Example Assignment 2
Example Assignment 2
Rémi Dhédin
15 October 2020
Assignment 2, K7015B Connection between gable beam and column
Problem
The assignment aim is to design a connection between 2 wood beams as follow:
Lc/c
With : 𝐿𝑐/𝑐 = 6𝑚 , ℎ = 6 𝑚, 𝑞𝑑,𝑟𝑜𝑜𝑓 = 3,05 𝑘𝑁. 𝑚−2 , 𝑞𝑑,𝑤𝑎𝑙𝑙 = 0,74 𝑘𝑁. 𝑚−2
Design will be made following EN 1995 recommendations linked to the Swedish national annex (EKS 10).
In this assignment, glued laminated timber resistance class G30c will be used. Compression properties
are:
𝑓𝑐,0,𝑘 = 24,5 𝑀𝑃𝑎 and 𝑓𝑐,90,𝑘 = 2,5 𝑀𝑃𝑎
I. Load’s way
1. Wind loads
In this part, wind loads only will be firstly considerate.
Wind is blowing on a wall of 60 m by 6 m. Wind stabilising system is only in the gable wall. If intermediary
structures are considered, these ones are not equipped with this system. Thus, they have no resistance
to the wind load, and all loads are distributed in the two gables structures. That give:
𝐿ℎ𝑎𝑙𝑙
𝑞𝑑,𝑤𝑖𝑛𝑑,𝑔𝑎𝑏𝑙𝑒 = 𝑞𝑑,𝑤𝑎𝑙𝑙 × 2
= 22,2 𝑘𝑁. 𝑚−1 , the loads in red on Figure 2
C
B
𝛼
𝛽
A D
ℎ
Static equations on beam 1 give: 𝑅1,𝐵,𝑤𝑖𝑛𝑑 = −𝑞𝑑,𝑤𝑖𝑛𝑑,𝑔𝑎𝑏𝑙𝑒 = −68,95 𝑘𝑁, the node B is
2.cos (𝛼)
considered as a ball joint.
Then this load is transfer by beam 2 to beam 3 (𝑁2,𝑤𝑖𝑛𝑑 = 68,95 𝑘𝑁)
Considering that all the wind load is supported by the wind stabilizing system, means that compression in
beam 2 is zero in left part of node C (worst case). Static equations on node C as a ball joint give:
cos(𝛼) cos(15)
𝑁3,𝑤𝑖𝑛𝑑 = 𝑁2,𝑤𝑖𝑛𝑑 = 68,95 × = −107,6 𝑘𝑁
cos(𝛽) cos(51,8)
𝑁4,wind = 𝑁2,𝑤𝑖𝑛𝑑 . sin(𝛼) + 𝑁3,𝑤𝑖𝑛𝑑 . sin(𝛽) = 68,95. sin(15) − 107,6. sin(51,8) = −66,6 𝑘𝑁
2. Roof loads
To design the connection, it is now important to add the load from the snow and the roof. If it is considered
a space of 6 meters between columns in all direction, and because the beam is at the end of the hall, the
gable beam will support half of the roof load exerted on the 6 m span (same as considering no roof
stiffness, a secure simplification for the gable beam). So, the load on the gable beam is 𝑞𝑑,𝑟𝑜𝑜𝑓,𝑔𝑎𝑏𝑙𝑒 =
3 × 𝑞𝑑,𝑟𝑜𝑜𝑓 = 9,15 𝑘𝑁. 𝑚−1.
Reactions on each columns is calculated with Autodesk Robot Structural Analysis Professional
(https://www.autodesk.com/products/robot-structural-analysis) and are given in Figure 4.
So, the load in column (beam 4) because of snow and roof is:
𝑁4,𝑟𝑜𝑜𝑓 = 64,2 𝑘𝑁
𝑁 65400
That give 𝐴 ≤ 13,4 ⇒ 𝐴𝑐𝑜𝑙𝑢𝑚𝑛 ≥ 15,6
= 4192 𝑚𝑚2
With: (1) Member is on discrete support, and 𝑙 ≤ 400 𝑚𝑚, 𝑘𝑐,90 = 1,75
𝑓𝑐,90,𝑘 2,5
(2) 𝑓𝑐,90,𝑑 = 𝑘𝑚𝑜𝑑 𝛾𝑀
= 0,8 1,25 = 1,6 𝑀𝑃𝑎
(3) 𝐴𝑒𝑓 = 𝑙 + 2 × 30
𝑁 65400
That give: 𝐴𝑒𝑓 ≥ 𝑘 = 1,75.1,6 = 23357 𝑚𝑚2
𝑐,90 𝑓𝑐,90,𝑑
A 165x115 mm2 connection area gives 𝐴 = 18975 𝑚𝑚2 > 4192 and 𝐴𝑒𝑓 = 28875 𝑚𝑚2 > 23357, so
this cross section is good.
So, with this contact area, column beam width is 115 𝑚𝑚 and gable beam width 165 𝑚𝑚 for pressure
connection resistance.
165 mm
Gable beam
Column
225 mm
115 mm
Because of screws on both side, fasteners will be only axially loaded. (see Figure 6). Force taken by both
√2
sides will be 𝐹𝑟𝑖𝑔ℎ𝑡 = 𝐹𝑙𝑒𝑓𝑡 = 2
∗ 𝐹 = 46,24 𝑘𝑁
𝐹𝑙𝑒𝑓𝑡
𝐹𝑟𝑖𝑔ℎ𝑡
§8.7.1 (2) EN 1995-1 gives different failure modes to check. Because screws are not used with steel plates
and is not in compression only the following failure modes must be checked:
• the withdrawal failure of the threaded part of the screw
To design resistance of one screw in this failure mode, it need to calculate before the penetration length
√2
of the threaded part: 𝑙𝑒𝑓 = (𝑙 − 30) = 117,57 𝑚𝑚
2
1
And the angle between the screw axis and the grain direction is 𝛼 = tan−1 (sin(15°)) = 75,5
So finally, the load resistance per screw is the minimum value of the three values above: (withdrawal
failure of the threaded part of the screw)
𝐹𝑡,𝑑
= 5,43 𝑘𝑁/𝑠𝑐𝑟𝑒𝑤
𝑛𝑒𝑓
So, the gable beam for the connection must be at least 335 mm high, that lead to choose a 360 mm high
beam. In real design conditions, the beam high may be upper because of loads applying in the span (This
is not studying in this assignment).
Conclusion
To support the loads, the connection must be as follow: (dimensions are in mm and not in right
proportions)