The document provides instructions for installing and wiring a DNFT lubrication monitor on a compressor. It describes attaching the DNFT to the divider valve magnet housing, adjusting it for proper operation, purging air from the system, and wiring connections depending on the DNFT model. Wiring must be properly grounded for reliable operation.
The document provides instructions for installing and wiring a DNFT lubrication monitor on a compressor. It describes attaching the DNFT to the divider valve magnet housing, adjusting it for proper operation, purging air from the system, and wiring connections depending on the DNFT model. Wiring must be properly grounded for reliable operation.
DNFT Installation remove magnet housing. Do not remove
magnet, spring, or spacer from magnet Figure: Typical DNFT Magnet Assemblies housing. 2. Remove piston enclosure plug from the end of desired divider valve. The DNFT installs on any of the divider valves of the divider block. The DNFT requires the correct magnet assembly to match the divider valve manufacturer. NOTE: Do not install a DNFT on Lincoln divider valves with cycle indicator pins. 3. If applicable, verify O-ring or metal gasket is in place on magnet housing. Thread magnet housing into the end of the divider valve. Torque to 15 lbs x ft (20 N•m) maximum. 4. Slide DNFT all the way onto hex of magnet housing. Torque Allen set screws on the hex 1 Trabon Style O-ring Seal 7/16-20 of magnet housing to 25 lbs x inch, (2.8 N•m) 2 Trabon Metal Gasket Seal 7/16-20 (1994 or earlier) maximum. 3 Lincoln O-Ring Seal 7/16-20 Extended Nose 5. The LED on the DNFT indicates each divider valve cycle to allow lubricator pump Figure: Typical DNFT Installation adjustment for Ariel recommended cycle time and oil consumption. If the LED fails to blink during compressor operation or by manually pumping oil into the divider valve, then the DNFT requires adjustment. 6. The divider valve must cycle during DNFT adjustment. To cycle, either run the compressor or manually pump oil through the distribution block with a purge pump. 7. To adjust, slide DNFT all the way onto hex of magnet housing. Tighten Allen set screws to 1 Divider Valve Piston 25 lbs x inch (2.8 N•m) maximum. A blinking 2 Magnet LED indicates correct adjustment. If the LED fails to blink with divider valve cycling, slide 3 Magnet Housing DNFT back on the hex of the magnet housing 4 Set Screws (2) in 1/16" increments until it does. 5 LED 6 Control Housing 8. Make all conduits and connections 7 Wire Leads appropriate for area classification. Insulate 8 O-Ring unused wires from the ground, other wires, and the case. Support conduit and fittings to 9 Divider Valve avoid bending the magnet housing. 10 Piston Enclosure Plug
compressor start-up, purge all air from the divider block lubrication system with a purge pump. NOTE: When installing multiple DNFTs, wire each to a separate alarm circuit of the control panel, annunci- ator, or PLC to simplify lubrication system and DNFT troubleshooting. Always secure the green ground wire to "earth ground" in the control panel. Do not ground to electrical conduit or skid. Improper grounding can result in unreliable monitor operation. Figure: A-10754 Programmable DNFT Wiring Connections for Unit in Operation
Figure: A-10753 and A-10772 DNFT Wiring Connections for Unit in Operation
Figure: A-20513 24 VDC Programmable DNFT Wiring Connections for Unit in Operation