High Efficiency Air Cooled Chillers

Air Cooled Chillers With Screw Compressors


CSRAT
CSRAT-D
CSRAT-R

Air cooled chillers


Chillers with partial heat recovery
Chillers with total heat recovery

NUMERICALLY SUPERIOR

High efficiency chillers

CSRAT-Y

Energy indices
Energy indices ESEER and IPLV
Increasingly closer attention is being paid towards the power consumption of air-conditioning
equipment. Indices have been introduced that also consider usage in part load conditions when the
external air temperature is lower than the rated value and when the separation stages of the cooling
compressors are used. The valuation index adopted in the United States is called IPLV (Integrated
Part Load Value) and is defined in the regulations issued by ARI (American Refrigeration Institute).

ARI Standard

IPLV ARI = (1*EER100% + 42*EER75% + 45*EER50% + 12*EER 25%) /100

where:
EER100%, EER75%, EER50% and EER25% are the efficiencies of the chiller in the various load conditions (100% - 75% - 50% and
25% respectively), calculated in the external air temperature conditions shown below. The temperature of the water leaving
the evaporator is considered constant at 6.7C in all load conditions, with a delta of 5C in the full load condition.
The multipliers 1, 42, 45 and 12 are the cooling performance coefficients in various load conditions statistically calculated by
ARI an the basis of surveys conducted, for various types of buildings and operating conditions, in 29 Amerian cities.
In normal European applications it is difficult to think of a chiller working at an external air temperature lower than 20C. Airconditioning is never used to this extent; design and legislative constraints tend to reduce power consumption and encourage
the adoption of systems based on the direct or indirect use of external air wherever possible (FreeCooling).
Concerning the ESEER index in Europe, reference is made to a proposed EECCAC (Energy Efficiency and Certification of
Central Air Conditioner).

Proposal EECCAC

ESEER = (3*EER100% + 33*EER75% + 41*EER50% + 23*EER25%) /100

High efficiency chillers

CSRAT-Y

Using the energy indices


After estimating the total cooling capacity required by the system in the
summer mode (in kWh), we can calculate seasonal electricity
consumption (in kWh) using the following formula:
Power absorbed = Power requested / Index of efficiency
This method allows us to make comparisons between similar or
equivalent systems using the same reference unit.

Size
0751
0851
0951
0961
1021
1301
1542
1742
1942
1962
2442
2642
1502
1702
1902
1922
1972
2022
2602
2652
2702
2712
2722
3152
3602
3902
4202
4212
4222
4822
5403
5703
5423
6903
7203
7223
8404

B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B

IPLV

ESEER

4.35
4.33
4.41
4.56
4.34
4.44
4.47
4.41
4.31
4.31
4.45
4.25
4.73
4.66
4.57
4.68
4.70
4.74
4.63
4.75
4.87
4.74
4.94
4.86
5.04
4.67
4.72
4.63
4.76
5.02
4.94
4.76
5.05
4.51
4.67
4.61
4.52

3.89
3.80
3.91
4.03
3.87
3.93
4.04
3.96
3.95
3.97
4.01
3.87
4.28
4.16
4.15
4.27
4.26
4.31
4.17
4.31
4.42
4.32
4.52
4.37
4.37
4.22
4.21
4.20
4.33
4.60
4.42
4.26
4.54
4.08
4.24
4.21
4.06

Size
0751
0851
0951
0961
1021
1301
1542
1742
1942
1962
2442
2642
1502
1702
1902
1922
1972
2022
2602
2652
2702
2712
2722
3152
3602
3902
4202
4212
4222
4822
5403
5703
5423
6903
7203
7223
8404

IPLV (Integrated Part Load Value)


ESEER (European Seasonal Energy Efficiency Ratio)

LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN

IPLV

ESEER

4.64
4.51
4.53
4.64
4.61
4.56
4.58
4.50
4.48
4.47
4.53
4.36
4.96
4.78
4.78
4.90
4.90
4.96
4.73
4.90
5.00
5.11
5.12
4.93
5.02
4.78
4.74
4.84
4.93
5.22
4.98
4.87
5.19
4.63
4.83
4.83
4.61

4.10
3.90
3.96
4.10
4.05
3.98
4.08
3.97
4.01
4.01
4.02
3.86
4.46
4.23
4.30
4.44
4.40
4.47
4.23
4.38
4.48
4.46
4.63
4.40
4.45
4.25
4.23
4.34
4.44
4.74
4.42
4.33
4.63
4.15
4.33
4.36
4.40

ARI Standard indices


Indices for EECCAC proposal

Size
0751
0851
0951
0961
1021
1301
1542
1742
1942
1962
2442
2642
1502
1702
1902
1922
1972
2022
2602
2652
2702
2712
2722
3152
3602
3902
4202
4212
4222
4822
5403
5703
5423
6903
7203
7223
8404

SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL

IPLV

ESEER

4.51
4.41
4.35
4.62
4.55
4.27
4.40
4.40
4.31
4.48
4.62
4.42
4.80
4.53
4.61
4.74
4.71
4.82
4.52
4.68
4.76
4.76
4.92
4.65
4.71
4.54
4.47
4.66
4.75
5.04
4.71
4.61
4.93
4.52
4.71
4.72
4.42

3.93
3.79
3.77
4.10
3.97
3.69
3.89
3.85
3.84
4.02
4.10
3.91
4.27
3.97
4.11
4.25
4.20
4.30
4.00
4.16
4.24
4.26
4.40
4.11
4.14
4.01
3.95
4.14
4.23
4.53
4.13
4.06
4.35
4.01
4.17
4.22
3.90

High efficiency chillers

CSRAT-Y

High efficiency series


This new series of units combines elevated efficiency rates (EER) with the use of R134a refrigerant.
The excellent level of performance was achieved thanks to the accurate sizing of all internal components in order to fully
exploit the characteristics of the ecological refrigerant used. Special attention was paid to all the heat exchange surfaces,
fans and compressors.
The newly designed condenser coils with special construction features have larger surfaces, as do the new asymmetrical
evaporators with improved and more efficient refrigerant distribution both in the liquid and steam phases.
The fans with elevated unit efficiency are suitably adjusted to optimise air flow to the condensing section and guarantee
maximum silent-running in all operating conditions.
The new screw compressors are specially designed for R134a refrigerant.
The continual adjustment feature constantly modulates the capacity of each compressor between 100% and 50% of its
potential. This adjustment mode also allows the exact power required by the system to be instantaneously delivered and
precisely adapted to load variations. This in turn reduces the number of start-ups and consequently improves reliability. The
accompanying unit adjustment feature, based on evaporator outlet water temperature control, guarantees extremely small
variations compared with the set point.
The advantages of the continual adjustment of individual compressors are enhanced with the use of electronic thermostat
valves (optional for the entire range). Their precision and rapidity of response optimise load variations and allow stable
conditions to be achieved in a very short time, even when operating in the part load mode. The accurate sizing of the system
combined with this series of units offers considerable energy saving and consequently significant reductions in running
costs.

Air-cooled water chillers


Air-cooled water chiller with axial fans for outdoor installation. The unit is supplied with anti-freeze oil and refrigerant and
has been factory tested. On-site installation therefore just involves making connections to the mains power and water
supplies.
Unit charged with R134a refrigerant.

STANDARD UNIT COMPOSITION


Supporting frame
Base and frame in thick hot-galvanised shaped sheet steel. All parts polyesters-painted.

Screw compressors
Semi-hermetic screw-compressors with 2 five and six-lobe rotors. The fivelobe rotor is directly splined onto the 2-pole motor
(2,950 rpm) without the use of overgears. Compression occurs five times every motor turn and the gas therefore discharges
continuously without the typical throbbing common to reciprocating compressors. Leading-edge numerical control machines
were used to make the rotors and machine the bearing seats. Compressor cooling power is continuously modulated from
100 to 50%. In addition to the standard no-load starting feature, the motors are fitted with electric starting devices which limit
the power absorbed during the compressor starting phase. A check valve on the coolant delivery line prevents the rotor from
reversing after stopping. Special maintenance-free bearings allow very long work cycles. Lubrication is forced, without the
use of an oil pump. The high efficiency built-in oil separator ensures the constant presence of oil in the compressor. The
rotors are dynamically balanced to ensure that the vibrations common to reciprocating compressors do not occur. The lack
of vibrations and the absence of delicate intake and delivery valves, in addition to very fine manufacturing tolerances,
sophisticated quality controls during the production process and a limited number of moving parts, guarantee quiet and
highly reliable operation. Each compressor is fitted with manual-reset motor thermal protection, delivery gas temperature
control, an oil level float, an oil level sight-glass and an electric resistance for heating the oil when the compressor is
stopped.

High efficiency chillers

CSRAT-Y

Water-refrigerant heat exchanger


Direct expansion heat exchanger type with asymmetric refrigerant paths to maintain the correct refrigerant velocity inside
the tubes during both liquid and gaseous phases. The steel shell is insulated with a closed-cell anticondensation lining. The
copper pipes are internally grooved so as to improve the heat exchange. The pipes are mechanically expanded onto the
tube plate ends. An antifreeze electric heater prevents the formation of ice inside the casing of the exchanger when the unit
is not operating but connected to the electrical supply. Differential pressure switch for controlling the water flow is fitted
standard.

Refrigerant-air heat exchanger


Aluminium fins and copper tubes type heat exchanger. The aluminium fins are correctly spaced to guarantee the best heat
exchange efficiency. The lower part of the exchanger functions as a sub-cooling circuit thus increasing the cooling capacity.

Fans
Axial electric fans, protected to IP 54, with external rotor and profiled diecast aluminium blades. Housed in aerodynamic
hoods complete with safety grille. 6-pole electric motor with built-in thermal protection. Pressure switch condensing control
by sequentially excluding certain fans.

Refrigerant circuit

Electric power and control panel

Main components of the refrigerant circuit:


- compressor discharge check valve,
- compressor discharge shut-off valve,
- liquid line shut-off valve,
- liquid line solenoid valve,
- dryer filter with replaceable cartridge,
- refrigerant line sight glass with humidity indicator,
- externally equalised thermostatic valve,
- high pressure safety valve,
- low pressure safety valve,
- high and low pressure transducers
- high pressure switches,
- differential pressure switch for water

Electric power and control panel, built to EN 60204-1/EC 204-1


standards, complete with:
- control circuit transformer,
- general door lock isolator,
- power circuit with bar distribution system,
- fuses and contactors for compressors and fans,
- terminals for cumulative alarm block (BCA),
- remote ON/OFF terminals,
- spring-type control circuit terminal board,
- electric panel for outdoor installation,
- electronic controller.
- phase sequence relay

Basic model
Unit without heat recovery.

Model with partial heat recovery (D)


Air cooled chiller with partial heat recovery. Compared with the basic configuration, this version features an additional
refrigerant/water heat exchanger on the gas delivery line. This heat exchanger, fitted in series before the traditional cooling
circuit condenser, is large enough to recover heat for the production of medium-to-high temperature water for domestic hot
water and the like. The heating capacity of the heat recovery circuit is approximately equal to the power input of the
compressor. Each exchanger is fitted standard with an antifreeze heater

High efficiency chillers

CSRAT-Y

Model with heat recovery (R)


Air cooled chiller with total heat recovery. Compared with the basic configuration, this version features an additional refrigerant/
water heat exchanger on the gas delivery line. This heat exchanger, fitted in parallel with the traditional cooling circuit
condenser, is large enough to recover heat for the production of domestic hot water and the like. The heating capacity of the
heat recovery circuit is approximately equal to the cooling power plus the power input of the compressors. Each exchanger
is fitted standard with an antifreeze heater

AVAILABLE VERSIONS
B (base)
Standard unit. Unit with Low Temperature Pressure Device for condensation control

LN (Low Noise)
Low noise version. This configuration features special soundproofing for the compressor chamber and reduced fan speed.
Unit with Low Temperature Variable Speed Device for condensation control

SL (Super Low Noise)


Super low noise version. This configuration features special soundproofing for the compressor chamber, reduced fan speed,
an oversized condensing section. Unit with Low Temperature Variable Speed Device for condensation control

Accessories (Option)
Increased noise insulation (only for B/LN versions)
Spring isolators
Rubber isolators
High temperature pressure control
Device for low outdoor air temperatures up to -18C (in addition to DP or DVV)
Compressor suction valve
Oversized electric heater on evaporator
Increased evaporator insulation.
Cu/Cu condensing coils
Condensing coils with epoxy-coated fins
Condensing coils with Fin Guard Silver treatment
Anti-intrusion grilles
Coil protection with peraluman grille
Flanges on evaporator
Evaporator water flow switch (supplied separately)
Power factor correction
Automatic circuit breakers
Free voltage contacts for compr. operation signalling
Command pump relay
Water pump kit
Numbered wires
Group devices (sequencer, manager3000). Supplied separately.
Electronic expansion valves
Remote keyboard (supplied separately)

High efficiency chillers

CSRAT-Y

Electronic control features


Microprocessor

W3000

Microprocessor

W3000

OPT

OPT

OPT

OPT

OPT

Par.

OPT

OPT

OPT

OPT

OPT

Par.

OPT

Par.

OPT

OPT

OPT

Standard

OPT Available on request


Par.

Available modifying a value of the configuration parameters

Nomenclature

CSRAT 2442 - D - HE - SL - Y
o~W=uWoQMT`
vWoNPQ~
wWoQNM^
oOO===~
_Wp~~=ikW=i=k=piWp=i=k
ebW=b=~=
aW=m~~=~==oW=q~=~=
p~~===~
`==
^=`=`==p=`

High efficiency chillers

CSRAT-Y

General Technical Data


CSRAT-B-Y

Standard
0751 0851 0951 0961 1021 1301 1542 1742 1942 1962

SIZE
Performance

CSRAT-Y
(1)

CSRAT-D-Y
(1)(5)

CSRAT-R-Y
(1)(6)

Cooling capacity
Power input
Total power input
Evaporator water flow
Evaporater water pressure drop
CVM microprocessor

kW
kW
kW
m3/h
kPa

161
48
53
28
40

183
58
64
31
37

203
65
71
35
37

Cooling capacity
Power input
Total power input
Desuperheater heating capacity
Evaporator water flow
Evaporator water pressure drop
Desuperheater water flow
Desuperheater water pressure
CVM microprocessor

kW
kW
kW
kW
m3/h
kPa
m3/h
kPa

167
46
51
42
29
43
7.2
35

188
56
62
52
32
40
9.5
53

W3000
211 233 271 312 333 380 424 468
86
95
105 126 143
63
70
75
95
104 118 139 155
69
76
84
80
88
97
117 131
58
65
69
54
57
65
73
81
36
40
47
44
58
75
64
44
40
39
43
10.4 11.5 12.2 13.6 15.5 17.1 20.7 22.9
57
34
24
35
24
67
38
43
W3000

Cooling capacity
Power input
Heat recovery capacity
Evaporator water flow
Evaporator water pressure drop
Heat recovery water flow
Heat recovery water pressure drop
CVM microprocessor

kW
kW
kW
m3/h
kPa
m3/h
kPa

165 191 212 236 269 307 338


46
54
61
65
71
84
90
208 242 270 297 336 386 423
28
33
36
41
46
53
58
42
41
40
40
43
42
59
36.1 42.4 47.3 51.5 58.1 66.5 73.4
68
67
66
64
67
68
42

225
72
78
39
36

261
78
87
45
40

301
89
98
52
41

321
98
107
55
53

367
109
122
63
70

383
102
479
66
76
83
53

408
131
143
70
60

426
123
542
73
65
93.7
39

451
148
160
78
41

482
128
602
83
47
104
48

W3000

Fans
n
4
4
4
4
6
6
6
6
6
6
m3/s 19.11 19.11 18.21 17.41 28.66 27.31 27.31 32.51 31.22 31.22

Fans number
Air flow
Compressors
Number of compressors/circuits
Number of economizers
Minimum resource step(7)

n
n

1/1 1/1 1/1 1/1 1/1 1/1 2/2 2/2 2/2 2/2
0
0
0
0
0
0
0
0
0
0
50% 50% 50% 50% 50% 50% 25% 25% 25% 25%

Charge
CSRAT-Y
CSRAT-D-Y
CSRAT-R-Y
Oil

R134a
R134a
R134a

kg
kg
kg
kg

27
28
35
15

28
29
36
15

36
38
47
15

44
46
57
15

41
44
54
22

53
56
69
22

64
67
83
30

74
78
96
30

91
96
119
30

99
104
129
30

Operating weight
CSRAT-Y
CSRAT-D-Y
CSRAT-R-Y

kg
kg
kg

1680 1710 1780 1860 2590 2720 3490 3680 3810 4100
1710 1730 1810 1880 2610 2740 3600 3820 3950 4250
1770 1810 1900 1980 2720 2870 3820 4010 4220 4510

Sound power level(4)

dB(A)

88

88

88

88

90

90

91

91

91

91

Sound pressure level(3)

dB(A)

70

70

70

70

71

71

72

72

72

72

(1) Chilled water (in/out) 12/7 C

(5) Desuperheater water (in/out) 40/45 C

(2) Condensing air (in) 35 C


(3) At 1 metre (see "Full load sound level" section)

(6) Recovery water (in/out) 40/45 C


(7) Partialization in % referred to compressors number.

(4) According to Eurovent (see "Full load sound level" section)

It does not correspond to the partialization of capacity

High efficiency chillers

CSRAT-Y

General Technical Data


Standard

CSRAT-B-Y
SIZE

2442 2642 1502

1702 1902 1922

1972 2022 2602

Performance

CSRAT-Y
(1)

Cooling capacity
Power input
Total power input
Evaporator water flow
Evaporater water pressure drop
CVM microprocessor

kW
kW
kW
m3/h
kPa

520
168
184
89
40

575
184
201
99
53

331
98
106
57
57

366
406
123
113
122
135
63
70
48
59
W3000

461
142
154
79
43

490
152
163
84
48

535
152
167
92
42

591
170
185
102
56

CSRAT-D-Y
(1)(5)

Cooling capacity
Power input
Total power input
Desuperheater heating capacity
Evaporator water flow
Evaporator water pressure drop
Desuperheater water flow
Desuperheater water pressure
CVM microprocessor

kW
kW
kW
kW
m3/h
kPa
m3/h
kPa

539
162
178
149
93
43
25.9
31

597
178
195
164
103
57
28.3
38

343
94
103
87
59
61
14.9
35

380
421
109
119
118
131
101
110
65
73
52
64
17.3 19.2
26
32
W3000

479
137
148
126
82
46
21.9
23

508
146
158
135
87
52
23
26

555
147
162
136
96
46
24
26

612
164
179
152
105
60
26
32

CSRAT-R-Y
(1)(6)

Cooling capacity
Power input
Heat recovery capacity
Evaporator water flow
Evaporator water pressure drop
Heat recovery water flow
Heat recovery water pressure drop
CVM microprocessor

kW
kW
kW
m3/h
kPa
m3/h
kPa

554
150
695
95
45
120
47

613
168
771
105
60
133
57

344
94
433
59
61
74.8
60

389
104
487
67
54
84.3
50

474
133
599
82
45
103
58

502
141
635
86
51
109
56

536
149
676
92
43
117
54

610
162
762
105
60
132
53

425
119
537
73
65
93.2
47

W3000

Fans
n
m3/s

Fans number
Air flow

8
8
6
6
8
8
8
10
10
43.35 41.63 31.20 31.20 39.27 41.18 42.24 47.37 47.37

Compressors
Number of compressors/circuits
Number of economizers
Minimum resource step(7)

n
n

2/2
0
25%

2/2
0
25%

2/2
0
25%

2/2
0
25%

2/2
0
25%

2/2
2
25%

2/2
2
25%

2/2
2
25%

2/2
0
25%

kg
kg
kg
kg

130
137
169
44

157
165
204
44

97
102
126
30

97
102
126
30

100
105
130
30

98
103
127
30

108
113
140
37

122
128
159
44

126
132
164
44

kg
kg
kg

5140
5290
5720

5340
5490
5930

3760
3910
4060

3790
4000
4100

3880
4080
4310

4360
4560
4800

5050
5250
5500

5560
5760
6030

5560
5760
6050

Sound power level(4)

dB(A)

93

93

92

92

93

93

93

93

93

Sound pressure level(3)

dB(A)

73

73

76

76

77

77

77

77

77

Charge
CSRAT-Y
CSRAT-D-Y
CSRAT-R-Y
Oil

R134a
R134a
R134a

Operating weight
CSRAT-Y
CSRAT-D-Y
CSRAT-R-Y

(1) Chilled water (in/out) 12/7 C

(5) Desuperheater water (in/out) 40/45 C

(2) Condensing air (in) 35 C


(3) At 1 metre (see "Full load sound level" section)

(6) Recovery water (in/out) 40/45 C


(7) Partialization in % referred to compressors number.

(4) According to Eurovent (see "Full load sound level" section)

It does not correspond to the partialization of capacity

High efficiency chillers

CSRAT-Y

General Technical Data


CSRAT-B-Y

Standard
SIZE

2652 2702 2712

2722 3152 3602

3902 4202 4212

Performance

CSRAT-Y
(1)

CSRAT-D-Y
(1)(5)

CSRAT-R-Y
(1)(6)

Cooling capacity
Power input
Total power input
Evaporator water flow
Evaporater water pressure drop
CVM microprocessor

kW
kW
kW
m3/h
kPa

627
181
195
108
63

667
193
208
115
50

701
201
219
121
55

759
217
234
131
46

814
254
271
140
53
W3000

875
273
291
151
61

927
288
309
160
69

1003
313
333
173
60

Cooling capacity
Power input
Total power input
Desuperheater heating capacity
Evaporator water flow
Evaporator water pressure drop
Desuperheater water flow
Desuperheater water pressure
CVM microprocessor

kW
kW
kW
kW
m3/h
kPa
m3/h
kPa

650
175
189
162
112
68
28.1
29

692
186
201
172
119
54
30
28

727
194
212
179
125
60
31.2
30

788
209
227
193
136
50
34
35

845
244
262
227
145
57
39.7
39

908
264
282
244
156
66
42.2
38

962
279
299
258
166
74
45.1
27

1041 1120
301 308
321 337
279 285
179 193
64
74
48.8 49.2
32
34

Cooling capacity
Power input
Heat recovery capacity
Evaporator water flow
Evaporator water pressure drop
Heat recovery water flow
Heat recovery water pressure drop
CVM microprocessor

kW
kW
kW
m3/h
kPa
m3/h
kPa

648
172
809
112
67
140
53

696
180
865
120
55
150
54

726
184
899
125
59
156
49

784
198
970
135
49
167
49

855
921
229
253
1070 1159
147
159
59
68
184
201
59
70
W3000

968
269
1221
167
75
211
60

1058
290
1330
182
66
229
70

1080
319
348
186
69

W3000
1106
296
1384
190
73
238
65

Fans
n
m3/s

Fans number
Air flow

10
10
12
12
12
12
14
14
20
48.82 49.75 61.13 57.00 49.22 53.19 69.47 65.39 101.88

Compressors
n
n

2/2
0
25%

2/2
0
25%

2/2
1
25%

2/2
2
25%

2/2
1
25%

2/2
0
25%

2/2
0
25%

2/2
1
25%

2/2
2
25%

kg
kg
kg
kg

136
143
177
44

154
162
200
44

138
145
179
44

164
172
213
44

177
186
230
50

190
200
247
56

268
281
348
56

311
327
404
56

229
240
297
56

kg
kg
kg

5660
5860
6150

5770
5990
6270

5940
6150
6450

6270
6480
6800

7360
7220
7530

8040
7900
8210

8470
8750
9310

8610 9430
8890 9710
9450 10530

Sound power level(4)

dB(A)

93

93

95

95

95

95

96

96

97

Sound pressure level(3)

dB(A)

77

77

78

78

78

78

79

79

79

Number of compressors/circuits
Number of economizers
Minimum resource step(7)
Charge
CSRAT-Y
CSRAT-D-Y
CSRAT-R-Y
Oil

R134a
R134a
R134a

Operating weight
CSRAT-Y
CSRAT-D-Y
CSRAT-R-Y

(1) Chilled water (in/out) 12/7 C

(5) Desuperheater water (in/out) 40/45 C

(2) Condensing air (in) 35 C


(3) At 1 metre (see "Full load sound level" section)

(6) Recovery water (in/out) 40/45 C


(7) Partialization in % referred to compressors number.

(4) According to Eurovent (see "Full load sound level" section)

It does not correspond to the partialization of capacity

High efficiency chillers

CSRAT-Y

General Technical Data


CSRAT-B-Y

Standard
SIZE

4222

4822

5403

5423

5703

6903

7203

7223

8404

1380
430
459
238
54

1602
483
533
276
72

1656
500
550
285
77

1801
549
600
310
91

1944
596
647
335
56

Performance

CSRAT-Y
(1)

CSRAT-D-Y
(1)(5)

CSRAT-R-Y
(1)(6)

Cooling capacity
Power input
Total power input
Evaporator water flow
Evaporater water pressure drop
CVM microprocessor

kW
kW
kW
m3/h
kPa

1152
330
359
198
53

1290
372
401
222
47

1336
413
443
230
69

1469
459
488
253
83

Cooling capacity
Power input
Total power input
Desuperheater heating capacity
Evaporator water flow
Evaporator water pressure drop
Desuperheater water flow
Desuperheater water pressure
CVM microprocessor

kW
kW
kW
kW
m3/h
kPa
m3/h
kPa

1195
318
347
294
206
57
50.9
36

1338
359
389
332
230
50
57.6
35

1386
399
428
369
239
74
63.8
39

1524
443
472
410
262
89
71.4
31

1432
415
444
384
246
58
66.3
27
W3000

1662
465
516
431
286
78
75
35

1718
482
533
446
296
83
77.3
37

1869 2017
530 575
581 623
490 533
322 347
98
60
85 92.7
35
29

Cooling capacity
Power input
Heat recovery capacity
Evaporator water flow
Evaporator water pressure drop
Heat recovery water flow
Heat recovery water pressure drop
CVM microprocessor

kW
kW
kW
m3/h
kPa
m3/h
kPa

1176
306
1464
202
55
255
73

1315
350
1644
226
49
283
76

1400
390
1766
241
76
305
72

1535
416
1926
264
91
334
66

1454
395
1825
250
59
316
59
W3000

1662
451
2086
286
78
361
58

1721
467
2160
296
83
373
58

1850
499
2319
319
96
402
66

n
m3/s

20
20
20
20
20
24
24
24
24
94.74 91.29 82.82 86.00 86.00 116.88 120.31 115.16 116.88

W3000

2075
560
2601
357
64
451
67

Fans
Fans number
Air flow
Compressors
Number of compressors/circuits
Number of economizers
Minimum resource step(7)

n
n

2/2
2
25%

2/2 3/3 3/3 3/3 3/3 3/3 3/3 4/4


0
3
0
0
0
0
0
0
25% 16.6%16.6% 16.6% 16.6% 16.6% 16.6% 12.5%

kg
kg
kg
kg

257
270
334
56

306
321
398
56

Charge
CSRAT-Y
CSRAT-D-Y
CSRAT-R-Y
Oil

R134a
R134a
R134a

307
322
399
84

307
322
399
84

333
349
433
84

278
291
361
84

294
309
382
84

294
309
382
84

447
469
581
112

Operating weight
CSRAT-Y
CSRAT-D-Y
CSRAT-R-Y

kg
kg
kg

9690 10110 11840 12020 11950 12390 12530 12670 16360


9970 10390 12170 12430 12370 12810 12940 13100 17290
10800 11240 12630 13280 13210 14060 14230 14370 18410

Sound power level(4)

dB(A)

97

98

99

99

99

99

99

99

99

Sound pressure level(3)

dB(A)

79

80

80

80

80

80

80

80

80

(1) Chilled water (in/out) 12/7 C

(5) Desuperheater water (in/out) 40/45 C

(2) Condensing air (in) 35 C


(3) At 1 metre (see "Full load sound level" section)

(6) Recovery water (in/out) 40/45 C


(7) Partialization in % referred to compressors number.

(4) According to Eurovent (see "Full load sound level" section)

It does not correspond to the partialization of capacity

10

High efficiency chillers

CSRAT-Y

General Technical Data


Low Noise

CSRAT-LN-Y

0751 0851 0951 0961 1021 1301 1542 1742 1942 1962

SIZE
Performance

CSRAT-Y
(1)

CSRAT-D-Y
(1)(5)

CSRAT-R-Y
(1)(6)

Cooling capacity
Power input
Total power input
Evaporator water flow
Evaporater water pressure drop
CVM microprocessor

kW
kW
kW
m3/h
kPa

157
49
52
27
38

175
59
63
30
34

195
66
70
34
34

217
74
77
37
34

255
85
90
44
38

Cooling capacity
Power input
Total power input
Desuperheater heating capacity
Evaporator water flow
Evaporator water pressure drop
Desuperheater water flow
Desuperheater water pressure
CVM microprocessor

kW
kW
kW
kW
m3/h
kPa
m3/h
kPa

163
47
49
43
28
40
7.1
36

181
57
59
52
31
37
9.2
54

202
63
67
58
35
36
9.9
67

225
71
74
66
39
36
11
39

265 296 307 359 399 459


83
87
101 118 134 158
84
91
102 120 139 159
77
81
94
108 124 145
46
51
53
62
69
79
41
39
49
67
57
42
13.6 14.1 16.7 18.8 21.3 24.9
53
59
39
30
39
30
W3000

Cooling capacity
Power input
Heat recovery capacity
Evaporator water flow
Evaporator water pressure drop
Heat recovery water flow
Heat recovery water pressure drop
CVM microprocessor

kW
kW
kW
m3/h
kPa
m3/h
kPa

165 191 212 236 269 307 338


46
54
61
65
71
84
90
208 242 270 297 336 386 423
28
33
36
41
46
53
58
42
41
40
40
43
42
59
36.1 42.4 47.3 51.5 58.1 66.5 73.4
68
67
66
64
67
68
42

285
90
95
49
37

296
105
110
51
45

346
122
129
59
62

384
138
146
66
53

442
163
170
76
39

W3000

383
102
479
66
76
83
53

426
123
542
73
65
93.7
39

482
128
602
83
47
104
48

W3000

Fans
n
4
4
4
4
6
6
6
6
6
6
m3/s 15.78 15.78 14.69 13.59 23.67 22.03 22.03 25.12 23.89 23.89

Fans number
Air flow
Compressors
Number of compressors/circuits
Number of economizers
Minimum resource step(7)

n
n

1/1 1/1 1/1 1/1 1/1 1/1 2/2 2/2 2/2 2/2
0
0
0
0
0
0
0
0
0
0
50% 50% 50% 50% 50% 50% 25% 25% 25% 25%

Charge
CSRAT-Y
CSRAT-D-Y
CSRAT-R-Y
Oil

R134a
R134a
R134a

kg
kg
kg
kg

27
28
35
15

28
29
36
15

36
38
47
15

44
46
57
15

41
44
54
22

53
56
69
22

64
67
83
30

74
78
96
30

91
96
119
30

99
104
129
30

Operating weight
CSRAT-Y
CSRAT-D-Y
CSRAT-R-Y

kg
kg
kg

1680 1710 1780 1860 2590 2720 3490 3680 3810 4100
1710 1730 1810 1880 2610 2740 3600 3820 3950 4250
1770 1810 1900 1980 2720 2870 3820 4010 4220 4510

Sound power level(4)

dB(A)

82

82

82

82

84

84

85

85

85

85

Sound pressure level(3)

dB(A)

64

64

64

64

65

65

66

66

66

66

(1) Chilled water (in/out) 12/7 C

(5) Desuperheater water (in/out) 40/45 C

(2) Condensing air (in) 35 C


(3) At 1 metre (see "Full load sound level" section)

(6) Recovery water (in/out) 40/45 C


(7) Partialization in % referred to compressors number.

(4) According to Eurovent (see "Full load sound level" section)

It does not correspond to the partialization of capacity

11

High efficiency chillers

CSRAT-Y

General Technical Data


Low Noise

CSRAT-LN-Y

2442 2642 1502 1702 1902 1922 1972 2022 2602

SIZE
Performance

CSRAT-Y
(1)

CSRAT-D-Y
(1)(5)

CSRAT-R-Y
(1)(6)

Cooling capacity
Power input
Total power input
Evaporator water flow
Evaporater water pressure drop
CVM microprocessor

kW
kW
kW
m3/h
kPa

490
178
188
84
36

Cooling capacity
Power input
Total power input
Desuperheater heating capacity
Evaporator water flow
Evaporator water pressure drop
Desuperheater water flow
Desuperheater water pressure
CVM microprocessor

kW
kW
kW
kW
m3/h
kPa
m3/h
kPa

509 558 332 368 409 469 497


172 188
98
113 123 139 148
180 195
97
116 129 144 154
159 174
90
105 114 129 137
88
96
57
63
70
81
86
38
50
57
49
60
44
50
27.4 30.5 15.9 18.3 20.2 22.3 24.2
36
42
37
28
34
23
26
W3000

544 592
159 175
158 181
147 161
94
102
44
56
25.6 28.4
31
36

Cooling capacity
Power input
Heat recovery capacity
Evaporator water flow
Evaporator water pressure drop
Heat recovery water flow
Heat recovery water pressure drop
CVM microprocessor

kW
kW
kW
m3/h
kPa
m3/h
kPa

554
150
695
95
45
120
47

536
149
676
92
43
117
54

538
194
204
93
46

320
101
106
55
53

355
117
122
61
45

394
128
135
68
56

452
144
151
78
41

480
153
160
83
46

524
164
173
90
41

571
181
189
98
52

W3000

613
168
771
105
60
133
57

344 389 425


94
104 119
433 487 537
59
67
73
61
54
65
74.8 84.3 93.2
60
50
47

474
133
599
82
45
103
58

502
141
635
86
51
109
56

610
162
762
105
60
132
53

W3000

Fans
n
m3/s

8
8
6
6
8
8
8
10
10
33.50 31.86 26.72 26.72 32.81 35.31 36.25 39.06 39.06

n
n

2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2


0
0
0
0
0
2
2
2
0
25% 25% 25% 25% 25% 25% 25% 25% 25%

kg
kg
kg
kg

130
137
169
44

157
165
204
44

97
102
126
30

100
105
130
30

100
105
130
30

98
103
127
30

108
113
140
37

122
128
159
44

126
132
164
44

kg
kg
kg

5140
5290
5720

5340
5490
5930

3800
3940
4100

3830
4030
4140

3920
4130
4360

4410
4610
4810

5090
5300
5550

5630
5830
6100

5630
5830
6120

Sound power level(4)

dB(A)

87

87

86

86

87

87

87

87

87

Sound pressure level(3)

dB(A)

67

67

70

70

71

71

71

71

71

Fans number
Air flow
Compressors
Number of compressors/circuits
Number of economizers
Minimum resource step(7)
Charge
CSRAT-Y
CSRAT-D-Y
CSRAT-R-Y
Oil

R134a
R134a
R134a

Operating weight
CSRAT-Y
CSRAT-D-Y
CSRAT-R-Y

(1) Chilled water (in/out) 12/7 C

(5) Desuperheater water (in/out) 40/45 C

(2) Condensing air (in) 35 C


(3) At 1 metre (see "Full load sound level" section)

(6) Recovery water (in/out) 40/45 C


(7) Partialization in % referred to compressors number.

(4) According to Eurovent (see "Full load sound level" section)

It does not correspond to the partialization of capacity

12

High efficiency chillers

CSRAT-Y

General Technical Data


Low Noise

CSRAT-LN-Y

2652 2702 2712 2722 3152 3602 3902 4202 4212

SIZE
Performance

CSRAT-Y
(1)

CSRAT-D-Y
(1)(5)

CSRAT-R-Y
(1)(6)

Cooling capacity
Power input
Total power input
Evaporator water flow
Evaporater water pressure drop
CVM microprocessor

kW
kW
kW
m3/h
kPa

608
193
201
105
59

Cooling capacity
Power input
Total power input
Desuperheater heating capacity
Evaporator water flow
Evaporator water pressure drop
Desuperheater water flow
Desuperheater water pressure
CVM microprocessor

kW
kW
kW
kW
m3/h
kPa
m3/h
kPa

631 673 706 768 817 890 934


187 200 207 221 260 275 287
195 208 217 231 270 285 299
172 184 192 204 240 254 266
109 116 122 132 141 153 161
64
51
56
47
53
63
70
29.7 31.7 32.8 35.8 41.7 44.7 45.7
34
31
35
39
45
42
30
W3000

Cooling capacity
Power input
Heat recovery capacity
Evaporator water flow
Evaporator water pressure drop
Heat recovery water flow
Heat recovery water pressure drop
CVM microprocessor

kW
kW
kW
m3/h
kPa
m3/h
kPa

648
172
809
112
67
140
53

649
207
215
112
47

696
180
865
120
55
150
54

681
214
225
117
52

726
184
899
125
59
156
49

740
230
240
127
44

784
198
970
135
49
167
49

787
269
279
136
50
W3000

857
284
295
148
59

901
297
309
155
65

972
312
324
167
56

1054
331
348
181
66

1008 1094
302 320
314 337
280 295
174 188
60
71
48.9 51.2
33
36

855 921 968 1058 1106


229 253 269 290 296
1070 1159 1221 1330 1384
147 159 167 182 190
59
68
75
66
73
184 201 211 229 238
59
70
60
70
65
W3000

Fans
Fans number
Air flow

n
m3/s

10
10
12
12
12
12
14
14
20
40.82 41.80 52.03 46.88 36.56 41.72 58.52 53.05 86.72

n
n

2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2


0
0
1
2
1
0
0
1
2
25% 25% 25% 25% 25% 25% 25% 25% 25%

Compressors
Number of compressors/circuits
Number of economizers
Minimum resource step(7)
Charge
kg
kg
kg
kg

136
143
177
44

154
162
200
44

138
145
179
44

164
172
213
44

177
186
230
50

190
200
247
56

268
281
348
56

311
327
404
56

kg
kg
kg

5730
5940
6220

5840
6060
6340

6010
6220
6520

6340
6550
6870

7330
7190
7500

7900
7770
8070

8550
8830
9390

8700 9530
8970 9810
9530 10630

Sound power level(4)

dB(A)

87

87

89

89

89

89

90

90

91

Sound pressure level(3)

dB(A)

71

71

72

72

72

72

73

73

73

CSRAT-Y
CSRAT-D-Y
CSRAT-R-Y
Oil

R134a
R134a
R134a

229
240
297
56

Operating weight
CSRAT-Y
CSRAT-D-Y
CSRAT-R-Y

(1) Chilled water (in/out) 12/7 C

(5) Desuperheater water (in/out) 40/45 C

(2) Condensing air (in) 35 C


(3) At 1 metre (see "Full load sound level" section)

(6) Recovery water (in/out) 40/45 C


(7) Partialization in % referred to compressors number.

(4) According to Eurovent (see "Full load sound level" section)

It does not correspond to the partialization of capacity

13

High efficiency chillers

CSRAT-Y

General Technical Data


CSRAT-LN-Y

Low Noise
4222 4822 5403 5423 5703 6903 7203 7223 8404

SIZE
Performance

CSRAT-Y
(1)

CSRAT-D-Y
(1)(5)

CSRAT-R-Y
(1)(6)

Cooling capacity
Power input
Total power input
Evaporator water flow
Evaporater water pressure drop
CVM microprocessor

kW
kW
kW
m3/h
kPa

1121 1261 1289 1438 1345


350 393 438 494 447
367 410 455 511 465
193 217 222 248 232
51
45
50
64
80
W3000

Cooling capacity
Power input
Total power input
Desuperheater heating capacity
Evaporator water flow
Evaporator water pressure drop
Desuperheater water flow
Desuperheater water pressure
CVM microprocessor

kW
kW
kW
kW
m3/h
kPa
m3/h
kPa

1163 1308 1337 1492 1395 1582 1645


339 379 423 476 432 498 516
356 396 440 493 449 524 541
312 351 391 441 399 460 477
200 225 230 257 240 272 283
55
48
70
54
76
69
86
54.3 60.6 68.2 76.7 69.6 79.9 83.3
29
39
39
40
42
44
36

Cooling capacity
Power input
Heat recovery capacity
Evaporator water flow
Evaporator water pressure drop
Heat recovery water flow
Heat recovery water pressure drop
CVM microprocessor

kW
kW
kW
m3/h
kPa
m3/h
kPa

1176 1315 1400 1535 1454


306 350 390 416 395
1464 1644 1766 1926 1825
202 226 241 264 250
59
55
49
76
91
255 283 305 334 316
59
73
76
72
66
W3000

n
m3/s

20
20
20
20
20
24
24
24
24
78.13 73.44 61.72 66.41 66.41 87.84 90.65 86.43 87.84

n
n

2/2 2/2 3/3 3/3 3/3 3/3 3/3 3/3 4/4


2
0
3
0
0
0
0
0
0
25% 25% 16.6% 16.6% 16.6% 16.6% 16.6% 16.6% 12.5%

1525 1585 1749


516 535 593
544 567 622
263 273 301
65
71
86

1872
636
664
322
52

1815
573
598
530
312
93
92.2
40

1942
613
638
567
334
56
98.3
34

1662 1721 1850


451 467 499
2086 2160 2319
286 296 319
78
83
96
361 373 402
58
58
66

2075
560
2601
357
64
451
67

W3000

Fans
Fans number
Air flow
Compressors
Number of compressors/circuits
Number of economizers
Minimum resource step(7)
Charge
CSRAT-Y
CSRAT-D-Y
CSRAT-R-Y
Oil

R134a
R134a
R134a

kg
kg
kg
kg

257
270
334
56

306
321
398
56

307
322
399
84

307
322
399
84

333
349
433
84

278
291
361
84

294
309
382
84

294
309
382
84

447
469
581
112

Operating weight
CSRAT-Y
CSRAT-D-Y
CSRAT-R-Y

kg
kg
kg

9800 10210 11730 11920 11850 12560 12690 12830 16110


10070 10500 12070 12330 12270 12970 13110 13260 17000
10900 11340 12530 13170 13110 14220 14390 14530 18130

Sound power level(4)

dB(A)

91

92

93

93

93

93

93

93

93

Sound pressure level(3)

dB(A)

73

74

74

74

74

74

74

74

74

(1) Chilled water (in/out) 12/7 C

(5) Desuperheater water (in/out) 40/45 C

(2) Condensing air (in) 35 C


(3) At 1 metre (see "Full load sound level" section)

(6) Recovery water (in/out) 40/45 C


(7) Partialization in % referred to compressors number.

(4) According to Eurovent (see "Full load sound level" section)

It does not correspond to the partialization of capacity

14

High efficiency chillers

CSRAT-Y

General Technical Data


CSRAT-SL-Y

Super Low Noise


0751 0851 0951 0961 1021 1301 1542 1742 1942 1962

SIZE
Performance
Cooling capacity
Power input
Total power input
Evaporator water flow
Evaporater water pressure drop
CVM microprocessor

kW
kW
kW
m3/h
kPa

150
54
57
26
34

168
62
64
29
32

185
72
75
32
30

CSRAT-D-Y
(1)(5)

Cooling capacity
Power input
Total power input
Desuperheater heating capacity
Evaporator water flow
Evaporator water pressure drop
Desuperheater water flow
Desuperheater water pressure
CVM microprocessor

kW
kW
kW
kW
m3/h
kPa
m3/h
kPa

155
52
55
48
27
37
8.5
45

175
60
62
55
30
34
9.2
59

W3000
192 228 258 276 307 342 386 436
87
72
107 116 139 149
69
95
91
77
111 122 146 157
72
99
81
66
107 127 137
98
64
88
75
44
66
39
59
53
33
47
38
39
53
37
61
49
33
34
11.1 11.4 13.6 15.1 17.4 18.7 22.3 23.6
27
58
42
39
30
43
81
69

CSRAT-R-Y
(1)(6)

Cooling capacity
Power input
Heat recovery capacity
Evaporator water flow
Evaporator water pressure drop
Heat recovery water flow
Heat recovery water pressure drop
CVM microprocessor

kW
kW
kW
m3/h
kPa
m3/h
kPa

165 191 212 236 269 307 338


46
54
61
65
71
84
90
208 242 270 297 336 386 423
28
33
36
41
46
53
58
42
41
40
40
43
42
59
36.1 42.4 47.3 51.5 58.1 66.5 73.4
68
67
66
64
67
68
42

CSRAT-Y
(1)

220
74
79
38
35

249
90
94
43
36

266
98
102
46
32

296
110
114
51
45

330
121
127
57
56

372
144
151
64
50

420
154
161
72
36

W3000
383
102
479
66
76
83
53

426
123
542
73
65
93.7
39

482
128
602
83
47
104
48

W3000

Fans
n
4
4
4
6
6
6
6
6
8
8
m3/s 12.62 11.50 10.76 18.93 17.26 17.26 16.14 19.25 28.21 26.94

Fans number
Air flow
Compressors
Number of compressors/circuits
Number of economizers
Minimum resource step(7)

n
n

1/1 1/1 1/1 1/1 1/1 1/1 2/2 2/2 2/2 2/2
0
0
0
0
0
0
0
0
0
0
50% 50% 50% 50% 50% 50% 25% 25% 25% 25%

Charge
CSRAT-Y
CSRAT-D-Y
CSRAT-R-Y
Oil

R134a
R134a
R134a

kg
kg
kg
kg

27
28
35
15

35
37
45
15

43
45
56
15

40
42
53
15

52
54
67
22

53
56
69
22

75
78
97
30

87
91
113
30

78
82
102
30

104
109
135
30

Operating weight
CSRAT-Y
CSRAT-D-Y
CSRAT-R-Y

kg
kg
kg

1680 1770 1840 1980 2670 2720 3580 3790 3960 4410
1710 1790 1870 2010 2700 2740 3690 3930 4100 4560
1770 1870 1960 2110 2810 2870 3910 4120 4370 4820

Sound power level(4)

dB(A)

78

78

78

78

80

80

81

81

81

81

Sound pressure level(3)

dB(A)

60

60

60

60

61

61

62

62

62

62

(1) Chilled water (in/out) 12/7 C

(5) Desuperheater water (in/out) 40/45 C

(2) Condensing air (in) 35 C


(3) At 1 metre (see "Full load sound level" section)

(6) Recovery water (in/out) 40/45 C


(7) Partialization in % referred to compressors number.

(4) According to Eurovent (see "Full load sound level" section)

It does not correspond to the partialization of capacity

15

High efficiency chillers

CSRAT-Y

General Technical Data


CSRAT-SL-Y

Super Low Noise


2442 2642 1502 1702 1902 1922 1972 2022 2602

SIZE
Performance

CSRAT-Y
(1)

CSRAT-D-Y
(1)(5)

CSRAT-R-Y
(1)(6)

Cooling capacity
Power input
Total power input
Evaporator water flow
Evaporater water pressure drop
CVM microprocessor

kW
kW
kW
m3/h
kPa

493
177
186
85
36

461
171
176
79
43

507
174
181
87
38

542
193
200
93
47

Cooling capacity
Power input
Total power input
Desuperheater heating capacity
Evaporator water flow
Evaporator water pressure drop
Desuperheater water flow
Desuperheater water pressure
CVM microprocessor

kW
kW
kW
kW
m3/h
kPa
m3/h
kPa

W3000
512 560 318 347 389 450 478
171 187 101 120 131 154 165
180 196 105 124 137 159 170
158 173
94
111 121 142 152
88
96
55
60
67
77
82
39
50
52
43
54
41
46
27.4 30.5 16.6 19.4 21.2 24.9 26.9
35
42
40
32
38
28
33

526
168
175
155
90
41
27
33

562
186
192
171
97
51
29.4
41

Cooling capacity
Power input
Heat recovery capacity
Evaporator water flow
Evaporator water pressure drop
Heat recovery water flow
Heat recovery water pressure drop
CVM microprocessor

kW
kW
kW
m3/h
kPa
m3/h
kPa

554
150
695
95
45
120
47

W3000
344 389 425
94
104 119
433 487 537
59
67
73
61
54
65
74.8 84.3 93.2
60
50
47

536
149
676
92
43
117
54

610
162
762
105
60
132
53

540
193
202
93
47

613
168
771
105
60
133
57

307
105
109
53
49

335
124
128
58
40

375
136
142
65
51

434
159
165
75
38

474
133
599
82
45
103
58

502
141
635
86
51
109
56

W3000

Fans
n
m3/s

Fans number
Air flow

10
10
6
6
8
8
8
10
10
33.67 32.08 21.43 21.43 25.98 28.21 29.32 30.62 30.62

Compressors
Number of compressors/circuits
Number of economizers
Minimum resource step(7)

n
2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
n
0
0
0
0
0
2
2
2
0
STD+OPT 25% 25% 25% 25% 25% 25% 25% 25% 25%

Charge
kg
kg
kg
kg

153
161
199
44

186
195
242
44

97
102
126
30

100
105
130
30

100
105
130
30

98
103
127
30

108
113
140
37

122
128
159
44

126
132
164
44

kg
kg
kg

5730
5880
6320

5970
6120
6560

3850
3990
4150

3880
4080
4190

3970
4180
4410

4460
4660
4900

5170
5370
5620

5700
5910
6170

5700
5910
6190

Sound power level(4)

dB(A)

83

83

79

79

80

80

80

81

81

Sound pressure level(3)

dB(A)

63

63

63

63

64

64

64

65

65

CSRAT-Y
CSRAT-D-Y
CSRAT-R-Y
Oil

R134a
R134a
R134a

Operating weight
CSRAT-Y
CSRAT-D-Y
CSRAT-R-Y

(1) Chilled water (in/out) 12/7 C

(5) Desuperheater water (in/out) 40/45 C

(2) Condensing air (in) 35 C


(3) At 1 metre (see "Full load sound level" section)

(6) Recovery water (in/out) 40/45 C


(7) Partialization in % referred to compressors number.

(4) According to Eurovent (see "Full load sound level" section)

It does not correspond to the partialization of capacity

16

High efficiency chillers

CSRAT-Y

General Technical Data


Super Low Noise

CSRAT-SL-Y

2652 2702 2712 2722 3152 3602 3902 4202 4212

SIZE
Performance
Cooling capacity
Power input
Total power input
Evaporator water flow
Evaporater water pressure drop
CVM microprocessor

kW
kW
kW
m3/h
kPa

580
206
213
100
54

746
278
287
128
45
W3000

809
304
312
139
52

856
318
327
147
59

916
341
350
158
50

CSRAT-D-Y
(1)(5)

Cooling capacity
Power input
Total power input
Desuperheater heating capacity
Evaporator water flow
Evaporator water pressure drop
Desuperheater water flow
Desuperheater water pressure
CVM microprocessor

kW
kW
kW
kW
m3/h
kPa
m3/h
kPa

601 641 678 738 774


199 212 221 235 269
206 219 229 244 277
184 196 205 218 248
104 110 117 127 133
58
46
52
44
48
31.8 34.6 35.5 37.9 43.4
39
36
39
45
48
W3000

840
293
301
271
145
56
47
48

888
306
316
284
153
63
49.7
34

950 1045
328 333
338 347
304 307
164 180
54
65
52.7 53.8
38
39

CSRAT-R-Y
(1)(6)

Cooling capacity
Power input
Heat recovery capacity
Evaporator water flow
Evaporator water pressure drop
Heat recovery water flow
Heat recovery water pressure drop
CVM microprocessor

kW
kW
kW
m3/h
kPa
m3/h
kPa

648
172
809
112
67
140
53

921 968 1058 1106


253 269 290 296
1159 1221 1330 1384
159 167 182 190
68
75
66
73
201 211 229 238
70
60
70
65

CSRAT-Y
(1)

618
220
226
106
43

696
180
865
120
55
150
54

653
229
237
112
48

726
184
899
125
59
156
49

711
245
253
122
40

784
198
970
135
49
167
48

855
229
1070
147
59
184
59
W3000

1007
345
359
173
60

Fans
Fans number
Air flow

n
m3/s

10
10
12
12
12
12
14
14
20
32.47 33.40 41.76 36.74 28.38 32.28 46.76 41.56 68.66

n
n

2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2


0
0
1
2
1
0
0
1
2
25% 25% 25% 25% 25% 25% 25% 25% 25%

Compressors
Number of compressors/circuits
Number of economizers
Minimum resource step(7)
Charge
kg
kg
kg
kg

136
143
177
44

154
162
200
44

138
145
179
44

164
172
213
44

177
186
230
50

190
200
247
56

268
281
348
56

311
327
404
56

kg
kg
kg

5800
6010
6290

5920
6130
6420

6080
6290
6590

6410
6620
6940

7410
7270
7580

8000
7860
8160

8640
8920
9480

8790 9620
9060 9900
9620 10730

Sound power level(4)

dB(A)

81

81

82

82

82

82

83

83

84

Sound pressure level(3)

dB(A)

65

65

65

65

65

65

66

66

66

CSRAT-Y
CSRAT-D-Y
CSRAT-R-Y
Oil

R134a
R134a
R134a

229
240
297
56

Operating weight
CSRAT-Y
CSRAT-D-Y
CSRAT-R-Y

(1) Chilled water (in/out) 12/7 C

(5) Desuperheater water (in/out) 40/45 C

(2) Condensing air (in) 35 C


(3) At 1 metre (see "Full load sound level" section)

(6) Recovery water (in/out) 40/45 C


(7) Partialization in % referred to compressors number.

(4) According to Eurovent (see "Full load sound level" section)

It does not correspond to the partialization of capacity

17

High efficiency chillers

CSRAT-Y

General Technical Data


Super Low Noise

CSRAT-SL-Y

4222 4822 5403 5423 5703 6903 7203 7223 8404

SIZE
Performance

CSRAT-Y
(1)

CSRAT-D-Y
(1)(5)

CSRAT-R-Y
(1)(6)

Cooling capacity
Power input
Total power input
Evaporator water flow
Evaporater water pressure drop
CVM microprocessor

kW
kW
kW
m3/h
kPa

1074 1213 1218 1371 1274 1458 1515 1686 1773


369 418 453 545 475 539 561 626 659
383 432 467 559 489 560 582 647 681
185 209 210 236 219 251 261 290 305
46
41
57
72
46
60
65
80
47

Cooling capacity
Power input
Total power input
Desuperheater heating capacity
Evaporator water flow
Evaporator water pressure drop
Desuperheater water flow
Desuperheater water pressure
CVM microprocessor

kW
kW
kW
kW
m3/h
kPa
m3/h
kPa

1114 1259 1264 1423 1321 1513 1572


356 404 438 526 459 521 541
370 417 451 540 472 542 563
329 373 405 486 424 481 501
192 217 218 245 227 260 271
50
45
62
78
49
64
70
57.1 64.9 70.4 84.1 73.9 83.6 86.9
45
45
47
44
33
43
47

Cooling capacity
Power input
Heat recovery capacity
Evaporator water flow
Evaporator water pressure drop
Heat recovery water flow
Heat recovery water pressure drop
CVM microprocessor

kW
kW
kW
m3/h
kPa
m3/h
kPa

W3000
1176 1315 1400 1535 1454
306 350 390 416 395
1464 1644 1766 1926 1825
202 226 241 264 250
55
49
76
91
59
255 283 305 334 316
73
76
72
66
59

W3000
1749 1840
603 635
625 657
558 589
301 317
86
50
97
102
45
36

1662 1721 1850 2075


451 467 499 560
2086 2160 2319 2601
286 296 319 357
78
83
96
64
361 373 402 451
58
58
66
67

W3000

Fans
Fans number
Air flow

n
m3/s

20
20
20
20
20
24
24
24
24
61.23 57.52 48.23 51.94 51.94 70.65 72.55 69.38 70.65

n
n

2/2 2/2 3/3 3/3 3/3 3/3 3/3 3/3 4/4


2
0
3
0
0
0
0
0
0
25% 25% 16.6% 16.6% 16.6% 16.6% 16.6% 16.6% 12.5%

Compressors
Number of compressors/circuits
Number of economizers
Minimum resource step(7)
Charge
CSRAT-Y
CSRAT-D-Y
CSRAT-R-Y
Oil

R134a
R134a
R134a

kg
kg
kg
kg

257
270
334
56

306
321
398
56

307
322
399
84

307
322
399
84

333
349
433
84

278
291
361
84

294
309
382
84

294
309
382
84

447
469
581
112

Operating weight
CSRAT-Y
CSRAT-D-Y
CSRAT-R-Y

kg
kg
kg

9890 10300 11870 12310 11990 12690 12830 12970 16290


10160 10590 12210 12720 12400 13110 13240 13900 17210
10990 11430 12670 13570 13240 14360 14530 14670 18330

Sound power level(4)

dB(A)

84

85

86

86

86

86

86

86

86

Sound pressure level(3)

dB(A)

66

67

67

67

67

67

67

67

67

(1) Chilled water (in/out) 12/7 C

(5) Desuperheater water (in/out) 40/45 C

(2) Condensing air (in) 35 C


(3) At 1 metre (see "Full load sound level" section)

(6) Recovery water (in/out) 40/45 C


(7) Partialization in % referred to compressors number.

(4) According to Eurovent (see "Full load sound level" section)

It does not correspond to the partialization of capacity

18

High efficiency chillers

Efficiency Enhanced Units

CSRAT-Y

Performance of the Efficiency Enhanced


Cooling Capacity Power input

In order to improve the cooling capacity and

EER

COP

Model
kW

RT

kW

EER

kW/RT

CSRAT1502-HE-Y

345

98

94.5

3.34

1.05

CSRAT1702-HE-Y

399

113

108.1

3.33

1.06

CSRAT1902-HE-Y

453

129

125.3

3.24

1.08

CSRAT1922-HE-Y

492

140

136.5

3.26

1.08

CSRAT1972-HE-Y

521

148

144.9

3.27

1.08

CSRAT2022-HE-Y

549

156

154.6

3.25

1.08

efficiency of the unit, Climaveneta makes the


following adjustment to the unit on the basis of
standard machines:
= = Enlarge

the evaporator of the unit, adopt

closely arranged small tubes, further enlarge


the heat exchanger, and adopt dual-face
rippled tube.

CSRAT2602-HE-Y

622

177

176

3.27

1.08

the condenser of the unit, change

CSRAT2652-HE-Y

662

188

185.4

3.26

1.08

the direction of inflow, and improve the

CSRAT2702-HE-Y

715

203

200.9

3.27

1.08

cooling effect.

CSRAT2712-HE-Y

743

211

207.6

3.3

1.07

CSRAT2722-HE-Y

770

219

214.8

3.32

1.06

CSRAT3152-HE-Y

870

247

224.5

3.29

1.07

CSRAT3602-HE-Y

947

269

273.4

3.22

1.09

CSRAT3902-HE-Y

1030

293

283.5

3.3

1.07

CSRAT4202-HE-Y

1074

305

299.1

3.27

1.08

CSRAT4212-HE-Y

1154

328

306.6

3.38

1.04

CSRAT4802-HE-Y

1214

345

332.7

3.3

1.07

CSRAT4822-HE-Y

1324

377

360.2

3.35

1.05

CSRAT5403-HE-Y

1406

400

399.3

3.24

1.09

CSRAT5414-HE-Y

1486

423

415.2

3.3

1.06

CSRAT5424-HE-Y

1540

438

429.5

3.32

1.06

== Enlarge

==Provide

liquid-spray cooling and improve the

gas discharging volume.


==Add

economizors to some systems.

19

20

Pf

7
P.a.c.
Pf

8
P.a.c.
Pf

9
P.a.c.
Pf
P.a.c.

10
Pf
P.a.c.

11
Pf
P.a.c.

12
Pf
P.a.c.

13
Pf
P.a.c.

14
Pf

P.a.c.

15
Pf

P.a.c.

18

0.814 1.197 0.841 1.214 0.868 1.230 0.895 1.247 0.922 1.262 0.949 1.278 0.976 1.293 1.003 1.308 1.030 1.322 1.057 1.337 1.084 1.350

0.801 1.222 0.827 1.239 0.854 1.256 0.881 1.273 0.907 1.289 0.934 1.304 0.960 1.319 0.987 1.334 1.014 1.349 1.040 1.363 1.067 1.377

0.774 1.274 0.799 1.292 0.825 1.309 0.851 1.326 0.877 1.342 0.903 1.358 0.928 1.374 0.954 1.389 0.980 1.404 1.006 1.418 1.031 1.432

0.746 1.328 0.771 1.346 0.796 1.364 0.821 1.381 0.846 1.398 0.871 1.414 0.895 1.430 0.920 1.445 0.945 1.460 0.970 1.475 0.995 1.489

45

48

50

0.827 1.172 0.855 1.189 0.882 1.205 0.909 1.221 0.937 1.237 0.964 1.252 0.992 1.267 1.019 1.282 1.047 1.296 1.074 1.310 1.102 1.324 1.184 1.363

44

46

0.878 1.078 0.907 1.094 0.936 1.109 0.965 1.124 0.994 1.140 1.023 1.154 1.052 1.169 1.081 1.183 1.110 1.197 1.139 1.211 1.168 1.224 1.256 1.263

0.853 1.124 0.881 1.140 0.909 1.156 0.938 1.172 0.966 1.187 0.994 1.202 1.022 1.217 1.051 1.232 1.079 1.246 1.107 1.260 1.135 1.273 1.220 1.312

40

42

0.927 0.991 0.957 1.006 0.988 1.021 1.018 1.035 1.048 1.050 1.079 1.064 1.109 1.078 1.140 1.092 1.170 1.105 1.201 1.118 1.231 1.132 1.323 1.170

0.903 1.033 0.933 1.049 0.962 1.064 0.992 1.079 1.022 1.094 1.051 1.108 1.081 1.122 1.111 1.136 1.141 1.150 1.170 1.164 1.200 1.177 1.290 1.215

36

0.939 0.971 0.969 0.985 1.000 1.000 1.031 1.014 1.061 1.029 1.092 1.043 1.123 1.056 1.154 1.070 1.185 1.083 1.216 1.097 1.247 1.110 1.340 1.147

35

38

0.973 0.912 1.005 0.926 1.036 0.940 1.068 0.954 1.100 0.968 1.131 0.981 1.163 0.995 1.195 1.008 1.227 1.021 1.259 1.034 1.291 1.047 1.387 1.084

0.950 0.951 0.981 0.965 1.012 0.980 1.043 0.994 1.074 1.008 1.105 1.022 1.137 1.035 1.168 1.049 1.199 1.062 1.230 1.075 1.262 1.088 1.356 1.126

32

34

1.016 0.841 1.049 0.854 1.082 0.867 1.115 0.881 1.148 0.894 1.181 0.907 1.214 0.919 1.247 0.932 1.280 0.945 1.314 0.957 1.347 0.970 1.447 1.006

0.995 0.876 1.027 0.889 1.060 0.903 1.092 0.916 1.124 0.930 1.157 0.943 1.189 0.956 1.222 0.969 1.254 0.982 1.287 0.995 1.319 1.007 1.417 1.044

28

30

1.057 0.777 1.091 0.790 1.125 0.802 1.159 0.815 1.194 0.827 1.228 0.839 1.262 0.852 1.296 0.864 1.330 0.876 1.365 0.888 1.399 0.900 1.503 0.936

1.037 0.808 1.071 0.821 1.104 0.834 1.138 0.847 1.171 0.859 1.205 0.872 1.238 0.885 1.272 0.897 1.306 0.909 1.340 0.922 1.373 0.934 1.475 0.970

24

26

1.077 0.749 1.111 0.761 1.146 0.773 1.181 0.785 1.215 0.797 1.250 0.809 1.285 0.821 1.319 0.833 1.354 0.844 1.389 0.856 1.424 0.868 1.529 0.903

P.a.c.

22

1.114 0.697 1.150 0.708 1.185 0.719 1.221 0.731 1.256 0.742 1.292 0.753 1.328 0.765 1.363 0.776 1.399 0.787 1.435 0.799 1.471 0.810 1.579 0.845

Pf

1.096 0.722 1.131 0.733 1.166 0.745 1.201 0.757 1.236 0.768 1.271 0.780 1.307 0.792 1.342 0.803 1.377 0.815 1.412 0.827 1.448 0.838 1.554 0.873

P.a.c.

18

20

Pf

Chilled water out temperature

2For application rating condition cooling capacity and power input,please use the standard rating data multiply the coefficient.
3For more details,please contact the company.

Note1100% cooling capacity and power input at standard rating condition.

Ambient Temperature ()

Cooling Capacity Performance in Application Rating Conditions

High efficiency chillers


CSRAT-Y

High efficiency chillers

CSRAT-Y

OPERATING RANGE
CSRAT-Y

CSRAT-D-Y

CSRAT-R-Y

Evapor.

Desuperh.

Heat Rec.

Water side
Min

Max

Min

Max

Min

Max

Thermal difference()

Exch. water (out)()

5 (1)

15 (1)

26 (1)(2)

26 (2)

60 (2)

Exch. water (in)()

8 (1)(6)

23 (1)

18 (1)(2)

18 (2)

55 (2)

Limits to exchanger water temperature are valid within the minimum maximum water flow range indicated in the Hydraulic Data section.

Air side

Vers.

Min

Min

Max(*)

Max (*)

()

SL

-10 (2)

-10 (2)(3)

35-37(2)(4)

46 (2)(5)

Temp. aria esterna (in) Ambient air temp. (in)

()

LN

10 (2)

-10 (2)(3)

36-40(2)(4)

46 (2)(5)

Temp. aria esterna (in) Ambient air temp. (in)

()

15 (2)

-10 (2)(3)

46(2)(5)

Temp. aria esterna (in) Ambient air temp. (in)

(*) According to unit size


(1) Condenser air (in) 35 C
(2) Evaporator water (in/out) 12/7 C
(3) With low ambient temperature control (STD/OPT)
(4) Condenser air-flow rate in low-noise operating mode
(5) Condenser air-flow rate in standard operating mode
(6) With temperatures down to -8C use anti-freeze mixtures. In case of lower temperatures, please contact our Sales Department. Always
indicate the evaporator outlet temperature when ordering

ETHYLENE GLYCOL MIXTURE


Ethylene glycol and water mixtures, used as a heat-conveying fluid, cause a variation in unit performance. For correct data, use
the factors indicated in the following table.
Freezing point ()
0

-10

-5

-15

-20

-25

-30

-35

Ethylene glycol percentage by weight


0

12%

20%

30%

35%

40%

45%

50%

cPf

0,985

0,98

0,974

0,97

0,965

0,964

0,96

cQ

1,02

1,04

1,075

1,11

1,14

1,17

1,2

cdp

1,07

1,11

1,18

1,22

1,24

1,27

1,3

cPf cooling capacity correction factor


cQ flow correction factor
cdp pressure drop correction factor
For data concerning other kind of anti-freeze solutions (e.g. propylene glycol) please contact our Sales Department.

FOULING FACTORS
Performances are based on clean condition of tubes (fouling factor =1). For different fouling values, performance should be
adjusted using the correction factors shown in the following table.
Fouling factors

Evaporator
f1

(m2/W)

4,4 x 10-5

(m2/W) 0,86 x 10-4


2

-4

(m /W) 1,72 x 10

fk1

Heat recovery

Desuperheater

fx1

f2

fk2

fx2

f3

fk3

fx3

0,99

1,03

1,03

0,99

1,03

1,03

0,96

0,99

0,99

0,98

1,04

1,04

0,98

1,04

1,04

0,93

0,98

0,98

0,95

1,06

1,06

0,95

1,06

1,06

f1 - f2 - f3 capacity correction factors


fk1 - fk2 - fk3 compressor power input correction factors
fx1 - fx2 - fx3 total power input correction factors

21

High efficiency chillers

CSRAT-Y

WATER FLOW AND PRESSURE DROP


Water flow in the heat exchangers is given by:
Q=Px 0,86/Dt

Pressure drop is given by:

Q: water flow (m3/h)

Q: water flow (m3/h)


Dp: pressure drop (kPa)

Dp=K x Q 2 /1000

Dt: difference between inlet and outlet water temp. (C)


P: heat exchanger capacity (kW)

K: unit size ratio

Evaporator
SIZE

Q
K

min

Rec. (1) - Cond (2)


max

C.a./W.c.

m3/h

m3/h

min m3

min

Desuperheater
max

m3/h

m3/h

Q
K

min

m3/h

max

m3/h

0751

51.6

15.5

41.6

1.3

51.6

20.4

41.1

652

0851

38

17.4

46.8

1.5

38

23.8

47.9

652

10.7

0951

30

19.5

52

1.6

30

26.7

53.6

652

12.4

0961

24.1

21.6

58

1.8

24.1

29.1

58.5

299

13.5

1021

19.9

25.1

67

2.1

19.9

33.2

66.7

299

15

1301

15.2

28.5

76

2.4

15.2

38

76.2

299

16.6

1542

17.5

29.7

80

7.6

40.6

81.5

149

18.6

1742

17.5

35.3

94

2.4

7.6

47.7

95.6

85.5

21.2

1942

12.1

39.3

105

2.6

4.4

53.5

107

85.5

24.6

1962

6.8

42.7

114

2.8

4.4

58.4

117

46.5

27.6

2442

50

134

3.3

3.2

68.7

138

46.5

31.5

2642

5.4

55.4

148

3.7

3.2

76

152

46.5

34.2

1502

17.5

31.5

84.4

2.1

10.7

41.7

83.7

149

18

1702

12.1

35.2

94.3

2.3

18.3

96.8

85.5

21.6

1902

12.1

39.1

105

2.6

5.4

23.4

107.1

85.5

23.7

1922

6.8

44.4

119

5.4

29.1

118.1

46.5

26.5

1972

6.8

47.2

126

3.2

4.6

32.7

125.1

46.5

28.2

2022

51.5

138

3.4

3.9

36.9

134.1

46.5

28.4

2602

5.4

56.8

152

3.8

45.9

152.1

46.5

33.1

2652

5.4

60.3

161

2.7

50.6

161.1

37.6

35.1

2702

3.8

64.3

172

4.3

2.4

56.2

172.1

31

37.6

2712

3.8

67.2

179

4.5

59.3

179.1

31

38.9

2722

2.7

73.2

196

4.9

1.7

65.4

191.1

31

39.7

3152

2.7

78.5

210

5.2

1.7

75.7

211.1

25.7

47.2

3602

2.7

84.3

225

5.6

1.7

85.4

231.1

21.6

52.9

3902

2.7

89.3

239

1.3

91.1

242.1

13.8

54.6

4202

97

258

6.4

1.3

101.5

263.1

13.8

58.5

4212

104

278

1.1

109

271.1

13.8

62.7

4222

1.4

111

297

7.4

1.1

118

271.1

13.8

68.5

4822

124

330

8.3

0.9

133

297.1

10.7

69

5403

1.3

129

344

8.6

0.8

145.1

350.1

9.6

78.1

5423

1.3

142

378

9.4

0.6

161.8

384.1

6.1

88.7

5703

133

330

8.9

0.6

151

363.1

6.1

81.9

6903

154

330

10.3

0.4

177

414.1

6.1

91.1

7203

160

330

10.7

0.4

184

428.1

6.1

94.2

7223

173

330

11.5

0.4

201

446.1

4.7

105

8404

0.5

188

500

12.5

0.3

228.9

518.1

3.4

115

Q min: minimum water flow admitted to the heat exchanger.


Q max: maximum water flow admitted to the heat exchanger.
W.c min.: minimum water content admitted in the plant.

(1) Rec. = Heat Recovery. For units with total heat recovery.
(2) Cond. = Condenser. For water to water type units. In units with heatrecovery ,
this data is valid for both the condensing and the heatrecovery exchangers.

22

High efficiency chillers

CSRAT-Y

Electrical Data
Maximum values
Compressor
Size
n

F.L.I.
(kW)

Fan motors (1)

F.L.A.

L.R.A.

F.L.I.

(A)

F.L.A.
(A)

Total unit (1) (2)


F.L.I.

F.L.A.

S.A.

(A)

(kW)

(kW)

(A)

(A)

0751

64.3

105

290

5.8

11.6

70.1

117

302

0851

70.2

115

350

5.8

11.6

76

127

362

0951

82.1

132

423

5.8

11.6

87.9

144

435

0961

82.1

132

423

5.8

11.6

87.9

144

435

1021

85.4

137

246

8.7

17.4

94.1

154

263

1301

112

184

360

8.7

17.4

121

201

377

1542

64.3

105

290

8.7

17.4

137

227

412

1742

70.2

115

350

12.6

22.8

153

253

488

1942

82.1

132

423

12.6

30.4

177

294

585

1962

82.1

132

423

12.6

30.4

177

294

585

2442

101

165

300

16.8

38

219

368

503

2642

112

184

360

16.8

38

241

406

582

1502

64.3

104.7

290

8.7

17.4

137

227

412

1702

70.2

114.9

350

8.7

17.4

152

253

488

1902

82.1

131.7

423

11.6

23.2

179

292

584

1922

82.1

131.7

423

11.6

23.2

179

292

584

1972

82.1/85.4

131.7/137

229/246

11.6

23.2

179

292

401

2022

85.4

137

246

14.5

29

185

303

412

2602

111.6

183.5

360

14.5

29

238

396

573

2652

111.6/127.3

183.5/208

360/404

14.5

29

253

421

617

2702

127.3

208

404

14.5

29

269

445

641

2712

127.3

208

404

17.4

34.8

272

451

647

2722

127.3

208

404

17.4

34.8

272

451

647

3152

127.3/170.7

208/272

404/465

17.4

34.8

315

515

708

3602

170.7

272

465

17.4

34.8

359

579

772

3902

170.7/191.1

272/310

465/586

20.3

40.6

382

623

899

4202

191.1

310

586

20.3

40.6

403

661

937

4212

191

310

586

29

58

411

678

954

4222

191

310

586

29

58

411

678

954

4822

217

351

650

29

58

463

760

1059

5403

170.7

272

465

29

58

541

874

1067

5423

170.7

272

465

29

58

541

874

1067

5703

171/191

272/310

465/586

29

58

562

912

1188

6903

191/217

310/351

586/650

50.4

91.2

675

1103

1402

7203

217

351

650

50.4

91.2

701

1144

1443

7223

217

351

650

50.4

91.2

701

1144

1443

8404

191.1

310

586

50.4

91.2

815

1331

1607

F.L.I. Full load power input at max admissible condition


F.L.A. Full load current at max admissible condition

(1) Values calculated referring to the version with the maximum number of fans
working at the max absorbed current

L.R.A. Locked rotor amperes for single compressor


S.A. Starting current

(2) Safety values to be considered when cabling the unit for power supply and lineprotections
Power supply 400/3/50
Voltage tolerance: 10%
Maximum voltage unbalance: 3%

23

High efficiency chillers

CSRAT-Y

Full Load Sound Level


Total sound level
Size

Sound
Power

Standard

Octave band [Hz] at 10 m

Sound Pressure
10m

1m

63

125

250

500

1000

2000

4000

8000

Sound pressure level [dB]

0751

88

50

70

64

70

70

66

67

60

57

48

0851

88

50

70

64

70

70

66

67

60

57

48

0951

88

50

70

64

70

70

66

67

60

57

48

0961

88

50

70

64

70

70

66

67

60

57

48

1021

90

52

71

67

71

71

67

69

59

55

47

1301

90

52

71

67

71

71

67

69

59

55

47

1542

91

53

72

68

73

70

70

69

62

54

45

1742

91

53

72

68

73

70

70

69

62

54

45

1942

91

53

72

68

73

70

70

69

62

54

45

1962

91

53

72

68

73

70

70

69

62

54

45

2442

93

55

73

68

73

70

72

70

62

52

45

2642

93

55

73

68

73

70

72

70

62

52

45

1502

92

54

76

77

75

71

69

73

70

64

55

1702

92

54

76

77

75

71

69

73

70

64

55

1902

93

55

77

78

75

71

71

74

71

64

53

1922

93

55

77

78

75

71

71

73

71

65

54

1972

93

55

77

78

75

71

71

73

71

65

54

2022

93

55

77

78

75

71

71

74

71

65

54

2602

93

55

77

78

75

71

70

74

72

66

54

2652

93

55

77

77

74

70

70

73

71

65

53

2702

93

55

77

77

74

70

70

73

71

65

53

2712

95

57

78

78

76

72

71

74

72

66

54

2722

95

57

78

78

76

72

71

74

72

66

54

3152

95

57

78

78

76

72

72

75

71

68

57

3602

95

57

78

77

75

71

71

74

70

69

57

3902

96

58

79

79

76

72

73

76

71

70

58

4202

96

58

79

79

76

72

73

76

71

70

58

4212

97

59

79

80

77

73

73

76

72

70

58

4222

97

59

79

80

77

73

73

76

72

70

58

4822

98

60

80

80

77

73

74

76

72

70

58

5403

99

61

80

80

77

73

74

77

72

71

59

5423

99

61

80

80

77

73

74

77

72

71

59

5703

99

61

80

80

77

73

74

77

73

72

60

6903

99

61

80

80

77

73

75

77

73

71

59

7203

99

61

80

80

77

73

75

77

73

71

59

7223

99

61

80

80

77

73

75

77

73

71

59

8404

99

61

80

74

71

67

73

76

70

73

61

Working conditions
Evaporator water (in/out) 12/7 [C]

Such certification refers specifically to the sound Power Level in


dB(A). This is therefore the only acoustic data to be considered as

Ambient air 35 [C]


Sound power

binding.
Sound pressure at 10 metres

Climaveneta gives the Sound Power level values based on

Free field sound pressure on a reflecting surface (directivity fact. Q=2), at a

measurements carried out according to ISO 3744, as required


by EUROVENT certification ( Eurovent 8/1 sound tests ).

distance of 10m from the external surface of the unit. Average value
calculated from the sound power.

24

High efficiency chillers

CSRAT-Y

LN

Full Load Sound Level


Total sound level

Size

Sound
Power

Low Noise

Octave band [Hz] at 10 m

Sound Pressure
10m

1m

63

125

250

500

1000

2000

4000

8000

Sound pressure level [dB]

0751

82

44

64

64

65

68

61

59

53

50

41

0851

82

44

64

64

65

68

61

59

53

50

41

0951

82

44

64

64

65

68

61

59

53

50

41

0961

82

44

64

64

65

68

61

59

53

50

41

1021

84

46

65

65

66

68

62

61

54

51

41

1301

84

46

65

65

66

68

62

61

54

51

41

1542

85

47

66

65

66

68

64

62

56

51

41

1742

85

47

66

65

65

67

64

62

56

51

41

1942

85

47

66

65

65

67

64

62

56

51

41

1962

85

47

66

65

65

67

64

62

56

51

41

2442

87

49

67

65

65

67

65

64

56

51

41

2642

87

49

67

65

65

67

65

64

56

51

41

1502

86

48

70

74

62

62

65

67

62

59

49

1702

86

48

70

74

62

62

65

67

62

59

49

1902

87

49

71

74

62

62

66

68

64

58

46

1922

87

49

71

74

62

62

67

67

64

59

47

1972

87

49

71

74

62

62

67

67

64

59

47

2022

87

49

71

74

61

61

66

67

64

59

46

2602

87

49

71

74

61

61

65

67

65

60

47

2652

87

49

71

74

61

61

65

67

65

60

47

2702

87

49

71

74

61

61

66

67

65

60

47

2712

89

51

72

75

62

63

67

68

66

61

48

2722

89

51

72

75

62

63

67

68

66

61

48

3152

89

51

72

74

61

62

67

68

64

63

50

3602

89

51

72

73

60

61

67

68

62

63

50

3902

90

52

73

75

62

63

68

70

64

65

52

4202

90

52

73

75

62

63

68

70

64

65

52

4212

91

53

73

75

62

63

68

70

64

64

51

4222

91

53

73

75

62

63

68

70

64

64

51

4822

92

54

74

76

63

64

70

71

65

65

52

5403

93

55

74

75

62

63

69

71

64

66

53

5423

93

55

74

75

62

63

69

71

64

66

53

5703

93

55

74

75

62

63

69

71

65

66

53

6903

93

55

74

75

63

63

70

71

65

66

53

7203

93

55

74

75

63

63

71

71

65

66

53

7223

93

55

74

75

63

63

71

71

65

66

53

8404

93

55

74

68

56

57

69

71

63

67

53

Working conditions
Evaporator water (in/out) 12/7 [C]

Such certification refers specifically to the sound Power Level in


dB(A). This is therefore the only acoustic data to be considered as

Ambient air 35 [C]


Sound power

binding.
Sound pressure at 10 metres

Climaveneta gives the Sound Power level values based on

Free field sound pressure on a reflecting surface (directivity fact. Q=2), at a

measurements carried out according to ISO 3744, as required


by EUROVENT certification ( Eurovent 8/1 sound tests ).

distance of 10m from the external surface of the unit. Average value
calculated from the sound power.

25

High efficiency chillers

CSRAT-Y

SL

Full Load Sound Level


Total sound level

Size

Sound
Power

Super Low Noise

Octave band [Hz] at 10 m

Sound Pressure
10m

1m

63

125

250

500

1000

2000

4000

8000

Sound pressure level [dB]

0751

78

40

60

64

61

64

59

53

48

46

38

0851

78

40

60

64

61

64

59

53

48

46

38

0951

78

40

60

64

61

64

59

53

48

46

38

0961

78

40

60

64

61

64

59

53

48

46

38

1021

80

42

61

64

63

65

59

55

51

47

40

1301

80

42

61

64

63

65

59

55

51

47

40

1542

81

42

61

64

63

65

59

55

51

47

40

1742

81

43

62

64

63

65

60

57

52

47

40

1942

81

43

62

64

63

65

60

57

52

47

40

1962

81

43

62

64

63

65

60

57

52

47

40

2442

83

45

63

64

63

65

62

58

52

48

40

2642

83

45

63

64

63

65

62

58

52

48

40

1502

79

41

63

61

52

52

57

60

54

54

45

1702

79

41

63

61

52

52

57

60

54

54

45

1902

80

42

64

61

51

52

60

61

57

53

41

1922

80

42

64

61

51

52

61

61

57

54

41

1972

80

42

64

61

51

52

61

61

57

54

41

2022

81

43

65

62

52

53

61

61

57

55

42

2602

81

43

65

61

52

52

58

61

59

56

42

2652

81

43

65

61

52

52

59

61

59

56

42

2702

81

43

65

61

52

52

60

61

59

56

42

2712

82

44

65

61

52

52

59

61

58

56

42

2722

82

44

65

61

52

52

59

61

58

56

42

3152

82

44

65

60

51

52

60

62

56

58

44

3602

82

44

65

59

50

51

61

62

54

58

45

3902

83

45

66

60

51

52

62

63

55

59

46

4202

83

45

66

60

51

52

62

63

55

59

46

4212

84

46

66

62

52

53

61

63

56

59

46

4222

84

46

66

62

52

53

61

63

56

59

46

4822

85

47

67

62

52

53

63

63

56

59

46

5403

86

48

67

61

51

53

62

64

56

60

47

5423

86

48

67

61

51

53

62

64

56

60

47

5703

86

48

67

61

51

53

62

64

56

60

47

6903

86

48

67

61

51

53

63

64

57

60

47

7203

86

48

67

61

51

53

64

64

57

60

47

7223

86

48

67

61

51

53

64

64

57

60

47

8404

86

48

67

53

43

48

62

63

55

60

46

Working conditions
Evaporator water (in/out) 12/7 [C]

Such certification refers specifically to the sound Power Level in


dB(A). This is therefore the only acoustic data to be considered as

Ambient air 35 [C]


Sound power

binding.
Sound pressure at 10 metres

Climaveneta gives the Sound Power level values based on

Free field sound pressure on a reflecting surface (directivity fact. Q=2), at a

measurements carried out according to ISO 3744, as required


by EUROVENT certification ( Eurovent 8/1 sound tests ).

distance of 10m from the external surface of the unit. Average value
calculated from the sound power.

26

27

10
11

CSRAT1542-2642-Y

data should be considered as indicative. CLIMAVENETA may modify them at any moment.

For installation purposes, please refer to the documentation sent after the purchase-contract. This technical

REMARKS:

Dimension Drawing
CSRAT0751-1301-Y

High efficiency chillers


CSRAT-Y

28

REMARKS:

data should be considered as indicative. CLIMAVENETA may modify them at any moment.

For installation purposes, please refer to the documentation sent after the purchase-contract. This technical

CSRAT5403-8404-Y

CSRAT1502-4822-Y

Dimension Drawing

High efficiency chillers


CSRAT-Y

29

INSTRUCTIONS

- Use a spread-bar (not included)


- Move the unit carefully and avoid abrupt movements.

- Use slings of equal length,

- Before lifting it, check the weight on the CE label.


- Use all, and only, the lifting points provided,

- Make sure that all the panels are firmly fixed in place before moving the unit.

Free Spaces - Lifting Mode - Symbols

High efficiency chillers


CSRAT-Y

0751
0851
0951
0961
1021
1301
1542
1742
1942
1962
2442
2642
1502
1702
1902
1922
1972
2022
2602
2652
2702
2712
2722
3152
3602
3902
4202
4212
4222
4822
5403
5423
5703
6903
7203
7223
8404

B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B

Size

A(mm)
3110
3110
3110
3110
4610
4610
4610
4610
4610
4610
5610
5610
4000
4000
4000
4900
4900
4900
4900
4900
4900
5800
5800
5800
5800
7000
7000
9400
9400
9400
10300
10300
10300
11200
11200
11200
11200

B(mm)
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260

H(mm)
2150
2150
2150
2150
2170
2170
2170
2420
2420
2420
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430

CSRAT-Y
P./W.(Kg) A(mm)
1680
3110
1710
3110
1780
3110
1860
3110
2590
4610
2720
4610
3490
4610
3680
4610
3810
4610
4100
4610
5140
5610
5340
5610
3760
4000
3790
4000
3880
4000
4360
4900
5050
4900
5560
4900
5560
4900
5660
4900
5770
4900
5940
5800
6270
5800
7360
5800
8040
5800
8470
7000
8610
7000
9430
9400
9690
9400
10110
9400
11840
10300
12020
10300
11950
10300
12390
11200
12530
11200
12670
11200
16360
11200
B(mm)
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
H(mm)
2150
2150
2150
2150
2170
2170
2170
2420
2420
2420
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430

CSRAT-D-Y
P./W.(Kg) A(mm)
1710
3110
1730
3110
1810
3110
1880
3110
2610
4610
2740
4610
3600
4610
3820
4610
3950
4610
4250
4610
5290
5610
5490
5610
3910
4000
4000
4000
4080
4000
4560
4900
5250
4900
5760
4900
5760
4900
5860
4900
5990
4900
6150
5800
6480
5800
7220
5800
7900
5800
8750
7000
8890
7000
9710
9400
9970
9400
10390
9400
12170
10300
12430
10300
12370
10300
12810
11200
12940
11200
13100
11200
17290
12700
H(mm)
2150
2150
2150
2150
2170
2170
2170
2420
2420
2420
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430

CSRAT-R-Y
B(mm)
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260

Dimensions And Weights

P./W.(Kg) R1(mm)
1770
2000
1810
2000
1900
2000
1980
2000
2720
2000
2870
2000
3820
2000
4010
2000
4220
2000
4510
2000
5720
2000
5930
2000
4060
2000
4100
2000
4310
2000
4800
2000
5500
2000
6030
2000
6050
2000
6150
2000
6270
2000
6450
2000
6800
2000
7530
2000
8210
2000
9310
2000
9450
2000
10530
2000
10800
2000
11240
2000
12630
2000
13280
2000
13210
2000
14060
2000
14230
2000
14370
2000
18410
2000
R2(mm)
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
R3(mm)
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800

FREE SPACES
R4(mm)
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500

High efficiency chillers


CSRAT-Y

30

0751
0851
0951
0961
1021
1301
1542
1742
1942
1962
2442
2642
1502
1702
1902
1922
1972
2022
2602
2652
2702
2712
2722
3152
3602
3902
4202
4212
4222
4822
5403
5423
5703
6903
7203
7223
8404

LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN
LN

Size

A(mm)
3110
3110
3110
3110
4610
4610
4610
4610
4610
4610
5610
5610
4000
4000
4000
4900
4900
4900
4900
4900
4900
5800
5800
5800
5800
7000
7000
9400
9400
9400
10300
10300
10300
11200
11200
11200
11200

B(mm)
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260

H(mm)
2150
2150
2150
2150
2170
2170
2170
2420
2420
2420
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430

CSRAT-Y
P./W.(Kg) A(mm)
1680
3110
1710
3110
1780
3110
1860
3110
2590
4610
2720
4610
3490
4610
3680
4610
3810
4610
4100
4610
5140
5610
5340
5610
3800
4000
3830
4000
3920
4000
4410
4900
5090
4900
5630
4900
5630
4900
5730
4900
5840
4900
6010
5800
6340
5800
7330
5800
7900
5800
8550
7000
8700
7000
9530
9400
9800
9400
10210
9400
11730
10300
11920
10300
11850
10300
12560
11200
12690
11200
12830
11200
16110
11200
B(mm)
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
H(mm)
2150
2150
2150
2150
2170
2170
2170
2420
2420
2420
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430

CSRAT-D-Y
P./W.(Kg) A(mm)
1710
3110
1730
3110
1810
3110
1880
3110
2610
4610
2740
4610
3600
4610
3820
4610
3950
4610
4250
4610
5290
5610
5490
5610
3940
4000
4030
4000
4130
4000
4610
4900
5300
4900
5830
4900
5830
4900
5940
4900
6060
4900
6220
5800
6550
5800
7190
5800
7770
5800
8830
7000
8970
7000
9810
9400
10070
9400
10500
9400
12070
10300
12330
10300
12270
10300
12970
11200
13110
11200
13260
11200
17000
12700
B(mm)
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
H(mm)
2150
2150
2150
2150
2170
2170
2170
2420
2420
2420
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430

CSRAT-R-Y

Dimensions And Weights

P./W.(Kg) R1(mm)
1770
2000
1810
2000
1900
2000
1980
2000
2720
2000
2870
2000
3820
2000
4010
2000
4220
2000
4510
2000
5720
2000
5930
2000
4100
2000
4140
2000
4360
2000
4810
2000
5550
2000
6100
2000
6120
2000
6220
2000
6340
2000
6520
2000
6870
2000
7500
2000
8070
2000
9390
2000
9530
2000
10630
2000
10900
2000
11340
2000
12530
2000
13170
2000
13110
2000
14220
2000
14390
2000
14530
2000
18130
2000
R2(mm)
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
R3(mm)
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800

FREE SPACES
R4(mm)
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500

High efficiency chillers


CSRAT-Y

31

0751
0851
0951
0961
1021
1301
1542
1742
1942
1962
2442
2642
1502
1702
1902
1922
1972
2022
2602
2652
2702
2712
2722
3152
3602
3902
4202
4212
4222
4822
5403
5423
5703
6903
7203
7223
8404

SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL
SL

Size

A(mm)
3110
3110
3110
4110
4610
4610
4610
4610
5610
5610
6610
6610
4000
4000
4000
4900
4900
4900
4900
4900
4900
5800
5800
5800
5800
7000
7000
9400
9400
9400
10300
11200
10300
11200
11200
11200
11200

B(mm)
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260

H(mm)
2150
2150
2150
2150
2170
2170
2170
2420
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430

CSRAT-Y
P./W.(Kg) A(mm)
1680
3110
1770
3110
1840
3110
1980
4110
2670
4610
2720
4610
3580
4610
3790
4610
3960
5610
4410
5610
5730
6610
5970
6610
3850
4000
3880
4000
3970
4000
4460
4900
5170
4900
5700
4900
5700
4900
5800
4900
5920
4900
6080
5800
6410
5800
7410
5800
8000
5800
8640
7000
8790
7000
9620
9400
9890
9400
10300
9400
11870
10300
12310
11200
11990
10300
12690
11200
12830
11200
12970
11200
16290
11200
B(mm)
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
H(mm)
2150
2150
2150
2150
2170
2170
2170
2420
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430

CSRAT-D-Y
P./W.(Kg) A(mm)
1710
3110
1790
3110
1870
3110
2010
4110
2700
4610
2740
4610
3690
4610
3930
4610
4100
5610
4560
5610
5880
6610
6120
6610
3990
4000
4080
4000
4180
4000
4660
4900
5370
4900
5910
4900
5910
4900
6010
4900
6130
4900
6290
5800
6620
5800
7270
5800
7860
5800
8920
7000
9060
7000
9900
9400
10160
9400
10590
9400
12210
10300
12720
11200
12400
10300
13110
11200
13240
11200
13900
11200
17210
12700
H(mm)
2150
2150
2150
2150
2170
2170
2170
2420
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430
2430

CSRAT-R-Y
B(mm)
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260

Dimensions And Weights

P./W.(Kg) R1(mm)
1770
2000
1870
2000
1960
2000
2110
2000
2810
2000
2870
2000
3910
2000
4120
2000
4370
2000
4820
2000
6320
2000
6560
2000
4150
2000
4190
2000
4410
2000
4900
2000
5620
2000
6170
2000
6190
2000
6290
2000
6420
2000
6590
2000
6940
2000
7580
2000
8160
2000
9480
2000
9620
2000
10730
2000
10990
2000
11430
2000
12670
2000
13570
2000
13240
2000
14360
2000
14530
2000
14670
2000
18330
2000
R2(mm)
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
R3(mm)
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800

R4(mm)
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500

FREE SPACES (See fol. page)

High efficiency chillers


CSRAT-Y

32

High efficiency chillers

CSRAT-Y

Heat Recovery Function of the Packaged Chiller


In addition to summer/winter air-conditioning, many users require abundant hot water all year
round. Although hotels are the first of such users that come to mind, medical clinics, gyms and
swimming pools all have similar needs. The Climaveneta solution is composed by a system with
partial or total heat recovery.
CSRAT-D-Y model with partial heat recovery (D)
Air cooled chiller with partial heat recovery. Compared with the basic configuration, this version
features an additional refrigerant/water heat exchanger on the gas delivery line. This heat exchanger,
fitted in series before the traditional cooling circuit condenser, is large enough to recover heat for
the production of medium-to-high temperature water for domestic hot water and the like.
CSRAT-R-Y model with heat recovery (R)
Air cooled chiller with total heat recovery. Compared with the basic configuration, this version
features an additional refrigerant/water heat exchanger on the gas delivery line. This heat exchanger,
fitted in parallel with the traditional cooling circuit condenser, is large enough to recover heat for the
production of domestic hot water and the like. The heating capacity of the heat recovery circuit is
approximately equal to the cooling power plus the power input of the compressors.

33

Climaveneta Italy:
36061 BASSANO DEL GRAPPA (VICENZA) ITALIA - VIA SARSON 57/c
TEL. +39 / 0424 509 500 (r.a.) - TELEFAX +39 / 0424 509 509
E-mail:info@climaveneta.com http://www.climaveneta.com
Climaveneta China:
No,88 Baiyun Road Xinghuo Developing Zone ,Shanghai,China Post Code:201419
TEL: +86-21-57505566 FAX: +86-21-57505797
E-mail:info@climaveneta.com.cn http://www.climaveneta.com.cn
Climaveneta Hongkong:
Room 2003,CCT Telecom Building, 11 Wo Shing Street,Fotan,Shatin,N.T.,Hongkong
TEL: +85-2-26871755 FAX: +85-2-26873078
E-mail:info@climaveneta.com.cn http://www.climaveneta.asia
Climaveneta Vietnam:
381A1 Cong Hoa Street Ward 13 Tan Binh District, HCM City, Vietnam
TEL: +84-8-38497529 FAX: +84-8-38124190
E-mail:info@climaveneta.com.cn http://www.climaveneta.asia

All specification and data are subject to change without notice

B113 CCU/01-12-2009EN-SH

You might also like