FCU Engineering Guide
FCU Engineering Guide
FCU Engineering Guide
Engineering Guide
Fan & Blower Coils
Please refer to the Price Engineers HVAC Handbook
for more information on Fan Coils & Blower Coils.
Engineering Guide
Product Fundamentals
Fan coils are a type of air handling unit
designed to supply conditioned air to a
room or zone. The basic components that
make up a fan coil unit are a finned-tube
heat exchanger, fan section and filter. The
fan produces forced convection across the
heat exchanger, which circulates either hot
or cold water to provide conditioned air to
the space. Individual zone thermostats are
coupled to the fan coils fan speed controller
and hydronic controls to maintain room
temperature. A well-designed fan coil
unit will have low air and water pressure
drops across the coil to reduce fan and
pump power requirements as well as an
efficient fan and motor assembly for quiet
operation. Also, any fan coil unit equipped
with a cooling coil should have a drain pan
installed to capture condensate, regardless
of whether or not the entering air is preconditioned. Fan coils are located in or
near the space to be conditioned for free
delivery of air into the zone or with minimal
duct work. Units generally operate with a
blow-through arrangement where the coil is
downstream of the fan. Most fan coil units
are supplied with a direct drive fan/motor
assembly.
Most manufacturers certify their fan coil
units cooling performance to the AirConditioning, Heating, and Refrigeration
Institute standard AHRI Standard 4402008: Performance Ratings for Room Fan
Coils. The purpose of the standard is to
provide classifications, test requirements,
and minimum data requirements for the
published ratings of fan coil units delivering
up to 1500 cfm.
Fan coils can be used in decentralized HVAC
systems or in conjunction with a central
air handling unit. The major advantages
of using fan coil units are that they allow
for local control of individual zones and
reduce the overall footprint of the system
by replacing ductwork with water piping
in a large portion of the system. They also
reduce the amount of cross-contamination
between zones and allow for unused areas
to be shut down. To receive ventilation air,
fan coils can either be ducted to a central
air handler or to a mixing plenum. When
attached to a mixing plenum, care must
be taken as fan coils do not typically have
provisions for controlling the amount of
outdoor air admitted, and the coil must be
protected from freezing in cold climates.
F1-2
Fan Assembly
Filter Rack
Discharge Panel
Discharge
Opening
Coils
Drain Pan
Supply Air
Fan Coil
Unit
Zone 2
T
CLASSROOM
AHU
CLASSROOM
Relief Air
Return Air
Fan Coil
Unit
Outdoor
Air
Zone 1
Zone 2
CLASSROOM
CLASSROOM
AHU
Relief Air
F1-3
Outdoor
Air
Zone 1
Fan Coil
Unit
Fan Coil
Unit
Coils
Fan
Filter
Return Air Opening
Duct
Coils
Ceiling
Fan
Filter
Concealed Units
Concealed units can be furred into a wall or
installed in a ceiling plenum and then are
typically ducted to a single discharge grille
or diffuser as shown in Figure 6.
Exposed Units
Exposed units are generally installed in
a visible location and therefore have an
attractive painted finish and return and
supply air grilles as shown Figure 7. Units
use fully insulated casings to reduce the
amount of noise delivered to the occupied
space, and the footprint is designed to be
small to minimize the amount of occupied
space they require.
Typical Applications
Low pressure fan coils are ideally suited
for applications where individual zone
temperature control is required. This
makes them an ideal candidate for hotels,
apartment buildings and office buildings
(ASHRAE, 2008a). In many cases vertical
units are installed so that the supply air
washes the window and helps lower the
thermal impact of the glass. Fan coils can be
used in health care facilities, but care should
be taken because of their low-efficiency
filters and because they are designed mostly
for re-circulated air which is not permitted
in certain types of spaces.
F1-4
Duct
High Performance
Fan Coil Unit
Supply
Return
Corridor
CLASSROOM
Typical Applications
High performance fan coils are an excellent
choice for applications where a high level of
individual zone temperature control and low
noise is required. This makes them an ideal
candidate for schools, hotels, apartments
and office buildings. Higher air volume and
static pressure capability also make them
ideal for larger spaces and applications
requiring longer duct runs and multiple air
outlets such as labs, meeting rooms, halls,
lecture theaters, etc.
F1-5
F1-6
Outdoor
Air
Supply Air
Return Air
Filter
Coils
Fan
Ceiling
Duct
Filter Rack
Insulation
Discharge Opening
Fan Assembly
Access Panel
Belt Drive
Access Panels
Direct Drive
Removable sheet metal section allows The motor shaft is directly secured to the
access to internal mechanical and electrical blower shaft. Each motor revolution is equal
components.
to one blower revolution.
Belt Drive
Discharge Collar
Blower/Fan
Filter Rack
Liner
Coil
Motor
Casing
Control Enclosure
Sheet metal shroud in which houses the
electrical connections, speed controller, and
transformer. The enclosure cover prevents
accidental electrical shock as well as protects
the contents from the environment.
F1-7
Paralled System
F1-8
Fan Coil U
Fan Coil U
F1-9
Capacity Control
In each of the above system and control
designs, capacity control can be on-off or
modulation. On-off control would provide
no water flow when the control system is
satisfied. Often in a fan coil system the fan
would also be turned off during this satisfied
mode. When the control system calls for
capacity, the water flow would be provided
at full design flow and the fan would be
energized to full air flow.
These systems can also utilize modulating
control. Water flow would be varied to
provide the desired amount. In systems
designed to experience varying entering
conditions, the flow can be varied to maintain
a constant leaving air temperature based
on a constant air volume. The water flow
can also be varied to provide less capacity
by changing the leaving air temperature
based on a constant flow. Also, variable
water flow and air flow can be provided. The
air flow is decreased as the load decreases
and the water flow is regulated to maintain
a constant leaving air temperature. This is
an uncommon control strategy for a fan
coil system, but would provide enhanced
Fan CoilatUnit
dehumidification performance
low load
conditions.
Separate or CommonHeating
CoolingCoil
and
Heating Coils
Fan coil units are readily available with
either a single coil or withCooling
both a heating
Coil and
cooling coils. When heating and cooling is
required, they are most often provided with
both heating and cooling coils. In this type
of system, each coil is piped and controlled
independently. Generally there is some
type of dead band in the control system
to eliminate the possibility of heating and
cooling simultaneously.
Heating Coil
Common Coil
Cooling Coil
F1-10
G1
G2
G3
SR1
SR2
Thermostat Terminals
Figure 23: Sequence of operation for manually selected fan speed and manual
heat-cool changeover
Dead Band
Heating ON
Cooling ON
High
High
Med
Off
Low
Cool
Med
Low
0.9oF 0.9oF
W/Y
Control Output
SR Jumpers
Valve Signal
Automatic
Temperature
Control Valve
Neutral
Low
Med
High
Line 1
Operating Voltage
Fan Coil
Terminal Block
Tset-point
Room Condition
Warm
F1-11
+24V Hot 1
-24V Com 2
-24V Com 2
+24V Open
-24V Com
+24V Closed
10
11 12 D1 GND
Fan Speed I (Low)
Potential-Free Operating
Mode Changeover Switch Input
Measuring Neutral
Changeover Sensor
Field Installed
Automatic
Temperature
Control Valve
Neutral
GREEN TIP
PI control and modulating water valves
minimize room temperature overshoot providing energy savings.
GREEN TIP
During occupied hours the fan should
be operated to maintain ventilation air
to the space.
Neutral
Thermostat Terminals
Heating ON
Cooling ON
High
High
Med
Closed
Med
Low
Low
3.6oF
Cool
F1-12
1.8oF
Tset-point
Room Condition
Warm
GREEN TIP
Reducing the supply air temperature
during overhead heating will limit
stratification and improve indoor air
quality.
If the fan coil is supplied with an ECM the
digital thermostat can be programmed to
provide modulating control of the fan flow
during both heating and cooling modes of
operation.This enhanced function provides
superior comfort control, energy savings and
improved acoustics. Figure 29 illustrates the
control sequence for automatic heat-cool
changeover, modulating control of heating
and cooling with discharge air temperature
control of the cooling and heating flow and
variable fan speed.
GREEN TIP
ECMs consume considerably less
power at part load operation than
standard PSC motors, providing
further energy savings.
Dead Band
10 Volts
High
High
Med
Med
0 Volts
Low
2 oF
Low
1oF
1oF
Tset-point
Room Condition
Cool
Warm
Figure 29: Sequence of operation for automatic heat /cool changeover, modulating
control of heating and cooling with discharge air temperature control of the cooling
and heating flow and variable fan speed.
Dead Band
Cooling
ON
Heating
ON
10 Volts
0 Volts
2 oF
Cool
Cooling
ON
Heating
ON
1oF
1oF
Tset-point
Room Condition
Warm
F1-13
Figure 28: Sequence of operation for automatic heat /cool changeover and modulating
control of heating and cooling, with discharge air temperature control of the cooling flow.
Valve Signal
Valve Signal
F1-14
Controls
Noise
Direct
Exposed
< 4,000
1.0 in.
Vertical
Direct
Exposed / Concealed
< 2,000
0.5 in.
Hi-rise
Direct
Concealed
< 2,000
0.5 in.
Fan
Cabinet
cfm
Ext Static
Horizontal
Belt
Exposed
< 8,000
1 in. to 3 in.
Vertical
Belt
Exposed
< 8,000
1 in. to 3 in.
Office Space,
Educational Facilities
Operating
Areas
Laboratory
Spaces
Unit Type
Blower Coils
Noise Sensitive
Applications
Hotels, Multi
Residential
Unit Type
Other Facilities
Often Used for this application Not Recommended for this application
- Sometimes used for this application (restrictions may apply)
F1-15
<0.5 in.
HorizontalHi press
Shopping
Centers
Ext Static
Patient
Areas
Outdoor Air
cfm
< 2,000
Public Use
Cabinet
Exposed / Concealed
Small
Buildings
Contaminant Control
Fan
Direct
Theaters
Type
Horizontal
Large
Buildings
Broadcast
Studios
References
AHRI (2001a). AHRI standard 260-2001: Sound ratings of ducted air moving and conditioning equipment.
Arlington, VA: Air-Conditioning, Heating, and Refrigeration Institute.
AHRI (2001b). AHRI standard 410-2001: Forced circulation air-cooling and air- heating coils. Arlington, VA:
Air-Conditioning, Heating, and Refrigeration Institute.
AHRI (2008a). AHRI standard 440-2008: Performance rating of room fan-coils. Arlington, VA: Air-Conditioning,
Heating, and Refrigeration Institute.
AHRI (2008b). AHRI standard 885-2008: Procedure for estimating occupied space sound levels in the
application of air terminals and air outlets. Arlington, VA: Air-Conditioning, Heating, and Refrigeration
Institute.
AHRI (2009). AHRI standard 430-2009: Performance rating of central station air- handling units. Arlington, VA:
Air-Conditioning, Heating, and Refrigeration Institute.
ASHRAE (2001). Standard 62-2001Ventilation for acceptable indoor air quality. Atlanta, GA: American
Society of Heating, Refrigeration and Air-Conditioning Engineers.
ASHRAE (2007a). ASHRAE handbookHVAC applications. Atlanta, GA: American Society of Heating,
Refrigeration and Air-Conditioning Engineers.
ASHRAE (2007b). Standard 52.2-2007Method of testing general ventilation air-cleaning devices for removal
efficiency by particle size. Atlanta, GA: American Society of Heating, Refrigeration and Air-Conditioning
Engineers.
ASHRAE (2008a). ASHRAE handbookHVAC systems and equipment (SI edition). Atlanta, GA: American
Society of Heating, Refrigeration and Air-Conditioning Engineers.
ASHRAE (2008b). Standard 130-2008Methods of testing air terminal units. Atlanta, GA: American Society
of Heating, Refrigeration and Air-Conditioning Engineers.
ASHRAE (2009). ASHRAE handbookFundamentals. Atlanta, GA: American Society for Heating, Refrigerating
and Air Conditioning Engineers, Inc.
Price Industries (2011). Price engineer's HVAC handbookA comprehensive guide to HVAC fundamentals.
Winnipeg, MB: Price Industries Limited.
F1-16