05 - Test-Run in High Speed
05 - Test-Run in High Speed
05 - Test-Run in High Speed
1) Connect power wire extends from car and hoistway with wiring in control box and field panel.
2) Adopt cable tie to fix and collate power wire.
Inspection Simplex L1 L2 L3 L4
-------00000088------
1 Floor 0.00m/s
Door locked F1
F3
F2
ENS ENTER
Monitor No. 0 L1 L2 L3 L4
Err.Code 11
Fault Record Floor 3 F1 F2
ENS ENTER
Door locked
8) After adjusting TOCI and COP to be NORMAL state, change control box switch into INSPECTION
state.
9) Implement up/down running, determine whether motor direction and speed etc. are normal.
; if error occurs, utilize error code to take measures
D1 D2 D3 D4
Func.Select L1 L2 L3 L4
---------------------------
Call Func
Shaft Teach F1
F3
F2
ENS ENTER
3) According to set parameter, make the car move to the lowest floor, and then move to the top floor.
Floor height indicates on SVT, “Shaft mode” occurs in running.
After finishing floor height measuring, convert Inspection mode into Normal mode.
After open/close door for 1 time, convert into Normal.
If there is abnormal action, it will stop automatically, and failing information for this item will occurs.
When the floor height measuring is finished, interlayer distance and overall distance in Monitor
Shaft data.
4) Utilize SVT to register destination floor. And determine whether the car run normally.
D1 D2 D3 D4
Func.Select L1 L2 L3 L4
---------------------------
Call Func
Shaft Teach F1
F3
F2
ENS ENTER
5) If there is the abnormal in the system, please refer to error code to take measures.
code Err. content Possible reason analysis
02 Door does not act in Safety circuit acts, but door contact point does not act, and
running determine the action state of door contact point.
03 Upper limit switch In high-speed mode, upper/lower limit switch acts at the
damaged (does not act) same time, but the top floor of the car can not run.
Determine the action state of upper limit switch.
04 Lower limit switch In high-speed mode, upper/lower limit switch acts at the
damaged (does not act) same time, but the lowest floor of the car can not run.
Determine the action state of lower limit switch.
05 Door can not be opened After sending output signal, if the door does not open
about 15s, determine mechanical/electric contact point of
door at hoistway side.
06 Door can not be closed After sending output signal, if the door does not close
about 15s, check CLS action state.
08 CANBUS If there is communication obstacle
communication is ; Determine terminal impedance.
wrong ; Determine car control panel SM-02 state.
19 Door position control In Normal state, if door is opened or closed completely for
fault more than 15s.
20 Anti-slip fault In automatic operating, if the level can not be found out
after time is set by parameter F62.
21 Motor overheat Determine the output signal of motor overheat.
23 Exceed allowed speed If speed feedback exceeds 0.1s than allowed speed,
(overspeed) -.if set speed is under 1m/s:
; allowed speed =set speed +0.25m/s
-. if set speed is over 1m/s:
; allowed speed =set speed *1.25
-. Allowed maximum speed < rated speed *108%
If car runs to final floor (the top/the lowest floor) in
0.8m/s2 speed, feedback value is over 0.1s continuously.
24 Under allowed speed If Feedback speed is under allowed speed for continuous
(Under speed) 0.5s
-.if set speed is under 1m/s:
; allowed speed =set speed -0.25m/s
-. if set speed is over 1m/s:
; allowed speed =set speed *0.5
27 Upper level sensor is in Upper level sensor does not start after high-speed running
fault stops,
If upper level sensor’s starting is larger than maximum
effective protection distance or maximum ineffective
protection distance, please report to fault 27.
If flat plate’s length is shorter than 300mm: maximum
effective protection distance for starting = 300mm x 4
times
If flat plate’s length is longer than 300mm: maximum
effective protection distance for starting = flat plate’s
length x 4 times
The top floor is lower than 3: maximum ineffective
protection distance for starting = height of the top floor x
1.5 times
The top floor is higher than 3: maximum ineffective
protection distance for starting = height of the top floor x
2.5 times
28 Lower level sensor is in Lower level sensor does not start.
fault If lower level sensor’s starting is larger than maximum
effective protection distance or maximum ineffective
protection distance, please report to fault 28.
If flat plate’s length is shorter than 300mm: maximum
effective protection distance for starting = 300mm x 4
times
If flat plate’s length is longer than 300mm: maximum
Unpublished Work Copyright © OTIS Elevator Company
IRIS1 NV
OTIS - SIGMA Date : 2011. 04. 10
FIELD ENGINEERING Page : 0 - 6 / 8