PowerReach

Cavotec is a leading cleantech company that designs and delivers connection


and electrification solutions to enable the decarbonization of ports and industrial
applications.

Cavotec pioneered ShorePower technology in the 80s. We design, manufacture and


deliver innovative turnkey ShorePower solutions that allow our customers to take
charge of their own futures.

Overview

PowerReach is a jib-crane solution that connects high-voltage (HV) vessels (typically Ro-
Ro and Ro-Pax), and low-voltage (LV) vessels (typically ferries), to shoreside electrical grids
quickly and securely. It can also be used to charge AC and DC systems.

The system performs rapid pay out and retrieval of HV and LV power cables and plugs,
(with pilots and FO if required), with a dedicated cable dragging unit. PowerReach has a
minimal quayside footprint, and its arm can be rotated and “parked” when not in use. The
system is manoeuvred using Cavotec’s robust, lightweight and ergonomic push-button
Radio Remote Control (RRC) units.

Safety features include operator alerts that are triggered when cables are fully payed in or
payed out and HV/LV shut-off in the event of excessive cable traction.

Benefits

Tailored for your needs Safe & reliable to use


• Ratings up to 1.1kV (LV), 12kV (HV), and • Double belt conveyor dragging system to
customisable above 12kV prevent cable slippage and reduce cable
• Able to accomodate up to 3 cables surface pressure
• Rapid connection to vessels with • Cable position sensing devices for cable
Cavotec PC5 or PC6 push-pull plugs length monitoring
• Highly customisable column height and • Motorised gearbox with frequency
arm length converter for smooth acceleration of arm
rotation and cable dispenser
Long lifetime • Detailed system status monitoring: local
• Anti-corrosion C5M marine coating and remote alerts for supervision
• Structural wind speed up to 36m/s • HV/LV cables supplied with cable grip
• HV/LV plugs anodised and treated with
clearcoat for harsh environments

DATASHEET | ShorePower Systems | PowerReach


April 2023 | DAS-SP-01
Options

• RRC for remote operation: multiple RRC units available for • Special paint or colours
multiple-vessel applications • Ultrasound vessel detection sensor
• Protection cages around cables • Hot dip galvanised structure
• Direct connection to shore power substation

Technical features

Electrical features
LV HV RoRo/RoPax (IEC 80005:1 Annex B)
Operating voltage Up to 1.1kV 6.6 or 11kV (Typically) 11kV
Connector PC5 or PC6 connector PC5 or PC6 connector PC6 connector according to IEC 80005:1
Maximum amperage: 660A Maximum amperage: 500A 7 pilot pins
Fibre optic Available on request 4 channels multimode
Cable Up to 300mm2, depending on project Up to 240mm2, depending on project 70 or 120mm2, depending on project
requirements requirements requirements
Power Up to 1.2MVA per cable Up to 9.5MVA per cable Up to 6.5MVA with 1 cable
IP rate IP56 Junction box and control panel (with anti-condensation heaters)
Aux power required 5kW at 400V
Additional features - Emergency stop for safe operation
- Cable position sensing devices

Mechanical features
Column height From 4 to 16m (column over 11m supplied in two parts)
Column arm From 2 to 10m
Active Cable lengh Up to 25m active length to compensate tide and vessel displacement (proportional to the dispenser height)
Cable traction Double belt conveyor cable dispenser powered by frequency converter motorised gearbox, to reduce cable wear and prevent slippage during
dispensing

Relation between height and active cable length


Height plug level (m) 4 6 8 10 12
Active cable length (m) 5.6 9.6 13.6 17.6 21.6

Equipment illustration

Approvals

PowerReach complies with Cable Management System (CMS) requirements of IEC/ISO/IEEE 80005:1 Utility connections in port – Part 1:
High Voltage Shore Connection (HVSC) Systems – General requirements and IEC PAS 80005:3 - Utility connections in port - Part 3: Low
Voltage Shore Connection (LVSC) Systems - General requirements.

For further details, please contact your local Cavotec sales office via cavotec.com. Disclaimer: specifications are subject to change without notice.

DATASHEET | ShorePower Systems | PowerReach


April 2023 | DAS-SP-01