72 - 36 - 318-1-2024 E11 Lecture 7 FEP 2023

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 69

Instructor: Freddy Pina

Live Load Due to Earthquakes

Part 2: Application of Code Provisions


The Equivalent Static Procedure
Instructor: Freddy Pina, Ph.D., P.Eng.
Coordinator: John Pao, P.Eng., Struct. Eng.

E11 National Building Code Part 4 Structural Design


Instructor: Freddy Pina

Useful documentation/access:
National Building Code of Canada 2015 & 2020

https://nrc.canada.ca/en/certifications-evaluations-standards/codes-canada/codes-
canada-publications/national-building-code-canada-2015

https://nrc-publications.canada.ca/eng/view/ft/?id=515340b5-f4e0-4798-be69-
692e4ec423e8

Covered Here can be found in:


Volume 1, Division B, Part 4, Section 4.1.8 and Appendix C

Seismic Hazard Data - National Building Code of Canada 2015 & 2020
https://earthquakescanada.nrcan.gc.ca/hazard-alea/interpolat/calc-en.php

https://www.seismescanada.rncan.gc.ca/hazard-alea/interpolat/nbc2020-cnb2020-
en.php

E11 National Building Code Part 4 Structural Design No. 2


Instructor: Freddy Pina

The Modal Response Analysis


Procedure is the default method…but

Base Shear must be scaled


to the Minimum Earthquake
Force of the Static Method

E11 National Building Code Part 4 Structural Design No. 3


Instructor: Freddy Pina
Applying Code Provisions

E11 National Building Code Part 4 Structural Design No. 4


Instructor: Freddy Pina
Applying Code Provisions

Restrictions on use of the Equivalent Static Force


Procedure

Low
Seismicity

E11 National Building Code Part 4 Structural Design No. 5


Instructor: Freddy Pina
Applying Code Provisions

Restrictions on use of the Equivalent Static Force


Procedure
• Regular structures with:
• Height < 60m
• Ta < 2s
• Short buildings (Height < 20m & Ta< 0.5s) that:
• Does not have Vertical Stiffness Irregularity
• Does not have Torsional Irregularity
• Does not have Gravity-induced Irregularity
• Does not have Sloped Column Irregularity
E11 National Building Code Part 4 Structural Design No. 6
Instructor: Freddy Pina
Applying Code Provisions

Minimum Earthquake Lateral Force, V

E11 National Building Code Part 4 Structural Design No. 7


Instructor: Freddy Pina
Applying Code Provisions

Minimum Earthquake Lateral Force, V

Where:
S = design spectral response acceleration
Ta = fundamental period of vibration of the building
Mv = factor to account for higher mode effects
IE = earthquake importance factor
W = Weight of the building
Rd = ductility-related force modification factor
Ro = Overstrength-related force modification factor

E11 National Building Code Part 4 Structural Design No. 8


Instructor: Freddy Pina
Applying Code Provisions

Design Spectral Acceleration, S

Where:
X is the Site Designation
Sa = 5% damped spectral response acceleration (ratio of gravity) varies with
region and building period

E11 National Building Code Part 4 Structural Design No. 9


Instructor: Freddy Pina
Applying Code Provisions

Site Designation, X

E11 National Building Code Part 4 Structural Design No. 10


Instructor: Freddy Pina
Applying Code Provisions

Site Designation, X

XV → Vs30 XS → Site Class

SPR
(blows/
0.3m)
Vs 30 m or 30 m
USR
(kPa)

E11 National Building Code Part 4 Structural Design No. 11


Instructor: Freddy Pina
Applying Code Provisions

Site Designation, XS

E11 National Building Code Part 4 Structural Design No. 12


Instructor: Freddy Pina
Applying Code Provisions

Site Coefficient, F

E11 National Building Code Part 4 Structural Design No. 13


Instructor: Freddy Pina
Applying Code Provisions

5% Damped Spectral Acceleration, Sa(T, XS)

E11 National Building Code Part 4 Structural Design No. 14


Instructor: Freddy Pina
Applying Code Provisions

5% Damped Spectral Acceleration, Sa(T, XV)

E11 National Building Code Part 4 Structural Design No. 15


Instructor: Freddy Pina
Applying Code Provisions

5% Damped Spectral Acceleration, Sa

Victoria RBCM - NBCC 2020 Sa vs T for Varied Site Class


2.2
2 Site Class A
Site Class B
1.8
Spectral Acceleration (g)

Site Class C
1.6 Site Class D
1.4 Site Class E
1.2
1
0.8
0.6
0.4
0.2
0
0 2 4 6 8 10
Period (s)

E11 National Building Code Part 4 Structural Design No. 16


Instructor: Freddy Pina
Applying Code Provisions

5% Damped Spectral Acceleration, Sa


Vancouver CH - NBCC 2020 Sa vs T for Varied Site Class
2
1.8 Site Class A
Site Class B
1.6
Spectral Acceleration (g)

Site Class C
1.4
Site Class D
1.2
Site Class E
1
Victoria Site Class C
0.8
0.6
0.4
0.2
0
0 2 4 6 8 10
Period (s)

E11 National Building Code Part 4 Structural Design No. 17


Instructor: Freddy Pina
Applying Code Provisions

5% Damped Spectral Acceleration – Diff. Cities

2
1.8 Sa - NBCC 2020 for X560 (Site Class C)
1.6
Spectral Acceleration, Sa (g)

Victoria
1.4
Vancouver
1.2 Montreal
1 Toronto
0.8 Winnipeg

0.6
0.4
0.2
0
0 2 4 6 8 10
Period, T (s)

E11 National Building Code Part 4 Structural Design No. 18


Instructor: Freddy Pina
Applying Code Provisions

5% Damped Spectral Acceleration - NBC 2015 VS NBC 2020

Victoria RM - NBCC 2015 vs 2020


2.2
2.0 NBC 2015 - A
1.8 NBC 2015 - B
NBC 2015 - C
Spectral Acceleration (g)

1.6
NBC 2015 - D
1.4 NBC 2015 - E
1.2 NBC 2020 - "A"
1.0 NBC 2020 - "B"
NBC 2020 - "C"
0.8
NBC 2020 - "D"
0.6 NBC 2020 - "E"
0.4
0.2
0.0
0 2 4 6 8 10
Period (s)

E11 National Building Code Part 4 Structural Design No. 19


Instructor: Freddy Pina
Applying Code Provisions

Fundamental Lateral Period, Ta

Two methods are available to


determine the Period of structure:

1. Empirical Formulae

2. Rational Analysis

E11 National Building Code Part 4 Structural Design No. 20


Instructor: Freddy Pina
Applying Code Provisions

Fundamental Lateral Period, Ta

E11 National Building Code Part 4 Structural Design No. 21


Instructor: Freddy Pina
Applying Code Provisions

Higher Mode Effect Factor, Mv

E11 National Building Code Part 4 Structural Design No. 22


Instructor: Freddy Pina
Applying Code Provisions

Higher Mode Effect Factor, Mv

S(0.2)/S(5.0)

Vancouver ≈ 10
Calgary ≈ 20
Winnipeg ≈ 42
Toronto ≈ 35
Halifax ≈ 14

E11 National Building Code Part 4 Structural Design No. 23


Instructor: Freddy Pina
Applying Code Provisions

Importance Factor, IE

E11 National Building Code Part 4 Structural Design No. 24


Instructor: Freddy Pina
Applying Code Provisions

Importance Factor, IE

E11 National Building Code Part 4 Structural Design No. 25


Instructor: Freddy Pina
Applying Code Provisions

Seismic Weight, W

E11 National Building Code Part 4 Structural Design No. 26


Instructor: Freddy Pina
Applying Code Provisions

Reduction Factors, Rd Ro

E11 National Building Code Part 4 Structural Design No. 27


Instructor: Freddy Pina
Applying Code Provisions

Example 1. Base Shear Calculations

• 4-storey timber on 2-storey


concrete
• 424 Homer St, Vancouver
• Vs30 = 250 m/s (Site D)
• Residential
• 25’ high – Concrete structure
• 36’ high – Timber structure
• 118’ E-W x 54’ N-S
• SFRS: Concrete Walls + Nailed
Shear Walls (Wood based
panels)

E11 National Building Code Part 4 Structural Design No. 28


Instructor: Freddy Pina
Applying Code Provisions

Example

Assume for Seismic Weight:


Roof Roof
Roof: 18 psf L6
Snow: 35 psf
Extra (at roof): 150 kips L5
36’ L4
Typ. Floor
L3
Floor: 20 psf
Walls + exterior: 25 psf
L2
ADL (max per code): 10 psf

E11 National Building Code Part 4 Structural Design No. 29


Instructor: Freddy Pina
Applying Code Provisions

Example

54’
118’

E11 National Building Code Part 4 Structural Design No. 30


Instructor: Freddy Pina
Applying Code Provisions

Design Note

E11 National Building Code Part 4 Structural Design No. 31


Instructor: Freddy Pina
Applying Code Provisions

Minimum Earthquake Lateral Force, V

Step 1. Period, Ta
Walls
Ta = 0.05 (h)^3/4
h = 36’ = 10.8m (11m)
Ta = 0.05 (11)^3/4 = 0.3 s

Step 2. Hazard Data PGA 0.494 g


Vs = 250 m/s Sa(0.2) 1.110 g
X = XV = X250 Sa(0.5) 1.070 g
Sa(1.0) 0.634 g
Sa(2.0) 0.387 g
Sa(5.0) 0.116 g
Sa(10.0) 0.046 g
PGAref (4.1.8.4 (4)) 0.494 g

E11 National Building Code Part 4 Structural Design No. 32


Instructor: Freddy Pina
Applying Code Provisions

E11 National Building Code Part 4 Structural Design No. 33


Instructor: Freddy Pina
Applying Code Provisions

E11 National Building Code Part 4 Structural Design No. 34


Instructor: Freddy Pina
Applying Code Provisions

Minimum Earthquake Lateral Force, V

Step 3. Design Spectrum

PGA = 0.494
S(0.2) = max(1.11, 1.07) = 1.11
S(0.5) = 1.07
S(1.0) = 0.634
S(2.0) = 0.387 PGA 0.494 g
S(5,0) = 0.387 Sa(0.2) 1.110 g
S(10.0) = 0.046 Sa(0.5) 1.070 g
Sa(1.0) 0.634 g
S(0.3) → Interpolation Sa(2.0) 0.387 g
S(0.3) = 1.11 – [(1.11-1.07)*(0.3-0.2)/(0.5-0.2)] Sa(5.0) 0.116 g
Sa(10.0) 0.046 g
S(0.3) = 1.097
PGAref (4.1.8.4 (4)) 0.494 g

E11 National Building Code Part 4 Structural Design No. 35


Instructor: Freddy Pina
Applying Code Provisions

Minimum Earthquake Lateral Force, V

1.2

1.0

0.8

0.6

0.4

0.2

0.0
0.00 2.00 4.00 6.00 8.00 10.00

E11 National Building Code Part 4 Structural Design No. 36


Instructor: Freddy Pina
Applying Code Provisions

Minimum Earthquake Lateral Force, V

Step 4. Higher Mode Factor, Mv


Walls
S(0.2)/S(5.0) = 1.11/0.116 = 9.6
Ta = 0.3s < 0.5
→ Mv = 1.0

Step 5. Importance Factor, IE


Residential → Normal Category
IE = 1.0

E11 National Building Code Part 4 Structural Design No. 37


Instructor: Freddy Pina
Applying Code Provisions

Minimum Earthquake Lateral Force, V

Step 6. Seismic Category

IES(0.2) = 1.0 * 1.11 = 1.11 > 0.75 → SC4

IES(1.0) = 1.0 * 0.634 = 0.634 > 0.3 → SC4

E11 National Building Code Part 4 Structural Design No. 38


Instructor: Freddy Pina
Applying Code Provisions

Minimum Earthquake Lateral Force, V

Step 7. Seismic Weight, W

Roof, W_roof
W_roof = (18psf + 35psf / 4)*118’ * 54’ = 170 Kips+150 Kips = 320 Kips (1455kN)

Typ., Wi
Wi = (20psf + 25psf + 10psf) * 118’ * 54’ = 350 Kips (1590kN)

Total Weight, W
W = 320 Kips + 3 * 350 Kips = 1370 Kips (6225 kN)

E11 National Building Code Part 4 Structural Design No. 39


Instructor: Freddy Pina
Applying Code Provisions

Minimum Earthquake Lateral Force, V

Step 8. Reduction Factors, Rd Ro


Timber Building
SFRS: Nailed shear wall: wood based panel (must follow CSA O86)
Rd = 3.0
Ro = 1.7

Restrictions for SC4


Maximum height = 20m > 11m → OK

E11 National Building Code Part 4 Structural Design No. 40


Instructor: Freddy Pina
Applying Code Provisions

Minimum Earthquake Lateral Force, V

Step 9. Base Shear, V

V = 1.097*1.0*1.0*1370 Kips / (3.0*1.7) = 295 Kips ( 0.22W)

Lower Bound for Walls


S(4.0) Mv IE W / (Rd Ro) = 0.1556*1.0*1.0*1370 / (3.0*1.7) = 42 Kips (0.03W)

Upper Bound
Max between:
2/3 S(0.2) Mv IE W / (Rd Ro) = 2/3*1.11*1370/(3*1.7) = 199 Kips (0.15W)
S(0.5) Mv IE W / (Rd Ro) = 1.07*1370(3*1.7) = 287 Kips (0.21W)

Then, V = 287 Kips (1274 kN)

E11 National Building Code Part 4 Structural Design No. 41


Instructor: Freddy Pina
Applying Code Provisions

Example 2 (Same but now Site Class C)

• 4-storey timber on 2-storey


concrete
• Vancouver, Site C
• Residential
• 25’ high – Concrete structure
• 36’ high – Timber structure
• 118’ E-W x 54’ N-S
• SFRS: Concrete Walls + Nailed
Shear Walls (Wood based
panels)

E11 National Building Code Part 4 Structural Design No. 42


Instructor: Freddy Pina
Applying Code Provisions

E11 National Building Code Part 4 Structural Design No. 43


Instructor: Freddy Pina
Applying Code Provisions

E11 National Building Code Part 4 Structural Design No. 44


Instructor: Freddy Pina
Applying Code Provisions

Minimum Earthquake Lateral Force, V

Step 1. Period, Ta
Walls
Ta = 0.05 (h)^3/4
h = 36’ = 10.8m (11m)
Ta = 0.05 (11)^3/4 = 0.3 s

Step 2. Hazard Data PGA 0.468 g


Site Class = C Sa(0.2) 1.080 g
Sa(0.5) 0.863 g
X = XS = XC
Sa(1.0) 0.501 g
Sa(2.0) 0.305 g
Sa(5.0) 0.087 g
Sa(10.0) 0.037 g
PGAref (4.1.8.4 (4)) 0.468 g

E11 National Building Code Part 4 Structural Design No. 45


Instructor: Freddy Pina
Applying Code Provisions

Minimum Earthquake Lateral Force, V

Step 3. Design Spectrum

PGA = 0.468
S(0.2) = max(1.08, 0.863) = 1.08
S(0.5) = 0.863
S(1.0) = 0.501
S(2.0) = 0.305 PGA 0.468 g
S(5,0) = 0.087 Sa(0.2) 1.080 g
S(10.0) = 0.037 Sa(0.5) 0.863 g
Sa(1.0) 0.501 g
Sa(2.0) 0.305 g
S(0.3) → Interpolation
Sa(5.0) 0.087 g
S(0.3) = 1.08 – [(1.08-0.863)*(0.3-0.2)/(0.5-0.2)] Sa(10.0) 0.037 g
S(0.3) = 1.008 PGAref (4.1.8.4 (4)) 0.468 g

E11 National Building Code Part 4 Structural Design No. 46


Instructor: Freddy Pina
Applying Code Provisions

1.2

1.0

0.8

0.6

0.4

0.2

0.0
0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 9.00 10.00

E11 National Building Code Part 4 Structural Design No. 47


Instructor: Freddy Pina
Applying Code Provisions

Minimum Earthquake Lateral Force, V

Step 9. Base Shear, V

V = 1.008*1.0*1.0*1370 Kips / (3.0*1.7) = 271 Kips ( 0.20W)

Lower Bound for Walls


S(4.0) Mv IE W / (Rd Ro) = 0.118*1.0*1.0*1370 / (3.0*1.7) = 32 Kips (0.02W)

Upper Bound
Max between:
2/3 S(0.2) Mv IE W / (Rd Ro) = 2/3*1.08*1370/(3*1.7) = 193 Kips (0.14W)
S(0.5) Mv IE W / (Rd Ro) = 0.863*1370(3*1.7) = 232 Kips (0.17W)

Then, V = 232 Kips (1031 kN)

E11 National Building Code Part 4 Structural Design No. 48


Instructor: Freddy Pina
Applying Code Provisions

Distribution of lateral Forces

E11 National Building Code Part 4 Structural Design No. 49


Instructor: Freddy Pina
Applying Code Provisions

Distribution of lateral Forces

E11 National Building Code Part 4 Structural Design No. 50


Instructor: Freddy Pina
Applying Code Provisions

Distribution of lateral Forces

E11 National Building Code Part 4 Structural Design No. 51


Instructor: Freddy Pina
Applying Code Provisions

Distribution of lateral Forces

E11 National Building Code Part 4 Structural Design No. 52


Instructor: Freddy Pina
Applying Code Provisions

Distribution of lateral Forces

E11 National Building Code Part 4 Structural Design No. 53


Instructor: Freddy Pina
Applying Code Provisions

Distribution of lateral Forces

E11 National Building Code Part 4 Structural Design No. 54


Instructor: Freddy Pina
Applying Code Provisions

E11 National Building Code Part 4 Structural Design No. 55


Instructor: Freddy Pina
Applying Code Provisions

Distribution of lateral Forces for Example 1


Distribution of Forces over Height
I-S Height Height at
Portion of W by level (kN)
(m) Level (m)
1455.0 Roof 2.7 10.8 15714 kN-m
1591.0 L6 2.7 8.1 12887 kN-m
Wx= 1591.0 L5 hi-s= 2.7 hx = 5.4 Wx · hx = 8591 kN-m
1591.0 L4 2.7 2.7 4296 kN-m
0.0 Base 0.0 0.0 0 kN-m

Σ Wx · hx = 41488 kN-m

Force concentrated at the top of building,

0.07 Ta V ≤ 0.25 V = 0.0 kN


Ft =
0 if Ta < 0.7 s
Σ Fx

495 kN 495 kN 37.9% Roof


406 kN 901 kN 31.1% L6
Fx = (V - Ft) Wx·hx/ Σ Wx·hx = 271 kN 1171 kN % Fx/V = 20.7% L5
135 kN 1307 kN 10.4% L4
0 kN 1307 kN 0.0% Base

E11 National Building Code Part 4 Structural Design No. 56


Instructor: Freddy Pina
Applying Code Provisions

Distribution of OTM for Example 1

Mx = Jx Σ{Fi (hi-hx)}
1.00 Roof
1 for hx>=0.6hn 1.00 L6 495 kN
Jx = =
J + (1-J)(hx/0.6hn) for hx<0.6hn 1.00 L5
1.00 L4 M6 = 495*2.7 = 1336 kN m
2.7m
1.00 Base 406 kN

0 kN-m Roof
M5 = 1336 + (495+406)*2.7
1336 kN-m
M5 = 3768 kN m
L6 271 kN 2.7m
Σ{Fi (hi-hx)} =
3768 kN-m L5
M4 = 3768 +
or, Σ{(Σ Fx) * hi-s} 6931 kN-m L4
(495+406+271)*2.7
10459 kN-m Base 135 kN
2.7m
M4 = 6931 kN m
0 kN-m Roof
1336 kN-m
M3 = 6931 + (495+406+271
Mx = L6 2.7m
+135)*2.7
3768 kN-m L5
M3 = 10459 kN m
6931 kN-m L4
10459 kN-m Base

E11 National Building Code Part 4 Structural Design No. 57


Instructor: Freddy Pina
Applying Code Provisions

Distribution of Shear and OTM for Example 1

V = 1307 kN M = 10459 kN m
M/V = 8 m ≈ 0.78H

E11 National Building Code Part 4 Structural Design No. 58


Instructor: Freddy Pina
Applying Code Provisions

Where is this Force applied in plan?

E11 National Building Code Part 4 Structural Design No. 59


Instructor: Freddy Pina
Applying Code Provisions

Where is this Force applied in plan?

E11 National Building Code Part 4 Structural Design No. 60


Instructor: Freddy Pina
Applying Code Provisions

Example

0.1D = 0.1*35.4 = 3.54m

16.5m
(54’)
135 kN

35.4m
(118’)

E11 National Building Code Part 4 Structural Design No. 61


Instructor: Freddy Pina
Applying Code Provisions

Example

135 kN*3.54m = 478 kN m

16.5m
(54’)
135 kN

35.4m
(118’)

E11 National Building Code Part 4 Structural Design No. 62


Instructor: Freddy Pina

How does Torsion


distribute?

V
T

E11 National Building Code Part 4 Structural Design No. 63


Instructor: Freddy Pina

V
V/2 V/2

E11 National Building Code Part 4 Structural Design No. 64


Instructor: Freddy Pina

Θ*b/2

Θ
Θ*a/2

T
b

k*Θ*b/2
a k*Θ*a/2

k: lateral stiffness of the wall

E11 National Building Code Part 4 Structural Design No. 65


Instructor: Freddy Pina

kΘ: can be obtained from equilibrium, ΣF = 0; ΣM = 0

k*Θ*b/2
b k*Θ*a/2
T

a
T = 2*k*Θ*a/2 * a/2 + 2*k*Θ*b/2 * b/2

T = k*Θ*(a2 + b2)/2 → kΘ = 2T / (a2 + b2)

E11 National Building Code Part 4 Structural Design No. 66


Instructor: Freddy Pina

3 F1 = V/2 – 2T / (a2 + b2) * a/2

F2 = V/2 + 2T / (a2 + b2) * a/2


b T
1 2
V F3 = 2T / (a2 + b2) * b/2
4

a F4 = 2T / (a2 + b2) * b/2

E11 National Building Code Part 4 Structural Design No. 67


Instructor: Freddy Pina

ex = 0.1 * 35.4 m = 3.54 m

3 T = 135 kN * 3.54 m = 478 kN m

F1 = 135/2 - 2*478 / (35.42 + 16.52) * 35.4/2


16.5m T F1 = 67.5 – 11.1 = 56.4 kN
1 2 F2 = 67.5 + 11.1 = 79 kN
135 kN
4 F3 = 2*478 / (35.42 + 16.52) * 16.5/2
F3 = 5.2 kN
35.4m F4 = 5.2 kN

E11 National Building Code Part 4 Structural Design No. 68


Instructor: Freddy Pina

The end