Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

800 Series Data Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 60

GE Zoneline packaged terminal air conditioners

2007 contract sales architects and engineers data manual

Quick Reference
Full Specs on pages 54 and 55 ALL UNITS REQUIRE POWER CONNECTION KIT Power Connection Kit determines resistance heat output 7000 Btuh units do not activate 5 KW resistance heater 2800 Series Cooling with Electric Heat
MODEL NUMBER
AZ28E07DA* AZ28E09DA* AZ28E12DA* AZ28E15DA* AZ28E07EA* AZ28E09EA* AZ28E12EA* AZ28E15EA*

Dry Air 25 2800 Series Cooling with Electric Heat


EER
12.7/12.7 12.0/12.0 11.5/11.5 10.2/10.2 12.7 12.0 11.5 10.2

COOLING (Btuh)
7100/6900 9300/8900 11800/11500 14600/14300 7100 9000 11700 14600

MODEL NUMBER
AZ28E07DAP AZ28E09DAP AZ28E12DAP AZ28E07EAP AZ28E09EAP AZ28E12EAP

COOLING (Btuh)
6800/6600 8600/8400 11200/11000 6800 8600 11200

EER
12.1/12.1 11.5/11.5 11.0/11.0 12.1 11.5 11.0

3800 Series Heat Pump with Backup Electric Heat


MODEL NUMBER
AZ38H07DA* AZ38H09DA* AZ38H12DA* AZ38H15DA* AZ38H07EA* AZ38H09EA* AZ38H12EA* AZ38H15EA*

COOLING (Btuh)
7100/6900 9000/8800 11700/11500 14600/14300 7100 9000 11700 14600

EER
12.7/12.7 12.0/12.0 11.5/11.5 10.0/10.0 12.7 12.0 11.5 10.0

REvERSE CyCLE BTUH


6400/6200 8400/8200 10900/10700 13400/13200 6400 8400 10900 13400

COP
3.6/3.6 3.6/3.6 3.4/3.4 3.2/3.2 3.6 3.6 3.4 3.2

2800 and 3800 Series Control Panel

5800 Series Heat Pump with Backup Electric Heat


MODEL NUMBER
AZ58H07DA* AZ58H09DA* AZ58H12DA* AZ58H15DA* AZ58H07EA* AZ58H09EA* AZ58H12EA* AZ58H15EA*

COOLING (Btuh)
7200/7000 9300/9050 11800/11600 14700/14400 7300 9300 11800 14700

EER
13.0/13.0 12.0/12.0 11.7/11.7 10.3/10.3 13.0 12.0 11.7 10.3

REvERSE CyCLE BTUH


6400/6200 8400/8200 10900/10700 13800/13800 6400 8400 10900 13800

COP
3.7/3.7 3.6/3.8 3.4/3.4 3.2/3.2 3.7 3.6 3.4 3.2

5800 Series Control Panel

*Dual rated 230/208-volt units are shown with ratings separated by /. Units with single rating are 265-volt units.

Power Connection Kits


20/208-Volt Line Cord Connection Units
Line Cord Kit
RAK15 RAK20 RAK0

ge.com 20/208-Volt Sub-Base and Direct Connected Units


Min. Circuit Protection (Amps)
15 20 0

Electric Heat BTUH


8600/7100 11700/9600 170100/1900

Electric Heater Watts


2550/2090 450/2820 5000/4090

Electric Heat Amps


11.6/10.6 15.5/14.1 22./20.

Sub-Base
RAK204D15P RAK204D20P RAK204D0P

Direct Connection Kit


RAK4157 RAK4207 RAK407

Electric Heat BTUH

Electric Heater Watts

Electric Heat Amps


11.6/10.6 15.5/14.1 22./20.

Min. Circuit Protection (Amps)


15 20 0

8600/7100 2550/2090 11700/9600 450/2820 170100/1900 5000/4090

Electric Heat Amps include electric heater and fan motor current draw. Each Line Cord Kit has an integral Leakage Current Detection and Interruption (LCDI) or Arc Fault Current Interrupter (AFCI) device as required by National Electrical Code (NEC) and Underwriters Laboratories (UL) for units manufactured after August 1, 2004.

Electric Heat Amps include electric heater and fan motor current draw. Units connected through sub-base do not require a LCDI or AFCI device since they are not considered to be line-cord connected. Each 20/208-volt sub-base kit consists of sub-base with appropriate receptacle for minimum circuit amperage, chaseway to route power connector from sub-base to chassis, wiring to connect sub-base to building wiring and a short line cord with 9-pin connector to connect to chassis and plug into receptacle in sub-base. Short sub-base line cord may not be used without sub-base. Junction box for 20/208-volt chassis must be purchased separately. RAK4002A for 2800 and 800 series units RAK4002B for 5800 series units.

265-Volt Sub-Base and Direct Connected Units


Sub-Base
RAK204E15 RAK204E20 RAK204E0

Power Connection Kit


RAK5172 RAK5202 RAK502

Direct Connection Kit


RAK5157 RAK5207 RAK507

Electric Heat BTUH


8600 11700 17000

Electric Heater Watts


2550 450 5000

Electric Heat Amps


9.6 1.0 18.9

Min. Circuit Protection (Amps)


15 20 0

Electric Heat Amps include electric heater and fan motor current draw. 265-volt units are to be permanently connected in compliance with National Electrical Code and local codes and have a factory-installed junction box on the chassis. Each 265-volt sub-base kit consists of sub-base with appropriate receptacle for minimum circuit amperage, chaseway to route power connector from sub-base to chassis and wiring to connect sub-base to building wiring. 265-Volt Power Connection Kit must be ordered separately.

Important
Essential Elements Ordering Overview
20/208-volt line cord connected units order line cord kit 20/208-volt sub-base connected units order sub-base and junction box 265-volt units order sub-base and power connection kit

Zoneline Chassis Nomenclature


The Zoneline chassis is identified by a model number defining the type of unit, cooling capacity, electrical information and optional features included on the unit. When specifying or ordering the Zoneline chassis, the use of this nomenclature will assure receiving the correct unit.

EXAMPLE
A Z 5 8 H 1 2 D A D
Chassis series Zoneline packaged 28=deluxe line cool/ electric heat terminal 8=deluxe line heat pump chassis 58=premium line heat pump Unit type E=cooling with electric resistance heat H=heat pump with electric resistance heat Nominal cooling capacity 07=7,000 BTUH cooling 09=9,000 BTUH cooling 12=12,000 BTUH cooling 15=15,000 BTUH cooling Universal power connection

Special Features B=base unit C=corrosion treated D=internal Voltage/Phase/ condensate Frequency removal (ICR) D=20/208-Volt, system (heat single-phase, 60 Hz pump models E=265-Volt, single-phase, only) (not for 60 Hz coastal areas) P=Dry Air 25 (2800 Series only)

The Zoneline 2800, 800 and 5800 Series have incorporated changes suggested by customers, along with enhancements by GEs Technology Team and changes necessary to meet new UL and NEC requirements.
L shaped condenser coil. The Partial Open Vent Air feature was a specific request by a customer. Heat Sentinel is an enhancement developed by GEs Technology Team to help lodging professionals welcome their guests with a moderate-temperature room and to help lower cooling costs. Devices have been added on cord-connected units to protect against injury from unsafe power cords. See the Features and Benefits section for in-depth explanation of these changes and the industry-leading features of GE Zoneline retained from the previous series.

The Deluxe 2800 Series Zoneline Models Includes The Dry Air 25 Models Which Remove 25% More Moisture Than Other Zoneline Models.
When the cold air from the evaporator comes in contact with the re-heat section of the heat pipe, the heat that was removed by the pre-cool section is added back to the air and the refrigerant in the heat pipe condenses and flows back to the indoor coil. The air discharged into the room by this process is much drier, creating a more comfortable room condition.

The Newest Innovation from GE


The Dry Air 25 Models center around GEs exclusive use of the patented Dinh Dehumidifier Heat Pipe from Heat Pipe Technology, Inc. This innovative NASA spin-off technology enables Dry Air 25 to remove 25% more moisture from the air than other leading manufacturers packaged terminal air conditioners. This helps maintain room comfort at a higher room temperature, reducing operating costs. The Dry Air 25 keeps a room cool and dry, and this is the most important benefit when it comes to the occupant of the room hotel guests, apartment residents, students. In a hot, humid climate, getting away from the humidity is just as important as the heat, and the Dry Air 25 is the perfect solution. The dehumidification of the Dry Air 25 has been verified by the same ARI test conditions that standard units are rated under. A list of customers using Dry Air 25 is available from GE.

Deluxe Dry Air 25 Models


Cooling With Resistance Heat
Remove 25% More Moisture than other Zoneline Models, up to 2.7 Additional Gallons Per Day Cool and Dry Air in Less Time than Standard Zoneline Models Heat Pipe is a Separate Sealed Refrigerant System No Mechanical Parts No Special Maintenance Required Helps Maintain Lower Relative Humidity In Rooms Maintains Comfort at Slightly Higher Room Temperatures Reduces Operating Costs Provides Comfort Without Overcooling Corrosion Treatment is Standard Excellent Choice for Humid Climates Available in 7000, 9000 and 12000 BTU Sizes The Dry Air 25 system, a heat pipe, is a hermetically sealed heat transfer surface installed in a saddlebag configuration around the indoor (evaporator) coil of the Zoneline. This coil arrangement will transfer heat from the front coil of the saddlebag to the rear coil without power consumption. This assembly uses R-22 as the refrigerant and is not connected to the regular Zoneline refrigerant circuit. As warm, humid air is pulled through the pre-cool (front) section of the heat pipe, the heat removed from the air is absorbed by the refrigerant, causing the refrigerant to change to a gas and flow to the re-heat (rear) section of the heat pipe. The air leaving the pre-cool section of the heat pipe is cooler and at a higher relative humidity level than the room air. The pre-cooled air is further cooled as it passes through the evaporator; consequently, the relative humidity increases allowing the evaporator coil to remove more moisture.
4

COMPARISON OF DRY AIR 25 DEHUMIDIFICATION*


GE Dry Air 25 GE 2500 Series Zoneline Amana Carrier
*Based on 12,000 BTU Units. NOTE: The Dry Air 25 models include all features of the 2800 series.

Removes More Moisture

25%

Table of Contents
Front Cover Mini Specs 2800, 800 and 5800 Series Mini Specs Power Connection Kits and Nomenclature The 2800/800/5800 and Dry 25 Table of Contents Introduction The Zoneline System Features and Benefits Features Table Features and Benefits Auxiliary Control Switches Central Desk Control Remote Thermostat Control Heat Pumps and Energy Savings Installation and Dimensions Application Comments Case Dimensions Wall Case/Sub-Base Installation Condensate Disposal Systems Ducted Installations Exterior Grilles Product Data Electrical Connection Essential Elements Ordering Overview Maximum Connected Load Cooling/Heat Pump Performance Data Latent System Capacity Normal Yearly Operating Data Schematics Product Specifications Suggested Bid Form Specifications Zoneline Chassis Nomenclature/Receptacles/Sub-bases Specifications Complete Accessory List General Installation Suggestions Warranty Alphabetical Index Back Cover 51-5 54 55 56 57-58 58 59 60 42 4 44 45 46 47 48-50 20 21 22- 4-6 7-9 40-41 8 9-11 12-1 14 15-17 18-19 1 2  4 5 6 7

ge.com

Important Notice
Equipment used as a primary source for heating or cooling is an integral part of the building in which it is installed. Proper application is essential for satisfactory performance over a wide range of operating conditions. It is strongly recommended that a professional engineer determine proper application. If this unit is a replacement unit, its specifications and performance may differ from those of the unit it is replacing. For that reason, we again strongly recommend that a professional engineer determine proper application.
5

Introduction
This manual is designed to provide product, performance and application information to our customers and their architects and engineers for use in selection and design of a zonal comfort control system utilizing GE Zoneline Packaged Terminal Air Conditioners (PTAC) and Packaged Terminal Heat Pumps (PTHP). GE Zoneline PTACs and PTHPs are self-contained units designed for through-the-wall installations in hotels, motels, apartments, hospitals, nursing homes, add-on rooms and many other installations. Zonelines provide individual room or zone control in both cooling and heating operation. There is a model for practically every application, ranging in cooling capacity from 7,100 to 14,700 BTUH and heating capacity from 6,400 to 1,400 BTUH in heat pump operation. See pages  and 55 for resistance heaters available. Zoneline offers a two-tier lineup: the Deluxe Line and the Premium Line. The Deluxe Line consists of the 2800 Series with electric resistance heat, the 2800 Series Dry Air 25 Models with enhanced dehumidification for hot and humid climates and the 800 Series heat pump. The 800 Series heat pump features reverse cycle defrost and simultaneous supplemental resistance heat, when needed, to maintain room comfort. The Premium Line features the 5800 Series heat pump with reverse cycle defrost and supplemental resistance heat, when needed, to maintain room comfort, plus tactile touch controls with digital display and standard corrosion protection.

Premium Line Standard Features:


All the Standard Features of the Deluxe Line Plus: Two fan motor system with Indoor Cross Flow Blower for quieter operation Digital Controls LED Temperature Display Easy Temperature Selection Tactile Touch Pad Unit Diagnostics Standard Corrosion Protection Treatment

Premium Line Optional Features:


Internal Condensate Removal (Not for use in seacoast or corrosive areas)

Advantages of the GE Zoneline System:


Flexible Application May be installed from flush to finished floor to " from the ceiling 7,100 to 14,700 BTUH units in same physical size Deluxe 2800 and 800 Series may be ducted to condition more than one room Compatible with Class 2 remote thermostat control Compatible with 2 wire CDC or many Energy Management systems Economical Installation No ductwork necessary No mechanical equipment rooms or pipes required for heating/cooling units Replacement units fit existing 42"-wide by 16"-high wall cases Quiet Operation Indoor double cut-off scroll: two fan motor 2800 and 800 Series units Indoor cross-flow blower: 2 fan motor 5800 Series units Energy-Saving Operation Units in unoccupied areas may be turned off Designed for efficient cooling operation EERs from 10.0 to 1.0 Efficient heat pump units COPs from .2 to .6 Extended heat pump operation without sacrificing room comfort Ease of Maintenance Permanently lubricated fan motors Upfront lift-out interchangeable filters Air Discharge area is easily accessed for cleaning Slide-out chassis for easy access for cleaning or if service is required Reverse Cycle Heat Pump Operation Both the 800 and the 5800 Series heat pumps utilize the unique GE PTAC heat pump operation to ensure a comfortable room. The logic used by the units is the same logic used by central system heat pumps to provide greater savings.

Deluxe Line Standard Features:


Universal Heaters 2 Fan Motors Heat Sentinel L Coil Design Condenser Locked-In-Place Control Knobs -Position Vent Door Freeze Sentinel Indoor Coil Frost Control Central Desk Control Interface Remote Thermostat Control Interface Random Restart Electronic Temperature Limiting Smart Fan Fan Cycle/Continuous Control Transfer Fan Interface Room Occupancy Sensor Interface Reverse Cycle Defrost and Simultaneous Supplemental Resistance Heat on Heat Pumps Quick Heat Recovery

Deluxe Line Optional Features:


Corrosion Protection Internal Condensate Removal (on 800 Series Heat Pump without Corrosion Protection)
NOTE: Dry Air 25 models include all the standard features of the 2800 Series plus standard corrosion protection.

The Zoneline System

ge.com

The typical Zoneline installation consists of the wall case (or sleeve), chassis, and exterior grille. Some installations may use a sub-base for support of the unit or for ease of electrical connections. Each of the components should be the standard products offered by GE or, in the case of the exterior grille, approved by GE Applications Engineering. Use of components not specifically designed or approved for use with the Zoneline can result in unsatisfactory operation and can be the cause of failure not covered by the warranty.

Components of the Zoneline System Typical Installation (Deluxe Series shown)


Chassis Room Cabinet Wall Case RAB71A (Steel-Insulated) RAB77 (SMC Molded) Wall Case Options (See page 22)

RAG67 (shown) Grill Options (See page 40)

Power Connection Kit (required on all units) Line Cord Kit shown See pages 42-4

Power Supply Cord

Optional Accessories of the Zoneline System


Chaseway

RAK204D20P Sub-Base (shown) RAK6052 Duct Adapter (For Deluxe Series)

Power Supply Cord (included with 208v/20v sub-bases)


See pages 2 and  for information on electrical sub-bases and chaseway. See pages 7-9 for information on ducted installations.

RAK601/602 (For Deluxe Series) Duct Extension, Register and Trim Flange

Zoneline Features
AZ 2800
Enhanced Dehumidification Dry Air 25 Cooling EER Range (20 Volts/265 Volts) Heating COP Range (20 Volts/265 Volts) Heat Source Electric Resistance Heat Heat Source Heat Pump With Selectable Full Time or On Demand Simultaneous/ Supplemental Resistance Heat Staged Heating Universal Heater UPC* Unit Controls Electronic Temperature Selection (Slews Up & Down) with Digital Display Unit Diagnostics Highly Featured Microprocessor Controls Electric Resistance Heat Lock-Out (above 46F) Automatic Emergency Heat Heat Pump Defrost System High Temperature Operation Protection Quick Heat Recovery Temperature Boost Service Indicator Fan Motors Permanently Lubricated 2-Speed Outdoor Fan Indoor Fan Speed Selections HIGH/LOW Fan Only Setting HIGH/LOW Fan Cycle Switch Constant-Run Fan Rotary Compressor Automatic Compressor Restart Delay Freeze Sentinel Heat Sentinel Indoor Coil Frost Control Transfer Fan Connections 7-Step Electronic Temperature Limiting Remote Control Capability with Wall Mounted Thermostat Central Desk Control Capability Energy Management System Interface with Load Shedding Option Reversible Indoor Air Louvers 40/50 Up-Front Filters Easy-Clean Air Discharge Area Concealed Manual Vent Control Ducted Installation Capability Corrosion Protection (Standard on Dry Air 25) Internal Condensate Removal (ICR) (Factory Installed Option. Cannot be used in Corrosion Areas.)
*UPC Universal Power Cord Connection (See pages 42 and 55). 265-volt units must be connected in a manner to meet National Electrical Code and all local codes.

AZ 800
N/A 10.0 - 12.7 .2 - .6

AZ 5800
N/A 10.2 - 1.0 .2 - .6

Optional 10.2 - 12.7 N/A Standard

Standard Rotary Knobs Standard 2 Standard Standard Standard Smart Fan Selectable Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard RAK6052 Optional N/A

Standard  Stage Standard Rotary Knobs Standard Standard Standard Reverse Cycle Standard Standard Selectable 2 Standard Standard Standard Smart Fan Selectable Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard RAK6052 Optional Optional

Standard  Stage Standard Touch Pad Standard Standard Standard-Plus Standard Standard Reverse Cycle Standard Standard Selectable Temp Display Blinks 2 Standard HIGH/LOW/AUTO Standard Smart Fan Selectable Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Optional

Features and Benefits


Standard Physical Dimensions
GE has maintained the same dimensions since 1961 42" wide x 16" high x 1-/4" deep Replacement of older units is made easy.

ge.com Reverse Cycle Heat Pump Defrost System


Standard on all Zoneline 800 and 5800 Series heat pumps. Enables heat pump to operate at lower temperatures when other systems switch to more expensive electric resistance heat. See pages 18 and 19 for discussion of heat pump operation and defrost systems.

Weather-Protected Electrical Components


Vital electrical components are protected from the weather by locating them on the indoor side of the weather barrier.

Weather-Resistant Superseal
Properly installed unit in undistorted case keeps air leakage to a minimum. 7 CFM air infiltration with 25 MPH wind on non-ICR units 10 CFM on units with ICR. Industry specification is 19 CFM of air infiltration.

High Temperature Heat Pump Operation Protection


Automatically protects the compressor if heat pump is operated with high outdoor temperatures. Power to the outdoor fan is turned off if the indoor coil gets too hot during heat pump operation to prevent damage to the compressor.

Heater Sizes to Meet Room Requirements


All units are equipped with a universal heater the resistance heat output is determined by power connection kit. 20/208-volt Line Cord Connected Units 2.55/2.09 KW with RAK15 15-amp circuit; .45/2.82 KW with RAK20 20-amp circuit; 5.0/4.09 KW with RAK0 0-amp circuit. 20/208-volt - Sub-Base Connected Units 2.55/2.09 KW with RAK204D15P 15-amp circuit; .45/2.82 KW with RAK204D20P 20-amp circuit; 5.0/4.09 KW with RAK204D0P 0-amp circuit. 265-volt 2.55 KW with RAK5172 15-amp circuit; .45 KW with RAK5202 20-amp circuit; 5.0 KW with RAK502 0-amp circuit.

Quick Heat Recovery Heat Pump Units


When the unit operation is changed from STOP or COOL to HEAT, the electric resistance heaters are used to warm the room to the thermostat set point. This provides faster room temperature increase for greater guest comfort.

Unit Diagnostics
The 5800 Series has a dip switch that activates each of the various components of the unit to operate briefly. This enables the technician to determine if individual components are functioning properly.

Service Indicator
On the 5800 Series, if the microprocessor detects a compressor malfunction, the digital temperature display will blink. If the malfunction occurs during cooling operation, the indoor fan will continue to operate. If the compressor malfunctions in heating mode, the unit will automatically switch to resistance heat to maintain room temperature set point. GE Service should be called to check the Zoneline.

Unit Controls
2800 and 800 Series locked-in-place rotary knobs for temperature and operation selection. 5800 Series touch pad controls with digital readout of temperature set point.

Fan Motors Permanently Lubricated


All units have two fan motors for quiet operation and maximum operating efficiency. Motors are permanently lubricated to reduce maintenance and totally enclosed to keep dirt and water out of the motor windings.

Highly Featured Microprocessor Controls


Microprocessor controls are programmed to interface with the temperature sensors to maximize comfort conditions for the room occupant and provide outstanding features. Thermistors are used to sense small changes in temperature to give excellent room control and allow the microprocessor to monitor and react to changing conditions.

2-Speed Outdoor Fan


The unit automatically selects the most efficient speed for the outdoor fan. The operating sound level is lower when the outdoor fan can operate in low speed yet there are situations where it must operate in high speed. The unit changes the fan speed automatically.

Electric Resistance Heat Lock-Out


To maximize the savings of the heat pump operation, the Zoneline heat pumps do not utilize the resistance heater when the outdoor temperature is above 46F during normal operation. The resistance heat is used in the Quick Heat Recovery feature.

Indoor Fan Speed Selections HIGH/LOW


Unit may be operated in HIGH HEAT or LOW HEAT or HIGH COOL or LOW COOL.

Automatic Emergency Heat


Automatically uses electric resistance heat if the heat pump output is not sufficient to maintain selected room temperature.
9

Features and Benefits


Fan-Only Setting HIGH/LOW
The unit provides the option of selecting either HIGH or LOW speed for Fan-Only operation.

Indoor Coil Frost Control


Prevents indoor coil from freezing and causing complaints due to lack of cooling. Frost can form on the indoor coil when the unit is operated in cooling when outdoor temperatures are low. The unit automatically shuts the compressor off until the indoor coil temperature warms to the point where frosting will no longer occur.

Fan-Cycle Switch SmartFan


Unique SmartFan allows unit to operate fan continuous in cooling operation and fan cycle in heating to provide better guest comfort. Eliminates complaint of cold air draft during heating operation. Eliminates need of changing fan-cycle switch seasonally. SmartFan settings are controlled by two dip switches on auxiliary control panel.

Transfer Fan Interface


24 VAC terminals are provided to operate a relay to control a fan mounted in a wall to move conditioned air into another space. The electrical power for the operation of the transfer fan itself is not provided by the Zoneline. Transfer fans and their controlling relays are field supplied.

Compressor Random Restart


In the event of a power failure, all compressors attempting to restart immediately when power is restored can result in a power surge that can cause another power interruption. The microprocessors in the Zonelines have a random restart logic system that prevents all units from starting at the same time.

Electronic Temperature Limiting


Seven independent programmable heating temperature limits and seven independent programmable cooling temperature limits. Eliminates need to reset the limits seasonally.

Rotary Compressor
Smoother operation for quiet, dependable service. GE has used rotary compressors since 1961.

Heating Temperature Limits


65 70 72 74 76 78 80

Highest Heat
85

Compressor Restart Delay


Zonelines are designed to provide a minimum of three minutes of compressor off time to allow refrigerant pressures to equalize before restarting to prevent compressor damage. Zonelines are also designed to provide a minimum of three minutes of compressor run time to prevent room occupant disturbance due to short-cycling of the air conditioner.

Lowest Cool
60 64

Cooling Temperature Limits


66 68 70 72 74 76

Limits are set by dip switches on auxiliary control panel.

Freeze Sentinel
Detects low room temperature and turns on heater to help protect against damage caused by freezing room temperature. Heater turns on at 41F and warms indoor thermistor temperature to 46F and shuts off. Freeze Sentinel may be turned off by dip switch on auxiliary control.

Remote Control Capability with Wall-Mounted Thermostat


See pages 15-17.

Central Desk Control Capability


See page 14.

Energy Management System Interface with Load Shedding Option


All units have a switch on the auxiliary control panel to allow the indoor fan to continue operating if the unit is connected to an Energy Management System that shuts off compressor or heater operation. By allowing the indoor fan to run when the heater or compressor is shut off by the Energy Management System, the guest is less likely to realize the operation of the unit has been altered. This helps reduce peak energy demand loads without disturbing the room occupant.

Heat Sentinel
The property owner may choose to activate the Heat Sentinel feature on the Zoneline. If the Heat Sentinel is activated and room temperature reaches 85F while the unit is in the STOP setting, the unit will automatically start in air conditioning operation and will shut off when the room temperature reaches 80F. This will help dehumidify the air and lower high temperatures so the guest will not be entering an extremely hot room.

Reversible Indoor Air Louvers


Allows air to be directed into room at 40 or 50 angle to provide better air distribution. Angle is changed by removing room front and screws holding louver in place, and rotating louver section.
10

Features and Benefits


Up-Front Air Filters
Two interchangeable up-front filters, easy to remove and reinstall, may be cleaned without opening or removing the room front. Clean filters by brushing, vacuuming or backflushing under faucet or shower head.

ge.com Corrosion Protection (Optional)


2800 and 800 Series units may be ordered with special protection to better withstand damage from salt air and salt water in seacoast areas. Corrosion protection is standard on the 5800 Series and on Dry Air 25 models. Heat Pump units with ICR are not available with corrosion protection and should not be installed in seacoast or corrosive environments. Units installed in corrosive areas should be examined and cleaned more frequently than normal installations.

Easy Clean Air Discharge Area


2800 and 800 Series units have an out-of-sight vertical protective screen over the indoor fan. This allows easy cleaning of air discharge area by simply removing room front and wiping clean. There is no screen directly below discharge louver to trap unsightly dirt and debris where it may be seen by room occupant.

Internal Condensate Removal (ICR)


See page 4 for a discussion of the Internal Condensate Removal system available on 800 and 5800 Series heat pumps.

Enhanced Dehumidification
Moisture removal is an important function of an air conditioner. People are more comfortable at higher temperatures when the humidity level is relatively low. Air conditioners operate with less energy consumption when the room temperatures are set higher. The GE Zoneline 2800 Series with the Dry Air 25 heat pipe application removes 25% more moisture than the base 2800 Series unit. The GE Zoneline Dry Air 25 chassis is the only PTAC available with the application of the patented Dinh Dehumidifier Heat Pipe under license from Heat Pipe Technology, Inc. Customers who are using the Dry Air 25 report a freshersmelling room as a result of the lower humidity levels, as well as lower operating costs.

Concealed Manual Vent Control


The -position manual vent door control may be closed, partially open or fully open.

Vent CFM High Speed


Unit 7000 9000 12000 15000 Full Open 50 70 75 75 Partial Open 40 45 45 45

Locking Door Kit


RAK802 A door with a lock that replaces the standard control cover door to prevent unauthorized changing of control setting is offered as an accessory.

CFM ratings at 20 volts and 265 volts. Greater amounts of air will be introduced if the room has an exhaust fan. An open vent door brings unconditioned outdoor air into the room, increasing heating and cooling costs. Positive vent door closure prevents accidental opening and unwanted air infiltration.

11

Auxiliary Control Switches


These switches are located behind the room cabinet under the control panel.

2800 and 800 Series


Switches Description Left Switches (1) ALL I2R (2) () (4) (5) (6) (7) (8) C: FAN H: FAN CLASS 2 LOAD SHED FREEZ S CONST FAN OCCUPIED Heat pump override Down Normal heat pump operation Up resistance heat only (800 Series only) Fan control for cooling operation Down Fan Continuous Up Fan Cycle Fan control for heating operation Down Fan Cycle Up Fan Continuous Remote Thermostat Mode Down Unit Control Up Remote Thermostat Load Shedding when connected to Central Desk Control System Down Fan shuts off with unit Up Fan under Smart Fan settings Freeze Sentinel Override Down Freeze Sentinel ON Up Freeze Sentinel OFF Constant Fan Down Fan runs normally Up Fan runs when unit is in STOP position Occupancy Sensor Mode Down Unit Control Up Occupancy Sensor Connected Cooling temperature limiting (See table at bottom of page) Heating temperature limiting (See table at bottom of page) Heat Sentinel switch Down Heat Sentinel OFF Up Heat Sentinel ON Heat Boost (800 series only) Down Heat Boost OF Up Heat Boost ON Auxiliary (2800 and 800 series)
UP DOWN

Right Switches TL1 TL TL4 TL6 (7) (8)

800 Series shown


2

ALLI R (All Electric Heat) (3800 Series models only) C: FAN CN (CoolingSmart Fan) H: FAN CY (HeatingSmart Fan) CLASS 2 (Remote Thermostat) LOAD SHEDDING (CDC) FREEZ Sen (Freeze Sentinel) CONST FAN (Constant ON Fan) OCCUPIED (Occupancy Sensor)

HIGH 4 5 COOL

UP DOWN

HEAT BOOST (3800 Series models only) Heat Sentinel TL1 (H) (Temp. Limit 1Heat) TL2 (H) (Temp. Limit 2Heat) TL3 (H) (Temp. Limit 3Heat) TL1 (C) (Temp. Limit 1Cool) TL2 (C) (Temp. Limit 2Cool) TL3 (C) (Temp. Limit 3Cool)

Cooling and Heating temperature limits are set independently, temperature limiting switches are in factory-set down position, except as noted.

Cooling Temperature Limits


Switches Up NONE 60 Switches Up 6 65
12

1 64 4, 6 70

1, 2 66 4, 5, 6 72

2 68 5, 6 74

2,  70 5 76

1, 2,  72 4, 5 78

1,  74 4 80

 76 NONE 85

Heating Temperature Limits

Auxiliary Control Switches


These switches are located behind the room cabinet under the control panel.

ge.com

5800 Series
Switches Description Left Switches (1) ALL I2R (2) () (4) (5) (6) (7) (8) C: FAN H: FAN CLASS 2 LOAD SHED FREEZ S CONST FAN OCCUPIED Heat pump override Down Normal heat pump operation Up resistance heat only Fan control for cooling operation Down Fan Continuous Up Fan Cycle Fan control for heating operation Down Fan Cycle Up Fan Continuous Remote Thermostat Mode Down Unit Control Up Remote Thermostat Load Shedding when connected to Central Desk Control System Down Fan shuts off with unit Up fan under Smart Fan settings Freeze Sentinel Override Down Freeze Sentinel ON Up Freeze Sentinel OFF Constant Fan Down Fan runs normally Up fan runs when unit is in STOP position Occupancy Sensor Mode Down Unit Control Up Occupancy Sensor Connected Cooling temperature limiting (See table at bottom of page) Heating temperature limiting (See table at bottom of page) Diagnostics Switch Heat Sentinel switch Down Heat Sentinel OFF Up Heat Sentinel ON Heat Boost Down Heat Boost OFF Up Heat Boost ON
UP DOWN

Right Switches TL1 TL TL4 TL6 (7) (8) (9)

5800 Series shown


2

ALLI R (All Electric Heat) (5800 Series models only) C: FAN CN (CoolingSmart Fan) H: FAN CY (HeatingSmart Fan) CLASS 2 (Remote Thermostat) LOAD SHEDDING (CDC) FREEZ Sen (Freeze Sentinel) CONST FAN (Constant ON Fan) OCCUPIED (Occupancy Sensor)

HIGH 4 5 COOL

UP DOWN

HEAT BOOST (5800 Series models only) Heat Sentinel Diagnostics Switch TL1 (H) (Temp. Limit 1Heat) TL2 (H) (Temp. Limit 2Heat) TL3 (H) (Temp. Limit 3Heat) TL1 (C) (Temp. Limit 1Cool) TL2 (C) (Temp. Limit 2Cool) TL3 (C) (Temp. Limit 3Cool)

Cooling and Heating temperature limits are set independently, temperature limiting switches are in factory-set down position, except as noted.

Cooling Temperature Limits


Switches Up NONE 60 Switches Up 6 65 1 64 4, 6 70 1, 2 66 4, 5, 6 72 2 68 5, 6 74 2,  70 5 76 1, 2,  72 4, 5 78 1,  74 4 80  76 NONE 85
1

Heating Temperature Limits

Central Desk Control


Some installations may want to govern the ability of the unit to operate from a control device remote to the unit or even remote to the room in which the unit is located. The general term given to systems such as this is Central Desk Control. The most common installation of this type of system is a switch mounted at the registration desk and, upon guest check-in, a button is pushed or a switch is moved to allow the air conditioner to operate. Likewise, when the guest checks out the device is put into the OFF position so the unit will not operate while the room is vacant. It is not necessary that the controlling device be located at a central desk to employ a device that will control the unit operation. For instance, in some resort areas devices are connected to sliding glass doors and opening the door causes a contact to close, turning the air conditioner off. This prevents energy being wasted by operating the air conditioner when warm, humid air is entering the room. Some systems operate by motion sensors or heat sensing detectors mounted in the room. These types of systems determine occupant presence in the room and allow the unit to operate; if no one is in the room the device signals the air conditioner to turn off. Zoneline models offer Load-Shedding capabilities on units connected to Central Desk Control Systems. For more information on the models Load-Shedding Feature, see page 10. There is a wide variety of devices available, each with its own benefits and constraints. While GE does not offer components that are external to the unit for a Central Desk Control (CDC) system, GE Zonelines are compatible with most CDC and Energy Management systems. Zonelines provide a 24 VAC circuit that powers the Central Desk Control system and no external power is needed. All Zoneline 2800, 800, and 5800 Series units are compatible with simple on/off 2-wire Central Desk Control systems. Consult with the provider of other energy management systems to be sure they are compatible with the GE Zoneline. Zonelines have standard connectors factory-installed to provide a CDC interface that permits the unit to be connected to most of the energy management systems. The devices connected to the Zoneline units require no power supply or transformers external to the unit. 4. Recommended wire size must be followed as a minimum requirement. Wire Size #AWG Maximum Allowable Length #22 600 Ft. #20 900 Ft. #18 1500 Ft. #16 2000 Ft. Freeze Sentinel remains operational when the unit is connected to a CDC system. Even if the unit is turned OFF at the central location, if the sensor at the unit detects the low temperature, the electric resistance heaters and the fan will automatically turn on. Connecting the Zoneline to a CDC system does not eliminate the ability to connect the unit to a remote thermostat. Once the circuit is opened, and control of the unit removed from the CDC system, the selected controls - either the unit mounted control or the remote thermostat - govern the operation of the unit. Please see page 57 for installation recommendations for the Central Desk Control wiring.

CDC Terminal Location and Typical Wiring


See page 15 for location of CDC terminals on unit.

Example of Common Bussing NOT PERMITTED

Unit #1

Unit #2

Unit #3

INCORRECT Common Bussing Normally Open Switch Unit Operational

Important CDC Comments (all series applicable)


1. When the switching device closes the circuit of the CDC conductors, the unit operation stops. 2. Do not use a common buss (at the unit or at the switch panel) in the wiring. Both wires comprising the circuit must connect to the unit connectors and to the controlling switch. Running one wire from one unit to another unit is common bussing and may damage internal components or cause erratic operation of the system. . A 24-volt transformer is contained within the Zoneline. No external voltage may be applied to the unit through the CDC terminals. (Voltage on the CDC conductors is 24 volts AC.)
14

CDC Terminals on Zoneline

Typical Wiring (All Wiring Shown Is Field Supplied)

Remote Thermostat Control


In some installations, control of the operation of the unit at a location remote from the unit itself may be desired. A unit mounted high in the wall or over a door, for instance, where the unit-mounted controls are inaccessible, can be connected to a wall-mounted thermostat. Other installations may use remote thermostat control for design or performance enhancement. The unit is connected to the thermostat by low-voltage wiring which permits the operation of the unit to be selected and the temperature sensed at the thermostat. Important Notes: Remote thermostat wiring should not be run through wall case. Thermostat wiring should exit the wall below the unit and enter the unit between room cabinet and chassis. Wire molding may be used to hide thermostat wiring. If a sub-base is used, the thermostat wiring may be concealed by the sub-base. Thermostat wiring should not be run parallel to line voltage wires since induced current may cause erratic operation. All Zoneline 2800, 800 and 5800 Series units are adaptable to Class 2 remote low-voltage thermostat. The only additional field-supplied components are the remote thermostat and wiring necessary to connect it. The controls on the unit are not functional when the remote control function is used.

ge.com
The AC voltage may not be compatible with some solid-state thermostats. The fan speed for the 2800 Series in remote thermostat operation is selected by the connection of the fan wire from the thermostat to either the HIGH or LOW terminal on the unit. See the sketch of the unit terminals for the location of the HIGH and LOW fan-speed terminals. Operating the unit in low fan speed reduces the operating sound level of the unit. Freeze Sentinel remains operational if the unit is connected to a remote thermostat. The unit may be connected to a Central Desk Control (CDC) system and controlled with a remote thermostat when the CDC system has the unit in operation. See page 14 for additional information on the CDC system. Unit temperature limiting switches are not functional when unit is connected to a remote thermostat.

Field Wiring Terminal


R GL GH B Y W C 24V AC Low-Speed Fan High-Speed Fan Not Used on 2800 Compressor Heater Common Ground

Resistance Heat Models


The Zoneline 2800 resistance heat units may be connected to a single-stage thermostat designed for use with cooling with electric heat systems. GE offers three thermostats compatible with the 2800 Series unit.
CDC GL GH W B R Y C

When a Zoneline unit is using a remote thermostat control, the RAK806 Universal Control Cover Label The Class 2 Mode Switch (dip switch #4 on the auxiliary control is recommended. The RAK806 is only board) must be set to the ON/UP mode to enable remote thermostat control. Refer to installation instructions packaged available in a package of 10 labels. with the chassis. The label is placed Please see page 57 for installation recommendations for over the control the remote thermostat wiring. panel directing the Compatibility of other thermostats considered for use with the Heat Pump Models user to the wall GE Zoneline is the responsibility of the customer. The control thermostat for voltage on the remote control conductors is 24 volts AC. operation of the Zoneline unit.
GL B GH R Y

RAK16A1 a mechanical manual changeover thermostat requiring four connection wires.

RAK164D1 a solid-state digital manual changeover thermostat requiring five connection wires.

RAK164P1 a solid-state digital programmable auto-changeover thermostat requiring five connection wires.

Resistance Heat Models

Common Ground White Heater Yellow Compressor Black Not Used On 2800 Green High-Speed Fan Green Low-Speed Fan Red 24V AC CDC Terminal

RAK806 Universal Control Cover Label

Common Ground White Heater Yellow Compressor Black Reversing Valve Green High-Speed Fan Green Low-Speed Fan Red 24V AC

15

Remote Thermostat Control


Heat Pump Models
The Zoneline 800 and 5800 Series heat pump units may be connected to a single-stage cooling/two-stage heating thermostat designed for use with heat pump systems. GE offers  thermostats compatible with the 800 and 5800 series units: Temperature Boost option should not be used with remote thermostat operation since this will cause the unit to switch to resistance heat when outdoor temperatures are below 46F. Feature
Indoor Frost Control Freeze Sentinel Auto Fan Speed Electronic Temperature Limiting Switch to Resistance Heat Based On Indoor Temperature Switch to Resistance Heat Based On Outdoor Temperature Reverse Cycle Defrost Simultaneous Resistance Heat with Heat Pump Resistance Heat Lockout Smart Fan Fan Cycle Central Desk Control
CDC GL GH R

Heat Pump
Yes Yes No No Determined by Remote Thermostat Yes Yes No

Electric Heat
Yes Yes No No N/A N/A N/A N/A

Please see page 57 for installation recommendations for the remote thermostat wiring. Compatibility of other thermostats considered for use with the GE Zoneline is the responsibility of the customer. The control voltage on the remote control conductors is 24 VAC. The Class 2 Mode Switch, dip switch #4 on the auxiliary control board on both the 800 series and the 5800 series, must be set to the ON/UP mode to enable remote thermostat control. Refer to installation instructions packaged with the chassis. The fan speed for the 800 and 5800 series in remote thermostat operation is selected by the connection of the fan wire from the thermostat to either the HIGH or LOW terminal on the unit. See the sketch of the unit terminals for the location of the HIGH and LOW fan speed terminals. Operating the unit in low fan speed reduces the operating sound level of the unit. When connected to a remote thermostat, the indoor air temperature sensing is shifted from the unit to the remote thermostat. For this reason, the units will operate slightly differently when connected to a remote thermostat. The following chart shows the unit operation when connected to a remote thermostat.

Yes N/A Common Ground Fan ON/AUTO Set On FanHeater White ON/AUTO Set On Remote Thermostat Remote Thermostat Yellow Compressor Yes BlackYesNot Used On 2800
Green High-Speed Fan Green Low-Speed Fan Red 24V AC CDC Terminal Fan Low-Speed

Field Wiring Terminal


R 24V AC GH High-Speed Fan Resistance Heat Models Y Compressor C Common - Ground

GL

GH

Common Ground White Heater Yellow Compressor Black Reversing Valve Green High-Speed Fan Green Low-Speed Fan Red 24V AC

Heat Pump Models

Remote Thermostat Control Selection Chart For Zoneline Packaged Terminal Units
Zoneline Series
2800

Thermostat Model
RAK16A1 RAK164D1 RAK164P1

Type
Mechanical Digital Digital Programmable Mechanical Digital Digital Programmable

Function
Cooling and Heating

RAK147 mechanical manual changeover thermostat requiring 6 connection wires.

RAK148D1 solid-state digital manual changeover thermostat requiring 6 connection wires.

RAK148P1 solid-state digital programmable auto-changeover thermostat requiring 6 connection wires.

GL B Reversing Valve W Heater

Low-Voltage Conductors
4 5 5 6 6 6

800 and 5800

RAK147 RAK148D1 RAK148P1

Single Stage Cooling 2 Stage Heating

Thermostat wire size up to 60 feet AWG20 up to 66 feet AWG18


16

Remote Thermostat Control


Multiple Units Connected to One Remote Thermostat (2800 Series)
One remote control thermostat may be used to control multiple resistance heat Zoneline units, however the units may not be wired direct. Since each Zoneline unit has an

ge.com
integral transformer, direct wiring can result in a bucking or boosting voltage condition, and is in violation of the National Electric Code. The diagram below shows the correct wiring for such an installation through the use of field supplied isolation relays.

For Use With Mechanical 4-Wire Systems Only

Remote Control (Low Voltage) Wiring


One stage Thermostat Controlling Three Zoneline Units Resistance Heat Zoneline 2800 Series Units (Not Applicable on Heat Pump Units)

Field-Supplied Relay Specifications


Number Of Units Controlled
2  4 MORE THAN 4

Relay Designation R1, R2, And R


POTTER and BRUMFIELD TYPE KA11AY-24 OR EQUIVALENT POTTER and BRUMFIELD TYPE KA14AY-24* OR EQUIVALENT POTTER and BRUMFIELD TYPE KU17A11-24* OR EQUIVALENT USE COMBINATION OF RELAYS SPECIFIED ABOVE

NOTE: Current draw through thermostat contacts should not exceed 1.0 amps. *Special order, 100 piece minimum order.

17

Heat Pumps and Energy Savings


GE Zoneline Heat Pumps are designed to provide cost-efficient heat pump operation while monitoring room conditions to maintain comfort. The units employ a logic system monitoring both outdoor and indoor temperatures to determine the heat source, thus increasing energy savings by operating longer in the heat pump mode. Heat pumps save energy and cost less to operate than units with electric resistance heaters as the only heat source. Just as the EER of an air conditioner is an indication of the efficiency of the unit, COP (Coefficient of Performance) is the indication of the efficiency of the heat pump. This relative efficiency of a heat pump compares the unit to electric resistance heat. If a unit has a COP of .0, it means the unit will produce three times as much heat at rating conditions for the same electrical input wattage used for electric resistance heat. The compressor is used in heat pump operation just as in air conditioning operation. In heat pump operation, the hot refrigerant gas is directed to the indoor coil rather than to the outdoor coil. Room air that circulates over the indoor coil gains heat from the coil rather than losing heat to the coil as during cooling operation. As the outdoor temperature falls, the heat pump is able to extract less heat from the outdoor air to raise the temperature of the indoor air. For this reason, all packaged terminal heat pumps also have electric resistance heaters as backup to heat pump operation. At some point, the heat pump is unable to provide sufficient heat to adequately warm the room. Many Packaged Terminal Heat Pumps cease heat pump operation and change to more expensive resistance heat at some pre-determined outdoor temperature to compensate for the inability of the heat pump to maintain room temperature. This point, called the switchover point, is usually at an outdoor temperature where savings from heat pump operation may still be realized, if the unit is designed to maintain room comfort at the lower outdoor temperatures.

Balance Point
An important consideration of the selection of a heat pump unit is the balance point of the installation. Virtually every room is unique with different insulation different sizes and types of windows different types of construction different directional exposures. All of these variables, as well as geographical location, must be considered in order to determine the balance point, the point at which the heat pump is unable to produce enough heat to compensate for the heat loss of the room or area being heated. For these reasons a consulting engineer should be engaged to calculate the heat loss and specify the heat pump unit required. GE offers two series of Zoneline Heat Pump units the 800 Series with Standard Microprocessor controls and the 5800 Series with Highly Featured Microprocessor controls and both series react to the indoor temperature as well as the outdoor temperature in determining the heat source to provide comfortable room conditions and energy savings. This determination of the heat source based on the indoor temperature helps provide a more comfortable room.

18

Heat Pumps and Energy Savings


Heat Pump Operation Zoneline 800 and 5800 Series
Heat sources: Heat pump, heat pump and simultaneous electric resistance heat or electric resistance heat. Zoneline heat pumps employ a highly featured microprocessor control system interfaced with thermistors to accurately measure indoor air temperature, outdoor air temperature, indoor coil temperature and outdoor coil temperature. This system allows the microprocessor to precisely and predictably react to changing conditions in order to provide a very advanced Packaged Terminal Heat Pump operating system. The Zoneline heat pumps are designed to help ensure a comfortable room. When HEAT is selected, the unit will determine if the room air is warm enough to satisfy the thermostat setting. If the temperature at the unit sensor is below the desired temperature, the electric resistance heater will be utilized to warm the room to the point where the thermostat is satisfied. This feature is designed to allow the temperature of an unoccupied room to be maintained at an energy-saving level without inconveniencing the room occupant. Once the thermostat has been satisfied, the resistance heater will turn off and the heat pump will operate as shown in the Heat Source Logic chart until the thermostat calls for heat again. The unit will operate in this manner even if connected to a Central Desk Control.

ge.com
The Quick Heat Recovery feature is not affected by the Heat Source Logic shown in the chart above. For more information about the Quick Heat Recovery Feature, see page 9. The full heat output of the resistance heater is dependent upon circuit amperage and the power connection kit used. See pages  and 42-4 for information on power connection kits and available heater capacities. A heat pump switch is provided in the auxiliary controls to allow the unit to operate only in resistance heat. The use of this option significantly increases the cost for heating.

Heat pump defrost Zoneline 800 and 5800 Series


Zoneline heat pumps utilize a reverse-cycle demand defrost system to extend heat pump operation and increase savings from extended operation. The microprocessor determines the need for defrosting by criteria based on continuous compressor running time, outdoor air temperature, outdoor coil temperature and the rate of temperature change of the outdoor coil. When defrosting is required, the unit reverses the flow of refrigerant to direct the hot gas into the outdoor coil to melt the frost build-up. Before and after the reverse-cycle defrosting, the unit shuts off the compressor to allow the refrigerant pressures to equalize throughout the system. This eliminates the possibility of a loud reversing noise. During these periods of pressure equalization, the full resistance heat capacity of the unit is activated to help ensure room comfort conditions during the defrost cycle. The unit remains in the defrost cycle for a minimum of two minutes up to a maximum of nine minutes. The defrost cycle terminates when the outdoor coil reaches a temperature of 68F or the maximum time has been reached.

Zoneline Heat Pump Heat Source Logic


ROOM TEMPERATURE VS. THERMOSTAT SET POINT Less Than 1.8F Below 1.8F to 2.7F Below More than 2.7F Below Above 46F Between 46F and 25F Below 25F

Heat Pump

Heat Pump* Heat Pump + Supplemental Heater Full Resistance Heat

Full Resistance Heat Full Resistance Heat Full Resistance Heat

Heat pump condensate


See page 4 for information on heat pump condensate. The Zoneline 800 Series heat pumps may be ordered with a factory-installed Internal Condensate Removal (ICR) system to minimize the amount of condensate water draining from the unit during heat pump operation. The ICR system has proven to be an effective means of minimizing the amount of heat pump condensate dripping from the unit. However, if the requirements of a particular installation will allow no dripping of condensate water from the wall case, the installation of an internal or external drain system is recommended. Units with ICR may not be installed in seacoast or corrosive environment applications.

Heat Pump

Heat Pump

*If the Temperature Boost switch (dip switch #8) is in the ON position the supplemental simultaneous heater will be used with heat pump operation. Simultaneous supplemental heater: 1.0 KW @ 20 V; 0.8 KW @ 208V; 1.0 KW @ 265V. The Temperature Boost option utilizes the supplemental simultaneous heater simultaneously with heat pump operation when the outdoor temperature is below 46F regardless of the indoor air temperature. The chart above indicates the heat source of the heat pump under various indoor and outdoor conditions. The unit is designed to provide heat pump savings without sacrificing room comfort.

19

Application Comments
Use and Care Manual and installation instructions are shipped with Zoneline units. It is important that any air conditioning system be properly sized and applied in order to achieve the desired temperature and humidity levels with the space to be conditioned. Air conditioners are designed primarily to provide heating and cooling with the additional benefit that during operation in the cooling mode, the units also remove some moisture from the conditioned space. The following are some brief application comments on undersizing, oversizing, heating, wall coverings, and air infiltration: all are important in the proper matching of the heating/air conditioning system to the building structure. Undersizing: If an air conditioner is undersized (cooling capacity is less than required for a specific application), the unit will typically not be able to cool the space down to the desired temperature (thermostat set point), nor be able to remove enough moisture from the air. A result could be a warm and humid or warm and dry conditioned space. Oversizing: If an air conditioner is oversized (cooling capacity is greater than required for the specific application), the unit will typically cool the space down to the desired temperature (thermostat set point) too quickly. The compressor then begins to cycle on and off. Dehumidification only takes place when the compressor is operating. A typical result in a hot/ humid climate could be a cool but excessively humid space. Heating: Undersizing can result in not being able to maintain the desired temperature level within the conditioned space. Wall Covering: Use of a non-permeable wall covering (some paints, some wallpapers, and other types of coverings) which severely restricts passage of air or water vapor can cause a severe moisture problem. Typical results could be staining of room surfaces, wall damage, as well as mold and mildew growth in hot/humid climates. Air Infiltration: Excessive air infiltration can magnify problems associated with undersizing or oversizing of an air conditioner unit and can be the root cause of insufficient cooling, dehumidification, or heating. Some sources of air infiltration include vents, gaps around windows and doors, and improperly sealed floor, ceiling and wall joints. Recommendation: For the above reasons it is strongly recommended that a professional engineer be retained to match the Zoneline unit with the building structure. High Wall Mount For units mounted high in the wall, the discharge louvers should be at a setting that provides the most horizontal air discharge. Recommended installation is at least " below the ceiling. In installations where units are close to the ceiling, the most horizontal discharge angle can be obtained by removing the discharge grill from the room cabinet. Supply Air Throw One Zoneline unit should not be required to do a job obviously requiring two or more units. Units should be located around large rooms according to calculated loads or in such fashion as to achieve balanced air distribution in all parts of the room. The single unit in the Incorrect illustration below obviously cannot condition the entire room. Add a second unit as shown in the Correct illustration.

50

40

INCORRECT

OVER 40 FT.

CORRECT

Air Distribution
Zoneline packaged terminal air conditioners and heat pumps discharge air from the top of the unit through reversible 2-position discharge louvers. Unit discharge louvers are reversed by removing the room cabinet from the unit, removing seven screws that hold the louver section in place, removing the louver section and rotating it end for end, reinstalling the louver section in the room cabinet with the seven screws, and reinstalling the room cabinet on the unit. The unit is shipped from the factory with the discharge louvers at an angle of 50 off vertical. In the alternate position, the louvers will be at an angle of 40 off vertical. All room cabinets return air through the front of the unit.
20

OVER 40 FT.

Dimensions
RAB71A WALL CASE
A
13 4" 3/
2-3/4" 1-1/2" TYP 16" 4" 1/2" 5-5/8" 42" 1/2" SQ. HOLE (2 REQ'D.)

ge.com
Additional Wall Case Depths RAB7116 - 16" RAB7124 - 24" RAB7128 - 28" RAB711 - 1"

WALL OPENING 16-1/4" MIN. x 42-1/4" MIN.

6" 21" 36" 1/2" DIA. HOLE (3 REQ'D.)

RAB77 WALL CASE


13-7/8"

42-1/8"

2-7/8" 1-1/2" 16-1/4" 4" 1/2" SQ. HOLE (2 REQ'D.) 9/16" 5-5/8"

WALL OPENING 16-1/2" MIN. x 42-/8" MIN.

6" 19" 36" 1/2" DIA. (3 REQ'D.)

WALL CASE WITH CHASSIS INSTALLED


RAB71 = 13-3/4" RAB77 = 13-7/8"

RAB71 = 42" RAB77 = 42-1/8"

GRILLE

RAB71 = 20-7/8" RAB77 = 21"


7-1/8"

GRILLE

TOP VIEW SIDE VIEW INSIDE RAB71 = 16" RAB77 = 16-1/4" OUTSIDE

42"

ROOM CABINET

ROOM CABINET

WALL CASE WITH SUB-BASE

FRONT VIEW* 1-5/16" 1-7/16" 3-1/2" 12-3/4" 12"


KNOCKOUTS (ENCLOSURE) 4 REAR; 4 BOTTOM

SIDE VIEW 2-3/8" MIN.


INTERIOR WALL

13"

9-3/8"

2-1/2" LEVELING SCREW

3" MIN. ADJUSTABLE TO 5" MAX.

SEE PAGE 32 FOR KNOCKOUT LOCATION DIMENSIONS.

FINISHED FLOOR

*SHOWN WITH ACCESS COVERS REMOVED. NOTE: CAUTION - REMOVE KNOCKOUTS FROM INSIDE OUT.

Installation Instructions Packed With Wall Case . . . See Page 25 For Additional Information Concerning Outdoor Weather Panel and Case Stiffener.
21

Wall Case
A choice of wall cases is available for the Zoneline. RAB71A This insulated case is constructed of heavy-gauge galvanized steel and finished with a protective baked-enamel finish for protection and appearance. Design of the case provides for support of the chassis and free draining of any water entering the wall case. A petroleum microcrystalline wax is applied at critical points of fabrication to seal against moisture. The dimensions of the RAB71 wall case are: 42" wide by 16" high by 1-/4" deep, the same dimensions as the original wall case for GE Zonelines built in 1961. The RAB71 wall case is also available in depths other than the standard depth. It is available on special order as: RAB7116 16" deep; RAB7124 24" deep; RAB7128 28" deep; and RAB711 1" deep. All of these special-order deep wall cases are insulated and have sheet metal dividers, or splitters, to prevent the recirculation of condenser discharge air. RAB77 This non-insulated wall case is molded from fiberglass-reinforced polyester compound. This SMC (Sheet-Molded Compound) wall case offers outstanding strength, durability, color retention, water integrity and corrosion resistance. The dimensions of the RAB77 wall case are: 42-1/8" wide by 16-1/4" high by 1-7/8" deep. Both wall cases are of universal design, accepting all Zoneline chassis of current design as well as all GE Zoneline chassis produced since 1961. Drain holes are provided in the rear of the wall case to permit excessive cooling condensate water, heat pump condensate or precipitation entering the wall case to drain freely. A drain kit may be connected to the wall case to control any water draining from the wall case. See page 4 for information on RAD10 Drain Kit. RAK901L For installations where the wall case extends into room, RAK901L is an insulation kit that can be used with the RAB77 or any existing non-insulated wall case to minimize the possibility of condensation forming on the indoor side of the case during the winter. Permanent Connection generally means wiring to the unit must be contained in an enclosed chaseway, where access to the wiring connections is more restrictive than a normal line cord plugged into a receptacle. NEC requirements may be met by using flexible or rigid conduit to contain the wiring between the unit and a junction box that contains the wiring connections. The conduit is connected to the unit and to the junction box with connectors to hold the conduit in place. The junction box may be located in the floor or the wall of the structure but only approved connectors may be used outside the unit or the junction box. The sub-base is UL listed as a junction box for permanent connection of a Zoneline. Using a sub-base in an installation requiring permanent connection provides a convenient, consistent location for unit wiring to be connected to building wiring. The use of a sub-base is not required, but the convenience and the improved aesthetics it offers makes the use of a sub-base a viable means of permanent connection. RAK204U The RAK204U Series of sub-bases provides a variety of designs that fit the site needs and are available for use with Zoneline PTAC/PTHP units. The RAK204U will most likely be used for support of the wall case and unit. The RAK204U is the same physically as the other sub-bases except there is no receptacle installed. Receptacles and wiring can be field installed and, by using the RAK205CW chaseway and the RAK4002 junction box perform the same function as any of the other sub-base kits by selecting the correct receptacle and installing it in the interior mounting plate inside the RAK204U. 208/20-volt receptacles can also be mounted in the cover plate for easy access when direct connect wiring is not required. 265-volt units are to be Permanently (or Direct) Connected and the external receptacle (when wiring is not enclosed in a chaseway) does not meet this requirement. A knockout for a fuseholder or a disconnect is also provided in the cover plate. RAK204U No receptacle, no wiring, will accept any 15-, 20-, 0-amp receptacle and wiring. No chaseway is included. RAK205CW chaseway must be ordered separately. The 20/208-volt sub-bases below include a short, sub-base power connection kit. Since sub-base connected units are not considered to be line-cord connected, a Leakage Current Detection and Interruption or Arc Fault Current Interrupter device is not necessary. The junction box (RAK4002A for 2800 and 800 Series units; RAK4002B for 5800 Series units) that mounts on the chassis of 20/208-volt sub-base connected units must be purchased separately. RAK204D15P 208/20-volt 15-amp receptacle. Receptacle is NEMA6-20R with 18" of #12AWG wires attached to the receptacle. Short power connection kit included. Chaseway included. RAK204D20P 208/20-volt 20-amp receptacle. Receptacle is NEMA6-20R with 18" of #12AWG wires attached to the receptacle. Short power connection kit included. Chaseway included.

Sub-Base
The sub-base is an optional accessory for the Zoneline and is presented with the wall case information since the decision to use or not to use a sub-base in the installation is a factor in the location of the wall opening for the unit. National Electrical Code requires that air conditioning units connected to voltages in excess of 250 volts be permanently connected. There are also some installations where units connected to voltage sources under 250 volts may also need to be permanently connected. If you are in doubt about the requirements for a particular installation, consult Article 440 of the NEC or the local electrical inspector. These requirements are designed to protect personal safety and should be strictly followed. Although NEC is cited here as a reference, all electrical wiring and installations must conform to any and all local electrical codes and regulations.

22

ge.com

Sub-Base (Continued)
RAK204D0P 208/20 volt 0-amp receptacle. Receptacle is NEMA6-0R with 18" of #12AWG wires attached to the receptacle. Short power connection kit included. Chaseway included. The junction box (RAK4002A for 2800 and 800 Series units; RAK4002B for 5800 Series units) that mounts on the chassis of 20/208 volt sub-base connected units must be purchased separately. Sub-bases for the 265 volt units: RAK204E15 265-volt 15-amp receptacle. Receptacle is NEMA7-15R with 18" of #12AWG wires attached to the receptacle. Chaseway included. RAK204E20 265-volt 20-amp receptacle. Receptacle is NEMA7-20R with 18" of #12AWG wires attached to the receptacle. Chaseway included. RAK204E0 265-volt 0-amp receptacle. Receptacle is NEMA7-0R with 18" of #12AWG wires attached to the receptacle. Chaseway included. The junction box for 265-volt units is shipped with the chassis since all 265-volt units are to be Permanently (or Direct) Connected. The Power Connection Kit is not included There are separate internal compartments to permit separation of low voltage (Class 2) connections from line voltage connections as required by NEC. Conduit containing building wiring enters the sub-base through knockouts located in the rear or bottom of the sub-base and is not accessible when the wall case is installed. The sub-base attaches to the RAB71 wall case with two clips (field-assembled) that are screwed into pre-drilled holes in the bottom front flange of the wall case. It attaches to the RAB77 wall case with clips that fit over molded ribs without requiring the use of screws into the wall case. See page  for illustration. Since the sub-base extends under the wall case, clearance from the inner edge of the wall case to the finished wall must be 2-/8" or greater. The sub-base has 4 leveling legs and adjustable side channels to enable the area under the wall case to be enclosed. Clearance from the bottom edge of the wall case to the finished floor must be between " and 5". The sub-base may be used as support for the chassis and wall case in installations where the wall is of insufficient thickness to provide secure mounting of the wall case. exterior wall. See pages 0 and 1 for information on this type of installation. The unit may be installed high in the wall and these installations usually require a remote thermostat and are discussed on pages 15 and 16. Regardless of the installation, there are several things to consider when selecting a location for installing the unit. For instance, drapery location could interfere with air discharge, and placement of furniture may have an impact on the performance of the unit. The following information is intended to minimize installation problems and assure you of trouble-free installation. Refer to page 21 for required wall opening dimensions. Minimum recommended interior and exterior case projection for standard wall thicknesses are shown in the drawings in this manual. The case may be installed flush with the finished indoor wall. Special attention must be paid to room-side case projection when the unit is installed in a ducted application as shown on page 9. In walls thicker than 1-1/2" for line cord-connected units and 11-1/8" for sub-base installations, it may be necessary to install a field-fabricated case extension or use one of the special order RAB71 deep wall cases. If you are unable to locate a local source for case extensions, please contact your salesperson for a possible supplier. Such extension must be carefully flashed and sealed both to the wall case and to the wall to ensure water integrity. This is necessary to ensure that any water entering the wall case, either from operation of the unit or from other sources, such as rain storms or from washing the exterior of the building, will drain from the case without the possibility of capillary action drawing the water into either the room or the wall cavity. In an installation where the case is recessed less than " from the outside surface, flashing and sealing may be all the modification necessary. In such an installation, the sides and top of the wall opening must be waterproof to prevent moisture from seeping into and damaging the walls. See pages 0 and 1 for suggested detail. Since the installation of a case extension requires a considerable amount of attention, we recommend using one of the deep wall cases if the standard case is not of sufficient depth. Mounting an outdoor grille or louver section to the building face may cause a space between the outdoor coil and the louver section. Air splitters, aligned with the ends of the outdoor coil, must be installed between the outdoor coil inlet and outlet air streams. Gaps between the outdoor coil and the louver section may allow condenser air recirculation and affect the operation of the unit. See page 41 for requirements for custom louver sections. The wall case should be level from side to side and from level to 1/4 bubble tilt to the outdoors. The condensate disposal system in the unit is designed to dissipate the condensate water generated during cooling operation in accordance with ARI standards and actually uses this water for maximum unit efficiency. A level unit will also ensure proper performance of the Internal Condensate Removal (ICR) system optional on heat pump units.
2

Wall Case Installation Data


General
Generally, Zoneline units are installed " to 5" above the floor (flush to finished floor installation is possible) as near to the center of the room as possible; underneath a window or a glass panel is typical. Normal installation of the wall case allows installation flexibility; from flush with the finished interior wall to a minimum of 1/4" of the wall case extending beyond the finished exterior of the building. Special consideration must be given to installations where the wall case does not extend a minimum of 1/4" beyond the finished

Wall Case Installation Data (Continued) Masonry Wall Construction


For new construction, early planning with the architect is necessary. Unit location, electrical connection locations, and wall openings of the proper dimensions are essential to avoid the necessity of rework, fillers, framing, moving electrical outlets, and other expensive modifications. For existing construction it is important that carpentry, masonry and electrical work be performed by competent, qualified personnel. Since installations in existing construction may involve removal of building material from the structure, locating the wall case must be done correctly. The wall case should be installed during construction and lintels should be used to support the blocks above the wall case. The wall case will not support the concrete block. The installation instructions show how the wall case must be secured to the masonry and caulked. Do not remove the cardboard stiffener supplied with the wall case until ready to install the chassis. See page 29 for details of installation in masonry wall. For existing masonry construction, wall openings must be made by removing concrete blocks to achieve the proper size opening. Consult the builder, architect, or owner to determine the necessity for lintels to support the block above the wall case. Anchor bolts are normally required to secure the case to the wall and shims may be required to prevent distortion of the wall case when securing the wall case to the wall. Field supplied case angles can be used to position and secure the wall case to the wall and to cover oversized wall openings.

Architectural Window/ Louver Installation


Many installations utilize an architectural window/louver combination to enhance the exterior appearance of the building. The exterior grille for the air conditioner is built as an integral part of the window frame. An internal drain system is highly recommended for these installations (see page 6). When this type of installation is made, there must be provision in the grille work for condensate water to drain to the exterior and not be routed back into the interior of the building or into the wall cavity. Failure to allow for the drainage of condensate water can cause extensive damage to structural components. The problems associated with the lack of condensate drain consideration often show up shortly after the air conditioners are turned on in a new building. New buildings that have been virtually wide open during construction have a significant amount of moisture in the air and in the building components that the air conditioners start removing as they operate. The free area in the louver section must also comply with the requirements shown on page 41. The wall case should be anchored to the architectural window/louver section to reduce air infiltration and excessive vibration of the chassis and wall case during unit operation. Field-fabricated and installed case angles are the recommended method of securing the wall case to the window/louver framework.

Brick, Frame, Stucco and Shingle Construction


For new construction, the opening for the wall case should be framed and the wall case inserted into the opening during construction. Lintels should be used when the building material is heavy and is not self-supporting (such as brick). The wall case will fit an opening of six courses of standard brick or five courses of jumbo brick. Wall framing in this type construction is normally on 16" centers and the wall case will fit a framed opening spanning three 16" O.C. 2" x 4" stud spaces. For existing construction the indoor and outdoor wall will need to be cut out, allowing for clearances of 1/8" on all sides of the wall case. Work should begin on the inside wall. Cut the correct dimensions and mark (using drill holes) the outside wall from each corner of the inside cutout. Studding that interferes with the opening must be removed and a suitable frame constructed to secure the wall case and provide adequate support for case and chassis. As shipped, the RAB71 Series or RAB77 is ready for installation.

Window, Curtain and Panel Wall Construction


With this type of construction, provision for support of the unit, other than by the wall itself, is often required. Such support may be in the form of wood or metallic material of the proper thickness to maintain a level case. This additional support should be located both near the wall and at the front of the wall case. Sub-base (RAK204 Series) with four leveling legs provides an excellent support for the unit in this type of installation. See page 28 for details of this type of installation. In existing construction, common practice is to remove a pane of glass, metal, wood, or other construction material and build a frame around the wall case. Similar filler panel material may be installed around the case for appearance and weather seal.
24

Preparation of the Wall Case for All Types of Construction


Do not remove the stiffener from inside the wall case or the weather closure panel from the outside face of the wall case until the outdoor grille and chassis are ready to be installed. Installation of Wall Case in Wall Opening 1. Position the wall case into the wall. The room side edge of the RAB71 or RAB77 wall case should be at least flush with the finished wall for line cord installations and permanent connection installations when no sub-base is used, and should project into the room at least 2-/8" when a subbase is used. If the minimum exterior dimensions are not met, refer to page 27 and 28. The outside edge of the wall case should extend at least 1/4" beyond the outside wall. This is necessary for proper caulking, to prevent sealing the drain holes in the rear flange of the wall case, and to facilitate the installation of an accessory drain, if used. The wall case should be level from side to side and from level to 1/4 bubble tilt to the outdoors. The condensate disposal system in the unit is designed to dissipate the condensate water generated during cooling operation in accordance with ARI standards and actually uses this water for maximum unit efficiency. A level unit will also ensure proper performance of the Internal Condensate Removal (ICR) system optional on heat pump units. 2. The wall case should be secured to the wall at both sides. Use a minimum of two screws or other fastening device on each side. See Figure 2 page 26. Mark the wall case on each side 2" from the bottom and 2" from the top at a point where basic wall structure is located. Drill wall case and use fasteners appropriate for wall construction. All holes for fasteners in the side of the wall case must be at least 2" up from the bottom of the wall case. Never locate screws or put other holes in the bottom of the wall case. The only exception is when an RAD10 drain kit is installed to connect to an internal drain system. See page 6 for RAD10 Drain Kit information. If the wall opening is greater than the case dimensions, spacers must be used on the sides between the wall case and the wall support structure to prevent distorting the wall case. . Caulk or gasket the entire opening on the outside between the wall case and exterior wall surface (4 sides) to provide total water and air seal. 4. Caulk or gasket room-side opening between wall case and interior wall surface (4 sides). Opening beneath or around the wall case can allow outdoor air to leak into the room resulting in increased operating costs and improper room temperature control. Care should be taken in location of electrical supply entry in relationship to wall sleeve to assure access to receptacle or junction box once unit is installed. Refer to page 4 for maximum power cord length. Permanent connected units close to finished floor must allow for conduit clearance.

Case Angles

ge.com

In some installations such as curtain walls, window walls, or where the structural material of the wall is insufficient to support or fasten wall case to, the use of case angles may be used. Case angles are pieces of steel or other material of similar structural strength that are formed to a 90 angle, with holes to fasten the case angle to the wall case and to the structural component of the wall surrounding the wall case. The following describes the procedure when field fabricated and installed case angles are applied. 1. Position case angles around top and sides of wall case at the desired location. Position case angles vertically on each side of wall case to provide a level installation. 2. Mark wall case through holes in case angles. The lowest hole on the sides of the wall case must be a minimum of 2" above the bottom of the case. . For RAB71 wall case drill 5/2" diameter holes at locations marked on wall case in Step 2, and assemble angles to wall case using #10 x 1/2" self tapping screws. For RAB77 wall case follow the same procedure except use a #10 x 1/2" bolt, washer and nut to attach case angles to case. Install screws or bolts from outside wall case. 4. Do not drill any holes in bottom of wall case. Do not distort wall case. 5. Do not use case angles for a lintel.

25

26

FRAMING FOR WALL CASE


MAIN STUDS HEADER JACK STUD HEADER 4" x 4" OR 2 - 2" x 4" ON EDGE LINTEL

FASTENING WALL CASE

Brick Veneer and Frame Construction

MAIN STUD

JACK STUDS

MOUNTING SCREW HOLE

Framing detail for this construction is as shown in Figure 1. Note use of lintel under first course of brick above the Zoneline case. Do not use the case as a lintel. Mounting screw holes shown are to be made by the installer.

16-1/4" MIN. RAB71 16-1/2" MIN. RAB77 ADJUSTABLE FRAMING TO SECURE THIS DIMENSION 42-1/4" MIN. (RAB71) 42-3/8" MIN. (RAB77)

NO HOLES PERMITTED IN BOTTOM OF CASE (EXCEPTION -RAD10 DRAIN KIT)

JACK STUD FINISHED FLOOR SUB-FLOOR

CRIPPLE WOOD SCREW MOLLY OR TOGGLE BOLT NO HOLES PERMITTED IN BOTTOM OF CASE
2" MIN.

EXPANSION ANCHOR BOLT

Note: Do not remove the stiffener support from inside the wall case until the chassis is to be installed.

(EXCEPTION - RAD10 DRAIN KIT) JACK STUD MAIN STUD

Choice of attachment devices through both ends of case or the top. Mounting screw holes and attachment devices by installer.

Figure 1

Figure 2

WALL SECTION DETAILED SIDE VIEW


Frame and Brick Veneer Installation Sub-Base Connected

Cord set connected

LINTEL 2-3/8" STEEL LINTEL CAULK* RAB71 13-3/4" RAB77 13-7/8" 20-7/8" (RAB71) 21" (RAB77) CAULK* 1/4" CAULK*

CAULK*

RAB71 13-3/4" RAB77 13-7/8" 20-7/8" (RAB71) 21" (RAB77)

MOUNTING SCREWS BY INSTALLER RAB71 16" RAB77 16-1/4" OUTDOOR GRILLE ROOM CABINET WALL CASE 2" MIN.
CAULK*

MOUNTING SCREWS BY INSTALLER RAB71 16" RAB77 16-1/4" WALL CASE SIDE CHANNEL 1-5/16" 3" MIN. 5" MAX. 3-11/16" 2" MIN. OUTDOOR GRILLE

ROOM CABINET

CAULK*

1/4" MIN. RAG60 1/4" RAG61, 62, 63 1-3/8" RAG64, 65, 66 1-3/8" POWER SUPPLY CONDUIT

FINISHED FLOOR OR TOP OF CARPET

SUB-BASE (RAK204) CAULK* POWER SUPPLY CONDUIT (ALTERNATE ENTRY)

*Caulk around perimeter of wall case all four sides where it joins the building - Interior and Exterior.

FINISHED FLOOR OR TOP OF CARPET

WALL RECEPTACLE (BY OTHERS)

*Caulk around perimeter of wall case all four sides where it joins the building - Interior and Exterior.

ge.com

27

28

WALL SECTION DETAILED SIDE VIEW


Window, 2" curtain or panel wall installation with rag rear grille extended beyond outer wall surface

Cord Set Connected


WALL OR WINDOW

Sub-Base Connected

Gasket and caulk around perimeter of wall case all four sides where it joins the building CASE ANGLE (FIELD SUPPLIED) Gasket and caulk around perimeter of wall case all four sides where it joins the building RAB71 22-1/4" RAB77 22-3/8" WITH RAG61-66 RAB71 21-1/8" RAB77 21-1/4" WITH RAG60 RAB71 16" RAB77 16-1/4" OUTDOOR GRILLE WALL CASE ROOM CABINET 16" RAB71 16" RAB77A 16-1/4" CASE ANGLE (FIELD SUPPLIED)

RAB71 22-1/4" RAB77 22-3/8" WITH RAG61-66 RAB71 21-1/8" RAB77 21-1/4" WITH RAG60

16"

OUTDOOR GRILLE

ROOM CABINET

WALL CASE

RECEPTACLE (BY OTHERS)

SIDE CHANNEL GASKET (FIELD SUPPLIED)

(RAK204) SUB-BASE LEVELING LEG

USE NO SCREWS IN BOTTOM OF CASE MIN. 2 SUPPORTS FIELD SUPPLIED FLOOR

3" MIN. 5" MAX.

FLOOR

POWER SUPPLY CONDUIT (ALTERNATE ENTRY)

WALL CASE INSTALLATION CORD SET CONNECTED


Example: block and veneer dimensional data and comments Are also applicable to other types of construction
CASE RAB71 42" RAB77 42-1/8" CAULK* A Dimension A B C RAB71 13-3/4" RAB77 13-7/8" CAULK* E C D
Manufacturer Required Minimum Installation Clearance 1/4" (See note 1) Allow For Electrical Wiring 0" Min. (See page 27) 0" Minimum 0" Minimum 2" Recommended See pages 38-39 for ducted application. 3" Minimum

CAULK*

FINISHED EXTERIOR WALL

CAULK*

NOTE: 1. FOR OUTSIDE FLUSH MOUNTING SEE PAGE 35 FOR DRAIN INSTALLATION.

D D

ROOM CABINET

FINISHED EXTERIOR WALL 27-1/4" ADJACENT WALL

MAX. WALL THICKNESS 13-1/8"

2-1/2"

ADJACENT WALL

TOP VIEW

*Caulk around perimeter of wall case all four sides where it joins the building - Interior and Exterior. LINTEL

SIDE VIEW OF ALTERNATE HIGH MOUNT With conduit power supply. E

CAULK* A CAULK*

ROOM CABINET

WALL OPENING 16-1/4" x 42-1/4" MIN. FOR RAB71 16-1/2" x 42-3/8" MIN. FOR RAB77

INSIDE ROOM CABINET 7-1/8" RAB71 13-3/4" RAB77 13-7/8"

16" RAB71 16-1/8" RAB77

CAULK* B CONDUIT FIELD SUPPLIED

ELECTRICAL RECEPTACLE (BY OTHERS). FLUSH MOUNTED.

FRONT VIEW

*Caulk around perimeter of wall case all four sides where it joins the building Interior and Exterior. FINISH FLOOR

ge.com

See page 42 for line cord length.

29

0

METAL CASE EXTENSION FOR WALLS DEEPER THAN 1-1/8" (11-1/8" WITH SUB-BASE)
5. Suggested materials for case extension and flashing should be non-ferrous metals. Minimal acceptable material: Galvanized G-90 painted.

Field fabricated ge recommends the use of one of the deeper RAB71 wall cases offered as special order items.

2. The wall case and extension should be connected prior to installation in the wall opening. A quality grade sealant should be applied to all four (4) butting flanges. Use bolts and nuts or oversized self tapping screws (driven from the wall case to the extension) to attach the two assemblies. Clean all drain holes of excess sealant. The assembly must be free draining. . Install flashing, using a quality grade sealant between the flashing and wall as shown in section A-A below. 4. Install the wall case/extension assembly following procedures described for a standard installation. See diagrams below. The assembly should be sealed or caulked to the wall around all four sides both outdoors and indoors. NOTE: The wall case/extension assembly should be level.
CAULK*
WALL ANY CONSTRUCTION

1/4" MIN. CAULK*

ROOM CABINET

RAB71/77

CASE EXT.

6-1/4" 1/4" SEALANT - ALL FOUR (4) FLANGES D

Zoneline units can be installed in walls of greater depth than the wall case. Where the case recession is less than " and where it is possible to waterproof the exposed sides and top of the opening, the suggested procedure is to apply a flashing to the bottom of the wall case as shown on page 1. Where waterproofing is questionable or not possible, or for installations in walls of greater depth, the following is a suggested application procedure. It involves the field fabrication of a case extension. Since the wall case is a water bearing container, the extension likewise must also be water bearing and the connection between the two must be watertight. The case extension must contain splitters to prevent recirculation of the outdoor air circuit. 1. The case extension is field fabricated. The extension depth D should allow for a minimum outdoor projection of 1/4". This allows for room cabinet clearance to the finished wall and ample surfaces to apply sealant or caulking for a tight weather seal between the completed wall case/extension assembly and the wall opening. It is recommended that the extension be painted and corner and lap joints be additionally sealed with a quality grade sealant.
AS REQ'D. CAULK*

CAULK*

SPLITTER BETWEEN AIR INTAKE AND DISCHARGE


" 1/4

SEE DETAIL SECTION A-A

*Caulk around perimeter of wall case all four sides where it joins the building - Interior and Exterior.

-5 10

/8"

SECTION A-A BASEPAN/FLANGE DESIGN SHOWING SEALANT LOCATIONS. ALL 4 FLANGES WALL CASE ALL 4 SIDES CUT DRAIN SLOTS IN BOTH FLANGES (FOUR REQUIRED) TO MATCH DRAIN HOLES IN RAB71/77 EXTENSION

RAB71/77 WALL CASE


EXTENSION (FIELD SUPPLIED)

1-1/2" (4 SIDES)

FLASHING

ALL 4 SIDES

FLASHING (FIELD SUPPLIED) 1" WIDE 45 DRIP LIP

FLANGES AND DRAIN HOLE LOCATIONS SAME AS ON WALL CASE

2" MIN.

WALL

13-3/4" + D"

ALTERNATE CASE RECESSION LESS THAN " WITH SIDES AND TOP OF WALL OPENING WATERPROOF, FLASHING ON BOTTOM ONLY

B D

For an installation that will provide better protection against water infiltration, GE recommends the use of one of the deeper RAB71 wall cases offered as special order items. See page 2.
B

OUTDOOR GRILLE

CASE CAULK* A

FLASHING

1" WIDE 45 DRIP LIP *Caulk around perimeter of wall case all four sides where it joins the building - Interior and Exterior.

DIMENSIONS: A. DISTANCE FROM GRILLE OR CASE TO OUTSIDE SURFACE OF WALL PLUS 2" TO 4" (TO INSERT UNDER CASE). B. 1" DRIP LIP (MINIMUM) C. 42" PLUS - SUFFICIENT TO FIT SNUGGLY UNDER AND UP AROUND THE CASE. D. 2" MINIMUM (CAUTION: WHEN CAULKING DO NOT BLOCK DRAIN HOLES IN CASE OR GRILLE.) IF GRILLE IS TO BE MOUNTED TO WALL SURFACE A SPLITTERS MUST BE USED, SEE PAGE 30.

ge.com

1

ROOM CABINET

2

RAB71/77 WALL CASE INSTALLATION - RAK204 SERIES SUB-BASE CONNECTED


Example: frame & brick veneer - dimensional data and comments Are also applicable to other types of construction
Dimension A B TOP VIEW LEVELING SCREW RAB71 13-3/4" RAB77 13-7/8" D C 3" Min. (5" MAX.) 2-3/8" Minimum 0" Minimum 2" Recommended See pages 38-39 for ducted application. 1/4" (See note 1) Manufacturer Required Minimum Installation Clearance

2-3/8" MIN.

LEVELING SCREW

FINISHED INTERIOR WALL


7.70" 18.86" 1.5"

NOTE: 1. FOR OUTSIDE FLUSH MOUNTING SEE PAGE 31 FOR FLASHING INSTALLATION.

5.15"

BACK VIEW
8.80"

5.15"

7.70"

SIDE VIEW WITH WALL CASE SHOWN IN PLACE 1-5/16" RAB71 16" RAB77 16-1/4" 2-3/8" INTERIOR WALL

MAX. WALL THICKNESS 11-1/8"

10.30"

RECOMMEND 2" TO INTERIOR ADJACENT WALL BOTH SIDES. 1-1/2" 7/8" 42" SEE NOTE LEFT SIDE FRONT VIEW D

3" MIN. ADJUSTABLE TO 5" FINISHED FLOOR MOUNTING SCREWS AND HOLES BY INSTALLER

CAULK* C A

*Caulk around perimeter of wall case all four sides where it joins the building - Interior and Exterior.

13-3/4"

RAB71 16" RAB77 16-1/4" 3-11/16"


2-3/8" MIN. CASE EDGE TO FINISHED WALL

INTERIOR ADJACENT WALL 12-7/8" 13"

12-3/4"

B FINISHED FLOOR LEVELING SCREW KNOCKOUT SIZE LARGE 1-1/8" DIA. SMALL 7/8" DIA. KNOCKOUTS (ENCLOSURE) 4 REAR; 4 BOTTOM

CAULK* CAULK* LEVELING SCREWS (2) SUB-BASE BODY (2) SIDE EXTENSIONS CONDUIT ENTRY (ALTERNATES) SIDE VIEW

*SHOWN WITH ACCESS COVERS REMOVED. NOTE: CAUTION - REMOVE KNOCKOUTS FROM INSIDE OUT.

RAK204 SERIES SUB-BASE INSTALLATION AND ELECTRICAL DATA


RAB71/77 Wall Case
CHASEWAY OPTION (Shown Without Chassis and Wall Case for Installation Location Only.) RAK4002B NOTE: TYPE E MOUNTING CLIP MUST BE USED WITH MOLDED CASE. GREEN GROUND SCREW (TYPE C) METAL CASE 6"

MOLDED CASE

6"

5/32" DIA. HOLE (SEE NOTE) FOR SECURING TYPE D CLIPS TO SLEEVE USING TYPE A SCREWS

TYPE B SCREW SCREW CLIP TYPE D TYPE A SCREW

SUB-BASE MOUNTING CLIP TYPE E

TO SECURE SIDE CHANNELS

TYPE A

TYPE B

TYPE C

TYPE A SCREW 2 REQD. 8 REQD.

TYPE D TYPE E

USE WITH RAB71 USE WITH RAB77

TYPE C TYPE C 6 REQD. SCREW SCREW ACCESS PLATES SIDE CHANNELS ARE ADJUSTABLE FROM 13-3/4" TO 2-3/8" IN LENGTH BY BREAKING OFF SECTIONS OF SIDE NOTE: IF METAL CASE DOES NOT HAVE SCREW HOLES, 5/32" DIA. HOLES MUST CHANNELS. BE DRILLED 6" FROM EACH SIDE IN FRONT FLANGE. (SEE INSERT).

Electrical wiring may enter the sub-base through any of the knockout holes provided in the sub-base. Knockout holes in the sub-base access plate may accommodate a receptacle, which allows the use of a power cord (if permitted by code for the particular installation). A knockout for a circuit breaker, fuseholder or a disconnect is also provided. See pages 22 and 2 for description of electrical contents of these sub-bases.

ge.com



Condensate Disposal Systems


Cooling Condensate
Air conditioners produce condensate water as a result of lowering the humidity of the area being conditioned. When the indoor coil temperature is below the dew point, moisture in the air condenses into water droplets on the coil. This water drains to a pan located under the indoor coil and is routed through the barrier, the partition separating the indoor and outdoor sides of the unit, to the base pan on the outdoor side. It is then picked up and dispersed against the outdoor coil, which is hot when the unit is in the air conditioning mode. The water is evaporated into the atmosphere by contact with the hot outdoor coil. This evaporation process also helps lower the temperature of the outdoor coil and improves the operating efficiency of the unit.

Heat Pump Condensate Disposal


Since the outdoor coil is cold during heat pump operation, the condensate water cannot be deposited on the outdoor coil as the water would cause frost to form on the coil. This frost would block the airflow through the coil and greatly reduce the outdoor air. Rather than allow this problem to occur, heat pump units must dispose of the condensate in another manner.

Temperature-Activated Drain Valve


The most widely used method of disposing of heat pump condensate is with a Temperature-Activated Drain Valve. This is a device mounted in the base pan of a heat pump unit with a bellows that expands on temperature rise and contracts with temperature drop. A shaft with a rubber plug on the end is connected to the bellows. When the outdoor temperature remains above a certain temperature, the bellows is expanded and the plug fits tightly into a hole in the bottom, or base pan, of the unit. When the plug is blocking the hole, as it should be during cooling operation, the condensate water is contained in the base pan. At temperatures when heating is required, the bellows contracts, the rubber plug is retracted from the hole and the heat pump condensate water is allowed to drain into the wall case. The valve is fully open at 49F.

Slinger Ring Systems


Packaged Terminal units employ various means of dispersing the condensate water against the outdoor coil. One of the most popular, and most effective, means is by the use of a slinger ring. A slinger ring is a ring around the circumference of the outdoor fan. The design of the unit positions the slinger ring very close to the bottom of the base pan so water in the base pan is lifted by the rotating ring. Water picked up by the slinger ring will be dispersed into the air stream and deposited on the hot outdoor coil where it evaporates. All Zoneline Series Packaged Terminal Air Conditioners and Packaged Terminal Heat Pumps utilize a slinger ring for cooling condensate disposal.

Certification Test Requirements


ARI (Air Conditioning & Refrigerating Institute) requires that all certified Packaged Terminal Air Conditioners and Packaged Terminal Heat Pumps pass a cooling condensate disposal test. One stipulation of the ARI test is that the test start with condensate collection pan brimful. In order to pass the ARI Condensate Disposal Test the unit must operate continuously for four hours without condensed water blowing, dripping, or running off the unit casing during the test or after the unit has been turned off. Under extremely high outdoor humidity conditions or extreme operating conditions, such as exceptionally high air infiltration (a door or window left open while the unit is running, for instance) it is possible for any air conditioner to be unable to dissipate all the cooling condensate generated. All Zoneline Series Packaged Terminal Air Conditioners and Packaged Terminal Heat Pumps meet the condensate disposal requirements of ARI standards 10-9 and 80-9.

Drain Kits
Although the Zoneline units are designed to dissipate all of the condensate generated during normal cooling operation, there may be times when abnormal operating conditions cause more condensate than the unit can dissipate. Heat pumps also generate condensate that the unit may not be designed to dissipate. For these reasons, if condensate dripping from the wall case is objectionable, an internal or external drain system should be installed. See pages 5 and 6 for information covering the drain systems and the RAD10 kit available to connect to the wall case.

Internal Condensate Removal (ICR) System


GE has developed an Internal Condensate Removal (ICR) System for Packaged Terminal Heat Pumps. This system has been offered as an option on Zoneline Packaged Terminal Heat Pumps since 1982, and thousands of them are in use. During heat pump operation the ICR system utilizes a small pump to lift the water from the base pan and pump it into a collector tray positioned above the indoor coil. The water drains from the collector tray and drips onto the warm indoor coil where it is evaporated into the room atmosphere. If an excess amount of water is pumped to the indoor side, it is routed back to the outdoor portion of the base pan. The ICR system has proven to be an effective means of minimizing the amount of heat pump condensate dripping from the unit. However, if the restrictions of a particular installation will allow absolutely no drippage of condensate water from the wall case, the installation of an internal or external drain system is recommended. Units with ICR may not be installed in seacoast or corrosive environment applications.

Heat Pump Condensate


During the operation of a unit in the heat pump, or reverse cycle, mode the outdoor coil becomes the cold coil and the indoor coil becomes the hot coil due to reversing the flow of the refrigerant. When the temperature of the outdoor coil is below the dew point, condensation will form on the outdoor coil just as it does on the indoor coil during cooling operation. Since the dew point is humidity- as well as temperaturerelated, there may be more condensate on days when the relative humidity is high.
4

WALL CASE WITH RAD10 DRAIN KIT


External Drain. See page 6 for internal drain.

SCREWS

METAL

PLASTIC

SEE PAGE 36 NOTE #6

SQUARE DRAIN HOLES 1/2" O.D. 90 ELBOW DRAIN TUBE NEOPRENE SPONGE GASKET

NOTE: SHADED PARTS AND SCREWS ARE INCLUDED WITH RAD10 DRAIN KIT. USE EITHER THE Alternate 90 ELBOW TUBE OR 6" long, 1/2" THE STRAIGHT TUBE O.D. straight DEPENDING UPON copper tube. THE REQUIREMENTS OF THE PARTICULAR INSTALLATION.

TYPICAL INSTALLATION CASE ANGLES (FIELD SUPPLIED) Caulk around perimeter of wall case all four sides where it joins the building.

STEEL MOUNTING PLATE

USE TYPE A SCREW FOR METAL CASE (RAB71) AND TYPE B SCREW FOR MOLDED CASE (RAB77)

WATER DRAINAGE - Precipitation entering the unit through the outdoor louver may not be removed entirely by the condensate removal system. The base pan flange is designed to allow excess water, either condensate water or precipitation, to flow into the wall case and drain through two drain holes in the rear of the wall case. If there is more water in the wall case than can be drained through these holes it will drain through the three overflow drain holes. These drain holes must not be blocked when mounting or caulking the wall case.

REAR GRILLE 90 ELBOW DRAIN TUBE PROJECTION BEYOND WALL CASE 3" 4"

WALL CASE

ROOM CABINET

For those installations where water draining from the drain holes is objectionable or where positive drainage is desired, the RAD10 drain kit is available with either a 90 elbow or a 6" straight tube to be used either to connect to a field supplied drain line or to allow the water to drip free rather than drain down the surface of the building.

NOTE: Drain kit using either the 90 elbow tube or the straight tube may be installed without modification when using RAG60 exterior grille. Drain kit using the 90 elbow tube may be installed without modification when using RAG61 through RAG66 exterior grilles. Modification must be made to the RAG61 through RAG66 exterior grilles when using the straight tube. Modification must be made to the RAG67 grille if using either the 90 elbow tube or the straight tube (see installation instructions with the RAG67 grille).

MIN. 2 SUPPORTS FIELD SUPPLIED

FLOOR

ge.com

5

6

WALL CASE WITH RAD10 DRAIN KIT


Internal Drain. See page 5 for external drain.

NOTE: SHADED PARTS AND SCREWS INCLUDED WITH RAD10 DRAIN KIT. THE 90 ELBOW TUBE IS RECOMMENDED FOR INTERNAL DRAIN INSTALLATION.

SCREWS

SEE DETAIL BELOW

A
OVERFLOW RELIEF DRAIN SEE NOTE 6 SQUARE DRAIN HOLES NEOPRENE SPONGE GASKET

METAL

PLASTIC

STEEL MOUNTING PLATE

NUT (MOLDED CASE (RAB77) ONLY) GASKET

USE TYPE A SCREW FOR METAL CASE (RAB71) AND TYPE B SCREW FOR MOLDED CASE (RAB77)

DETAIL

CABINET BOTTOM

TUBE 1/2" OD COVER PLATE

1. The RAD10 drain kit is installed in the bottom of the wall case when it is desired to drain condensate to an internal drain system in the building. 2. The drain kit is mounted on the bottom of the wall case prior to installation of the case in the wall. It may be located anywhere on the room side portion except for sub-base installations. For these the drain should be at least " from the indoor edge of the case so as to adequately clear the sub-base. . A template is furnished with the kit for locating the necessary  holes in the case bottom - two to provide a securing means and one to provide a drain hole for the 1/2" od tubing. (See details at left) 4. A tube or hose 1/2" I.D. (Obtained locally) must be installed on the drain tube and connected to the internal drain system in the building. 5. With the RAD10 the two square drain holes in the bottom outer flange of the wall case are sealed by the gaskets and mounting plates shown above. 6. Three () 1/2" diameter holes located 1/4" above the case bottom in the bottom outer flange provide overflow drainage to the outdoors when wind driven rain enters the chassis.

USE TYPE A SCREWS FOR BOTH RAB71 AND RAB77

Ducted Installations
2800 and 800 Series Zoneline units may be used in ducted installations.
With a ducted installation it is possible to condition the air in two areas that have a common wall separating them. A special adapter mounts on the wall case and a transition piece directs the air from the unit into the adapter. Instructions for mounting the adapter to the wall case are included with the duct adapter. The adapter contains a grille that allows air from the unit to be discharged into the primary room and the adapter connects to a duct extension that allows the air to flow to the adjoining room. Ducting a unit may allow a single unit to be used rather than a separate unit in each room, providing a means of reducing initial equipment cost. The duct may extend a total of 15 feet (with a field fabricated insulated duct extension) in one direction, either to the right or to the left of the unit. A baffle in the adapter allows up to 50% of the discharge air to be delivered to the secondary room. The installation of the wall case and sub-base, if used, is the same for units being ducted as for free-standing units. The duct adapter support bracket overlaps the wall case by 1" and the bracket and mounting screws add approximately /8" (/16" on each side) to the width of the wall case. If less than 1" of the wall case projects into the room it will be necessary to allow for the additional width in the opening for the wall case. The duct adapter mounting brackets should be mounted prior to installing the case in the wall. Refer to pages 8 and 9 for drawings of ducted installations. Prior to the installation of the transition from the room cabinet to the adapter, it will be necessary to remove the discharge grille from the room cabinet. Instructions for this modification are included with the duct adapter.

ge.com
RAK601 Duct Extension, Mounting Collar and Register one end of the duct to accept the collar and supply register. Mounting Collar and Supply Register RAK602 These components are included in the Duct Extension Kit RAK601. They may be ordered separately for installations where two duct extensions are made from one RAK601.

Ducted Application Considerations


When designing a ducted application some application considerations to be made include: 1. Do not exceed the 15-foot length maximum for the duct extension. Field supplied duct extension must be completely insulated with minimum of 1/2" insulation 2. The duct must be a straight run. Turns or bends in the duct extension create air pressure drops that the unit is not designed to overcome. . Minimum recommended clearance between the unit and the adjacent wall is 2". 4. Provisions for return air must be made to allow air circulation from secondary room. Doors in both secondary and primary rooms may be undercut or a return grille may be installed through a common wall. 5. When calculating the heat gain/heat loss take both areas into consideration.

Replacements of Existing Ducted Units


Since the design of the Zoneline chassis has changed over the years to provide better performance and appearance, some of the components used in ducted applications have changed. Select the proper components from the information below. The best procedure in determining the correct kit is to measure duct extension cross section.

New Ducted Installations


Duct Adapter RAK6052

Flat Top-Discharge Units (Zoneline Units Built Prior to 1988)

Components
Duct Adapter RAK6052 The duct adapter is secured to each side of the wall case and requires the drilling of mounting holes in the wall case during installation. A template for the hole location is in the installation instructions. By securing the duct adapter to the wall case, the chassis retains the slide-out feature for servicing after the transition piece is removed. Duct Extension RAK601 This kit contains a 44"-long insulated duct, a register mounting collar, and an air supply register. It can be secured to the duct adapter at either end of the adapter. This duct may be cut at any dimension and used in two applications providing the sum of the two duct lengths necessary do not exceed the 44" length. Even in single applications the mounting flange must be cut off

Existing Duct Extension Cross Section Measurements: 8-/8" height x 6-1/2" width Duct Adapter RAK7012 This duct adapter will allow the replacement of a new chassis (2800 or 800 Series unit) into an existing ducted application. This adapter will align properly with the duct extension and will eliminate the need to modify the wall opening. In order to minimize replacement costs, some of the components of the old duct adapter must be removed and used in the new installation. Consult the Installation Instructions of the RAK7012 before removing and discarding the old duct adapter. See additional notes page 58.

Slope-Front Discharge Units (Models With AZC, AZR, AZW, or AZ21 or AZ1 Prefix)
Existing Duct Extension Cross Section Measurements: 7-/2" height x 6-1/2" width Duct Transition RAK7022 This duct transition will allow the replacement of a new slope-front discharge Zoneline chassis (2800 or 800 Series unit) into a previous design slope-front 7 ducted installation. See additional notes page 58.

8

DUCTED APPLICATION (AZ2800/800 SERIES)

44" RAK601 44" LENGTH

RAK6052 ADAPTER 8" high

TRANSITION

8" 3/ 7- de i w

RECOMMENDED MINIMUM CLEARANCE 2" TO SIDE WALL

Notes: 1. RAK6052 kit includes duct adapter, transition and mounting hardware. 2. RAK601 duct extension may be installed at either end of the RAK6052 duct adapter. Maximum duct extension length is 15'. Duct extension must be field fabricated for installations where length of duct exceeds length of RAK601 (44"). Field fabricated duct extension must be insulated to prevent condensation from forming on exterior. Duct extension may not contain bends or turns. . Ducted units may need to be permanently connected. Check local code for specific electrical installation requirements. 4. Duct extension kit RAK601 contains 44" duct extension, discharge grille mounting collar, and discharge grille. Duct extension must be cut to required length. Two ducted installations may be made from one kit if the combined ducted length is less than 44". RAK602 kit contains mounting collar, discharge grille and mounting hardware necessary for second installation. 5. Filler strip (field supplied) actual width depends upon wall case projection into room. A flush installation to finished wall (I.E., No filler strip) can be made. 6. Unit must be installed to provide at least a 2" clearance between side of unit and wall. 7. Provisions for return air must be made in order to allow air circulation from secondary room. Doors in both secondary and primary rooms may be undercut or a return grille may be installed through common wall. 8. For replacement of previous design units, see pages 7 and 58.

DUCT ADAPTER EXTENSION HAS 1/2" INSULATION

DUCTED DETAILED SIDE VIEWS (AZ2800/800 SERIES)


See page 8 for all notes Sub-Base Installation

Line Cord Installation

ANY CONSTRUCTION 2-3/8"* MIN. 6-1/2" 11-1/8" MAX. 12-3/4" MAX.

6-1/2"

10"

7-3/32"

RAK6052 ADAPTER 7-3/32" RAK6052 ADAPTER

2-29/32" 2-29/32"

1/4" MIN.

1/4"

TRANSITION

3/4" MIN. WALL TO CASE EDGE

TRANSITION

Caulk around perimeter of wall case all four sides where it joins the building - Interior and Exterior. WALL CASE

16-1/8" WALL CASE

16-1/8" ROOM CABINET

FINISHED FLOOR

FINISHED FLOOR 3" MIN. 5" MAX. RAK 204

RECEPTACLE CAULK* (BY OTHERS ALT. LOCATIONS) CAULK*

RAG60 - 1/4" RAG61-66 - 1-3/8"

FILLER STRIP (SEE NOTE 5 ON PAGE 36)

ROOM CABINET

RAG60 - 1/4" RAG61-66 - 1-3/8"

3-11/16"

*Caulk around perimeter of wall case all four sides where it joins the building - Interior and Exterior.

*2-3/8" min. when installed with RAK204.

ge.com

9

Exterior Grilles
Four styles of outdoor grilles are available for exterior treatments. The standard stamped aluminum grille (RAG60), the molded architectural louvered exterior grilles (RAG61-6), the molded architectural louvered exterior grilles with flange (RAG64-66), and the extruded aluminum architectural louvered grille (RAG67). All grilles include air deflectors and gaskets to prevent condenser air recirculation.

RAG67

RAG60 Outdoor Grille RAG60 Outdoor Grille The standard exterior grille is made of durable aluminum to protect chassis components and prevent air recirculation.

RAG67 Extruded Aluminum Grille The RAG67 is made from extruded anodized aluminum for use where an aluminum architectural grille is preferred. The RAG67 is available in a clear finish and may be special ordered from GE in other colors. Minimum order quantities may be required. Contact your General Electric salesperson for details. All grilles are installed and secured to the wall case from the inside. Keyhole slots in the rear flange of the case allow the grille to be placed in position before securing it firmly to the wall case. Replacement of existing units: If an existing grille is not replaced, capacity and efficiency will be reduced and the unit may fail to operate properly or fail prematurely. A deflector kit, RAK40, may be used with grilles that were not designed for current AZ Series GE Zoneline units. The RAK40 contains air deflectors and gaskets that mount to the chassis to direct the hot exhaust air away from the air intake to allow the unit to function properly. All grilles used with GE Zoneline units must comply with requirements of Exterior Architectural Treatments and Special Outdoor Grilles as follows.

RAG61 Outdoor Grille

RAG61, 62, 6 Architectural Grille One-piece optional molded grille and frame assembly provides improved appearance, protection and weatherability. Molded of durable polycarbonate, the surfaces of the grille have a colorfast, slightly textured finish which blends well with most types of wall surfaces. The grilles can be painted in the field to match the building for improved aesthetics.

RAG64 Outdoor Grille

RAG64, 65, 66 Architectural Grille with Flange Identical to RAG61-6 grilles with the addition of a 1/2" flange around the top and sides to help conceal the juncture of the RAB71 wall case and the wall opening. The best appearance is achieved with this grille when the wall case extends minimally (between 1/4" and 1/2") beyond the exterior face of the building. Colors: RAG61 and 64 Beige; RAG62 and 65 Dark Maple RAG6 and 66 Bittersweet Chocolate.

40

Exterior Architectural Treatments and Special Outdoor Grilles


The architectural design of a building may dictate the use of special or oversized louvers for aesthetic reasons. Louvers other than standard Zoneline exterior grilles may be used on the Zoneline unit, however, these special louvers, or any special exterior architectural treatments of the building facade that may restrict the free circulation of condenser airflow, should be referred to GE Application Engineering for evaluation and approval. The following guidelines should be followed in selecting a louver: 1. The louver must have a minimum of 65% free area. ASHRAE defines free area as the minimum area of the opening in an air inlet or outlet through which air can pass. Percent (%) free area equals the X dimension divided by the Y dimension. 2. The louver should be attached to the wall case in a manner that will prevent recirculation of condenser discharge air into the air inlet. If the louver is not attached directly to the wall case, a field supplied splitter or gasket is required between the chassis and the louver to prevent recirculation. It is important that the above criteria be followed since a louver that is too restrictive or allows recirculation will reduce the units capacity and efficiency, increase the electrical current draw, cause intermittent operation due to the compressor overload protector shutting the compressor off, and cause failure of the compressor overload and shorten compressor life. Using the unit with a grille that is too restrictive or allows recirculation may constitute improper installation. A scale drawing of the louver section should be sent to GE Application Engineering. To assure the proper performance of the Zoneline unit and comply with Underwriters Laboratories requirements, it may be necessary to send a sample louver section (at least 16" x 42") to GE to be tested with the Zoneline unit.
Sample Calculations x Free Area (%) = x 100 x = 1" y = 1.5" y 1 F.A. % = 1.5 x 100 = 66.7%

ge.com

41

Power Connection for 2800, 800 and 5800 Series Zonelines


All 2800, 800, and 5800 Series Zonelines are equipped with universal heaters allowing chassis installation flexibility. The Zoneline units are connected to the building power supply by a unique power connection kit. By utilizing a separate universal power connection (UPC) kit, each unit is capable of providing various outputs of electric resistance heat to more closely meet the heating requirements of the particular room, thereby increasing the installation flexibility of the particular chassis. This power connection kit is the only means of supplying power to the Zoneline chassis. The appropriate kit is determined by the voltage, the means of electrical connection, either line cord connected or permanently connected, and the desired resistance heat output that may be supported by the branch circuit. For 2800 and 800 Series 20/208-volt units where a permanent installation using flexible conduit is desired, the RAK4002A forms an enclosed junction box on the chassis. The RAK4002A has a 7/8" diameter hole to allow conduit to be connected to the junction box. A line cord kit, shown above under Line-Cord Connected units, must be purchased and modified to allow direct connection to the building wiring. The line cord kit should be cut about 8" from the nine-pin connector. Strip insulation off 5/8" of each conductor to expose wires for field connection. These wires are then connected to the building wiring by field-supplied connectors. For 5800 Series 20/208-volt units, the permanent installation using flexible conduit procedure is the same as for the 2800 and 800 Series units, except the junction box kit is RAK4002B.

20/208-Volt Line-Cord Connected Units


Line Cord Kits consist of a self-aligning nine-pin molded connector that plugs into a mating connector on the Zoneline chassis and insulated line cord with an electrical plug on the end. The configuration of the electrical plug conforms to NEC standards for the circuit amperage and the position of the wires in the nine-pin connector determines the heater wattage and current requirements when it is plugged into the Zoneline chassis. The power connection kit is selected by the amperage of the circuit where it will be installed. Each line cord kit has an integral Leakage Current Detection and Interruption (LCDI) or Arc Fault Current Interrupter (AFCI) device as required by the National Electrical Code (NEC) and Underwriters Laboratory (UL) for line-cord connected air conditioners manufactured on or after August 1, 2004. The line-cord power connection kits are shown in the table below.

20/208 Volt Sub-Base and Direct Connected Units


Sub-Base
RAK204D15P RAK204D20P RAK204D0P

Direct Connection Kit


RAK4157 RAK4207 RAK407

Electric Heat BTUH

Electric Heater Watts

Electric Heat Amps


11.6/10.6 15.5/14.1 22./20.

Min. Circuit Protection (Amps)


15 20 0

8600/7100 2550/2090 11700/9600 450/2820 170100/1900 5000/4090

Electric Heat Amps include electric heater and fan motor current draw.

265- or 277-Volt Unit Installation Permanently Connected Units


National Electric Code (Article 440 Section G) requires permanent connection for units connected to power sources over 250 volts; therefore these units must be permanently connected (direct wired) with field-supplied connectors. Units connected using a sub-base meet the requirement for permanent connection since all wiring is internal wiring between the sub-base and the chassis. Since 265-volt units may not be line cord connected, an LCDI device is not required.

20/208-Volt Line-Cord Connected Units


Line Cord Kit
RAK15 RAK20 RAK0

Electric Heat BTUH


8600/7100 11700/9600 17000/1900

Electric Heater Watts


2550/2090 450/2820 5000/4090

Electric Heat Amps


11.6/10.6 15.5/14.1 22./20.

Min. Circuit Protection (Amps)


15 20 0

265 Volt Sub-Base and Direct Connected Units


Sub-Base
RAK204E15 RAK204E20 RAK204E0

Electric Heat Amps include electric heater and fan motor current draw.

20/208-Volt Permanently Connected Units


Permanently connected units do not require the LCDI or AFCI device. Permanent connection is usually made through the use of a sub-base. Each 20/208-volt sub-base consists of a sub-base with appropriate receptacle for minimum circuit amperage, a chaseway to route power connector from the sub-base to the chassis, wiring to connect the sub-base to building wiring and a short-line cord with a self-aligning nine-pin connector to connect to chassis and plug into the receptacle in the sub-base. Permanent, or direct wired, installation of a 20/208-volt unit requires a junction box kit, RAK4002A, which attaches to the chassis to form an enclosed junction box. The short sub-base line cord may not be used without the sub-base.
42

Power Direct Electric Electric Electric Min. Circuit Connection Connection Heat Heater Heat Protection Kit Kit BTUH Watts Amps (Amps)
RAK5172 RAK5202 RAK502 RAK5157 RAK5207 RAK507 8600 11700 17000 2550 450 5000 9.6 1.0 18.9 15 20 0

Electric Heat Amps include electric heater and fan motor current draw. Each 265-volt sub-base kit consists of a sub-base with appropriate receptacle for minimum circuit amperage, a chaseway to route the power connector from the sub-base to the chassis and wiring to connect the sub-base to the building wiring.

The 265-volt power connection kit must be ordered separately. All wiring must conform to local electrical regulations and codes.

ge.com

Essential Elements Ordering Overview


20/208-volt line-cord connected units order line cord kit. 20/208-volt sub-base connected units order sub-base (includes power connection kit) and junction box for chassis. 265-volt units order sub-base and power connection kit separately.

Permanent Connected Units With Sub-Base


If the existing unit is connected to a sub-base the installation of the new unit may involve modifying the existing installation slightly. It is recommended these modifications be made by a qualified electrician. If the existing sub-base is the full width of the wall case, RAK201 sub-base access plate may be ordered and used to replace the cover on the old sub-base. Field-supplied wiring, conduit and conduit connectors should be used to make a connection between the new chassis and the center knockout of the RAK201. The wiring connections should be made inside the sub-base and the RAK201 attached to the sub-base with the two screws provided. If the existing sub-base is not the full width of the wall case, the electrician will have to modify the existing cover plate to allow field-supplied wiring, conduit and conduit connectors to be run from the permanent connection kit to the sub-base.

Electrical Wiring Information 2800/800/5800 Series


All Zonelines are single-phase 60 hertz units. For all installations, the feeder, sub-feeder, branch circuit and electrical protective devices and selection must conform to the National Electrical Code and to local codes. Maximum connected load in amperes, including demands for the electric heater and the fan motor, are shown on page 44. Branch circuit ampacity and electrical protective device sizing are shown on page 42 for 20/208-volt units and on this page for 265-volt units. More than one unit per branch circuit is not recommended. When in doubt, consult the National Electrical Code. All wiring, including installation of receptacle, must conform to local electrical regulations and codes.

Replacement of Existing Chassis


20/208-Volt and 265-Volt Units
There have been changes to NEC and improvements and modifications to the Zoneline chassis and sub-bases since the unit was first introduced. Some of these changes require alterations to be made when replacing an older unit with a new chassis.

Line-Cord Connected Units


The plug configuration of new line cord connected units complies with the current NEC standards. Older installations may have wall receptacles that conformed to NEC standards at the time the building was constructed and may not match the configuration of the plug on the new line cord. The recommended solution is to change the wall receptacle to conform to current standard plug configuration. See chart on this page for current receptacle configuration. Enclosure cover removed. RAK4002A Wiring harness can be ordered separately as RAK4002CW.

Receptacle
Type
15 AMP Tandem NEMA6-15R 20 AMP Perpendicular NEMA6-20R 0 AMP Large Tandem NEMA6-0R

Mfg
Hubbell P&S

Part No
5661 5661

Configuration

58" 21" Inside

Hubbell P&S

5461 5871

Typical Line Cord Power Connection Kit RAK20 shown

Maximum Cord Extension

Hubbell P&S

90 590

4

Maximum Connected Load


The maximum connected load of a Zoneline unit occurs when the unit is in resistance heating operation. The maximum amperage shown in the tables below is the combined total of the resistance heater and the indoor fan motor.

20/208-Volt Line Cord Connected Units


Power Connector Kit RAK15 RAK4157 RAK204D15P MODEL NUMBER
AZ28E07DA* AZ28E09DA* AZ28E12DA* AZ28E15DA* AZ8H07DA* AZ8H09DA* AZ8H12DA* AZ8H15DA* AZ58H07DA* AZ58H09DA* AZ58H12DA* AZ58H15DA*

RAK20 RAK4207 RAK204D20P 208 V


10.5 10.5 10.6 10.6 10.5 10.5 10.6 10.6 10.5 10.5 10.6 10.6

RAK0 RAK407 RAK204D0P 208 V


14.1 14.1 14.1 14.2 14.1 14.1 14.1 14.2 14.1 14.1 14.1 14.2

20 V
11.5 11.5 11.6 11.6 11.5 11.5 11.6 11.6 11.5 11.5 11.6 11.6

20 V
15.5 15.5 15.5 15.6 15.5 15.5 15.5 15.6 15.5 15.5 15.5 15.6

20 V
N/A 22. 22. 22.4 N/A 22. 22. 22.4 N/A 22. 22. 22.4

208 V
N/A 20. 20. 20.4 N/A 20. 20. 20.4 N/A 20. 20. 20.4

*All versions Electric Heat Amps include electric heater and fan motor current draw. Values shown in table above are also the total connected loads for units installed with sub-bases. RAK204D15P same as RAK15 RAK204D20P same as RAK20 RAK204D0P same as RAK0

265-Volt Units
Sub-Base/Power Connector Kit RAK204E15 RAK5172 RAK5157 MODEL NUMBER
AZ28E07EA AZ28E09EA* AZ28E12EA* AZ28E15EA* AZ8H07EA* AZ8H09EA* AZ8H12EA* AZ8H15EA* AZ58H07EA* AZ58H09EA* AZ58H12EA* AZ58H15DA*

RAK204E20 RAK5202 RAK5207 265 V


1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7

RAK204E0 RAK502 RAK507 265 V


N/A 19.6 19.6 19.6 N/A 19.6 19.6 19.6 N/A 19.6 19.6 19.6

265 V
10.2 10.2 10. 10. 10.2 10.2 10. 10. 10.2 10.2 10. 10.

*All versions Electric Heat Amps include electric heater and fan motor current draw.

44

Cooling Performance Data


Total Capacity - BTUH BTUH at 80 F D.B. - 67 F W.B.
Zoneline 2800 & 800 Series
Nominal Capacity Temperature of Air Entering Condenser 75 82 85 95 105 115 7000 7750 7500 7400 7100 6700 600 9000 9950 9700 9500 9000 8400 7800 12000 12950 12600 1250 11700 11000 10400 15000 15850 15500 1500 14600 1600 1200 7000 7400 7200 6950 6800 6400 6000

ge.com

Zoneline 2800 Dry Air 25


Nominal Capacity 9000 9500 9200 9050 8600 8100 7650 12000 12250 11900 11750 11200 10600 10000 7000 7750 7500 7400 7100 6700 600

Zoneline 5800 Series


Nominal Capacity 9000 9950 9700 9500 9000 8400 7800 12000 12950 12600 1250 11700 11000 10400 15000 15850 15500 1500 14600 1600 1200

Heat Pump Performance Data


Capacities and COP at Various Outdoor Temperatures BTUH at 70 F Indoor Temperature
Zoneline 800 Series
Outdoor Temperature F 65 60 55 50 47 45 40 5 0 25 7000 7500 7200 6900 6600 6400 6250 5950 5600 5250 4700 .85 .80 .75 .65 .60 .55 .45 .5 .20 .05 10000 9600 9100 8700 8400 8200 7700 7100 6500 5900 9000 .85 .80 .75 .65 .60 .55 .45 .5 .20 .05 12950 12500 11850 1100 10900 10600 9800 9200 800 7500 12000 .65 .60 .55 .45 .40 .5 .20 .10 .00 2.85 15950 1500 14650 1850 1400 1050 12250 1100 1000 9250 15000 .45 .40 .5 .25 .20 .15 .05 2.95 2.85 2.75

All data at 20 volts and 265 volts.

Zoneline 5800 Series


Outdoor Temperature F 65 60 55 50 47 45 40 5 0 25 7000 7500 7200 6900 6600 6400 6250 5950 5600 5250 4700 .85 .80 .75 .65 .60 .55 .45 .5 .20 .05 10000 9600 9100 8700 8400 8200 7700 7100 6500 5900 9000 .85 .80 .75 .65 .60 .55 .45 .5 .20 .05 12950 12500 11850 1100 10900 10600 9800 9200 800 7500 12000 .65 .60 .55 .45 .40 .5 .20 .10 .00 2.85 15950 1500 14650 1850 1400 1050 12250 1100 1000 9250 15000 .45 .40 .5 .25 .20 .15 .05 2.95 2.85 2.75

All data at 20 volts and 265 volts.

45

Latent System Capacity


The total capacity of an air conditioner is made up of the Sensible capacity, the output of the unit used to remove heat from the air in the area being conditioned, and the Latent capacity, the output of the unit used to dehumidify the air in the area being conditioned. For humid climates and applications, the Sensible/Latent capacity split of the unit should be considered. The Sensible capacity listed in the specification charts on page 55 is at a standard rating condition of 95F dry bulb/75F wet bulb outdoors; 80F dry bulb/67F wet bulb indoors. The Latent system capacity is 1.00 minus the Sensible capacity. (If the Sensible capacity is listed at .74 the Latent capacity is .26. This means that 74% of the capacity of the unit is used to remove heat from the air and 26% is used to remove moisture form the air at standard test conditions.) In some applications information about the Sensible/Latent split, or ratio, at conditions other than the standard rating conditions is needed. The chart below provides data at various indoor conditions.

Cooling Sensible Heat Ratio (SHR) at Various Indoor WB and DB Temperatures


MODEL
All 7000 BTUH units except Dry Air 25

Indoor WB (F)

Indoor Ambient DB Temperature (F)


60 0.51 65 0.67 0.46 70 0.8 0.62 0.42 0.65 0.54 0.5 0.77 0.55 0.42 0.60 0.42 0.2 0.71 0.54 0.41 0.60 0.41 0.1 0.71 0.54 0.41 75 0.99 0.77 0.60 0.42 0.80 0.68 0.52 0.2 0.9 0.70 0.55 0.8 0.75 0.57 0.45 0.0 0.88 0.68 0.54 0.6 0.75 0.56 0.44 0.1 0.88 0.68 0.54 0.6 80 1.00 0.92 0.75 0.54 0.95 0.80 0.66 0.45 1.00 0.8 0.68 0.49 0.92 0.7 0.58 0.8 1.00 0.81 0.67 0.47 0.92 0.72 0.57 0.40 1.00 0.81 0.67 0.47 85 1.00 1.00 0.88 0.66 1.00 1.00 0.79 0.58 1.00 0.96 0.81 0.60 1.00 0.90 0.70 0.48 1.00 0.9 0.80 0.58 1.00 0.89 0.70 0.50 1.00 9.00 0.80 0.58 90 1.00 1.00 1.00 0.78 1.00 1.00 0.92 0.7 1.00 1.00 0.9 0.71 1.00 1.00 0.85 0.61 1.00 1.00 0.9 0.71 1.00 1.00 0.84 0.61 1.00 1.00 0.9 0.71 95 1.00 1.00 1.00 0.90 1.00 1.00 1.00 0.85 1.00 1.00 1.00 0.82 1.00 1.00 1.00 0.74 1.00 1.00 1.00 0.82 1.00 1.00 0.99 0.7 1.00 1.00 1.00 0.82 100 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0.9 1.00 1.00 1.00 0.85 1.00 1.00 1.00 0.9 1.00 1.00 1.00 0.84 1.00 1.00 1.00 0.9

59 6 67 71 AZ28E07DAP/EAP 59 (Dry Air 25) 6 67 71 All 9000 BTUH 59 units except 6 Dry Air 25 67 71 AZ28E09DAP/EAP 59 (Dry Air 25) 6 67 71 All 12000 BTUH 59 units except 6 Dry Air 25 67 71 AZ28E12DAP/EAP 59 (Dry Air 25) 6 67 71 All 15000 BTUH 59 units except 6 Dry Air 25 67 71 Capacities are nominal capacity

0.8

0.49 0.8

0.42

0.59 0.40

0.0

0.45 0.2

0.8

0.54 0.40

0.0

0.45 0.0

0.8

0.54 0.40

46

Normal Yearly Operating Data


(Cooling Hours based on 75F indoor temperature with air conditioner sized to meet the design conditions.)
ASHRAE Heating Degree Days Estimated Cooling Hours ASHRAE Heating Degree Days Estimated Cooling Hours ASHRAE Heating Degree Days

ge.com

Location

Location

Location

Estimated Cooling Hours

ALABAMA Birmingham Huntsville Mobile Montgomery ARIZONA Flagstaff Phoenix Tucson Yuma ARKANSAS Fort Smith Little Rock CALIFORNIA Bakersfield Fresno Los Angeles Sacramento San Diego San Francisco COLORADO Colorado Springs Denver Grand Junction CONNECTICUT Hartford DISTRICT of COLUMBIA Washington DELAWARE Wilmington FLORIDA Jacksonville Miami Orlando Tallahassee Tampa GEORGIA Atlanta Augusta Macon Savannah IDAHO Boise Lewiston Pocatello ILLINOIS Chicago Moline Springfield INDIANA Evansville Fort Wayne Indianapolis South Bend IOWA Burlington Des Moines Sioux City KANSAS Dodge City Goodland Topeka Wichita

2,551 ,070 1,560 2,291 7,152 1,765 1,800 974 ,292 ,219 2,122 2,611 2,061 2,502 1,458 ,015 6,42 6,28 5,641 6,25 4,224 4,90 1,29 214 766 1,485 68 2,961 2,97 2,16 1,819 5,809 5,542 7,0 6,155 6,408 5,429 4,45 6,205 5,699 6,49 6,114 6,588 6,951 4,986 6,141 5,182 4,620

1,90 1,40 1,640 1,580 10 2,280 1,920 2,520 1,410 1,0 1,50 1,210 10 1,00 90 110 520 550 910 480 1,010 770 1,690 2,850 1,90 1,500 2,50 1,10 1,400 1,440 1,510 670 600 570 780 760 890 1,090 710 820 600 70 710 770 1,020 800 880 1,070

KENTUCKY Lexington Louisville LOUISIANA Alexandria Baton Rouge New Orleans Shreveport MAINE Portland MARYLAND Baltimore MASSACHUSETTS Boston MICHIGAN Detroit Flint Grand Rapids MINNESOTA Duluth Minneapolis MISSISSIPPI Jackson MISSOURI Columbia Kansas City Springfield St. Louis MONTANA Billings Glasgow Great Falls Missoula NEBRASKA Grand Island Omaha NEVADA Ely Las Vegas Reno NEW JERSEY Newark NEW MEXICO Albuquerque Clayton Silver City NEW YORK Albany Binghamton Buffalo New York Rochester Syracuse NORTH CAROLINA Asheville Charlotte Raleigh Winston-Salem NORTH DAKOTA Bismarck Fargo Williston

4,68 4,660 1,921 1,560 1,85 2,184 7,511 4,654 5,64 6,29 7,77 6,894 10,000 8,82 2,29 5,046 4,711 4,900 4,900 7,049 8,996 7,750 8,125 6,50 6,612 7,7 2,709 6,2 4,589 4,48 5,158 ,705 6,875 7,286 7,062 4,811 6,748 6,756 4,042 ,191 ,9 ,595 8,851 9,226 9,24

80 1,10 1,670 1,860 1,790 1,470 290 850 500 590 440 50 200 550 1,560 960 1,210 970 1,080 520 410 420 50 770 750 500 1,980 520 710 1,040 720 1,260 480 10 450 790 470 500 690 1,20 1,070 960 510 490 580

OHIO Cincinnati Cleveland Columbus Dayton Toledo OKLAHOMA Oklahoma City Tulsa OREGON Medford Pendleton Portland PENNSYLVANIA Harrisburg Philadelphia Pittsburgh Scranton Williamsport RHODE ISLAND Providence SOUTH CAROLINA Charleston Columbia Greenville SOUTH DAKOTA Rapid City Sioux Falls TENNESSEE Chattanooga Knoxville Memphis Nashville TEXAS Corpus Christi Dallas El Paso Houston Lubbock San Antonio UTAH Milford Salt Lake City VERMONT Burlington VIRGINIA Norfolk Richmond Roanoke WASHINGTON Seattle Spokane Yakima WEST VIRGINIA Charleston Huntington WISCONSIN Madison Milwaukee WYOMING Casper Cheyenne Sheridan

5,265 6,51 5,660 5,622 6,494 ,725 ,860 5,008 5,127 4,65 5,251 5,144 5,987 6,254 5,94 5,954 2,0 2,484 2,980 7,45 7,89 ,254 ,494 ,22 ,578 914 2,6 2,700 1,96 ,578 1,546 6,497 6,052 8,269 ,421 ,865 4,150 5,145 6,655 5,941 4,476 4,446 7,86 7,65 7,410 7,81 7,680

840 610 810 740 590 1,200 1,410 620 590 270 70 810 590 440 600 470 1,90 1,440 1,120 580 610 1,180 1,070 1,20 1,220 2,80 1,900 1,580 1,850 1,10 1,920 910 80 10 1,010 1,020 870 180 40 50 860 820 50 450 600 420 50

Formula for Calculating Operating Costs Using Above Data:


Heating* Heat Loss KW x Heating Degree Days x C x Cost Per KWH = Operating Cost Outdoor Design Temperature Difference
*The above formula is for electric resistance heating only. Power consumption using the Zoneline Heat Pumps should be adjusted by Seasonal Performance Factor (SPF).

The local power supplier should be consulted for recommended value of C. This factor will vary between 17 and 24. Calculated Heat Gain (BTUH) Unit Cooling Watts Cooling x= x Cooling Hours x Cost per KWH = Operating Cost Installed unit capacity (BTUH) 1000 Watts/KW
47

Typical 2800 Series, 208/20-Volt Wiring Diagram

Typical 2800 Series, 208/20-Volt Schematic Diagram

48

Typical 800 Series, 208/20-Volt Wiring Diagram

ge.com

Typical 800 Series, 208/20-Volt Schematic Diagram

49

Typical 5800 Series Wiring Diagram


COLOR BK : BLACK BL : BLUE BR : BROWN GR : GREEN GY : GRAY OR : ORANGE RD : RED WH : WHITE YL : YELLOW RD*1 : RED (208/230V), : BLUE (265V)
OUTDOOR OD. COIL HEATER ID. COIL ROOM

(265V) 1 2 3 6 5 4 8 9 (208/230V) 1 2 3 4
BK BR

5 6 7 9
BL OR

GY WH

GY RD GR WH

O.L.P . C
RUNNING CAPACITOR BK RD COMPRESSOR

RD S

CM

CN105

RY102
RY101

RY109

1 RD*1 3 RD*1

1 2 3 4 5 6 7 8 9 10
CN104 CN5 CN2

CN101

CN6 & 7 WH

CN3 1 2 WH

CN103

YL 1 YL 2

FM

RY103

CN301 & 302 OPERATION BOARD UNIT

5 BK 7 BK TRANSFORMER
CN202

CN107

CN106 1 3 RD RD
CN201

BL

BR

1 2

CN203 ICR BOARD UNIT (OPTIONAL)

1 YL 3 YL

PM

ICR (OPTIONAL)

Typical 5800 Series Schematic Diagram


UNIVERSAL CONNECTOR FUSE
HEATER HEATER HEATER

HEATER UNIT

FAN MOTOR CAPACITOR

FAN MOTOR CAPACITOR

ID. FAN MOTOR

CN1 MAIN BOARD UNIT

1 RD 3 WH 5 V ARISTOR BK 1 3 5

CN102

OR OR BK BK BL BL RD RD

YL YL

BK

CN8 NR101

OD. FAN MOTOR BL

FM

WH

RD

RV

REV . VAL VE SOLE.

DRIVE BOARD UNIT

1 RD WH 2 BK 3 BL 4 GY 6 RUNNING CAPACITOR RD RD WH BK OR OR

GY RUNNING CAP ACITOR

BL HEATER WH WH 6 WH WH 3 HEATER RD RD 5 RD RD 2 HEATER BR BK 4 BK BK 1 FUSE RD 2 BK BK RD 1 BK PROTECTOR HEATER UNIT

R RUNNING . COMP CAPACITOR MOTOR S

(OPTIONAL) OUTDOOR FAN MOTOR INDOOR FAN MOTOR REVERSE VALVE SOL. ICR PUMP

PROTECTOR

O. L. P .

RY109

RY107

RY103

RY106

RY104

RY105

RY108

OPE OPE

RY102

RY101

DECODER

CN102

CN101

CN105

CN201

OPERATION BOARD

FAN HEAT

CURRENT DETECTOR (CT1)

TRANSFORMER

MODE HIGH LOW AUTO FAN SPEED

CN103

(TR1)

THERMO

CN3

UP DOWN

CN6 & 7

(OPTIONAL)

DRIVE BOARD UNIT

REGULATOR

ICR BOARD UNIT

Varistor (NR101)

Capacitor (C101, C102)

CN8

CN106

COOL

FUSE (FU101)

RY201

CN107

(for setting) DIP SW RY108

CN203

REMOTE T' STAT CDC CONTROL CIRCUIT RY107 RY106 RY105 RY104

RY201

CN5

MOTION SENSOR DOOR SWITCH ROOM ID. COIL OD. COIL OUTDOOR HEATER

MAIN BOARD UNIT


INTERFACE

CN2

TRANSFER FAN

CN104

CN1

RY103 RY102 RY101 RY109

50

CN202

WH

Suggested Bid Form Specifications


The following are suggested specifications for the Zoneline 2800 Series Packaged Terminal Air Conditioner, the 800 Series Packaged Terminal Heat Pump and the 5800 Series Packaged Terminal Heat Pump. The contractor will furnish Packaged Terminal Air Conditioners of the sizes and capacities shown on the schedule and in the specifications. The units shall be located as shown on the drawings and each shall consist of a chassis, room cabinet, wall case, sub-base if specified, and outdoor grille. Units shall be listed by UL, and ARI and cUL certified as to capacity and efficiency and shall be GE Zoneline models or equal. Unit dimensions shall not exceed 42-1/8" wide and 16-1/4" high with room cabinet in place. Units shall be designed to operate on (208) (20) (265) volts, 60 Hz., single-phase power. Chassis. The air conditioner chassis shall be the standard product of the manufacturer and shall be shipped in protective cartons to prevent damage. Cartons shall be appropriately marked at the factory with wording sufficient to warn handlers against improper stacking, up-ending, rolling or dropping. The chassis shall be the slide-in type, ready to operate after installation. Each shall consist of the following sections and components: Each unit shall have a matching, easily removable, textured finish, wrap-around room cabinet molded of hightemperature styrene to resist corrosion and damage. The room cabinet shall have slide-out washable filters accessible without requiring removal of room cabinet from chassis; Hermetically sealed refrigerant system with external vibration isolated rotary-type compressor, condenser and evaporator coils and capillary refrigerant control. Cooling shall be possible to outdoor temperature of 5F without damage to the compressor. Airflow system consisting of one permanently lubricated two-speed fan motor for the outdoor fan and a separate permanently lubricated two-speed fan motor for the indoor fan. Outdoor fan shall be multi-blade axial-flow design made of non-corrosive material. Indoor fan shall be of a design to optimize airflow and operating sound. All motors on the exterior side of the weather barrier shall be of an enclosed design to reduce the effects of moisture and corrosion; Line-cord connected units shall require a line cord power connection kit with integral Leakage Current Detection and Interruption device or Arc Fault Current Interrupter as required by National Electrical Code and Underwriters Laboratories. The unit shall have a universal resistance heater with output determined by connection to the power source with the appropriate power connection kit to provide specified heat output; A fan-cycle switch to permit continuous fan operation or fan cycle operation, independently selectable for heating and cooling operation; Fan-only operation in either high or low fan speed selectable by room occupant;

ge.com
A positive cooling condensate disposal system which meets the test requirements of applicable A.R.I. Standard 10-9 (for Packaged Terminal Air Conditioners) and 80-9 (for Packaged Terminal Heat Pump) (80F dry bulb, 75F wet bulb, 80% relative humidity); Condenser and evaporator coils to be constructed of copper tubing and aluminum plate fins designed to achieve EER and COP rating of the unit; Indoor and outdoor airflows that match the capacity of the coils for efficient heat transfer. Water blow-off shall not occur on the indoor coil; Adjustable indoor discharge air louvers that provide a 50 off vertical air pattern with an alternate position to provide a 40 off vertical air pattern; Easily accessible controls for selection of unit operation and thermostat setting. Controls shall be covered by a hinged door; Air discharge area accessible for cleaning without tools when room front is removed for 2800 and 800 Series; Positive-closing, manually controlled, three-position fresh-air vent capable of providing selection of fully open, partially open or closed setting. Vent door is to be secured for shipping; Solid-state thermostat control to sense room temperature; Electronic temperature limiting with seven independent heating and cooling settings to limit maximum and minimum temperatures without restricting movement of thermostat control knob; Freeze Sentinel to automatically activate the electric resistance heater and fan motor to warm and circulate indoor air to help prevent damage due to freezing temperatures. Freeze Sentinel shall operate as long as unit is connected to powered electrical circuit and unit shall provide ability for owner to defeat the Freeze Sentinel operation; Heat Sentinel to automatically activate air conditioner operation when the unit is in the STOP setting when the room temperature warms to 85F and turns air conditioner operation off when the room temperature cools to 80F, if selected by owner; Compatible with two-wire Central Desk Control systems; Remote Thermostat compatibility with Class 2 remote thermostat; Connections to interface with a transfer fan to move air into another room; Connections to interface with occupancy sensors; Unit shall have means of electrical connection listed by Underwriters Laboratories and compatible with the units required voltage and ampacity in conformance with National Electrical Code (NEC) and local codes.

51

Suggested Bid Form Specifications (continued)


Additional specifications for GE Zoneline 800 or 5800 Series Packaged Terminal Heat Pump Heat pump units shall provide operation that will either: A) automatically phase-in partial electric resistance heat, if outdoor temperature is below 46F, simultaneously with heat pump if heat pump alone is unable to maintain room temperature; or B) use partial electric resistance heat simultaneous with heat pump operation any time the outdoor temperature is below 45F. Selection of A or B operation is made by means of a selector switch concealed from room occupant. In either A or B operation, the unit will switch to full resistance heat if room temperature continues to decline or the outdoor temperature falls below 25F. If the outdoor temperature is above 46F, unit will lock-out electric resistance heat and operate on heat pump only. Heat pump unit shall include Reverse Cycle Defrost that automatically begins a defrost cycle when microprocessor determines criteria for defrosting has been met. Defrosting shall be accomplished by systematically ceasing heat pump operation, pausing to allow internal refrigerant pressures to equalize, then operating the compressor with the flow of refrigerant reversed to allow the hot gas to flow through the outdoor coil melting the accumulated frost. The unit shall automatically resume heat pump operation, after pausing to allow refrigerant pressures to equalize, at conclusion of defrost cycle. The unit shall be equipped with a temperature-activated drain valve to allow water generated in heat pump operation and defrost cycles to drain into the wall case rather than being deposited on the outdoor coil. In the event of compressor failure during heat pump operation, The unit shall automatically switch to electric resistance heat to maintain selected room temperature regardless of outdoor temperatures. The unit shall have a switch concealed from room occupant to allow heat pump operation to be overridden and heat provided by electric resistance heat regardless of outdoor temperature. In the event of compressor failure during heat pump operation, unit shall automatically switch to electric resistance heat to maintain selected room temperature regardless of outdoor temperatures. Specifications for Optional Internal Condensate Removal (ICR) system for 800 or 5800 series heat pump units. The unit shall have a factory-installed Internal Condensate Removal (ICR) system to permit unit to automatically dispose of heat pump generated condensate water with no overflow to outdoors during heating under outdoor ambient of 55F Dry Bulb, 90% Relative Humidity; indoor ambient 70F Dry Bulb, 52% Relative Humidity, for four hours of continuous run time. (Wall Cases and Grilles are needed for new installations.) (Alternate specification for steel wall case.) Wall Case. The wall case shall be constructed of heavy-gauge, insulated, zinc-coated phosphated steel with a protective baked-on enamel finish. Bottom critical points of the steel wall case shall be coated with petroleum microcrystalline wax for added corrosion protection and shall meet ASTM B-117, 1800-hour hot air aerated salt spray test. (Alternate specification for molded wall case.) Wall Case. The wall case shall be constructed of a non-corroding fiberglass-reinforced polyester compound. Cases shall be installed through exterior walls where shown on the plans and shall be installed per manufacturers installation instructions. In no instance shall fasteners be used through the bottom in order to retain the water integrity of the bottom of the wall case. Outside weather panels shipped with the cases shall remain in place until the outdoor air louvers and chassis are installed, at which time they are to be removed and discarded by the installer. Outside Grille. Each unit shall be equipped with a standard exterior grille that has been designed to allow unit operation in high ambient conditions. Grilles shall be of material and design specified. Special grilles or customer louver sections to be supplied by others will conform to a minimum of 65% free area to allow for proper unit operation and shall be submitted to the PTAC/ PTHP manufacturer, if requested, for feasibility and airflow characteristics. Specifications for Sub-Base (if required) Sub-Base. Each unit shall have a field-installed UL-listed electrical sub-base. The sub-base shall be attached to the lower inside flange of the wall case prior to installation in the exterior wall. It shall include adjustable screws at the bottom corners to permit exact leveling of the wall case. The sub-base shall have a factory-installed receptacle to allow unit line cord to plug into mating receptacle and shall have a chaseway to contain and conceal the line cord. The sub-base shall have side panels adjustable from a minimum of 2-/8" to a maximum of 1-/4" to enclose the area under the wall case.

52

Suggested Bid Form Specifications (continued)


Weather Resistance. Complete unit including outside louver shall be submitted to an independent agency for weather resistance and water infiltration tests. Air infiltration test to be conducted in accordance with ASTM E28-91. With static air pressure differential of 1.57 lb./ft.2 (." H2O) equivalent to 25 mph wind, allowable air infiltration shall not exceed 7 ft./min. Water infiltration test to be conducted in accordance with ASTM E1-86 with static air pressure differential of 10.0 lb./ft2 (1.9" H2O) equivalent to 6 mph wind, 5.0 gal./ft.2 (8" rain/ft.2/hr.) for 15 minutes and there shall be no leakage into the room. Approvals. Units shall be certified under the ARI and cUL certification program and listed by UL. Service. Submit complete information with bid covering service availability to whom service on units will be assigned, along with complete address and phone number, including phone number of emergency service personnel. Start-Up, Adjust, Demonstrate. Contractor shall be responsible for the initial starting of units, adjustments thereto, etc., to place the units in required operating condition. Contractor shall demonstrate to the owner or his representative the operation of units for both summer and winter functions. Warranty. The warranty shall be a full one-year parts and labor on the entire unit, plus an additional full four years parts and labor for the sealed refrigerating system, including service call for diagnosis and transportation to and from service shop (if necessary) at no charge to the customer. The warranty shall also include a limited second through fifth year parts only warranty for fan motors, switches, thermostat, heater, heater protectors, compressor overload, solenoids, circuit boards, auxiliary controls, thermistors, frost controls, ICR pump, capacitors, varistors and indoor blower bearing. Installation Responsibility. Units shall be installed according to the manufacturers recommendations and the manufacturer shall not be responsible for unit failure as a result of improper installation, or unit performance when installed with accessories not approved by the manufacturer.

ge.com

5

Zoneline Chassis Nomenclature


The Zoneline chassis is identified by a model number defining the type of unit, cooling capacity, electrical information and optional features included on the unit. When specifying or ordering the Zoneline chassis use of this nomenclature will assure receiving the correct unit.

EXAMPLE
A Z 5 8 H 1 2 D A D
Chassis series Zoneline packaged 28=deluxe line cool/ electric heat terminal 8=deluxe line heat pump chassis 58=premium line heat pump Unit type E=cooling with electric resistance heat H=heat pump with electric resistance heat Nominal cooling capacity 07=7,000 BTUH cooling 09=9,000 BTUH cooling 12=12,000 BTUH cooling 15=15,000 BTUH cooling Universal power connection

Special Features B=base unit C=corrosion treated D=internal Voltage/Phase/ condensate Frequency removal (ICR) D=20/208 Volt, single system (heat phase, 60 Hz pump models E=265 Volt, single phase, only) (not for 60 Hz coastal areas) P=Dry Air 25

Receptacles/Sub-Bases
Premium Line: 5800 Series

Tandem 20/208V 15 Amp NEMA6-15R

Perpendicular 20/208V 20 Amp NEMA6-20R

Large tandem 20/208V 0 Amp NEMA6-0R

265V 15 Amp NEMA7-15R

265V 20 Amp NEMA7-20R

265V 0 Amp NEMA7-0R

Sub-Bases RAK204U
Voltage Amps Receptacle N/A N/A N/A

RAK204D15P
20/208 15 NEMA6-20R

RAK204D20P
20/208 20 NEMA6-20R

RAK204D0P
20/208 0 NEMA6-0R

RAK204E15
265 15 NEMA7-15R

RAK204E20
265 20 NEMA7-20R

RAK204E0
265 0 NEMA7-0R

20/208-Volt sub-bases include appropriate power cord kit. 265-Volt units are to be direct connected. Cordset through enclosed chaseway into interior sub-base receptacle meets the NEC requirements.

Power connection kits are required on all Zoneline chassis (see chart below).
The correct kit for the installation is determined by the voltage and amperage of the electrical circuit and the means of connecting the unit to the building wiring. If the unit is to be plugged into a receptacle, a line cord kit would be used; if the unit is to be permanently connected, a permanent connection kit would be used. 265-volt cord set units must be installed in compliance with National Electrical Code.

Power connection kits required on all models. See specification sheet for heater KW and branch circuit ampacity.

RAK15 and RAK20 20/208-volt line cord connection kit

RAK0 20/208-volt line cord connection kit

20/208-volt
LCDI Power Connection Kit
Heater KW Watts BTUH Amps Min. circuit amps Recommended protective device *To be used with sub-base

Line cord connected units


RAK15
2.55/2.09 2,550/2,090 8,600/7,100 11.0/10.0 15 15-amp time-delay fuse or breaker

265-volt
RAK0
5.00/4.09 5,000/4,090 17,000/1,900 21.7/19.7 0 0-amp time-delay fuse or breaker

Permanent connected units* (Cord set)


RAK5202
.45 ,450 11,700 1.0 20 20-amp time-delay fuse

RAK20
.45/2.82 ,450/2,820 11,700/9,600 15.0/1.6 20 20-amp time-delay fuse or breaker

RAK5172
2.55 2,560 8,600 9.6 15 15-amp time-delay fuse

RAK502
5.0 5,000 17,000 18.9 0 0-amp time-delay fuse

54

Specifications
Deluxe series cooling & electric heat
20/208V Models Capacity
Cooling BTUH EER (BTU/Watt) Dehumidification Pts/Hr Sensible heat ratio @ 20 volts CFM, indoor fan high CFM, indoor fan low Vent CFM (full open/partial open)

ge.com

Dry Air 25
AZ28E15D
14,600/14,00 10.2/10.2 4.5 67% 10 260 75/45 89/90 140/1400 7.0/7.5 8.0 115/10 29

AZ28E07D
7,100/6,900 12.7/12.7 1.7 75% 250 215 50/40 86/87 560/545 2.8/.0 19.0 100/115 29

2800 series units AZ28E09D AZ28E12D


9,00/8,900 12.0/12.0 2.7 68% 275 25 70/45 86/86 750/75 .8/4.1 21.0 101/116 29 11,800/11,500 11.5/11.5 .6 67% 00 240 75/45 91/91 1020 4.9/5. 1.0 105/120 29

AZ28E07DAP
6,800/6,600 12.1/12.1 2.2 66% 210 175 50/40 87/87 560/545 2.8/.0 19.0 100/115 29

Dry Air 25 AZ28E09DAP


8,600/8,400 11.5/11.5 .4 58% 20 200 70/45 86/86 750/70 .6/.9 21.0 101/116 29

AZ28E12DAP
11,200/11,000 11.0/11.0 4.5 57% 240 210 75/45 91/91 1020 4.9/5. 1.0 105/120 29

Power/Ratings
Power factor Watts Amperes, F.L. Amperes, L.R.

Weight (Net/Ship) Sound Transmission Class (STC) 265V Models Capacity


Cooling BTUH EER (BTU/Watt) Dehumidification Pts/Hr Sensible heat ratio @ 265 volts CFM, indoor fan high CFM, indoor fan low Vent CFM (full open/partial open)

AZ28E07E
7,100 12.7 1.7 75% 250 215 50/40 87 560/545 2.4/.0 16.0 100/115 29

AZ28E09E
9,000 12.0 2.7 68% 270 25 70/45 86 750 . 18.0 101/116 29

AZ28E12E
11,700 11.5 .6 67% 290 240 75/45 87 1020 4.4 24.0 105/120 29

AZ28E15E
14,600 10.2 4.5 67% 10 260 75/45 90 141 6.0 1.0 115/10 29

AZ28E07EAP
6,800 12.1 2.2 66% 210 175 50/40 88 560 2.4 16.0 100/115 29

AZ28E09EAP
8,600 11.5 .4 58% 25 200 70/45 86 750 . 18.0 101/116 29

AZ28E12EAP
11,200 11.0 4.5 57% 240 210 75/45 87 1020 4.4 24.0 105/120 29

Power/Ratings
Power factor Watts Amperes, F.L. Amperes, L.R.

Weight (Net/Ship) Sound Transmission Class (STC)

Deluxe series heat pump units


800 series units 20/208V Models Capacity
Cooling BTUH EER (BTU/Watt) Dehumidification Pts/Hr Sensible heat ratio @ 20 volts CFM, indoor fan high CFM, indoor fan low Vent CFM (full open/partial open) AZ8H07D 7,100/6,900 12.7/12.7 1.7 75% 250 215 50/40 86/87 560/545 2.8/.0 19.0 6400/6200 .6 520/505 2.4/2.6 102/117 29 AZ8H09D 9,000/8,800 12.0/12.0 2.7 68% 270 250 70/45 96 750/75 .8/4.1 21.0 8400/8200 .6 685/670 .2/.5 109/124 29 AZ8H12D 11,700/11,500 11.5/11.5 .6 67% 00 260 75/45 97 1020/1000 4.9/5. 1.0 10900/10700 .4 940/925 4./4.7 11/128 29 AZ8H15D 14,600/14,00 10.0/10.0 4.5 67% 10 260 75/45 94 1460/140 7.0/7.5 8.0 1400/1200 .2 120/1210 5.8/6. 1/18 29

Premium series heat pump units


5800 series units
AZ58H07D 7,100/7,000 1.0/1.0 1.7 75% 240 220 50/40 95 560/540 2.7/2.8 19.0 6,400/6,200 .7/.7 505/490 2.4/2.5 108/122 29 AZ58H09D 9,000/8,800 12.0/12.0 2.8 67% 290 270 70/45 96 760/75 .6/.8 21.0 8,400/8,200 .6/.6 685/670 .2/.4 11/128 29 AZ58H12D 11,800/11,600 11.5/11.5 .6 68% 0 10 75/45 94 1010/990 4.6/5.0 .0 10,900/10,700 .4/.4 940/920 4./4.7 118/1 29 AZ58H15D 14,700/14,400 10.2/10.2 4.8 65% 50 0 75/45 95 1425/1400 6.5/7.0 8.0 1,800/1,800 .2/.2 1,265/1,25 5.7/6.2 127/142 29

Power/Ratings
Power factor Watts Amperes, F.L. Amperes, L.R. Reverse cycle heat BTUH COP Watts Amps

Weight (Net/Ship) Sound Transmission Class (STC) 265V Models Capacity


Cooling BTUH EER (BTU/Watt) Dehumidification Pts/Hr Sensible heat ratio @ 265 volts CFM, indoor fan high CFM, indoor fan low Vent CFM (full open/partial open)

AZ8H07E
7,100 12.7 1.7 75% 250 215 50/40 96 560 2.4 16.0 6,400 .6 520 2.2 102/117 29

AZ8H09E
9,000 12.0 2.7 68% 270 25 70/45 94 750 .2 18.0 8,400 .6 685 2.8 109/124 29

AZ8H12E
11,700 11.5 .6 67% 00 260 75/45 94 1020 4.4 24.0 10,900 .4 940 .9 11/128 29

AZ8H15E
14,600 10.0 4.5 67% 10 260 75/45 96 1460 6.0 1.0 1,400 .2 120 5.0 12/18 29

AZ58H07E
7,100 1.0 1.7 75% 240 220 50/40 96 570 2.2 16.0 6,400 .7 505 2.2 108/122 29

AZ58H09E
9,000 12.0 2.8 67% 290 270 70/45 94 760 .2 18.0 8,400 .6 685 2.7 11/128 29

AZ58H12E
11,800 11.5 .6 68% 0 10 75/45 94 1010 4.4 24.0 10,900 .4 940 .9 118/1 29

AZ58H15E
14,700 10.2 4.8 65% 50 0 75/45 96 1425 5.8 1.0 1,800 .2 1,265 5.0 127/142 29

Power/Ratings
Power factor Watts Amperes, F.L. Amperes, L.R. Reverse cycle heat BTUH COP Watts Amps

Weight (Net/Ship)* Sound Transmission Class (STC)


*ICR adds  pounds to unit weight

55

Complete Accessory List


Kit Number RAA6 RAB71A RAB7116 RAB7124 RAB7128 RAB711 RAB77 RAD10 RAF45 RAG60 RAG61 RAG62 RAG6 RAG64 RAG65 RAG66 RAG67 RAK40 RAK147 RAK148D1 RAK148P1 RAK16A1 RAK164D1 RAK164P1 RAK201 RAK204D15P RAK204D20P RAK204D0P RAK204E15 RAK204E20 RAK204E0 RAK204U RAK205CW RAK15 RAK20 RAK0 RAK4002A RAK4002B RAK4002CW RAK4157 RAK4207 RAK407 RAK5157 RAK5207 RAK507 RAK5172 RAK5202 RAK502 RAK601 RAK602 RAK6052 RAK7012 RAK7022 RAK802 RAK806 RAK901L
56

Description Spare Filters for AZ2800, AZ800 and AZ5800 Series units (10 pairs per box) Steel Wall Case 1 /4" deep Steel Wall Case 16" deep Steel Wall Case 24" deep Steel Wall Case 28" deep Steel Wall Case 1" deep Molded Wall Case Interior/Exterior Drain kit Room Front for AZ2800, AZ800 and AZ5800 Series units (included with chassis) Stamped Aluminum Exterior Grille Architectural Exterior Grille, Beige Molded High-Impact Plastic Architectural Exterior Grille, Maple Molded High-Impact Plastic Architectural Exterior Grille, Bittersweet Chocolate Molded High-Impact Plastic Architectural Exterior Grille w/Flange, Beige Molded High-Impact Plastic Architectural Exterior Grille w/Flange, Maple Molded High-Impact Plastic

For Additional Information Refer to Page 11 22 22 22 22 22 22 5 11 40 40 40 40 40 40 40 40 40 16 16 16 15 15 15 4 22 22 2 2 2 2 22 22 42 42 42 42 42 4 42 42 42 42 42 42 42 42 42 7 7 7 7 7 11 15 22

Architectural Exterior Grille w/Flange, Bittersweet Chocolate Molded High-Impact Plastic Aluminum Architectural Grille (Custom Colors Available by Special Order) Condenser Air Deflector Kit Wall Thermostat For Heat Pump Models Mechanical Wall Thermostat For Heat Pump Models - Electronic Digital Wall Thermostat For Heat Pump Models Electronic Digital Programmable Wall Thermostat For Resistance Heat Models Mechanical Wall Thermostat For Resistance Heat Models Electronic Digital Wall Thermostat For Resistance Heat Models Electronic Digital Programmable Sub-Base Cover Plate with Knockouts Sub-Base - 208/20-Volt with NEMA 6-20R 15/20 Amp Receptacle power cord and Chaseway included Sub-Base - 208/20-Volt with NEMA 6-20R 15/20 Amp Receptacle power cord and Chaseway included Sub-Base - 208/20-Volt with NEMA 6-0R 0 Amp Receptacle power cord and Chaseway included Sub-Base 265-Volt with NEMA 7-15R 15 Amp Receptacle Chaseway included Sub-Base 265-Volt with NEMA 7-20R 20 Amp Receptacle Chaseway included Sub-Base 265-Volt with NEMA 7-0R 0 Amp Receptacle Chaseway included Sub-Base non-electrical Chaseway not included Chaseway for Sub-Base Universal Power Cord 2800/800/5800 series 15-Amp 20/208 V 2.55/2.09 kW heat Universal Power Cord 2800/800/5800 20-Amp 20/208 V .45/2.82 kW heat Universal Power Cord 2800/800/5800 0-Amp 20/208 V 5.0/4.09 kW heat Direct Connect Junction Box 20/208-volt units 2800/800 Series Direct Connect Junction Box 20/208-volt units 5800 Series Wiring Harness w/ Inline Connector - Adapt Line Cord to Direct Connection 208/20V Universal Power Supply, 15 Amp for 2800, 800, 5500, 5800, 7500 only 208/20V Universal Power Supply, 20 Amp for 2800, 800, 5500, 5800, 7500 only 208/20V Universal Power Supply, 0 Amp for 2800, 800, 5500, 5800, 7500 only 265/275V Universal Power Supply, 15 Amp for 2800, 800, 5500, 5800, 7500 only 265/275V Universal Power Supply, 20 Amp for 2800, 800, 5500, 5800, 7500 only 265/275V Universal Power Supply, 0 Amp for 2800, 800, 5800, 7500 only Universal Connection Kit 265V 15 Amp Use w/ RAK204E15 Sub-Base 2.55 kW heat Universal Connection Kit 265V 20 Amp Use w/ RAK204E20 Sub-Base .45 kW heat Universal Connection Kit 265V 0 Amp Use w/ RAK204E0 Sub-Base 5.0 kW heat Duct extension Insulated 44" long includes Register and Mounting Flange Register and Trim Flange (Included with RAK601) Duct Adapter for New Installation (or older non-GE Duct Adapter Installation) Duct Transition for 2800/800 Replacing Existing Chassis (Original Installation Pre-1988) Duct Transition for 2800/800 Replacing Existing Chassis (19881998 Original Installation) Locking Door Kit Control Panel Cover (for use with remote thermostat) Wall Case Insulation Kit

General Installation Suggestions


Many times poor or non-existent caulking around the exterior of the wall case results in air infiltration causing the unit to run excessively. One way to check for air infiltration is to look under and around the unit to the outdoors. If you can see light, there is air infiltration. The first floor of a building is where this problem most frequently occurs since caulking the bottom of the wall case may require lying outside in the dirt while working. This has been the cause of many complaints about the short cycling of the Freeze Sentinel. Curtains, furniture or other obstructions interfering with the discharge air circulation will make the unit cycle turn off too soon since the cooled (or heated) discharge air is pulled back into the unit. This results in a room that is not adequately heated or cooled. Blocking the discharge air on the left side during heating operation can result in the air getting hot enough to distort the plastic room front. If you have a property where this may occur we recommend a tent card advising room occupants not to put anything on the unit.

ge.com
visible to someone standing or sitting in the room. Do not run the low-voltage wiring in conduits with line-voltage wiring or near uninsulated line-voltage wiring since induced current can interrupt the low-voltage controls. Consult the electrical inspector early in the project, especially if the power to the air conditioner is to be 265 volts, to understand what is required to comply with local electrical codes.

Wall Case/Exterior Grille


When making an installation where the exterior grille is flush with the exterior wall, or part of a custom window/louver section, make sure the installer caulks the wall case to the exterior wall, especially the bottom of the case. Many times the air conditioners are run during construction and the building is not closed. This can result in excessive humidity from the warm humid air entering the building, or from the drying out of the building materials. Many problems have been caused by condensate water or rainwater running back into the building where proper caulking has not been done.

Electrical Wiring Installation


Do not allow the installer to drill a hole in the wall case to run the electrical wiring. If this is done, the wiring will have to be run between the chassis and the edge of the wall case so it can be connected to the unit wiring on the room side of the wall case. When the chassis is removed for servicing or cleaning, the insulation on the wires can be cut and can create a safety hazard. If the electrical connection on a 20-volt or 208-volt installation is to be made by the line cord plugged into a wall-mounted receptacle, the receptacle should be located in the wall under the case or close to the side of the wall case. This installation makes a much neater appearance than a line cord running a foot or more across the floor. The electrician may want to place the receptacle as far from the unit as possible to save a few feet of wiring without considering how the installation may appear.

Capacity Considerations
A unit that has a greater cooling capacity than required will cool the room quickly but will usually not run long enough under normal operation to adequately dehumidify the room. Most musty odors in rooms are due to excess humidity. Using a smaller capacity unit or using Dry Air 25 units will provide better dehumidification. The largest factor in causing mold and mildew in the room is excess moisture, and a smaller unit running longer or a Dry Air 25 model can remove more moisture. Mold behind wall coverings that do not allow water vapor to pass through vinyl wallpaper or oil-base paints, for example is not a problem of excessive moisture in the room, but rather is caused by moisture trapped in the walls. Using a resistance heater larger than required using a 5 kW heater when a .45 kW heater would suffice for example may not cost any more in electrical consumption since the larger heater will operate for less time. The Demand Charge portion of the utility bill which is based on the highest electrical load for a period of time may be a significant portion of the utility bill. Some customers have reported the Demand Charge actually being more than the usage charge. In a 100-room property it would be possible for the demand of the 5.0 kW heater versus a .45 kW heater to be 155 kW more than the demand charge if the lower wattage heaters were used. Working with the utility companies to understand their method of billing and taking advantage of any rebates they may offer can reduce the utility bill.

Central Desk Control and Remote Thermostat Wiring


Do not allow the installer to drill a hole in the wall case to run Central Desk Control wiring or remote thermostat wiring to the unit terminals. CDC and remote thermostat wiring is classified as low-voltage wiring and does not have to be run in conduit unless required by local code. CDC and remote thermostat wiring should be run in the walls and exit the wall under the wall case about 2" from the right-hand side. The base pan is designed with a clearance for the line cord and the low-voltage wiring can be run to the chassis in this area also. Wire molding can be used to hold the wiring close to the bottom of the wall case. If a sub-base is used, the wiring can be run through the sub-base, entering the rear and exiting through one of the front panels. When the room cabinet is in place the CDC or remote thermostat wiring is usually not

Exterior Grilles
When replacing an older unit the existing outdoor grille may need to be changed or modified. Outdoor airflow patterns have changed and this may dictate the need for outdoor grille replacement or modification.

57

General Installation Suggestions


Ducted Installation Comments
New Installations The GE Zoneline 2800 and 800 series are approved for ducted installation using the GE Duct Adapter model RAK6052 and the GE Duct Extension RAK601. A field-fabricated duct extension with the same interior measurements as the RAK601 may be used with the RAK6052 duct adapter. GE does not recommend ducting in more than one direction. The use of a duct adapter other than the RAK6052 is not approved by GE and may cause problems such as inadequate airflow to the secondary room or the unit shutting off on one of the overload devices. Failure to allow for adequate air return from the secondary room is often the cause of less than satisfactory performance of a ducted installation. If the chassis is a slope-front discharge and the duct dimensions are 8-/8" high by 6-1/2" wide then the chassis has already been replaced and the purchase of a new duct adapter is not required. The only piece that needs to be replaced in this installation is the transition piece, model RAK7022, which fits between the chassis and the duct adapter. If the chassis being replaced has a model number that begins with AZ22E, AZ22, AZ25, AZ2, AZ2H or AZ5, the new 2800 or 800 Series unit can be installed using the same components that were used for the 2200 or 200 Series unit. If the existing chassis is a slope-front discharge and the duct dimensions are 7-/2" high by 6-1/2" wide only the RAK7022 transition piece is required to install a 2800 or 800 Series unit in the ducted installation. There were a number of Zoneline units installed in ducted installations that did not use a GE duct adapter. The easiest way to determine if the existing duct adapter is a GE duct adapter is to compare the duct adapter dimensions to the dimensions above. If the dimensions are different than the dimensions above or it the duct adapter is not made of sheet metal, it is not a GE duct adapter. In such installations GE recommends the removal of the old duct adapter and duct extension and the installation of a RAK6052 duct adapter and a RAK601 duct extension. Zoneline units installed in installations not using GE duct adapters and an extension with the same cross-section dimensions as the duct adapter may not be covered by the warranty.

Replacement Installations
GE offers duct adapters to allow for easy replacements of previous design chassis in ducted installations where a GE duct adapter was used in the original installation. A duct adapter is available that will align with the duct extension when GE-built components were used in the original installation. The duct extension used from the early 1960s until late 1987 was 8-/8" high by 6-1/2" wide. If the chassis to be replaced is the flat-top discharge (design until late 1987) the duct adapter model RAK7012 will align with the existing duct extension. This means the duct extension will not have to be changed. However, to keep the cost of the replacement to a minimum there are components that will need to be taken off the existing installation and used on the RAK7012 duct adapter. The wall case mounting brackets, screws, discharge grille, damper, and end cap will need to be retained.

Zoneline warranty*
What is covered
Limited one-year warranty For one year from date of original purchase, we will provide, free of charge, parts and service labor on-site to repair or replace any part of the Zoneline that fails because of a manufacturing defect. Limited five-year warranty For five years from the date of original purchase, we will provide, free of charge, parts and on-site service labor to repair or replace any part of the sealed refrigerating system (the compressor, condenser, evaporator and all connecting tubing) that fails because of a manufacturing defect. Limited 2nd through 5th year parts warranty For the second through the fifth year from date of original purchase, GE will provide, free of charge, parts that fail as a result of a manufacturing defect. Parts covered are fan motors, switches, thermostat, heater, heater protectors, compressor overload, solenoids, circuit boards, auxiliary controls, thermistors, frost controls, icr pump, capacitors, varistors, and indoor blower bearing. This is a limited parts-only warranty, and does not include labor or transportation to and from the service shop. All warranty service will be provided by our factory service centers or by our authorized customer care servicers during normal working hours.
*See written warranty for details

58

Alphabetical Index
Category Accessory List Application Comments Auxiliary Control Switches Case Dimensions Central Desk Control Condensate Disposal Systems Cooling/Heat Pump Performance Data Ducted Installations Dry Air Electrical Connection Essential Elements Ordering Overview Exterior Grilles Features and Benefits Features Table General Installation Suggestions Heat Pumps and Energy Savings Introduction to Zoneline Latent System Capacity Maximum Connected Load Mini Specs 2800 Mini Specs 3800 Mini Specs 5800 Mini Specs Power Connection Kits and Nomenclature Normal yearly Operating Data Remote Thermostat Control Schematics Specifications Suggested Big Form Specifications Table of Contents Wall Case/Sub Base Installation Warranty Zoneline System Page No. 56 20 12-13 21 14 34-36 45 37-39 4 42 43 40-41 9-11 8 57-58 18-19 6 46 44 2 2 2 3 47 15-17 48-50 55 51-53 5 22-33 58 7

Exterior Grille Color Samples

ge.com

Warm Gray Beige

Maple

Bittersweet Chocolate
Colors may vary slightly due to printing process.

59

A century of quality and innovation


For more than a century, GE has been committed to producing innovative products that change the way people live. The result of thorough research and rigorous testing, GE appliances are designed for years of dependable performance. Today, the GE tradition of quality and innovation continues.

Before purchasing an appliance, read important information about its estimated annual energy consumption or energy efficiency rating that is available from your retailer or ge.com

GE Consumer & Industrial


Appliances General Electric Company Louisville, KY 40225 ge.com

GE has a policy of continuous improvement of its products and reserves the right to change materials and specifications without notice.
2007 GE Company Pub. No. 20-S087 PC48947

You might also like