigy 2.0 Release History • Setup wizard for DACH and no electric heat
enhancement
• Improved Prodigy 2.0 low ambient test mode operations
• Enhanced Prodigy 2.0 Humiditrol setpoint operations
08.11.0103 – Processor change release - 5/26/2022 • Enhancement on Model Numbers allowed now includes
• Support for firmware updates on -25 boards. Strategos units 08.02.0143 – Firmware update released on 8-17-
• Enhanced Outdoor Air CFM setup 15
08.10.0103 – Enhancement only release 9/21/2020 • Enhanced alarm reporting and error code tables to
• Added the reheat option to LC,LGH300,360H4M units. • Enhanced communications when used in L Connection
eliminate nuisance error codes in the heating cycle.
networks
08.09.0118 New support of Strategos 2.0 Models • Enhanced Humiditrol operation for better control and
9/26/2019 08.05.0108 – Supports introduction of Prodigy 2.0 improved setpoint tolerance.
• Strategos 2.0 adds the Humiditrol option. into D & E Box units release on 1-09-2018 • Improved smoke detector options and operations in
• Added support for 380/420V, 3Ø, 50Hz (M Voltage) - D remote demand mode.
• Strategos 2.0 A Boxes added 2-stage compressor
support . box RTU’s • Enhanced status screen alarm notification.
• Strategos 2.0 A Boxes add EBM blower type. • Enhanced timings and settings to allow better starting
08.05.0107 – Supports introduction of Prodigy 2.0 and operations in Energence single compressor units.
• Strategos 2.0 A Boxes have different gas heat options into D & E Box units release on 9-22-2017
from the original Strategos. • Enhanced re-establishing communication with the L
• Enhanced Heat error code reporting Connection Zone Link after a communication loss or
08.08.0104 – Enhancement only release 4-12-2019 • Enhanced firmware update reporting with shutdown.
• Two heat speeds for single phase (P voltage type) high acknowledgement • Enhanced alarm reporting on four compressor Ultra units.
efficiency A-Boxes with ECM blowers and gas heat types • Enhanced add on board communication reporting • Enhanced unit BACnet network identification options
B, D, U, H, Q and X.
• Enhanced back up sensor sequence of operation • Improved override functionality in room sensor mode.
• A-Box dedicated heating speed
• Changed default outdoor air temperature for free cooling 08.02.0129 – C Box operations released on 4-13-
• New 25T C Ultra (LCH/LGH300U4M) to 60°F
15
08.07.0135 – Enhancement only release 1-22-2019 • Enhanced heating data information
• General Purpose Digital and Analog IO on GP3 card
• Enhanced minimum position setting reliability • Enhanced S-Bus communication functionality release.
• Enhanced B Box (150H) low ambient control operations • Enhanced MSAV/CAV options • C-Ultra Box operations.
• Energence A Box Humiditrol reheat operation • Enhanced discharge air control functionality • Capable of four stages of heating.
enhancements • Enhanced E Box modulating gas functionality • L Connection Zone Bypass Damper on High Efficiency
• Update to “Figure 14. M3 Unit Connections Diagram” on • Enhanced VFD power exhaust functionality A-Box units.
page 74 to reflect part number change for the P267
connector. • Enhanced error code reporting • Outdoor air control with velocity sensor.
• Enhanced blower in Humiditrol mode • Enhanced UI for EP in test mode.
08.07.0130 – Supports introduction of Prodigy 2.0 • Building Pressure Control – using factory economizer and
• Enhanced error reporting ability for smoke detection
iCON OTA firmware updates release on 7-31-2018 modes power exhaust.
• iCON has the ability to update Prodigy M3 firmware • Crankcase heater control on Standard and High
remotely - (OTA) over the air • Enhanced Test and Balance menu path
Efficiency A-Box units.
• Enhanced error code reporting and explanations 08.04.0105 – Release supports for two new
• Enhanced Prodigy 2.0/BACnet operations models- on 5-23-2017 08.01.0136 – Firmware update released on 12-11-
• Added Prodigy 2.0/BACnet MOAD actuator feedback • Enhanced high pressure switch trip reset speed 14
monitoring • Enhanced room sensor calibration.
• Enhanced economizer operations
• Enhanced Strategos power exhaust control options • Enhanced communications to NOVAR LSE.
• Updated the scaling factors for Parameters 58, 65, 78, 08.03.0120 – CS8500 as a BACnet sensor release • Enhanced communications to L Connection (NCP).
141, and 169 to be adjusted at the local UI in minutes on 3-1-17 • BACnet enhancements for Title 24.
instead of seconds • Adds the ability to use the CS8500 in conjunction with
BACnet as an adjustable sensor with display • Enhanced communications with LonTalk integration.
• Enhanced load shedding operations when Prodigy 2.0 is
in zone sensor mode • Enhanced setup function for field installed electric heat • Enhanced options for A Box load shedding.
• Enhanced Energence A Box Humiditrol reheat operations • Enhanced error codes reporting for room sensor failures.
08.03.0112 – Energence Ultra High Efficiency 3-6
• Enhanced Energence VAV operations and error code Ton Family (A Box) release on 3-11-16 08.01.0121 – A Box operations released on 9-5-14
reporting • Enhanced BACnet protocol communication.
• Energence Ultra High Efficiency 3-6 ton unit operations
08.06.0105 – Supports introduction of Prodigy 2.0 • Enhanced low ambient operation for single compressor • Enhanced tolerances to error codes.
into Strategos RTU units release on 4-11-2018 units • Enhanced humidity sensor operations.
• Implement UI command for BACnet commands viewed in • Enhanced no current alarm messaging
App mode 08.00.0604 – Firmware update released on 7-9-14
• Improved firmware updating operations • Enhanced enthalpy sensor operations.
• Allow thermostat occupancy input DIN 317 to work in • Improved Prodigy 2.0 BACnet useable object
conjunction with iCON, BACnet and Lon functionality 08.00.0603 – Original B Box released 5-12-14
• Better BACnet object documentation descriptions
• Improved Prodigy 2.0 performance with BACnet
87
Index J
Jumpers 3 Alarm Status Display 6
Network Status 6
L Normal Mode and Status Messages 6
A L CONNECTION 34 Unit Operation 6
Abbreviations 35 LED Operation Indicators 4
Alarms 37 LEDs 3
Alarm Status Display 6 Low Ambient Set Point 29 T
Thermal Protection Switches (S5, S7, S8, S31 and
B M S180) 26
Thermostat / Humidistat Common Isolation 4
Blower Operation with Effective Occupancy 26 Menu Selection Overview 10 Thermostat Input LED Indicators 4
Minimum Damper Position 30
C MODBUS 4
U
Motorized Outdoor Air Damper 30
Communication Module Interface 4 Unit Operation 6
Configuration ID 1 9 N USB Flash Drive Interface Usage 4
Configuration ID 1 and 2 8 USB Service Report Example 36
Configuration ID 2 9 Network Types 6
Normal Mode 6
Connections 3
Controller Signal References 73
W
O Wiring Diagram 85
D Outdoor Air Suitable for Free Cooling 29
Damper Operation During Free Cooling 29 Overview 3
Data 11
Demand Control Ventilation 32 P
E Parts and Kits 36
Phase - Voltage Detection 37
Economizer 29
Economizer Checkout 30 Q
Enabling Economizer and Settings 29
Enthalpy Set Point 30 Quick Start Guide 84

F S
Firmware Update 7 Saving and Loading USB Profile 8
Free Cooling Compressor Lockout Mode 29 Saving and Loading User Profile 8
Free Cooling Damper Maximum Position 30 Service 20
Service Relays 38
H Settings 22
Setup 15
Heart Beat LED Indicators 4 SmartWire™ 4
Start-Up Procedure 3
I Status Messages 6
System Status Display 5
ICON Setting 71 System Status Screen 5
Inputs/Outputs 3 System Status Screen
88

You might also like