Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

FCU Engineering Guide

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

SECTION F1

Engineering Guide
Fan & Blower Coils
Please refer to the Price Engineers HVAC Handbook
for more information on Fan Coils & Blower Coils.

Fan Coils and Blower Coils

Engineering Guide

ENGINEERING GUIDE - FAN COILS & BLOWER COILS

Product Fundamentals
Fan coils are a type of air handling unit
designed to supply conditioned air to a
room or zone. The basic components that
make up a fan coil unit are a finned-tube
heat exchanger, fan section and filter. The
fan produces forced convection across the
heat exchanger, which circulates either hot
or cold water to provide conditioned air to
the space. Individual zone thermostats are
coupled to the fan coils fan speed controller
and hydronic controls to maintain room
temperature. A well-designed fan coil
unit will have low air and water pressure
drops across the coil to reduce fan and
pump power requirements as well as an
efficient fan and motor assembly for quiet
operation. Also, any fan coil unit equipped
with a cooling coil should have a drain pan
installed to capture condensate, regardless
of whether or not the entering air is preconditioned. Fan coils are located in or
near the space to be conditioned for free
delivery of air into the zone or with minimal
duct work. Units generally operate with a
blow-through arrangement where the coil is
downstream of the fan. Most fan coil units
are supplied with a direct drive fan/motor
assembly.
Most manufacturers certify their fan coil
units cooling performance to the AirConditioning, Heating, and Refrigeration
Institute standard AHRI Standard 4402008: Performance Ratings for Room Fan
Coils. The purpose of the standard is to
provide classifications, test requirements,
and minimum data requirements for the
published ratings of fan coil units delivering
up to 1500 cfm.
Fan coils can be used in decentralized HVAC
systems or in conjunction with a central
air handling unit. The major advantages
of using fan coil units are that they allow
for local control of individual zones and
reduce the overall footprint of the system
by replacing ductwork with water piping
in a large portion of the system. They also
reduce the amount of cross-contamination
between zones and allow for unused areas
to be shut down. To receive ventilation air,
fan coils can either be ducted to a central
air handler or to a mixing plenum. When
attached to a mixing plenum, care must
be taken as fan coils do not typically have
provisions for controlling the amount of
outdoor air admitted, and the coil must be
protected from freezing in cold climates.

F1-2

Figure 1: View of Fan Coil Unit


Coil Connections

Fan Assembly

Filter Rack
Discharge Panel

Discharge
Opening

Coils

Drain Pan

Fan Coil Components


Access Panel Removable sheet metal section allows access to internal mechanical
and electrical components.
Belt Drive The motor turns the blower by a belt connected to pulleys on each shaft
end. Each motor revolution will usually not be equal to one blower revolution.
Blower/Fan Multi-bladed, driven rotor enclosed so that air from an inlet is
compressed to a higher discharge pressure.
Casing Structural sheet metal box or shell to which all components are secured.
Coil A heat exchanger in which liquid is circulated to provide heating or cooling to
the air which passes through the heat sink fins.
Control Enclosure Sheet metal shroud which houses the electrical connections,
speed controller and transformer. The enclosure cover prevents accidental electrical
shock as well as protects the contents from the environment.
Direct Drive The motor shaft is directly secured to the blower shaft. Each motor
revolution is equal to one blower revolution.
Discharge Collar Rectangular fitting attached to the unit outlet allowing for quick
attachment of downstream ductwork.
Drain Pan Pan located under the cooling coil to catch condensate formed during
cooling.
Filter Rack Tray in which a filter can be pulled out for maintenance or replacement.
Liner Internal blanket adhered to the casing that is used to reduce the radiated and/
or discharge sound levels. Materials used vary based on application and performance
required.
Motor Electrical component of an air movement device that provides work to turn
the blade assembly.

All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.

Copyright Price Industries Limited 2011.

Fan Coils and Blower Coils


Engineering Guide

Fan Coils with Dedicated Outdoor Air Systems (DOAS)

Supply Air

Fan Coil
Unit

Zone 2
T

CLASSROOM

AHU

CLASSROOM
Relief Air

Return Air

Figure 3: Outdoor air ducted into fan coil unit

Fan Coil
Unit
Outdoor
Air

Zone 1

Zone 2

CLASSROOM

CLASSROOM

AHU

Relief Air

Copyright Price Industries Limited 2011.


All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.

F1-3

ENGINEERING GUIDE - FAN COILS & BLOWER COILS

Outdoor
Air
Zone 1

Fan Coil
Unit

In Figure 2 the outdoor air is delivered


directly to the space through a separate
diffuser, independent of the fan coil unit.
This allows the fan coil unit to be turned
off or run at low speed during part load
conditions. Note that if a low supply air
temperature (less than 55 F) is required
for dehumidification, a high induction
diffuser should be selected to prevent
drafts. Another option is to duct the
outdoor air into the fan coil unit (Figure 3).
In this case the fan coil must run during part
load, however ductwork is minimized.

Figure 2: Outdoor air ducted through separate diffusers

Fan Coil
Unit

Often fan coil units are applied in a


dedicated outdoor air system (DOAS). In this
configuration the air handler is selected to
dehumidify and condition the outdoor air
as well as to handle the space latent load.
The fan coil unit provides sensible cooling
or heating at the zone (Figure 2). This
configuration has several advantages over
a conventional VAV system. Decoupling the
sensible and latent loads ensures proper
humidity control at each zone. Additionally,
the exact outdoor air requirements to each
zone can be maintained, eliminating overventilation and ensuring compliance with
ASHRAE Standard 62-2001Ventilation for
Acceptable Indoor Air Quality (IAQ). Energy
savings can be realized due to reduced
terminal reheat and reduced outdoor air.
Additionally, the DOAS system can be
turned off during unoccupied hours with the
fan coils maintaining local zone temperature
control.

Fan Coils and Blower Coils


Engineering Guide

Fan Coil Unit Types

ENGINEERING GUIDE - FAN COILS & BLOWER COILS

Low Pressure Fan Coils


Low pressure fan coils are generally
located in or adjacent to the space to be
conditioned. They are usually selected for
free delivery of air into the zone or with
minimal ductwork having a static resistance
of less than 0.25 in. w.g. A well-designed
unit should be equipped with an easily
removable filter, drain pan and fan/motor
assembly to reduce maintenance costs
and improve indoor air quality. They
are normally offered in nominal air flow
sizes up to 1200 cfm and use multispeed,
high-efficiency motors. Units commonly
have single point power connections and
three position (plus shutdown) fan speed
controllers. Units are available in vertical or
horizontal configurations for exposed and
concealed applications as shown in Figure
4 and Figure 5.

Figure 4: Vertical Updraft Fan Coil


Arrangement

Figure 5: Horizontal Fan Coil


Arrangement

Cross Section View


Discharge Air Opening

Cross Section View

Coils

Fan
Filter
Return Air Opening
Duct

Coils

Ceiling

Fan

Filter

Concealed Units
Concealed units can be furred into a wall or
installed in a ceiling plenum and then are
typically ducted to a single discharge grille
or diffuser as shown in Figure 6.

Figure 6: Horizontal Concealed Fan Coil

Exposed Units
Exposed units are generally installed in
a visible location and therefore have an
attractive painted finish and return and
supply air grilles as shown Figure 7. Units
use fully insulated casings to reduce the
amount of noise delivered to the occupied
space, and the footprint is designed to be
small to minimize the amount of occupied
space they require.
Typical Applications
Low pressure fan coils are ideally suited
for applications where individual zone
temperature control is required. This
makes them an ideal candidate for hotels,
apartment buildings and office buildings
(ASHRAE, 2008a). In many cases vertical
units are installed so that the supply air
washes the window and helps lower the
thermal impact of the glass. Fan coils can be
used in health care facilities, but care should
be taken because of their low-efficiency
filters and because they are designed mostly
for re-circulated air which is not permitted
in certain types of spaces.

F1-4

Figure 7: Vertical Exposed Fan Coil

All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.

Copyright Price Industries Limited 2011.

Fan Coils and Blower Coils


Engineering Guide

Fan Coil Unit Types


High Performance Fan Coils

To achieve the higher flows and static


pressures and still maintain efficiency, high
performance fan coils are often equipped
with electronically commutated motors
(ECM). ECMs also allow for full range
digital speed controllers and constant flow
programming. Full range speed control
allows the fan speed to be optimized at
the setting which meets the room load
and acoustic design goals. Constant flow
programming ensures the fan flow will be
maintained even as the filter resistance
increases due to dust buildup.
When coupled with electronic or DDC
controls ECMs can also be operated to
provide variable volume of both cooling and
heating fan flows, contributing to further
energy savings and enhanced comfort. See
page 608 for details.
High performance fan coils can be
performance certified up to 1500 cfm
under the AHRI Standard 440-2008. Units
operating beyond the scope of this standard
should still be tested and rated under
the same conditions to ensure reliable
performance in the field.

Copyright Price Industries Limited 2011.


Figure 8: Classroom installation

Duct

High Performance
Fan Coil Unit

Supply
Return

Corridor
CLASSROOM

Figure 9: Horizontal High Performance Fan Coils

Typical Applications
High performance fan coils are an excellent
choice for applications where a high level of
individual zone temperature control and low
noise is required. This makes them an ideal
candidate for schools, hotels, apartments
and office buildings. Higher air volume and
static pressure capability also make them
ideal for larger spaces and applications
requiring longer duct runs and multiple air
outlets such as labs, meeting rooms, halls,
lecture theaters, etc.

The high cooling capacity available with


high performance fan coils meets the needs
of high load spaces such as labs, perimeter
zones with high solar loads, and high
occupancy spaces. High performance fan
coils are also well-suited for hospitals and
laboratories because of their constant flow
programmability and their ability to use
higher efficiency filters. The high efficiency
and VAV capability of ECM technology,
coupled with the energy efficient benefits
of hydronic cooling or heating and the
IAQ benefits of a DOAS system lends well
to LEED certification and green building
design.

All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.

F1-5

ENGINEERING GUIDE - FAN COILS & BLOWER COILS

High performance fan coils are designed


for higher air volumes, higher static
pressures, low noise levels and better room
temperature control. To achieve the lower
sound levels the high performance fan
coils typically utilize larger fan blowers to
reduce outlet velocity and fully enclose the
fan/motor assembly in an insulated casing.
They are normally offered in a horizontal
concealed configuration as shown in Figure
9 and are ducted to one or more supply
air grilles. Because of their higher static
pressure capabilities, high performance fan
coils can be equipped with higher efficiency
filters and more rows of heating-cooling
coils. A well-designed unit should still be
capable of quietly and efficiently delivering
maximum flow when fully equipped with
coils and filter at 0.5 in. w.g. of external static
resistance. Another benefit of the higher
static pressure capability is that the unit
can accommodate longer discharge duct
runs with multiple air outlets. This allows
the fan coil to be mounted farther from the
occupied space reducing acoustic concerns.
As an example for a classroom application,
the fan coil unit can be located above
the hallway where noise levels are less
critical. Additionally, the longer length of
downstream ductwork can be acoustically
lined for further noise reduction. Due to their
higher air flow capacity and static pressure
capability, larger rooms or spaces can be
supplied with high performance fan coil
units.

Fan Coils and Blower Coils


Engineering Guide

Blower Coil Unit Types

ENGINEERING GUIDE - FAN COILS & BLOWER COILS

Blower Coils Overview


Blower coils are a type of air handling unit
that can be used to provide one or multiple
zones with conditioned air. They consist of
a finned-tube heat exchanger, fan, and filter
in a draw-through configuration as shown
in Figure 10. The heat exchanger usually
consists of a water coil for hot or chilled
water, but steam coils and direct expansion
coils may also be used. Regardless of the
type of coil, all the conditioned fluid must
be piped to the unit from another piece
of localized equipment such as a boiler or
chiller. Unlike fan coil units where the fan is
directly coupled to the motor, blower coils
typically use a belt drive system to transmit
power from the motor to the fan.This allows
the fan to run at whatever speed is required
simply by changing the pulley set in the unit.
A well-designed blower coil unit should be
compact, have low air and water pressure
drops across the coil to reduce fan and
pump power requirements, be an efficient
blower and belt drive system, and provide
good access to all of the units components
for regular maintenance. It should also have
a fully insulated casing to reduce heat loss
to/from the conditioned air and a tight filter
rack to eliminate filter bypass.
Blower coils are a compact solution to a
variety of ducted applications that require
flexibility between the traditional fan coil
unit and a central station air handling unit.
They are generally capable of handling at
least 1 in. w.g. of external static resistance
and can be equipped with more rows of
coils and higher efficiency filters than fan
coils. This allows them to be used as a
central station air handler for constant
volume systems or to be coupled with a
variable frequency drive and used for a
variable air volume (VAV) system. Their
small size also allows them to be used as a
constant volume fan coil to condition only
one room if required. Because of the large
flow and static pressure ranges, blower
coils are available with single and three
phase motors ranging from 1/3 hp up to
10 hp. They are typically located outside
the conditioned space in an area such as
a service room or basement, but they can
be installed in the area if conditions permit.
Blower coils come in vertical and horizontal
configurations as shown in Figures 11 and
12, depending on if they are to be installed
on the floor or hung from the ceiling.

F1-6

Figure 10: Draw -Through Unit


Cross Section View

Outdoor
Air

Supply Air

Return Air

Filter

Coils

Fan

Ceiling

Duct

Figure 11: Floor-Mounted Vertical Unit

Figure 12: Ceiling-Mounted Horizontal Unit

All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.

Copyright Price Industries Limited 2011.

Fan Coils and Blower Coils


Engineering Guide

Blower Coil Unit Types


Figure 13: Fan Coil/ Blower Coil Product Components (Exploded View)
Coils
Heavy Gauge
Insulated Casing

Filter Rack

Insulation

The design engineer needs to specify many


parameters such as supply air temperature
and volume, outside air requirements, fluid
temperatures and flow rates, external static
resistances and more, before an equipment
supplier can provide the proper blower coil
unit.
Manufacturers can certify their blower coil
units fan performance to the AHRI Standard
430-2009: Performance Rating of Central
Station Air-Handling Units. The purpose of
the standard is to provide classifications,
test requirements and minimum data
requirements for the published ratings of
central station air-handling units. Water
coils used in blower coil units should also
be AHRI certified to AHRI 410-2001: Forced
Circulation Air-Cooling and Air-Heating
Coils. By using equipment that is certified
to these standards, the design engineer can
be confident that units will function properly
under the conditions that are specified.
Typical Applications
Blower coils are an excellent choice for
applications where high cooling capacities
or external static pressures cannot be met
with standard or high performance direct
drive fan coil units. This makes them an ideal
candidate for schools, hotels, apartments
and office buildings. Also, with their ability
to operate with up to 100% outdoor air and a
variety of options such as mixing boxes, UV
lights and solid metal liner, blower coils are
also well-suited for hospital and laboratory
application.
Fan coil system and zone piping can be
configured in several ways to meet the
requirements and priorities of the system
designer. System efficiency, flexibility and
first cost are the primary drivers of the
system piping design. The entire system
(fan coils, piping, pumping, chillers and
boilers) needs to be considered to confirm
that appropriate compromises are made to
meet the system goals.

Copyright Price Industries Limited 2011.


Coil & Drain


Connections

Discharge Opening
Fan Assembly

Access Panel

Belt Drive

Access Panels

Direct Drive

Removable sheet metal section allows The motor shaft is directly secured to the
access to internal mechanical and electrical blower shaft. Each motor revolution is equal
components.
to one blower revolution.
Belt Drive

Discharge Collar

The motor turns the blower by a belt


connected to pulleys on each shaft end.
Each motor revolution will usually not be
equal to one blower revolution.

Rectangular fitting attached to the unit outlet


allowing for quick attachment of downstream
ductwork.

Blower/Fan

Tray in which a filter can be pulled out for


maintenance or replacement.

Multi-bladed, driven rotor enclosed so that


air from an inlet is compressed to a higher
discharge pressure.

Filter Rack

Liner

Structural sheet metal box or shell to which


all components are secured.

Internal blanket adhered to the casing that is


used to reduce the radiated and/or discharge
sound levels. Materials used vary based on
application and performance required.

Coil

Motor

A heat exchanger in which liquid is circulated


to provide heating or cooling to the air which
passes through the sink fins.

Electrical component of an air movement


device that provides work to turn the blade
assembly.

Casing

Control Enclosure
Sheet metal shroud in which houses the
electrical connections, speed controller, and
transformer. The enclosure cover prevents
accidental electrical shock as well as protects
the contents from the environment.

All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.

F1-7

ENGINEERING GUIDE - FAN COILS & BLOWER COILS

While blower coils may be rated for a


nominal flow, they are not restricted by
a limited number of incremental motor
speeds. They are capable of operating at
any flow and static pressure within their
operating range. This ability, coupled with
a large number of coil combinations and
accessories such as electric reheat, mixing
plenums and UV lights, means that blower
coils, like other air handlers, can be more
complicated to specify or order.

Fan Coils and Blower Coils


Engineering Guide

Fan Coil Piping

ENGINEERING GUIDE - FAN COILS & BLOWER COILS

Series and Parallel Piping


The piping system can be designed with two
basic piping concepts series or parallel
piping. In a series type system, a single pipe
loop is utilized to supply water in a loop. The
individual fan coils take water from this loop
and discharge back to the loop. As more fan
coils take from and return water to the series
loop, the temperature in the loop is changed.
It progressively increases in a chilled water
loop and progressively decreases in a hot
water loop. The fan coils at the end of the
loop see water temperatures that provide
less potential capacity than the fan coil at
the beginning of the loop. These fan coils at
the end of the loop will require larger coils
to provide similar capacity. The benefit of
this type of system is the elimination of the
return piping and the cost associated with
it, but must be weighed against the cost of
larger coils in the fan coils that are later in
the loop.

Figure 14: Piping Systems


Series System With Load Pumps

Paralled System

Fan Coil Unit

Fan Coil Unit

Fan Coil Unit

Fan Coil Unit

Fan Coil Unit

Fan Coil Unit

In a parallel system, there is a supply pipe


and a return pipe. Each fan coil unit receives
water at the same temperature giving each
the same capacity opportunity. Coils can
be selected with similar temperature
characteristics providing for more consistent
smaller coils.
Load Pumps
In a series piping system, load pumps is
a way to pull water from the water flow in
the series piping and supply it to the coil
in the fan coil unit. As capacity is required
to meet the load, the pump pulls water
from the loop to provide the heating or
cooling capacity required. This type of
design provides simple design and control
of the loop and the loads. The loop piping
experiences constant flow and pressure.
The load pump and piping at each fan coil
unit is designed to only meet the pressure
and flow requirements of the loop. Each
operates and is controlled independently of
the other. In some cases, control valves are
provided in the loop piping to confirm that
there is no flow in the loop system when the
loop system is shut down. See Figure 14.

F1-8

All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.

Copyright Price Industries Limited 2011.

Fan Coils and Blower Coils


Engineering Guide

Fan Coil Piping


Direct & Reverse Return
Figure 15: Direct Return

Fan Coil Unit

Fan Coil U

Fan Coil Unit

Fan Coil U

ENGINEERING GUIDE - FAN COILS & BLOWER COILS

An important consideration in designing


the system is ensuring that each fan coil
can receive the desired chilled water or hot
water flow rates during system operation.
Two types of systems can be utilized
direct return or reverse return. In a direct
return system, as shown below, the piping
is run in the shortest method possible and
balancing valves are used to manipulate the
pressure drop through each piping zone to
ensure each fan coil receives the required
water flow. This requires the system to
be balanced. These valves must be set
through an iterative process to verify the
flow through each coil. As each valve is
changed the rest of the system is affected
and they must be adjusted until the system
achieves steady state flow at each fan coil.
See Figure 15.

Figure 16: Reverse Return

In a reverse return system, the pipe length


through each piping zone is laid out to be
equal. This ensures that the pressure drop
Fan Coil Unit
through the piping system is equal for each
fan coil unit. This works well if the pressure
drop through each coil and piping loop is
very similar. This can be accomplished by
Fan
Coil Unit
using the same pressure drop
criteria
for the
coils, and the same pressure drop criteria
per foot of pipe. While more piping needs
to be installed, the balancing requirement
of the system is eliminated. See Figure 16.

Fan Coil Unit

Fan Coil Unit

2 Way and 3 Way Valves


The fan coil zone piping system can be
designed for constant volume or variable
volume water flow. A constant volume
system would require 3 way type control
valves to modulate the water flow through
the coil or around the coil to provide a
constant water flow through the zone
piping. A balancing valve is installed in the
bypass to maintain constant pressure drop
as the water flow is modulated around the
water coil. This type of constant flow system
with 3 way control valves is very simple
from a control and layout perspective, but
continues to run the pump at full power
during part-load conditions.
For a variable flow, 2 way control valves are
required. In this type of system the pressure
in the supply piping header is measured
and the pump output is varied to control
the constant pressure in the system. As 2
way valves are closed the system rides
the pump curve. At lower flow the pump
increases the pressure in the system. The
pressure control then slows the pump
down to provide a lower flow at constant
system pressure. As flow is lowered the
pump requires significantly less power. A
pump with a curve that has good predictive
performance throughout the anticipated

Copyright Price Industries Limited 2011.


Figure 17: Constant Flow

Figure 18: Variable Flow

Fan Coil Unit


Fan Coil Unit
Fan Coil Unit
Fan Coil Unit

water flow rate should be selected. Pumps


with very flat curves should be avoided
as small changes in pressure would lead
to large changes in flow, creating system
control issues.

All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.

F1-9

Fan Coils and Blower Coils


Engineering Guide

Fan Coil Piping

ENGINEERING GUIDE - FAN COILS & BLOWER COILS

Capacity Control
In each of the above system and control
designs, capacity control can be on-off or
modulation. On-off control would provide
no water flow when the control system is
satisfied. Often in a fan coil system the fan
would also be turned off during this satisfied
mode. When the control system calls for
capacity, the water flow would be provided
at full design flow and the fan would be
energized to full air flow.
These systems can also utilize modulating
control. Water flow would be varied to
provide the desired amount. In systems
designed to experience varying entering
conditions, the flow can be varied to maintain
a constant leaving air temperature based
on a constant air volume. The water flow
can also be varied to provide less capacity
by changing the leaving air temperature
based on a constant flow. Also, variable
water flow and air flow can be provided. The
air flow is decreased as the load decreases
and the water flow is regulated to maintain
a constant leaving air temperature. This is
an uncommon control strategy for a fan
coil system, but would provide enhanced
Fan CoilatUnit
dehumidification performance
low load
conditions.
Separate or CommonHeating
CoolingCoil
and
Heating Coils
Fan coil units are readily available with
either a single coil or withCooling
both a heating
Coil and
cooling coils. When heating and cooling is
required, they are most often provided with
both heating and cooling coils. In this type
of system, each coil is piped and controlled
independently. Generally there is some
type of dead band in the control system
to eliminate the possibility of heating and
cooling simultaneously.

Figure 19: Separate Coils 4 Pipe System

Fan Coil Unit


Fan Coil Unit

Heating Coil

Common Coil

Cooling Coil

Figure 20: Common Coil 4 Pipe System

Fan Coil Unit


Common Coil

In a single coil system, where it operates in


either heating or cooling, the system can
be a 2 pipe or 4 pipe system. In a 2 pipe
system, either hot water or chilled water is
supplied to the entire system depending on
the season. The fan coils are controlled to
maintain the required heating or cooling
leaving air condition. In a 4 pipe system,
each fan coil can be heating or cooling.
This allows some parts of the system to
provide cooling while other parts provide
heating. This is often required in buildings
with interior zones that require cooling all
year in all seasons. In this case 3 way valves
can be used to select either heating supply
and return or cooling supply and return.
This type of system provides the greatest
flexibility while lowering the first cost of the
fan coil units.

F1-10

All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.

Copyright Price Industries Limited 2011.

Fan Coils and Blower Coils


Engineering Guide

Fan Coil Controls


Figure 21: Manually Switched Fan Coil Thermostat

ENGINEERING GUIDE - FAN COILS & BLOWER COILS

Generally fan coils are applied to control


the space temperature of a room or zone.
A typical control system would consist of a
thermostat, multi speed fan, a heating coil
with control valve and/or a cooling coil with
control valve. Some systems may include
cooling only and some heating only. Several
levels of control sophistication are available
depending on the accuracy of temperature
control and energy efficiency required.
Basic Electric Control

Figure 22: Typical Wiring Diagram - Basic Electric

G1

G2

G3

Factory Electrical Wiring


Field Electrical Wiring

Fan Speed II (Med)

Fan Speed III (High)

SR1

SR2

Thermostat Terminals

Figure 23: Sequence of operation for manually selected fan speed and manual
heat-cool changeover
Dead Band

3 Speed Fan Flow


On

Heating ON

Cooling ON

High

High

Med

Off

Low

Cool

Copyright Price Industries Limited 2011.

Max. Air Flow

Med
Low

Min. Air Flow

0.9oF 0.9oF

W/Y
Control Output

SR Jumpers

Valve Signal

An enhancement to the above sequence is


automatic control of heating or cooling by
the thermostat. If a 2 pipe system is used a
water temperature sensor is adhered to the
supply water pipe to allow the thermostat to
detect if hot or cold water is available and
automatically switched between heating
or cooling mode. With a 4 pipe system
the thermostat will automatically activate
cooling mode when the room temperature
is above the thermostat set-point and
heating mode when the room temperature
is below set-point. A further enhancement
to the same sequence is automatic control
of the fan. The thermostat energizes the fan
at the selected speed when there is a call
for heating or cooling. The level of control
enhancement will be determined by the
thermostat model selected.

Automatic
Temperature
Control Valve

Fan Speed I (Low)

Figure 23 illustrates the control sequence


for a manually controlled heat-cool
changeover fan coil control system. During
cooling mode the cooling coil will be turned
on if the room temperature rises above setpoint. During heating mode the heating coil
will be turned on if the room temperature
drops below set-point. The operation of
the cooling or heating coil is full on or off.
Either a 2 pipe or 4 pipe water supply can
be accommodated.

Neutral
Low
Med
High
Line 1

Operating Voltage

Fan Coil
Terminal Block

The simplest and most basic control


system would be manual adjustment of
the fan flow and manual activation of the
heating or cooling coil. In this case the
thermostat has a temperature adjustment
dial, a manual switch for fan operation at
one of three speeds or off, and a manual
switch for selecting either cooling or heating
mode. Figure 21 illustrates a typical
manually switched thermostat. Generally
the thermostats are powered by line voltage
and directly connected to the fan and valve
actuator (Figure 22).

Tset-point
Room Condition

All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.

Warm

F1-11

Fan Coils and Blower Coils


Engineering Guide

Fan Coil Controls

Figure 25: Typical Wiring Diagram - Analog Electronic


+24V Hot 1

+24V Hot 1

-24V Com 2

-24V Com 2

+24V Open

-24V Com

+24V Closed

10

11 12 D1 GND
Fan Speed I (Low)

Potential-Free Operating
Mode Changeover Switch Input

Factory Electrical Wiring


Field Electrical Wiring

Fan Speed II (Medium)

Fan Speed III (High)

Measuring Neutral

Air Temperature Sensor


(Not Included)

Return Air Temp Input

Changeover Sensor Input

3 Position Valve, Open Signal

Changeover Sensor
Field Installed

3 Position Valve, Close Signal

Automatic
Temperature
Control Valve

Neutral

GREEN TIP
PI control and modulating water valves
minimize room temperature overshoot providing energy savings.

Oparating Voltage 24 VAC

GREEN TIP
During occupied hours the fan should
be operated to maintain ventilation air
to the space.

Figure 24: Analog Thermostat with LCD display

Neutral

Analog electronic control systems


offer several advantages over the basic
electric package, including more precise
proportional integral (PI) control of room
temperature, optional modulating control of
the cooling and heating coil, and an optional
LCD display for user-friendly monitoring
and selection of control parameters. Figure
24 illustrates a typical analog thermostat
with LCD display. Generally the thermostats
are powered by 24 VAC from a control
transformer (Figure 25). Figure 26 illustrates
the control sequence for an automatic
heat-cool changeover fan coil system with
modulating control of heating and cooling.

Thermostat Terminals

Figure 26: Sequence of operation for automatic heat-cool changeover and


modulating control of heating and cooling
3 Speed Fan Flow
Open
Valve Signal

ENGINEERING GUIDE - FAN COILS & BLOWER COILS

Analog Electronic Control

Heating ON

Cooling ON

High

High

Med

Closed

Med
Low

Low

3.6oF

Cool

F1-12

Max. Air Flow

Min. Air Flow

1.8oF

Tset-point
Room Condition

All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.

Warm

Copyright Price Industries Limited 2011.

Fan Coils and Blower Coils


Engineering Guide

Fan Coil Controls


Digital Programmable Control

GREEN TIP
Reducing the supply air temperature
during overhead heating will limit
stratification and improve indoor air
quality.
If the fan coil is supplied with an ECM the
digital thermostat can be programmed to
provide modulating control of the fan flow
during both heating and cooling modes of
operation.This enhanced function provides
superior comfort control, energy savings and
improved acoustics. Figure 29 illustrates the
control sequence for automatic heat-cool
changeover, modulating control of heating
and cooling with discharge air temperature
control of the cooling and heating flow and
variable fan speed.
GREEN TIP
ECMs consume considerably less
power at part load operation than
standard PSC motors, providing
further energy savings.

Dead Band
10 Volts

High

Copyright Price Industries Limited 2011.

High

Med

Max. Air Flow

Med

0 Volts

Low
2 oF

Low
1oF

1oF

Min. Air Flow


2 oF

Tset-point
Room Condition

Cool

Warm

Figure 29: Sequence of operation for automatic heat /cool changeover, modulating
control of heating and cooling with discharge air temperature control of the cooling
and heating flow and variable fan speed.
Dead Band
Cooling
ON

Heating
ON

10 Volts

Max. Air Flow ECM

0 Volts
2 oF

Cool

Cooling
ON

Heating
ON

1oF

1oF

Min. Air Flow ECM


2 oF

Tset-point
Room Condition

All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.

Warm

F1-13

ENGINEERING GUIDE - FAN COILS & BLOWER COILS

Figure 28: Sequence of operation for automatic heat /cool changeover and modulating
control of heating and cooling, with discharge air temperature control of the cooling flow.

Valve Signal

More custom or specialized control


sequences can also be accommodated.
One example is control of discharge air
temperature to a selectable set-point with
the addition of a discharge temperature
sensor. During cooling a minimum
discharge air temperature may be desired
to maintain control of humidity. During
heating a maximum air temperature may
be desired to prevent stratification in the
room if ceiling mounted outlets are utilized.
Figure 28 illustrates the control sequence
for automatic heat-cool changeover and
modulating control of heating and cooling,
with discharge air temperature control of
the cooling flow.

Figure 27: Field Programmable Thermostat

Valve Signal

Similar to the analog control system, the


digital thermostat includes proportional
integral (PI) control of room temperature,
modulating control of the cooling and
heating coil, and an optional LCD display.
However the addition of an on-board
microprocessor provides enhanced
functionality and flexibility. Digital
thermostats typically are shipped preprogrammed for the desired sequence of
operation but can be easily reconfigured
in the field if required. Figure 27
illustrates field configuration of the
programmable thermostat with a laptop
PC and interface module.

Fan Coils and Blower Coils


Engineering Guide

ENGINEERING GUIDE - FAN COILS & BLOWER COILS

Application of Fan Coil and Blower Coil Units


While blower coils and fan coils are
fundamentally very similar, deciding which
type of unit to use and in what configuration
is not always straightforward. Consultations
between the designer and owner may
be required to weigh the benefits of
performance, flexibility and maintainability
versus cost.
Capacity
Blower Coils are capable of higher air flows
and static pressures than Fan Coils. For this
reason, Fan coils are typically smaller and
are used to condition the room in which
they are located, whereas Blower Coils
are moderate-sized and can be ducted to
condition several rooms. This is not always
the case though as High Performance Fan
Coils have filled the gap between the two
products by offering capacities close to
those of blower coils while still retaining
the small size of a fan coil unit.

F1-14

Controls

Noise

Fan coils are typically controlled by either


a thermostat or fan speed switch in the
room that they are conditioning (ASHRAE,
2008a). This makes them well-suited for
applications where a high level of individual
control is desirable, such as hotel rooms, or
where there are infrequent loads, such as a
meeting room. Blower coils on the other
hand are typically operated as constant air
flow units. If required, they can be equipped
with variable frequency drives for VAV
control, however the cost will be higher.
High performance fan coils can be equipped
with ECMs programmed to deliver constant
air flow within a range of static pressures.

Both fan coils and blower coils generate


a significant amount of fan noise so their
application and location needs to be
carefully considered. Fan coils tend to
be quieter so they can be located in the
conditioned space as an exposed unit or
directly adjacent to the space in a ceiling
plenum or wall cavity. Exposed units should
be fully lined with fiberglass insulation to
reduce radiated noise.
Fan coils by design are intended to be
located in or directly adjacent to the
occupied space. They can be installed in
walls, ceiling plenums, closets, and many
other areas close to the room they serve.
Noise is a large concern as there is often
limited ability to provide sound attenuation
techniques in the building material between
the unit and the space or in the supply and
return ductwork. The location of the fan
coils needs to be reviewed to confirm that
the sound level in the adjacent space is
acceptable.

All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.

Copyright Price Industries Limited 2011.

Fan Coils and Blower Coils


Engineering Guide

Application of Fan Coil and Blower Coil Units

Copyright Price Industries Limited 2011.


Direct

Exposed

< 4,000

1.0 in.

Vertical

Direct

Exposed / Concealed

< 2,000

0.5 in.

Hi-rise

Direct

Concealed

< 2,000

0.5 in.

Ext Static is external static pressure, in. w.g.

Table 2: Blower Coil Configurations


Type

Fan

Cabinet

cfm

Ext Static

Horizontal

Belt

Exposed

< 8,000

1 in. to 3 in.

Vertical

Belt

Exposed

< 8,000

1 in. to 3 in.

Ext Static is external static pressure, in. w.g.

Table 3: Application Guidelines


Hospitals,
Clean Rooms,
Laboratories

Office Space,
Educational Facilities

Operating
Areas

Laboratory
Spaces

Unit Type

Low Pressure Fan Coils

High Performance Fan Coils

Blower Coils

Noise Sensitive
Applications

Low Pressure Fan Coils


High Performance Fan Coils
Blower Coils

Hotels, Multi
Residential

Unit Type

Other Facilities

Often Used for this application Not Recommended for this application
- Sometimes used for this application (restrictions may apply)

All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.

F1-15

ENGINEERING GUIDE - FAN COILS & BLOWER COILS

<0.5 in.

HorizontalHi press

Shopping
Centers

Fan coils should not be used to condition


outdoor air as they are not designed to
handle high levels of humidity. They do not
typically have deep enough coils to provide
the level of dehumidification required,
and condensate carryover can occur in
high humidity locations due to high face
velocities on coils caused by the typical
blow-through configuration. Blower coils
on the other hand have the static pressure
capabilities required to use deep coils and
can be equipped with mixing boxes to
combine re-circulated air with outdoor air.
One notable exception is that fan coils are
well-suited for heating only applications
where there are high infiltration rates of
outdoor air such as using an exposed
vertical fan coil to heat a vestibule or lobby
(ASHRAE, 2008a).

Ext Static

Patient
Areas

Outdoor Air

cfm
< 2,000

Public Use

Most fan coils and blower coils are equipped


with a filter, but the level of filtration varies
greatly. Low pressure fan coils are typically
only equipped with MERV 3 filters because
they are not capable of overcoming the large
pressure drop caused by higher efficiency
pleated filters. High performance fan coils
can be equipped with medium efficiency
filters up to MERV 13. If a high degree of
contaminant control is required, blower
coils can be equipped with high-efficiency
filters (up to MERV 15) and UV lights. Blower
coils can also be equipped with HEPA filters
if special care is taken to seal the unit casing
against infiltration of non-filtered air.

Cabinet
Exposed / Concealed

Small
Buildings

Contaminant Control

Fan
Direct

Theaters

Blower coils can be equipped with integral


silencers to significantly reduce their
discharge noise. They can then be located
away from the noise sensitive space and
ducted to the room.

Type
Horizontal

Large
Buildings

Larger fans running at slower speeds often


provide improved noise characteristics,
but will require greater first cost of the
unit. Sound data from the manufacturer
should be reviewed with options to reduce
the noise levels to achieve acceptable space
noise design.

Table 1: Fan Coil Configurations

Broadcast
Studios

Locating the fan coil unit in or over spaces


with higher sound criteria is often used to
minimize the occupant objections. Locating
them above a bathroom ceiling would be
an example of this technique. Selecting the
units at lower than the maximum air flow
the unit can produce is a method of lowering
the noise produced by the fan coil unit.

Fan Coils and Blower Coils


Engineering Guide

References
AHRI (2001a). AHRI standard 260-2001: Sound ratings of ducted air moving and conditioning equipment.
Arlington, VA: Air-Conditioning, Heating, and Refrigeration Institute.
AHRI (2001b). AHRI standard 410-2001: Forced circulation air-cooling and air- heating coils. Arlington, VA:
Air-Conditioning, Heating, and Refrigeration Institute.

ENGINEERING GUIDE - FAN COILS & BLOWER COILS

AHRI (2008a). AHRI standard 440-2008: Performance rating of room fan-coils. Arlington, VA: Air-Conditioning,
Heating, and Refrigeration Institute.
AHRI (2008b). AHRI standard 885-2008: Procedure for estimating occupied space sound levels in the
application of air terminals and air outlets. Arlington, VA: Air-Conditioning, Heating, and Refrigeration
Institute.
AHRI (2009). AHRI standard 430-2009: Performance rating of central station air- handling units. Arlington, VA:
Air-Conditioning, Heating, and Refrigeration Institute.
ASHRAE (2001). Standard 62-2001Ventilation for acceptable indoor air quality. Atlanta, GA: American
Society of Heating, Refrigeration and Air-Conditioning Engineers.
ASHRAE (2007a). ASHRAE handbookHVAC applications. Atlanta, GA: American Society of Heating,
Refrigeration and Air-Conditioning Engineers.
ASHRAE (2007b). Standard 52.2-2007Method of testing general ventilation air-cleaning devices for removal
efficiency by particle size. Atlanta, GA: American Society of Heating, Refrigeration and Air-Conditioning
Engineers.
ASHRAE (2008a). ASHRAE handbookHVAC systems and equipment (SI edition). Atlanta, GA: American
Society of Heating, Refrigeration and Air-Conditioning Engineers.
ASHRAE (2008b). Standard 130-2008Methods of testing air terminal units. Atlanta, GA: American Society
of Heating, Refrigeration and Air-Conditioning Engineers.
ASHRAE (2009). ASHRAE handbookFundamentals. Atlanta, GA: American Society for Heating, Refrigerating
and Air Conditioning Engineers, Inc.
Price Industries (2011). Price engineer's HVAC handbookA comprehensive guide to HVAC fundamentals.
Winnipeg, MB: Price Industries Limited.

F1-16

All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.

Copyright Price Industries Limited 2011.

You might also like