GN 300 001
GN 300 001
GN 300 001
M P T TP CHWR
M
BUTTERFLY VALVE
CHWR
NC VODRV P T TP AHU WORK IN PROGRESS ISSUE
RECOMMENDED FIELD
CHWR NC FAN COIL UNIT PRESSURE GAUGE
PIPING ARRANGEMENT
15000 MIN
(17500 FOR COMPRESSOR)
CHWS
NC
SUBJECT TO CHANGE AND
CHWS
NC P T TP AHU
CHWS
NC
TO DRAIN VIBRATION ISOLATOR
VIBRATION ISOLATOR
SYSTEM OUTLET
BY-PASS VALVE FOR CONTRACTOR) Y-STRAINER INSULATED AUXILIARY IN-LINE
Y-STRAINER
CLEANING AND FLUSHING PRESSURE DRAIN PAN STRAINER CONCRETE PLINTH A.H.U MODULATING CONTROL VALVE
INDEPENDENT
BUTTERFLY VALVE FAN COIL UNIT TWO PORT MOTORIZED VALVE
CONTROL VALVE SPRING ISOLATOR WITH 2 LAYERS OF 700 NEOPRENE NOTE: TO RETAIN CALIBRATED ACCURACY OF THE CLOSE-COUPLED COMMISSIONING SET, A
DRAIN CONNECTION
Y-STRAINER A.H.U MODULATING CONTROL VALVE FRICTION PADS SEPARATED WITH 300 STEEL SHIM. MINIMUM LENGTH OF UNRESTRICTED STRAIGHT PIPE ADJACENT TO THE CLOSE-COUPLED
COMMISIONING SET SHOULD BE MAINTAINED AS FOLLOWS
INERTIA BASE HEADER
NOTE: TO RETAIN CALIBRATED ACCURACY OF THE CLOSE-COUPLED COMMISSIONING SET,
NOTE: WITH SPRING ISOLATORS SUPPORT
A MINIMUM LENGTH OF UNRESTRICTED STRAIGHT PIPE ADJACENT TO THE
COLUMN
CLOSE-COUPLED COMMISSIONING SET SHOULD BE MAINTAINED AS FOLLOWS SIZE UPSTREAM "A" DOWNSTREAM "B"
1) WHERE VALVES LOCATED CLOSE TO THE FCU, EXTEND THE AUXILIARY DRAIN (D) (IN PIPE DIAMETER) (IN PIPE DIAMETERS)
PAN TO CATCH LEAKS (IF ANY) FROM VALVES & JOINTS. TRIPLE VALVE NOTE:
SIZE UPSTREAM DOWNSTREAM "B" (FUNCTIONS :) 0-05000∅ 10 3
2) FOR TWO OR MORE FCU's IN CLOSE VICINITY, INSTALL STRAINER IN COMMON CHWF CONCRETE MASS TO BE 1.5 TIMES MASS OF EQUIPMENT MOUNTED
(D) (IN"A"
PIPE DIAMETER) (IN PIPE DIAMETERS) - NON-SLAM CHECK VALVE.
LINE. PROVIDE ISOLATING VALVE BEFORE AND AFTER FOR MAINTENANCE. ON THE BASE
- FLOW THROTTLING VALVE.
0-05000∅ 10 3 - SHUT-OFF VALVE.
3) FOR SERVING ELEC AND SUBSTATION ROOMS SHOULD HAVE MASTER SHUT OFF VALVE LOCATED
OUTSIDE THE ROOM, LINKED TO LEAK DETECTOR
TYP. AIR HANDLING, PAHU AND HEAT RECOVERY FOR INSTALL IN THREE LARGE AIR HANDLING OR PAHU W/
TYPICAL FAN COIL UNIT DETAIL PUMP DETAIL INERTIA BASE DETAIL (TYPICAL) COOLING COIL UNIT FURTHEST FROM PLANTROOM.
1 C/W COOLING COIL UNIT CONNECTION DETAIL 2
NTS
3
NTS
0
NTS
5 NTS
NTS
D
WITH CLOSED-CELL NEOPRENE FOAM OR LIGHT-DENSITY METAL SCREW 10000 WIDE "C" 20 MM TYPE "D" 25 INSULATION WITH C T
CENTERS; TYPE 'C' 38x38x5 ANGLE, MAX. SPACING 2000 CENTERS; TYPE "D" 50x50x6 GALV. STL. G DU MAX. OFFSET=2500
GLASS FIBER (32kg/cu0) SEAL AIRTIGHT AT PENETRATION METAL COVER STRAP (TYP.) G.I. NO.16 MM VAPOR BARRIER
AC
IN A IR
PERIMETER WITH NON-HARDENING ACOUSTICAL CAULK MAX. SPACING 1200 CENTERS. . SP
INSULATION X
SHEET INSULATION WITH GALV. STOL. DOUBLE MA
3. MAX. SPACING FOR TYPE "A" HANGER = 2000. SHIELD
PACKED ROCKWOOL METAL VAPOR BARRIER NUTS & WASHERS RECTANGULAR DUCT
DUCT ANGLE HARD CONNECTION WHERE
ACOUSTICALLY LINED SHEET METAL DUCT 50 x 50 PREFORMED FLEX. CONN.
ANCHOR TO BRACING ALIGNMENT AND SPACE
GAUGE G.I. CORNER ROUND DUCT
CONCRETE SLAB (SEE NOTE) DICTATE ONLY
BEAD SHEET METAL DUCT R=DEPTH OF
STEEL ROD
DUCT / PIPE DUCT HANGER DUCT
HANGER TYPE - A HANGER TYPE B, C, & D HANGER R
CHANNEL FLEX. CONN.
RAMSET STUD ISOMETRIC VIEW OF TYPICAL
STEEL ROD HANGER FULLY WELDED PORTION DUCT SCHEDULE DUCT HANGER RECTANGULAR DUCT
ANCHORED TO OF DUCT
16 GAUGE SHEET
CONCRETE SLAB DUCT WIDTH TYPE OF
ANGLE IRON DUCT SIZE 00] ROD & ANGLE MM HANGER
FIBERGLASS INSULATION SHEET METAL DUCT FLEX. CONN. REFER TO SPECS FOR
SUPPORT SIZES & CENTRES (METERS) WHEN HEIGHT DOES NOT ALLOW FLEX. CONN. INSULATED TYPE
INSULATION (IF ANY) UP TO 050 'A'
DETAIL A HARD-DUCT BUT BE SURE BRANCH IS 10000
0 - 060 0 - 760 10 DIA., 25 x 25 x 3 @ 2.0 'B' SUPPLY DIFFUSER
075 --- 1500 WIDER THAN COLLAR TO ALLOW ALIGNMENT
38(MIN.) 38(MIN.) 080 - 760 530 - 1220 10 DIAZ., 00 x 00 x 3 @ 1.8 REGISTER (TYP.)
1525 --- 2000 'C' OF TERMINAL WITHIN GRID WITHOUT FISHMOUTHING
790 - 1520 1250 & ABOVE 10 DIAZ., 50 x 50 x 6 @ 1.8
ANGLE IRON 1.50
OVER 2000 'D' MAX. OFFSET=2500 D
SUPPORT
FIRE-RATED DUCT DETAIL DETAILS OF DIFFUSER AND REGISTER INSULATED PIPING & SUPPORT DETAILS TYPICAL PIPE HANGER TYPICAL EXPOSED PIPING INSULATION DETAIL
10 11 12 13 10
NTS NTS NTS NTS NTS
STRUCTURAL ENGINEER
WALL VIBRATION ISOLATORS
50 MM THICKNESS 50 MM
HANGER ROD MOUNT
0 TO STRUCTURE
5
DUCT HANGER MOUNT
TO STRUCTURE
Meinhardt (Singapore) Pte Ltd
1 - PIPE TO BE COVERED
GA 20 PLAIN G.I CAULK OR NON-SHRINK 168 Jalan Bukit Merah, #09-01, Surbana One
INSULATION PIPE O.D. INCLUDING
SHEET PIPE CLAD GROUT 2 - 2500 INSULATION MATERIAL IS WRAPPED & TAPED OR IT
UN FLEXIBLE CONNECTION SINGAPORE 150168
WIRED IN PLACE (WIRE POINTS MUST NOT PROJECT) IL
0 CO
FAN SUPPLY AIR DUCT W/ TEL: +65 6273 5255 FAX: +65 6274 0788
OPENING
3 - MASS LOADED VINYL (E.G. KINETICS KNM NOISE BARRIER 25 (1") THK. INSULATION
3
MATERIAL WITH 5.0kg/M1 DENSITY) IS WRAPPED OVER
INSULATION LEAVE 2500 OVERLAP ALONG LONGITUDINAL &
TRANSVERSE SEAMS, TO KEEP MOISTURE OUT OF INSULATION,
25 MM THK. ANGULAR LONGITUDINAL SEAM SHOULD BE ON UNDERSIDE OF PIPE.
PROJECT
RUBBER SEAL
ROLLED B.I. PLATE G.I 16 WELDED
JOINT PIPE SLEEVE ALL
PROPOSED MIXED-USE DEVELOPMENT COMPRISING
0
1 15 UND
O TO SUPPLY OF A 63-STOREY TOWER BLOCK WITH A 2-STOREY
AR
2 0 - TAPE ALL VINYL SEAMS WITH 5000 WIDE PRESSURE
SENSITIVE CLOTH TAPE.
AIR GRILLE
PODIUM FOR SHOP & RESTAURANT USE, 1ST STOREY
FOR OFFICE/HOTEL/RESIDENTIAL LOBBIES WITH
5 - IF OUTER JACKET IS USED, STAGGER JACKET SEAMS TO
NOTE VINYL SEAMS (OPTIONAL) PLAZA SPACE AND OFFICE, HOTEL (100 ROOMS) AND
CEILING
TYPICAL DETAIL FOR UNINSULATED PIPE EXCEPT WITHOUT CLAD.
ACCESS PANEL SIZES ANGLE BARS RESIDENTIAL FLATS (268 UNITS) WITH SKY TERRACES,
SHALL BE FCU SIZE
PLUS 150 ALL AROUND
COMMUNAL/ANCILLARY FACILITIES AND 4 BASEMENT
CONSISTING AN UNDERGROUND PEDESTRIAN LINK
(UPL) AND BASEMENT CARPARK ON LOTS 00144C(PT)
& 00147V TS 30 AT 8 SHENTON WAY (DOWNTOWN
CORE PLANNING AREA)
PIPE INSULATION THRU CONCRETE WALL DETAIL PIPE LAGGING - GENERAL
15 16 17 FAN COIL UNIT MOUNTING DETAIL DRAWING DESCRIPTION
NTS NTS NTS
ACMV SERVICES
STANDARD DETAILS
(SHEET 1 OF 2)
SCALE N.T.S
BY DATE
DRAWN NSN OCT 2021
208048.02 AC GN-300-001 -