Fanuc Manuals 2418
Fanuc Manuals 2418
Fanuc Manuals 2418
New In Stock!
GE Fanuc Manuals
http://www.pdfsupply.com/automation/ge-fanuc-manuals/motion-
solutions/GFK-1866
motion-solutions
1-919-535-3180
www.pdfsupply.com
Email: sales@pdfsupply.com
GFK-1866
New In Stock!
GE Fanuc Manuals
http://www.pdfsupply.com/automation/ge-fanuc-manuals/motion-
solutions/GFK-1866
motion-solutions
1-919-535-3180
www.pdfsupply.com
Email: sales@pdfsupply.com
GE Fanuc Automation
S2K Series
Brushless Servo Amplifier
User's Manual
GFK-1866A September 2002
GFL-002
Warnings, Cautions, and Notes
as Used in this Publication
Warning
Warning notices are used in this publication to emphasize that hazardous voltages,
currents, temperatures, or other conditions that could cause personal injury exist in this
equipment or may be associated with its use.
In situations where inattention could cause either personal injury or damage to
equipment, a Warning notice is used.
Caution
Caution notices are used where equipment might be damaged if care is not taken.
Note
Notes merely call attention to information that is especially significant to understanding and
operating the equipment.
This document is based on information available at the time of its publication. While efforts
have been made to be accurate, the information contained herein does not purport to cover all
details or variations in hardware or software, nor to provide for every possible contingency in
connection with installation, operation, or maintenance. Features may be described herein
which are not present in all hardware and software systems. GE Fanuc Automation assumes no
obligation of notice to holders of this document with respect to changes subsequently made.
Related Publications
GFK-1464, Motion Mate DSM302 for Series 90-30 PLCs User’s Manual
GFK-1742, Motion Mate DSM314 for Series 90-30 PLCs User’s Manual
GFK-0840, Power Mate APM for Series 90-30 PLC Standard Mode User’s Manual
GFK-0781, Power Mate APM for Series 90-30 PLC Follower Mode User’s Manual
Motion Mate and Series 90 are trademarks of GE Fanuc, Power Mate is a trademark of Fanuc
GFK-1866A iii
Contents
GFK-1866A v
Contents
Appendix C Interfacing With GE Fanuc APM or DSM Series Motion Controllers......... C-1
C.1 Wiring the S2K Amplifier to the APM300 Motion Controller.............. C-1
C.2 Wiring the S2K Amplifier to a DSM Motion Controller....................... C-2
C.1.1 Auxiliary Terminal Board Description and Mounting Dimensions....... C-4
C.1.2 Converting the Terminal Board From DIN-Rail to Panel Mounting..... C-5
C.1.3 Auxiliary Terminal Block Pin Assignments .......................................... C-6
Figure 3-1. SSD104, SSD107 and SSD407 S2K Series Amplifier Dimensions and Weight....................... 3-4
Figure 3-2. SSD216, SSD228 and SSD420 S2K Series Amplifier Dimensions and Weight....................... 3-5
Figure 3-3. Dimensions for 30-100 Watt SL Series Motors......................................................................... 3-6
Figure 3-4. Dimensions for 200 Watt S-Series Servo Motor ....................................................................... 3-7
Figure 3-5. Dimensions for 400 Watt S-Series Servo Motor ....................................................................... 3-8
Figure 3-6. Dimensions for 750 Watt S-Series Servo Motor ....................................................................... 3-9
Figure 3-7. Dimensions for 1000 Watt and 2500 W S-Series Servo Motors ............................................. 3-10
Figure 3-8. Dimensions for 4500 Watt and 5000 W S-Series Servo Motors ............................................. 3-11
Figure 3-9. Dimensions for MTR-3T1x-Series Servo Motors ................................................................... 3-12
Figure 3-10. Dimensions for MTR-3T2x-Series Servo Motors .................................................................. 3-13
Figure 3-11. Dimensions for MTR-3T4x-Series Servo Motors .................................................................. 3-13
Figure 3-12. Dimensions for MTR-3T5x-Series Servo Motors .................................................................. 3-14
Figure 3-13. Dimensions for MTR-3T6x-Series Servo Motors .................................................................. 3-14
Figure 3-14. Dimensions for MTR-3N2x-Series Servo Motors .................................................................. 3-15
Figure 3-15. Dimensions for MTR-3N3x-Series Servo Motors .................................................................. 3-16
Figure 3-16. Dimensions for MTR-3S2x-Series Servo Motors................................................................... 3-17
Figure 3-17. Dimensions for MTR-3S3x-Series Servo Motors................................................................... 3-18
Figure 3-18. Dimensions for MTR-3S4x-Series Servo Motors................................................................... 3-19
Figure 3-19. Dimensions for MTR-3S6x-Series Servo Motors................................................................... 3-20
Figure 3-19. Dimensions for MTR-3S8x-Series Servo Motors................................................................... 3-21
Figure 3-20. S-Series Servo Motor Serial Encoder Feedback Connectors.................................................. 3-25
Figure 3-21. S-Series Motor Power Connections ........................................................................................ 3-27
Figure 3-22. MTR-3T Series Motor/Brake Power Connections.................................................................. 3-28
Figure 3-23. MTR-3N and MTR-3S Series Motor Power Connections..................................................... 3-28
Figure 3-24. MTR-3N and MTR-3S Series Optional Brake Power Connections ...................................... 3-28
Figure 3-25. MTR-Series Resolver Feedback Connections ........................................................................ 3-29
Figure 3-26. Connection Diagram for the 4.3 A 115/230 VAC Serial Encoder-Based Servo Amplifier
(SSD104) ........................................................................................................................... 3-37
Figure 3-27. Connection Diagram for the 4.3 A 115/230 VAC Resolver-Based Servo Amplifier
(SSD104R) ........................................................................................................................ 3-38
Figure 3-28. Connection Diagram for the 7.2A 115/230 VAC Serial Encoder-Based Servo Amplifier
(SSD107) ........................................................................................................................... 3-39
Figure 3-29. Connection Diagram for the 7.2A 115/230 VAC Resolver-Based Servo Amplifier (SSD107R)3-40
Figure 3-30. Connection Diagram for the 16 A & 28 A 230 VAC Serial Encoder-Based Servo Amplifiers
(SSD216 & SSD228)......................................................................................................... 3-41
Figure 3-31. Connection Diagram for the 16 A & 28 A 230 VAC Resolver-Based Servo Amplifiers
(SSD216R & SSD228R) ................................................................................................... 3-42
viii S2K Series Brushless Servo Amplifier User's Manual–September 2002 GFK-1866A
Contents
Figure 3-32. Connection Diagram for the 7.2A 460 VAC Resolver-Based Servo Amplifier (SSD407R).. 3-43
Figure 3-33. Connection Diagram for the 20A 460 VAC Resolver-Based Servo Amplifier (SSD420R)... 3-44
Figure 3-34. Typical Brake Wiring Diagram............................................................................................... 3-47
Figure 3-35. Regenerative Discharge Resistor Mounting and Wiring Dimensions .................................... 3-50
Figure 3-36. Typical External Dynamic Brake Circuit............................................................................... 3-55
Figure C-1. APM300 Terminal Block and Cable Connections ................................................................... C-1
Figure C-2. APM300 to S2K Amplifier Connections Using Terminal Block 44A726268-001.................. C-2
Figure C-3. DSM Terminal Boards and Cables for S2K Amplifier Interface ............................................. C-3
Figure C-4. Auxiliary Terminal Board with Mounting Dimensions ........................................................... C-4
Figure C-5. Auxiliary Terminal Board Assembly Drawings....................................................................... C-5
Figure C-6. Auxiliary Terminal Board Assembly Side View ..................................................................... C-6
Figure C-7. DSM Analog Interface to SSD104, SSD107, and SSD407 Amplifier (With external Enable) C-8
Figure C-8. DSM Analog Interface to SSD216, SSD228, and SSD420 Amplifier (With external Enable) C-8
GFK-1866A Contents ix
Contents
Table 1-1. S-Series Motor/Amplifier Compatibility for Serial Encoder-based Amplifiers.......................... 1-5
Table 1-2. MTR-Series Motor/Amplifier Compatibility for Resolver-based Amplifiers............................. 1-6
Table 2-1. Hardware Resources.................................................................................................................... 2-1
Table 2-2. Amplifier Power Specifications .................................................................................................. 2-2
Table 2-3. Environmental Specifications ..................................................................................................... 2-2
Table 2-4. Serial Communication Specifications ......................................................................................... 2-3
Table 2-5. Input and Output Specifications .................................................................................................. 2-3
Table 2-6. Encoder and Resolver Input/Output Specifications .................................................................... 2-4
Table 2-7. S-Series Motor Specifications ..................................................................................................... 2-5
Table 2-8. MTR-3N Series Motor Specifications......................................................................................... 2-7
Table 2-9. MTR-3S Series Motor Specifications ......................................................................................... 2-8
Table 2-10. MTR-3T Series Motor Specifications ..................................................................................... 2-10
Table 2-11 Mounting Configurations for Servo Motors.............................................................................. 2-17
Table 3-1. Power Terminal Connections and Wire Sizes for SSD104 4.3 A Amplifier ............................ 3-23
Table 3-2. Power Terminal Connections and Wire Sizes for SSD107 7.2 A Amplifier ............................ 3-23
Table 3-3. Power Terminal Connections and Wire Sizes for SSD216 16A & SSD228 28A Amplifier .... 3-24
Table 3-4. Power Terminal Connections and Wire Sizes for SSD407 7.2 A 460 VAC Amplifier ........... 3-24
Table 3-5. Power Terminal Connections and Wire Sizes for SSD420 20A Amplifier .............................. 3-25
Table 3-6. Serial Encoder Position Feedback Connections........................................................................ 3-26
Table 3-7. Resolver Position Feedback Connections ................................................................................. 3-29
Table 3-8. Auxiliary I/O Connector Pin-out............................................................................................... 3-31
Table 3-9. Cables Available from GE Fanuc.............................................................................................. 3-45
Table 3-10. S-Series Servo Motor Connector Mates.................................................................................. 3-46
Table 3-11. Regenerative Discharge Resistor Kits...................................................................................... 3-48
Table 3-12. Amplifier Regenerative Discharge Ratings............................................................................. 3-52
Table 6-1. LED Display Status Codes .......................................................................................................... 6-1
Table C-1. Auxiliary Terminal Board Components .................................................................................... C-5
Table C-2. Terminal Block Pin Assignments for DSM300 Analog Servo Axes.......................................... C-7
S2K Series amplifiers are optimized for use with the GE Fanuc S-Series or MTR series servo
motors. Overload and possible component damage may occur if the motor and amplifier are not
properly matched. Tables 1-1 and 1-2 show the proper pairing of the components.
The 30—1000W S-Series servo motors (SLM models) are designed with standard NEMA shaft and
flange mounting configurations for easy mounting to off-the-shelf gear reducers and couplings. The
750W motor uses an oversized shaft diameter (0.625 in.) for the NEMA 34 mounting to handle the
peak torque rating of this model. SLM motors from 2.5 to 5kW, and all SDM and SGM models
have metric mounting configurations. All servo motors are available with an optional 24VDC
holding brake for holding stationary loads that is spring-set and electrically-released. You must
supply a separate 24 VDC brake power supply. The 30—750W S-Series and all MTR-series
motors have a pigtail cable with box style connectors for motor power, encoder, and brake
connections for MTR-3T and 1-SKW S-Series motors. The 1000—5000W motors have MS style
connectors, and brake power is integrated with the motor power connections in a common power
connector/cable.
S2K Series amplifiers are configured using Motion Developer software running on a personal
computer. This software is a standalone application that works in the Machine Edition software
environment.
The following sections outline what should be accomplished before operating the S2K Series
amplifiers.
1-1
1
Note
If you find any damage, please contact your local dealer/distributor or GE Fanuc
directly.
1.3 Storage
Store S2K components in a clean, dry location that is not exposed to direct sunlight, rain, excessive
temperatures (exceeding -20°C to 80°C), corrosive gasses or liquids.
For maximum protection, store all components in the original shipping container.
IC800 SL M ttt m v b e rr
Series Encoder Resolution
SL = Low Inertia Series 25 = 2500 lines
SD = Med. Inertia Series
SG = High Inertia Series
Encoder Type
E = Incremental data with serial commutation
Motor Brake
Power N = No Key and No Brake (Std. On 30 to 100 W models)
003 = 30 Watt B = Brake and No Key (Opt.on 30 to 100 W models)
005 = 50 Watt K = Key and No Brake (Std. On 200 W and larger models)
010 = 100 Watt X = Brake and Key (Opt.on 200 W and larger models)
020 = 200 Watt
040 = 400 Watt
075 = 750 Watt Voltage
100 = 1000 Watt
1 = 115 VAC Motor (100 to 400 W models only)
250 = 2500 Watt
350 = 3500 Watt 2 = 230 VAC Motor
450 = 4500 Watt 3 = 115/230 VAC Motor
(available only for 30 & 50 W models)
500 = 5000 Watt
Mounting
N = NEMA
M = Metric
MTR- 3N - fs -w -R- b - m - s
Shaft Seal
Series 0 = No seal (3T4x, 3T5x & 3T6x only)
S = Shaft seal (standard on all models except 3T4x, 3T5x
3N = Neodymium
and 3T6x)
3S = Samarium
3T = Metric Mounting Flange
N = NEMA (NEMA23; 3N2x, 3S2x; NEMA34: 3N3x, 3S3x)
E = English (standard on 3S4x, 3S6x or 3S8x)
Frame/Stack C = NEMA 56C (option on 3S4x only)
M = Metric (standard on 3T)
3N Series:
21, 22, 24, 31, 32, 33
Brake
3S Series: 0 = No Brake
22, 23, 32, 33, 34, 35, 43, 45, B = 24 Vdc Brake (not available for 3S20 series)
46, 63, 65, 67, 84, 86, 88
3T Series: Feedback
11, 12, 13, 21, 22, 23, 24, 42, R = Resolver
43, 44, 45, 53, 54, 55, 57, 65,
66, 67, 69
Winding
IC800 SSD104 R S1
S2K Options
Type S1 = Standard Amplifier Configuration
S = Servo
Motor Feedback Type
Blank = GE Fanuc serial encoder (S-Series motors only)
Power R = Resolver
D = Servo Drive Only
Continuous Current
Supply Voltage 04 = 4.3 Amp Servo Model (230 Vac only)
07 = 7.2 Amp Servo Model (230 or 460 VAC)
1 = 90 – 250 VAC (4.3 & 7.2 amp models only) 16 = 16 Amp Servo Model (230 VAC only)
2 = 180-250 VAC (16 & 28 amp models only) 20 = 20 Amp Servo Model (460 VAC only)
4 = 324-528 VAC (7.2 or 20 amp models only) 28 = 28 Amp Servo Model (230 VAC only)
IC800SL R xxx
SL Series
Regen Resistor Kits
Type
001 = 50 ohm, 100 W w/mounting
002 = 100 ohm, 225 W w/mounting hardware
003 = 20 ohm, 300 W w/mounting hardware
004 = 15 ohm, 1000 W w/mounting hardware
2.1 Specifications
The S2K Series amplifiers are available in two 115/230 VAC ratings, two 230 VAC ratings and
two 460 VAC ratings. The 115/230 VAC and 230 VAC models are available with either a serial
encoder or resolver motor feedback interface while the 460 VAC models are only available with a
resolver feedback interface. The S2K series encoder-based amplifiers are used with the S-Series
servo motors while the resolver-based amplifiers are used with MTR-Series servo motors. This
chapter contains the specifications for each of these components. Table 2-1 shows the hardware
resources available on the S2K amplifiers.
2-1
2
Inductance (phase) mH 2.4 2.8 1.7 5.0 3.2 7.8 1.9 5.1 3.2
Electrical Time
ms 0.6 0.67 0.89 0.88 3.5 3.4 4.6 3.5 7.4
Constant
Continuous Current A(rms) 1.0 1.0 1.6 1.0 2.5 1.6 4.3 2.5 4.3
Environmental Data
Humidity (non-
RH 85%
condensing)
Ambient Temperature o
C 0 to 40
(operating)
o
Storage Temperature C -20 to 80
Vibration3 G 5
Shock G 10
1. Torque shown is available up to a certain ambient temperature. See Speed/Torque curve notes.
2. Radial shaft loads are specified at a position centered along the length of the shaft
3. Vibration tests are described in the section “Motor Vibration Testing” later in this chapter.
Output Power W 1000 1000 2500 2500 3500 5000 5000 5000
Continuous Stall in-lb 43 28 70 104 97 140 210 322
Torque1 [Nm] [4.8] [3.18] [7.94] [11.8] [11] [15.8] [23.8] [36.3]
in-lb 110 56 140 240 252 421 420 644
Peak Torque
[Nm] [12.4] [6.3] [15.8] [27.1] [28.5] [47.6] [47.5] [72.8]
Rated Speed RPM 2000 3000 3000 2000 3000 3000 2000 3000
Maximum Speed RPM 3000 5000 5000 3000 5000 4500 3000 4500
Feedback 2500 lines (10,000 counts/rev) Incremental Encoder (5 VDC ±5% @0.3 A; 250 kHz max.)
lb 15 9.9 16.5 28.2 24 38 55 38
Weight
[kg] [6.8] [4.5] [7.5] [12.8] [10.9] [17.3] [25] [17.3]
in-lb-s2 x 10-4 54.6 14.91 38.14 169.9 69.92 157.5 537.2 157.5
Rotor Inertia
[kg-m2 x 10-4] [6.17] [1.69] [4.31] [19.2] [7.90] [17.8] [60.7] [17.8]
lb 44 33 44 77 44 77 77 77
Shaft Thrust Load
[kg] [20] [15] [20] [35] [20] [35] [35] [35]
lb 110 88 110 176 110 176 176 176
Shaft Radial Load2
[kg] [50] [40] [50] [80] [50] [80] [80] [80]
Mechanical Time
ms 0.70 0.78 0.52 0.72 0.45 0.46 0.9 0.46
Constant
in-lb/A(rms) 7.61 3.9 4.34 7.52 4.51 5.04 7.52 11.5
Torque Constant
[Nm/A(rms)] [0.86] [0.44] [0.49] [0.85] [0.51] [0.57] [0.85] [1.3]
Resistance (phase) Ohms 0.56 0.27 0.1 0.18 0.05 0.028 0.068 0.028
Specification Units 3N21-H 3N22-H 3N24-G 3N31-H 3N32-G 3N32-H 3N33-G 3N33-H
Specification Units 3S22-G 3S23-G 3S32-G 3S33-G 3S34-G 3S35-G 3S43-G 3S43-H 3S45-G 3S45-H
Resistance (phase) Ohms 22 20 7.3 6.9 8.1 9.2 10 2.5 3.2 0.81
Electrical Time
ms 0.95 1.3 3.2 3.2 3.7 4.6 5.3 5.3 6.3 6.1
Constant
Continuous Current A(rms) 1.4 1.5 2.9 3.2 3.0 2.9 2.9 5.6 5.5 10.9
Optional Brake Data
in-lb-s2 x 10-4 0.34 0.34 0.34 0.34 5.0 5.0 5.0 5.0
Inertia Adder N/A N/A
[kg-m2 x10-4] [0.38] [0.38] [0.38] [0.38] [0.565] [0.565] [0.565] [0.565]
lb 2.5 2.5 2.5 2.5 4.0 4.0 4.0 4.0
Weight Adder N/A N/A
[kg] [1.14] [1.14] [1.14] [1.14] [1.82] [1.82] [1.82] [1.82]
Voltage VDC± 10% N/A N/A 24 24 24 24 24 24 24 24
Current A N/A N/A 0.72 0.72 0.72 0.72 0.71 0.71 0.71 0.71
Engage Time ms N/A N/A 10 10 10 10 20 20 20 20
Release Time ms N/A N/A 30 30 30 30 120 120 120 120
in-lb 32 32 32 32 72 72 72 72
Torque N/A N/A
[Nm] [3.62] [3.62] [3.62] [3.62] [8.14] [8.14] [8.14] [8.14]
Environmental Data
Humidity
RH 98%
(non-condensing)
Ambient
o
Temperature C -20 to 40
(operating)
Storage o
C -30 to 150
Temperature
1. Torque shown is available up to an ambient temperature of 25o C with motor mounted to a 10’ x10’ x
0.25’ aluminum heat sink.
2. Shaft loads are based on L10 bearing life at 3000 rpm and assume force is applied to center of shaft.
3. Peak torque ratings are for the motor only and may be limited by the specific amplifier based on
the amplifiers peak current limitations.
Specification Units 3S46-G 3S46-H 3S63-G 3S63-H 3S65-G 3S65-H 3S67-G 3S67-H 3S84-G 3S86-G 3S88-G
Continuous Stall in-lb 64 64 70 70 115 115 168 168 190 255 338
Torque1 [Nm] [7.23] [7.23] [7.9] [7.9] [13] [13] [19] [19] [21.5] [28.8] [38.2]
in-lb 179 179 181 181 295 295 433 433 394 590 762
Peak Torque 3
[Nm] [20.2] [20.2] [20.5] [20.5] [33.3] [33.3] [48.9] [48.9] [44.5] [66.6] [86.1]
Maximum Speed RPM 2100 4200 3850 7700 2300 4600 1650 3300 3400 2600 2600
Feedback 4096 counts/rev resolver (control transmitter; 0.5 transformation ratio)
lb 25 25 29 29 39 39 49 49 60 77 94
Weight
[kg] [11.3] [11.3] [13] [13] [18] [18] [22] [22] [27] [35] [43]
in-lb-s2 x 10-4 35.8 35.8 72 72 112 112 152 152 392 582 762
Rotor Inertia
[kg-m2 x 10-4] [4.0] [4.0] [8.1] [8.1] [12.6] [12.6] [17.2] [17.2] [44.3] [65.7] [86.1]
lb 50 50 70 70 70 70 70 70 100 100 100
Shaft Thrust Load 2
[kg] [22.7] [22.7] [32] [32] [32] [32] [32] [32] [45] [45] [45]
lb 125 125 185 185 185 185 185 185 250 250 250
Shaft Radial Load 2
[kg] [56.8] [56.8] [84] [84] [84] [84] [84] [84] [114] [114] [114]
in-lb/A(rms) 12.4 6.2 7.1 3.5 11.5 5.3 15.9 8.0 7.1 9.7 12.4
Torque Constant
[Nm/A(rms)] [1.4] [0.7] [0.8] [0.40] [1.30] [0.6] [1.8] [0.9] [0.8] [1.1] [1.4]
Resistance (phase) Ohms 3.7 0.93 0.93 0.23 1.2 0.34 1.5 0.37 0.26 0.25 0.28
Inductance (phase) mH 25 6.2 8.9 2.2 13.7 3.4 18.2 4.6 3.2 3.6 4.0
Electrical Time
ms 6.8 6.7 9.6 9.6 11.4 10.0 12.1 12.4 12.3 14.4 14.2
Constant
Continuous Current A(rms) 5.5 11 11 22 10.7 21.4 11.3 22.5 26.9 30.2 29.4
Optional Brake Data
in-lb-s2 x 10-4 5.0 5.0 3.7 3.7 3.7 3.7 3.7 3.7 14.9 14.9 14.9
Inertia Adder
[kg-m2 x10-4] [0.565] [0.565] [0.418] [0.418] [0.418] [0.418] [0.418] [0.418] [1.68] [1.68] [1.68]
lb 4.0 4.0 9 9 9 9 9 9 15 15 15
Weight Adder
[kg] [1.82] [1.82] [4.1] [4.1] [4.1] [4.1] [4.1] [4.1] [6.82] [6.82] [6.82]
Voltage VDC± 10% 24 24 24 24 24 24 24 24 24 24 24
Current A 0.71 0.71 1.14 1.14 1.14 1.14 1.14 1.14 1.51 1.51 1.51
Engage Time ms 20 20 25 25 25 25 25 25 50 50 50
Release Time ms 120 120 50 50 50 50 50 50 100 100 100
in-lb 72 72 180 180 180 180 180 180 180 180 180
Torque
[Nm] [8.14] [8.14] [20.3] [20.3] [20.3] [20.3] [20.3] [20.3] [20.3] [20.3] [20.3]
Environmental Data
Humidity (non-
RH 98%
condensing)
Ambient
o
Temperature C -20 to 40
(operating)
Storage o
C -30 to 150
Temperature
1. Torque shown is available up to an ambient temperature of 25o C with motor mounted to a 10’ x10’ x 0.25’
aluminum heat sink.
2. Shaft loads are based on L10 bearing life at 3000 rpm and assume force is applied to center of shaft.
3. Peak torque ratings are for the motor only and may be limited by the specific amplifier based on the
amplifiers peak current limitations.
Units 3T11-G 3T12-G 3T13-G 3T21-G 3T22-G 3T23-G 3T24-H 3T42-H 3T43-H 3T43-J 3T44-J
Specification
Continuous Stall in-lb 2.3 5.3 8 5.6 11.5 17.7 23 33 54 54 72
Torque1 [Nm] [0.26] [0.6] [0.9] [0.63] [1.3] [2.0] [2.6] [3.72] [6.1] [6.1] [8.13]
in-lb 12.4 25.6 38 20.4 41.6 63.7 85 129 192 192 260
Peak Torque 3
[Nm] [1.4] [2.9] [4.3] [2.3] [4.7] [7.2] [9.6] [14.6] [21.7] [21.7] [29.4]
Maximum Speed RPM 6000 6000 6000 9250 7100 4700 4350 4000 2600 4000 3000
Feedback 4096 counts/rev resolver (control transmitter; 0.5 transformation ratio)
lb 2.6 3.3 4.2 3.7 5.0 6.4 7.7 13.6 16.7 16.7 20
Weight
[kg] [1.2] [1.5] [1.9] [1.7] [2.3] [2.9] [3.5] [6.2] [7.6] [7.6] [9.0]
in-lb-s2 x 10-4 1.02 1.64 2.26 1.9 3.4 4.9 6.4 32 46 46 60
Rotor Inertia
[kg-m2 x 10-4] [0.12] [0.19] [0.26] [0.22] [0.38] [0.55] [0.72] [3.6] [5.2] [5.2] [6.8]
lb 17 17 17 17 41.5 41.5 41.5 41.5
Shaft Thrust Load 2 N/A N/A N/A
[kg] [7.7] [7.7] [7.7] [7.7] [18.9] [18.9] [18.9] [18.9]
lb 62 62 62 62 157 157 157 157
Shaft Radial Load 2 N/A N/A N/A
[kg] [28.1] [28.1] [28.1] [28.1] [71.5] [71.5] [71.5] [71.5]
in-lb/A(rms) 2.4 2.9 2.9 3.3 4.3 6.5 7.0 7.7 11.9 7.5 10.2
Torque Constant
[Nm/A(rms)] [0.27] [0.32] [0.32] [0.37] [0.49] [0.74] [0.79] [0.87] [1.34] [0.85] [1.15]
Resistance (phase) Ohms 16.3 6.8 3.9 8.8 4.81 6.1 4.6 3.2 3.9 1.54 1.8
Inductance (phase) mH 7.1 4.3 2.7 10.5 7.4 10.6 8.9 8.9 13.0 5.3 7.1
Electrical Time
ms 0.43 0.63 0.69 1.19 1.54 1.73 1.93 2.78 3.33 3.44 3.94
Constant
Continuous
A(rms) 0.96 1.88 2.73 1.72 2.65 2.7 3.3 4.7 4.6 7.2 7.2
Current
Optional Brake Data
in-lb-s2 x 10-4 5.49 2.25 3.81 16.82 6.99 16.82 53.1 16.82 16.82 16.82 16.82
Inertia Adder
[kg-m2 x10-4] [0.62] [0.26] [0.43] [1.9] [0.79] [1.9] [6] [1.9] [1.9] [1.9] [1.9]
lb 0.4 0.4 0.4 0.4 0.4 0.4 0.4 1.3 1.3 1.3 1.3
Weight Adder
[kg] [0.2] [0.2] [0.2] [0.2] [0.2] [0.2] [0.2] [0.6] [0.6] [0.6] [0.6]
Voltage VDC± 10% 24 24 24 24 24 24 24 24 24 24 24
Current A 0.33 0.33 0.33 0.33 0.33 0.33 0.33 0.66 0.66 0.66 0.66
Engage Time ms 25 25 25 25 25 25 25 20 20 20 20
Release Time ms 25 25 25 25 25 25 25 30 30 30 30
in-lb 10.6 10.6 10.6 10.6 10.6 10.6 10.6 88.5 88.5 88.5 88.5
Torque
[Nm] [1.2] [1.2] [1.2] [1.2] [1.2] [1.2] [1.2] [10] [10] [10] [10]
Environmental Data
Humidity (non-
RH 98%
condensing)
Ambient
o
Temperature C -20 to 40
(operating)
Storage o
C -30 to 150
Temperature
1. Torque shown is available up to an ambient temperature of 25o C with motor mounted to a 10’ x10’ x 0.25’ aluminum heat sink.
2. Shaft loads are based on L10 bearing life at 3000 rpm and assume force is applied to center of shaft.
3. Peak torque ratings are for the motor only and may be limited by the specific amplifier based on the amplifiers peak current limitations.
Specification
Units 3T45-H 3T45-I 3T54-H 3T55-H 3T55-I 3T57-H 3T66-H 3T67-G 3T69-G
Continuous Stall in-lb 90.3 90.3 120 151 151 195 266 372 478
Torque1 [Nm] [10.2] [10.2] [13.5] [17.0] [17.0] [22] [30] [42] [54]
in-lb 326 326 363 456 456 611 1009 1177 1505
Peak Torque3
[Nm] [36.8] [36.8] [41] [51.5] [51.5] [69] [114] [133] [170]
Maximum Speed RPM 2350 3300 2700 2150 4300 3050 2000 1700 1300
Feedback 4096 counts/rev resolver (control transmitter; 0.5 transformation ratio)
lb 22.9 22.9 28.6 33 33 41.9 79.3 92.5 54
Weight
[kg] [10.4] [10.4] [13] [15] [15] [19] [36] [42] [119]
in-lb-s2 x 10-4 74 74 220 271 271 373 833 965 1230
Rotor Inertia
[kg-m2 x 10-4] [8.4] [8.4] [24.9] [30.6] [30.6] [42.1] [94] [109] [139]
lb 41.5 41.5 31.5 31.5 31.5 31.5 48.3 48.3 48.3
Shaft Thrust Load 2
[kg] [18.9] [18.9] [18.9] [18.9] [18.9] [18.9] [21.9] [21.9] [21.9]
lb 157 157 115 115 115 115 200 200 200
Shaft Radial Load 2
[kg] [71.5] [71.5] [52.3] [52.3] [52.3] [52.3] [45] [45] [45]
in-lb/A(rms) 12.9 9.2 11.3 14.2 7.1 10 15.4 18 23.3
Torque Constant
[Nm/A(rms)] [1.46] [1.04] [1.27] [1.6] [0.8] [1.13] [1.74] [2.04] [2.63]
Resistance (phase) Ohms 2.1 1.1 0.8 0.9 0.2 0.3 0.32 0.35 0.41
Inductance (phase) mH 8.7 4.4 7.1 8.8 2.2 3.1 6.5 7.7 10
Electrical Time
ms 4.1 4 8.9 9.8 11 10.3 20.3 22 24.4
Constant
Continuous Current A(rms) 7.1 10 10.6 10.6 21.3 19.5 20.7 20.7 20.6
Optional Brake Data
in-lb-s2 x 10-4 9.7 9.7 31.9 31.9 31.9 31.9 84.1 84.1 84.1
Inertia Adder
[kg-m2 x10-4] [1.1] [1.1] [3.6] [3.6] [3.6] [3.6] [9.5] [9.5] [9.5]
lb 1.3 1.3 3.3 3.3 3.3 3.3 4.8 4.8 4.8
Weight Adder
[kg] [0.6] [0.6] [1.5] [1.5] [1.5] [1.5] [2.2] [2.2] [2.2]
Voltage VDC± 10% 24 24 24 24 24 24 24 24 24
Current A 0.48 0.48 0.41 0.41 0.41 0.41 0.73 0.73 0.73
Engage Time ms 20 20 25 25 25 25 25 25 25
Release Time ms 30 30 50 50 50 50 75 75 75
in-lb 88.5 88.5 15 159 159 159 354 354 354
Torque
[Nm] [10] [10] [16] [16] [16] [16] [40] [40] [40]
Environmental Data
Humidity
RH 98%
(non-condensing)
Ambient Temperature o
C -20 to 40
(operating)
Storage o
C -30 to 150
Temperature
1. Torque shown is available up to an ambient temperature of 25o C with motor mounted to a
10’ x10’ x 0.25’ aluminum heat sink.
2. Shaft loads are based on L10 bearing life at 3000 rpm and assume force is applied to center of shaft.
3. Peak torque ratings are for the motor only and may be limited by the specific amplifier based on
the amplifiers peak current limitations.
6000 6000
Speed (RPM)
Speed (RPM)
5000 5000
4000 4000
3000 3000
2000 2000
1000 1000
6000 6000
Speed (RPM)
Speed (RPM)
5000 5000
4000 4000
115 VAC
3000 3000
2000 2000
1000 1000
6000 6000
Speed (RPM)
Speed (RPM)
5000 5000
4000 4000
3000 115 VAC 3000
2000 2000
1000 1000
0 6 12 18 24 30 36 0 10 20 30 40 50 60
Torque (in-lb) Torque (in-lb)
3000 6000
Speed (RPM)
Speed (RPM)
2500 5000
2000 4000
1500 3000
1000 2000
500 1000
0 20 40 60 80 100 120 0 10 20 30 40 50 60
Torque (in-lb) Torque (in-lb)
3000 6000
Speed (RPM)
Speed (RPM)
2500 5000
2000 4000
1500 3000
1000 2000
500 1000
6000 3000
Speed (RPM)
2500
Speed (RPM)
5000
4000 2000
3000 1500
2000 1000
1000 500
0 50 100 150 200 250 300 0 70 140 210 280 350 420
Torque (in-lb) Torque (in-lb)
Note: Continuous torque available for each motor model depends on the ambient temperature.
These curves depict the maximum continuous torque available for each model up to the
following ambient temperatures:
• SLM003, SLM100, SDM100, SDM250 & SGM450 = 40 oC
• SLM005, SLM250, SLM500 = 20oC
• SLM350 = 25 oC
• SDM500 = 35oC
Higher ambient temperatures require motor derating as shown in the temperature derating
curves in Section 2.3.
0 10 20 30 40 50 0 10 20 30 40 50
Motor Ambient Temperature ( oC) Motor Ambient Temperature ( oC)
0 10 20 30 40 50 0 10 20 30 40 50
Motor Ambient Temperature ( oC) Motor Ambient Temperature ( oC)
100 100
Motor Rated Torque Output (%)
90 70
0 10 20 30 40 50 0 10 20 30 40 50
Motor Ambient Temperature ( oC ) Motor Ambient Temperature ( oC )
SLM350
Motor Rated Torque Output (%)
100
70
0 10 20 30 40 50
Motor Ambient Temperature ( oC)
Caution
The brake should only be used to hold motor position once the axis is
stopped. Using the brake to stop a moving load may result in damage or
premature failure of the brake mechanism. Use an external mechanical
brake to stop moving loads during an emergency stop or loss of power.
The brakes require a finite time to engage and release the load as shown in the brake specifications
in Table 2-7. These times must be considered in the brake sequencing logic when employing brake
motors on vertical axes to prevent the load from falling. The amplifier must remain enabled until
the brake is fully engaged or the load will not be adequately restrained.
The brake power supply is the user’s responsibility and must comply with the brake specifications
shown in Tables 2-7 to 2-10. GE Fanuc offers a 24VDC, 5-amp DIN-rail mounted power supply
(IC690PWR024) that may be appropriate as a brake supply on multi-axis systems. A panel
mounting conversion kit is also available (IC690PAC001). Brake power cables are available from
GE Fanuc in several pre-finished lengths as shown in Table 3-9.
GFK-1866A 3-1
3
Caution
Since a misuse of the amplifier may lead to improper operation, or may
damage the amplifier, carefully read the following cautions and warnings:
• Be sure to ground the amplifier properly using the ground terminals on the front of the
amplifier. Proper grounding includes conforming to applicable national and local electrical
codes.
• Do not apply higher than rated voltage to the power input terminals (L1, L2 and L3)
3-2 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
• Do not apply the main input power to terminals other than terminals L1, L2 and L3 or
damage will occur. Refer to Section 3.6 for wiring information.
• The power supply uses a capacitor filter. When you turn on power, a high charging current
flows and you may see a large voltage drop. We recommend that you install line reactors to
limit the charging current if this presents problems with other equipment on the machine.
• Do not perform a dielectric strength test or megger test on the amplifier or damage may
occur. (When you perform a dielectric strength test or megger test to an external circuit,
please disconnect all terminals to the amplifier so that no test voltage is applied to the
amplifier.)
• Do not operate the amplifier under overload conditions (such as continuous overcurrent
operation).
• If you use a ground fault breaker, use one rated for "Inverter," to withstand high frequency
leakage current.
• Use the motor and amplifiers only in the designated combinations (Table 1-1).
• When transporting, use caution to prevent damage to the S2K components. Do not grasp the
cables when carrying the amplifier.
Figure 3-1. SSD104, SSD107 and SSD407 S2K Series Amplifier Dimensions and Weight
3-4 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
SSD216
Code in
Feature Units SSD228
Diagram
SSD420
N/A Weight lb (kg) 14 (6.4)
A Depth inch (mm) 10.15 (258)
B Total Width inch (mm) 5.25 (133.4)
C Height inch (mm) 12.20 (309.9)
Position Feedback Connector Depth
D (includes mating connector supplied inch (mm) 1.26 (32)
on GE Fanuc cable)
E User I/O Connector Depth inch (mm) 0.75 (19)
Figure 3-2. SSD216, SSD228 and SSD420 S2K Series Amplifier Dimensions and Weight
Lead Lengths
C1 L1
AH
L2
BB 4 x H dia on
Bolt circle AJ
2
C
AJ
U AK
G
A
L
Model Units A AH AJ AK BB G
SLM003 inches 2.27 ± 0.024 0.7874 ± 0.028 2.625 ± 0.024 1.502+−00.001 0.118 ± 0.008 0.236 ± 0.012
(30 Watts) mm 57.658 ± 0.6 20 ± 0.7 66.675 ± 0.6 38.1508+−00.025 3 ± 0.2 6 ± 0.3
SLM005 inches 2.27 ± 0.024 0.7874 ± 0.028 2.625 ± 0.024 1.502+−00.001 0.118 ± 0.008 0.236 ± 0.012
(50 Watts) mm 57.658 ± 0.6 20 ± 0.7 66.675 ± 0.6 38.1508+−00.025 3 ± 0.2 6 ± 0.3
SLM010 inches 2.27 ± 0.024 0.7874 ± 0.028 2.625 ± 0.024 1.502+−00.001 0.118 ± 0.008 0.236 ± 0.012
(100 Watts) mm 57.658 ± 0.6 20 ± 0.7 66.675 ± 0.6 38.1508+−00.025 3 ± 0.2 6 ± 0.3
L L1
L2 (With or
Model Units H U L (With L1 (With
Without Brake)
Brake) Brake)
SLM003 inches 0.1968 ± 0.010 0.25+−00.0004 2.559 3.819 1.772 3.031 0.709
(30 Watts) mm 5 ± 0.25 6.35+−00.009 65 97 45 77 18
SLM005 inches 0.1968 ± 0.010 0.25+−00.0004 2.874 4.134 2.087 3.346 1.024
(50 Watts) mm 5 ± 0.25 6.35+−00.009 73 105 53 85 26
SLM010 inches 0.1968 ± 0.010 0.25+−00.0004 4.055 5.315 3.268 4.528 2.205
(100 Watts) mm 5 ± 0.25 6.35+−00.009 103 135 83 115 56
3-6 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
L1
C1
AH
L2
4 x H dia on
BB Bolt circle AJ
2
C
AJ
XD S
R
U AK R
L A
Model Units A AH AJ AK BB G H
0.2165 ± 0.010
inch 3.42 ± 0.024 1.181 ± 0.028 3.875 ± 0.024 2.877+−00.0012 0.118 ± 0.008 0.315 ± 0.012
SLM020
(200 Watt)
mm 86.868 ± 0.6 30 ± 0.7 98.425 ± 0.6 73.0758+−00.030 3 ± 0.2 8 ± 0.3 5.5 ± 0.25
L2 (With or Without
Model Units C1 C2 L1 L1 (With Brake)
Brake)
SLM020 inch 8.662 7.874 2.854 4.154 1.535
(200 Watt) mm 220 200 72.5 105.5 39
L
Model Units U L R S XD
(With Brake)
L1
C1
AH
L2
4 x H dia on
BB Bolt circle AJ
2
C
AJ
XD S
R
U AK R
L A
Model Units A AH AJ AK BB G H
inch 3.42 ± 0.024 1.181 ± 0.028 3.875 ± 0.024 2.877+−00.0012 0.118 ± 0.008 0.315 ± 0.012 0.2165 ± 0.010
SLM040
(400 Watt)
mm 86.868 ± 0.6 30 ± 0.7 98.425 ± 0.6 73.0758+−00.030 3 ± 0.2 8 ± 0.3 5.5 ± 0.25
L2 (With or Without
Model Units C1 C2 L1 L1 (With Brake)
Brake)
SLM040 inch 8.662 7.874 4.016 5.315 2.697
(400 Watt) mm 220 200 102 135 68.5
L (Without L
Model Units U R S XD
Brake) (With Brake)
3-8 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
L1
C1
AH
L2
4 x H dia on
BB Bolt circle AJ
2
C
AJ
XD S
R
U AK R
L A
Model Units A AH AJ AK BB G H
inch 3.42 ± 0.024 1.181 ± 0.028 3.875 ± 0.024 2.877+−00.0012 0.118 ± 0.008 0.315 ± 0.012 0.2165 ± 0.010
SLM075
(750 Watt)
mm 86.868 ± 0.6 30 ± 0.7 98.425 ± 0.6 73.0758+−00.030 3 ± 0.2 8 ± 0.3 5.5 ± 0.25
L2 (With or Without
Model Units C1 C2 L1 L1 (With Brake)
Brake)
SLM075 inch 8.662 7.874 4.764 6.142 3.346
(750 Watt) mm 220 200 121 156 85
L (Without L
Model Units U R S XD
Brake) (With Brake)
L1
L2
AH
BB 4 x H dia on
Bolt Circle AJ
C2 C1
AJ
S
XD
U AK R
T
AL
G
L
A
Model Units A AH AJ AK AL BB G
Figure 3-7. Dimensions for 1000 Watt and 2500 W S-Series Servo Motors
3-10 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
L1
L2
AH
BB 4 x H dia on
Bolt Circle AJ
C2 C1
AJ
S
XD
U AK R
T
AL
G
L
A
Model Units A AH AJ AK AL BB G
42 +−00.016 8
SGM450 mm 13.5 289 337.5 37 +−00.2 12 +−00.043 90
Figure 3-8. Dimensions for 4500 Watt and 5000 W S-Series Servo Motors
L Max
Motor mm Inches
3T11 125 4.921
3T12 150 5.906
3T13 175 6.890
Figure 3-9. Dimensions for MTR-3T1x-Series Servo Motors
3-12 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
L Max
Motor
mm Inches
3T21 143 5.6
3T22 168 6.6
3T23 193 7.6
3T24 218 8.6
Figure 3-10. Dimensions for MTR-3T2x-Series Servo Motors
L Max
Motor
mm Inches
3T42 185 7.3
3T43 210 8.3
3T44 235 9.2
3T45 260 10.2
L Max
Motor
mm Inches
3T54 230 9.0
3T55 255 10.0
3T57 305 12.0
L Max
Motor
mm Inches
3T66 320 12.6
3T67 345 13.6
3T69 395 15.6
3-14 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
3-16 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
L1 Max L2
Motor
mm Inches mm Inches
3S22 187.9 7.4 149.9 5.9
3S23 212.9 8.38 176.0 6.93
L1 Max L2
Motor Brake
mm Inches mm Inches
No 180.1 7.09 142.7 5.62
3S32
Yes 236.5 9.31 142.7 5.62
No 205.5 8.09 168.1 6.62
3S33
Yes 261.9 10.31 168.1 6.62
No 230.9 9.09 193.5 7.62
3S34
Yes 287.3 11.31 193.5 7.62
No 256.3 10.09 218.9 8.62
3S35
Yes 312.7 12.31 218.9 8.62
3-18 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
Optional
Brake Connector
Location
Optional
NEMA 56C Flange
3.95
3-20 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
3.95
3.6 Wiring
Caution
Use vinyl-sheathed or equivalent wire rated at 250 VAC or greater for 230
VAC S2K models or 600VAC or greater for 460 VAC S2K models . Wire size
should be determined considering ampacity and codes.
Warning
When using this equipment in a Hazardous (classified) location:
Explosion hazard--do not disconnect equipment unless power has been switched
off or the area is known to be non-hazardous.
3-22 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
Table 3-1. Power Terminal Connections and Wire Sizes for SSD104 4.3 A Amplifier
Terminal Wire Size
Description Connect to…
Symbol AWG
Ground Motor Ground 18-14
T Motor Output Phase T Motor Phase T 18-14
S Motor Output Phase S Motor Phase S 18-14
R Motor Output Phase R Motor Phase R 18-14
Ground Power System Ground 18-14
Drive input power 90 - 250 VAC 18-14
L3
(do not connect for 1 phase input)
L2 Drive Input Power 90 - 250 VAC 18-14
L1 Drive Input Power 90 - 250 VAC 18-14
Table 3-2. Power Terminal Connections and Wire Sizes for SSD107 7.2 A Amplifier
Terminal Wire Size
Description Connect to…
Symbol AWG1
Ground Motor Ground 18-14
T Motor Output Phase T Motor Phase T 18-14
S Motor Output Phase S Motor Phase S 18-14
R Motor Output Phase R Motor Phase R 18-14
Ground Power System Ground 18-14
2L2
Logic Input Power 90 - 250 VAC 18-14
2L1
Drive Input Power
1L3 90 - 250 VAC 18-14
(do not connect for 1 phase input)
1L2
Drive Input Power 90 - 250 VAC 18-14
1L1
EXT External Regen Resistor2 INT 18-14
INT Internal Regen Resistor2 EXT 18-14
DC+ High Voltage DC Bus Ext. Regen Resistor 18-14
1) AWG size for stranded copper wire. Minimum wire size required will depend on motor and load.
Consult National Electrical Code Handbook ampacities tables for proper wire size.
2) The S2K amplifiers dissipate regenerated energy in an internal regeneration resistor. If the application produces more
regenerated power than the rating of the internal resistor, the amplifier will report an EC fault code (excessive clamp
dissipation). Contact GE Fanuc to determine if an external clamp resistor is required.
Table 3-3. Power Terminal Connections and Wire Sizes for SSD216 16A & SSD228 28A Amplifier
Terminal Wire Size
Description Connect to…
Symbol AWG1
R Motor Output Phase R Motor Phase R 16-10
S Motor Output Phase S Motor Phase S 16-10
T Motor Output Phase T Motor Phase T 16-10
Ground Motor Ground Terminal 16-10
DC+ High Voltage DC bus External Regen Resistor 16-10
INT Internal Regen Resistor2 EXT 16-10
EXT External Regen Resistor2 INT 16-10
DC- High Voltage DC bus No Connection 16-10
1L1
1L2 Drive Input Power 180 - 250 VAC 16-10
1L3
Ground Power System Ground 16-10
2L1
Logic Input Power 180 - 250 VAC 18-14
2L2
1) AWG size for stranded copper wire. Minimum wire size required will depend on motor and load.
Consult National Electrical Code Handbook ampacities tables for proper wire size.
2) The S2K amplifiers dissipate regenerated energy in an internal regeneration resistor. If the application produces more
regenerated power than the rating of the internal resistor, the amplifier will report an EC fault code (excessive clamp
dissipation). Contact GE Fanuc to determine if an external clamp resistor is required.
Table 3-4. Power Terminal Connections and Wire Sizes for SSD407 7.2 A 460 VAC Amplifier
Terminal Description Connect to Wire Size
Symbol AWG1
Ground Motor ground terminal 16-10
T Output phase T Motor phase T 16-10
S Output phase S Motor phase S 16-10
R Output phase R Motor phase R 16-10
DC+ High voltage motor power bus External clamp resistor 16-10
INT Internal clamp resistor EXT 16-10
EXT External clamp resistor INT 16-10
1L1
1L2 Drive input power 324 – 528 VAC 16-10
1L3
Ground Power system ground 16-10
COM
Logic input power 18 – 30 VDC 18-14
+24V
3-24 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
Table 3-5. Power Terminal Connections and Wire Sizes for SSD420 20A Amplifier
Terminal Description Connect to Wire Size
Symbol AWG1
R Output phase R Motor phase R 16-10
S Output phase S Motor phase S 16-10
T Output phase T Motor phase T 16-10
Ground Motor ground terminal 16-10
DC+ High voltage motor power bus External clamp resistor 16-10
INT Internal clamp resistor EXT 16-10
EXT External clamp resistor INT 16-10
DC- High voltage motor power bus No connection
1L1 i
1L2 Drive input power 324 – 528 VAC 16-10
1L3
Ground Power system ground 16-10
COM
Logic input power 18 – 30 VDC 18-14
+24V
1) AWG size for stranded copper wire. Minimum wire size required will depend on motor and load.
Consult National Electrical Code Handbook ampacities tables for proper wire size.
2) The S2K amplifiers dissipate regenerated energy in an internal regeneration resistor. If the application produces more
regenerated power than the rating of the internal resistor, the amplifier will report an EC fault code (excessive clamp
dissipation). Contact GE Fanuc to determine if an external clamp resistor is required.
A B
M C
1 2 3 4 5 L T N P D
6 7 8 9 10
K S R E
11 12 13 14 15
J
F
H G
Note
The S2K amplifiers with encoder feedback include a proprietary serial
encoder interface (RX, TX) that determines the motor rotor position to
properly commutate the motor currents. Only GE Fanuc S-Series servo
motors can be used with these S2K amplifiers.
3.6.4 S-Series Servo Motor Power and Brake Wiring and Grounding
Motor power and brake cables as shown in Table 3-9 are available from GE Fanuc for the S2K Series
Servo Amplifiers. Cables for S-Series motors with brakes include two 18 AWG leads for connection
of a 24Vdc brake power supply (see Table 2.1 for brake power requirements) and brake control logic.
The brakes are of a fail-safe design, engaged by internal springs and disengaged by the application of
24 Vdc power.
The motor cable must have a motor ground wire that connects one of the frame ground terminals on
the amplifier to the frame ground pin on the motor connector. Tables 3-1 to 3-5 show the proper wire
size and Figure 3-22 shows the motor connector pin-out for each S-Series motor model. For noise
sensitive applications a shielded motor power cable may be necessary. When used, the power cable
shield should connect to the frame ground stud on the bottom of the amplifier and to the connector at
the motor end. GE Fanuc’s standard motor power cables do not include a shield.
On the 30 – 750 Watt S-series motors, the power connectors shown below are wired to the motors
with short leads and include a separate connector (and require a separate brake cable) when the
optional holding brake is included. On the 1.0 – 5.0 kW motors, the MS-style connectors shown are
mounted directly on the motor’s frame and the brake connections are included in the same connector
and cable.
3-26 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
G H A
F I B D A
E D C
1 2 1
C B
3 4 2
A B C
Wiring Side
D E F D A
G H I
1 2 C B
3 4
Front
Side With Brake Without Brake
3.6.5 MTR-Series Servo Motor Power and Brake Wiring and Grounding
Motor power and brake cables as shown in Table 3-9 are available from GE Fanuc for the S2K Series
Servo Amplifiers. MTR-3T series motors with brakes include two additional leads for connection of a
24Vdc brake power supply (see Tables 2-8 through 2-10 for brake power requirements) and brake
control logic into the motor power cable. MTR-3N and MTR-3S series motors with brakes use a
physically separate brake power cable and connector. The brakes are of a fail-safe design, engaged by
internal springs and disengaged by the application of 24 Vdc power.
The motor cable must have a motor ground wire that connects one of the frame ground terminals on
the amplifier to the frame ground pin on the motor connector. Tables 3-1 to 3-5 show the proper wire
size and Figures 3-23 and 3-24 show the motor connector pin-out for each motor model. For noise
sensitive applications a shielded motor power cable may be necessary. When used, the power cable
shield should connect to the frame ground stud on the bottom of the amplifier and to the connector at
the motor end. GE Fanuc’s standard motor power cables do not include a shield.
Figure 3-25. MTR-3N and MTR-3S Series Optional Brake Power Connections
3-28 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
A B
M C
L T N P D
K S R E
J
F
H G
3-30 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
3-32 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
25 K
AIx +
OP-AMP
25 K
AIx -
25 K
Analog
Common
20 K
.0022
20 K +12V
AO
100
-12V Analog
Common
IN_A -
3-34 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
OP-AMP
Tie
+ 2.5 V 1K
OUT_A -
Enable Input
The Enable discrete input allows the host controller to enable or disable the power output stage of the
amplifier. The Enable input must be active to run the servo motor. The Enable input is also use to
reset faults on the amplifier. When a fault occurs the Enable input must be cycled low to high to reset
the faults. The current state of the Enable input can be queried using the Fault Code (FC) register in
the terminal window. The Enable input should be connected as shown in the connection diagrams in
Section 3.6.9. The internal schematic for the enable input circuit is shown below.
OPTOCOUPLER
2000
ENABLE +
499
OK Output
The OK discrete output allows the S2K to communicate status information to the host controller. The
OK output is active when the amplifier is enabled and no faults are present. The S2K LED status
register will display OK when this output is active. The internal schematic for the OK output circuit is
shown below.
SOLID STATE
RELAY OK +
3-36 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
Figure 3-27. Connection Diagram for the 4.3 A 115/230 VAC Serial Encoder-Based Servo Amplifier (SSD104)
Figure 3-28. Connection Diagram for the 4.3 A 115/230 VAC Resolver-Based Servo Amplifier (SSD104R)
3-38 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
Figure 3-29. Connection Diagram for the 7.2A 115/230 VAC Serial Encoder-Based Servo Amplifier (SSD107)
Figure 3-30. Connection Diagram for the 7.2A 115/230 VAC Resolver-Based Servo Amplifier (SSD107R)
3-40 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
Figure 3-31. Connection Diagram for the 16 A & 28 A 230 VAC Serial Encoder-Based Servo Amplifiers (SSD216 & SSD228)
Figure 3-32. Connection Diagram for the 16 A & 28 A 230 VAC Resolver-Based Servo Amplifiers (SSD216R & SSD228R)
3-42 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
Figure 3-33. Connection Diagram for the 7.2A 460 VAC Resolver-Based Servo Amplifier (SSD407R)
Figure 3-34. Connection Diagram for the 20A 460 VAC Resolver-Based Servo Amplifier (SSD420R)
3-44 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
IC800SKCI010 Interface Cable, S2K Auxiliary I/O to 44A726268-001 Terminal Board Assembly, 1 m
IC800SKCI030 Interface Cable, S2K Auxiliary I/O to 44A726268-001 Terminal Board Assembly, 3 m
Aux. I/O Interface
IC800SKCFLY010 Interface Cable, S2K Auxiliary I/O connector to Flying Leads, 1 m
IC800SKCFLY030 Interface Cable, S2K Auxiliary I/O connector to Flying Leads, 3 m
Serial IC800SKCS030 S2K Serial Communication Cable for PC (Motion Developer) Interface, 3 m
S-Series Servo IC800SKCEZxxx Encoder Cable, S2K to 30-750 W S-Series Motor, x xx=050 (5 m) or 100 (10 m)
Motor Encoder IC800SKCEVxxx Encoder Cable, S2K to 1 kW-5 kW S-Series Motor, xxx=050 (5 m) or 100 (10 m)
IC800SKCPZxxx Power Cable, S2K to 30 - 750 W S-Series Motor, xxx=050 (5 m) or 100 (10 m)
IC800SKCPVxxx Power Cable, S2K to 1 kW-2.5 kW S-Series Motor, xxx=050 (5 m) or 100 (10 m)
S-Series Servo
IC800SKCPVLxxx Power Cable, S2K to 4.5 kW-5 kW S-Series Motor, xxx=050 (5 m) or 100 (10 m)
Motor Power
IC800SKCBVxxx* Power/Brake Cable, 1 kW-2.5 kW S-Series Motor with Brake, xxx=050 (5 m) or 100 (10 m)
IC800SKCBVLxxx* Power/Brake Cable, 4.5 kW-5 kW S-Series Motor with Brake, xxx=050 (5 m) or 100 (10 m)
S-Series Servo
Motor Brake IC800SLCBZ0xxx Brake Cable, 30 - 750 W S-Series Motor with Brake, xxx=050 (5 m) or 100 (10 m)
(30-750 W Motors Only)
MTR-Series Motor CBL-3C-RD-xx Resolver Cable, S2K to MTR-3N or MTR-3S Series Servo Motor, xx=10, 20 or 30 (feet)
Resolver CBL-3T-RD-xx Resolver Cable, S2K to MTR-3T Series Servo Motor, xx=10, 20 or 30 (feet)
CBL-34-MP-xx Power Cable, S2K to MTR-3N Servo Motor, xx=10, 20 or 30 (feet)
CBL-34-MP-xx Power Cable, S2K to MTR-3S2x, 3S3x & MTR-3S43-H Servo Motor, xx=10, 20 or 30 (feet)
CBL-38-MP-xx Power Cable, S2K to MTR-3S8x Servo Motor, xx=10, 20 or 30 (feet)
MTR-Series Motor Power Cable, S2K to MTR-3S43-G, 3S45, 3S46 & 3S6x-G Servo Motor, xx=10, 20 or 30
CBL-3C-MP-xx
Power (f ) Cable, S2K to MTR-3S6x-H Servo Motor, xx=10, 20 or 30 (feet)
CBL-3P-MP-xx Power
CBL-3T-MP-xx Power Cable, S2K to MTR-3T4x, 3T5x & 3T6x Servo Motor, xx=10, 20 or 30 (feet)
CBL-T7-MP-xx Power Cable, S2K to MTR-3T1x & 3T2x Servo Motor, xx=10, 20 or 30 (feet)
Power/Brake Cable, S2K to MTR-3T4x, 3T5x & 3T6x Servo Motor with Brake, xx=10, 20
CBL-3T-MB-xx
or 30 (feet)
MTR-Series Motor Power/Brake Cable, S2K to MTR-3T1x & 3T2x Series Servo Motor with Brake, xx=10, 20
Brake CBL-T7-MB-xx
or 30 (feet)
CBL-30-BT-xx Brake Cable, S2K to MTR-3N & 3S Series Servo Motor with Brake, xx=10, 20 or 30 (feet)
*The 1kW-5kW S-Series servo motors incorporate the brake power and motor power into a single cable. When a brake is required this cable
should be used in place of the motor power cable IC800SKCPVxxx or IC800SKCPVLxxx. The 30–750W S-Series servo motors require a
separate cable (IC800SLCBZxxx) for motor brake power when the brake option is required.
3-46 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
120 VAC
L N
+ -
CR1
Low Power Brake
Control Contact
(Close to release brake)
D1
D2
Caution
Under normal operation the regenerative discharge resistor may become very
hot. To prevent being burned, never touch the resistor. Mount the resistor well
away from heat sensitive components or wiring to prevent damage. Also, the
terminals of this resistor are at a high voltage potential. Either insulate the
connections or provide adequate shielding to eliminate this shock hazard.
Table 3-11. Regenerative Discharge Resistor Kits
3-48 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
The resistor values included with the kits are average values for a variety of conditions. Smaller
capacity (wattage) resistors may work in some applications and larger resistors may be required in
others. The lower the resistance value, the faster the regenerative energy can be dissipated.
Applications with large inertial loads, high speeds, and high deceleration rates regenerate more
energy and may require a resistor with a lower resistance and/or larger capacity (wattage). As an
alternative, when the capacity or resistance of the standard external regenerative resistor is
insufficient for the application, reducing load inertia, maximum speed, deceleration rate, increasing
vertical axis counterbalance or some combination of these measures can decrease the regenerative
energy. See Section 3.8.1 for details on selecting the proper resistor based on application
requirements.
The wiring between the amplifier and the regenerative resistor should be kept as short as possible
(less than 20 inches or 50cm) to prevent possible damage to the switching transistor from voltage
transients due to cable inductance. The regenerative resistor may become very hot during normal
operation. Therefore, route all wiring away from the resistor so that the wiring does not touch the
resistor and has a minimum clearance of 3 inches (76mm).
Connect one terminal of the resistor to the amplifier’s “EXT” power terminal and the other resistor
terminal to the “DC+” amplifier power terminal. See Figures 3-30 and 3-34.
Note: If you are not using an external resistor, a wire jumper must be connected
between the power terminals “INT” and “EXT” as shown in the “Clamp
Connections-External” section of Figures 3-30 and 3-34. If this jumper is
not installed, the internal resistor is disabled and the amplifier may exhibit
symptoms associated with excessive regeneration. This note does not
apply to the SSD104 model amplifier.
When mounting the resistor, tighten the lock nut sufficiently to compress the lock washer. Although
the lock nut should be tightened securely, avoid over-tightening so as not to strip the bolt threads.
MICA WASHER
(2 REQ.)
Connect tabs
to amplifier
terminals CENTERING WASHER
LOCK
(2 REQ.)
WASHER
THREADED
BOLT
LL
TERMINAL DETAIL
CC
IC800SLR002 10.5 1.312 2.13 1.5 11.562 .875 .281 X.562 .625 .375 .020 .173
IC800SLR003 8.5 1.125 1.75 1.25 9.562 .750 .218 X.437 .625 .375 .020 .173
IC800SLR004 15 2.50 4.25 3.0 17.0 1.25 .281 X.562 .625 .500 .025 .188
3-50 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
Ef = (5.91 × 10 )× t
−3
a
× (ω i − ω f ) × Tf Joules
Where:
ωi Initial motor speed at the beginning of deceleration (RPM)
ωf Final motor speed at the end of deceleration (RPM)
ta Deceleration time (Sec)
Tf Axis friction torque (as seen by the motor) (in-lb)
This step must be calculated for each deceleration in the motion profile and then the values summed
to arrive at a total regenerated energy for this step. For multi-speed (compound) moves the starting
and ending velocity must be used for ωI and ωf for each deceleration segment.
Ev = (1.182 × 10 )×T−2
h
×ω m × t d Joules
where:
Th Upward supporting torque applied by the motor during (in-lb)
downward rapid traverse to hold the load against gravity
td Time of downward motion (Sec)
If the Average Regenerative Power exceeds the Maximum Continuous Power indicated in Table 3-12
for the amplifier you are using, an external regenerative discharge resistor is required:
If the calculated value exceeds the storage capability of the amplifier, then an external regenerative
resistor is required (see Step 5).
3-52 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
The peak power determines the maximum rate at which the regenerated energy must be dissipated to
prevent overvoltage faults on the amplifier. The peak power must be calculated for each deceleration
period of the profile by dividing the regenerated energy for that period by the time over which the
energy is released.
This value must be lower than the Peak Power rating for the resistor selected (see Table 3-11). If a
non-standard resistor is substituted, its peak power can be calculated as follows:
Assume a vertical axis using an SLM100 motor (Jm = 0.001491 lb-in-s2) with a load inertia (JL) of
0.0139 lb-in-s2. The SLM100 motor uses an SSD107 amplifier. The friction torque in the axis (Tf) is
10 in-lb and the torque that is required to support the load against gravity (Th) is 15 in-lb. The axis
requires the following compound velocity profile:
Up 2000 RPM
1000 RPM
Total Cycle Time = 2 seconds
t1
t3
0
t2
t1 = 0.2 seconds
t2 = 0.2 seconds
t3 = 1.0 seconds
Down 2000 RPM
Since the example machine cycle involves a number of periods where regeneration occurs, the
determination of the regenerated energy is more complicated. Regeneration occurs for each
deceleration period when the axis is moving in the upward direction (against gravity) and during the
period when the axis is moving in the downward direction. These areas are shaded in the profile
shown above. The regeneration for each of these periods must be calculated as follows:
3-54 S2K Series Brushless Servo Amplifier User's Manual – September 2002 GFK-1866A
Installation 3
Enable
S
S2K Motor
T
DB Contactor
Resistor
Resistor
Resistor
Figure 3-37. Typical External Dynamic Brake Circuit
This chapter documents the process for completing a basic setup for an S2K amplifier for the
various modes of operation. Various software parameters can be configured which allow you to
configure the amplifier for your application requirements. Chapter 5 includes a detailed reference
for the software commands and registers supported by the S2K Series amplifiers.
This chapter assumes that the amplifier power, motor power, and motor encoder have been wired
correctly according to the guideline in Chapter 3, and that power is applied. The motor should not
be connected to a load until the basic setup has been completed.
Windows is a registered trademark of Microsoft, Incorporated
4-1
4
From the File menu, select New Connection and the Connection Description screen will be
displayed.
Select an icon from the scrolled list and enter a name for the connection (the example uses S2K
Amplifier). Click the OK button.
The Phone Number screen should be displayed as shown below. On this screen, in the Connect
Using list box, you must select the serial port associated with the physical port where you
connected your serial cable to the amplifier. Our example uses the Direct to Com 1 option. Click
the OK button.
The COM1 Properties box will appear next. Configure the settings for the COM port as shown in
the example below and then click OK.
You will be returned to the main Hyper Terminal screen. You must now configure the properties of
the connection by selecting Properties from the File menu as shown below:
The Properties dialog box will be displayed as shown below. In the emulation list box, select
VT100 and then click the OK button.
You are now in the main terminal window and should be properly connected to the amplifier. Press
the Enter key on your keyboard several times and the “INVALID COMMAND” prompt should be
displayed on the screen as shown below.
If this prompt does not appear, then you are not communicating with the amplifier. Make sure your
serial cable is properly connected, the Hyper Terminal connection properties are correct, and AC
power has been applied to the amplifier.
The INVALID COMMAND message is displayed because the S2K amplifier is expecting a node
address as a prefix to the terminal command. Any digit between 0 and 9 will work and no space is
required as a separator from the command text. In the terminal, type 1 and then press the
<ENTER> key, and the “GE Fanuc S2K Series” prompt should be displayed.
Next, try to query the contents of the Fault Code register (FC) using the query command (Q or ?).
In the terminal window, type 1FC? and then press the <Enter> key. The Lost Enable and Power
Failure messages should be displayed as shown below. This is normal since the Enable digital input
is not yet connected and the power failure fault is present each time the amplifier is energized.
Congratulations, you have successfully established communications with the amplifier and are
ready to move on to Configuring the Operating Mode.
Software Introduction
Motion Developer software runs inside the GE Fanuc CIMPLICITY Machine Edition environment.
Those using additional Machine Edition applications will appreciate the benefits and convenience
of using this one common programming environment. For the S2K amplifier only models, the
terminal window is the only feature required. Therefore, many of the optional windows are not
used and can be turned off as described in this section.
Navigator
Toolchest
Inspector
Editor
Workspace
You will probably want to turn most of the individual windows off since they are not used for the
S2K amplifier-only models. Keep only the Navigator and Inspector windows open.
To close the windows you do not want to display simply click the appropriate toolbar buttons or
use the keyboard hot keys as shown below:
2 4 6 8
1 3 5 7
To access the Motion Developer terminal window, you must first create a new project as follows.
My Computer
Navigator Window
Manager Tab
Enter the name of your project, then click the OK button. The “Motion Developer Wizards”
window will appear, shown in the next figure. Do not click any of the options on this window.
They apply only to the S2K controller models.
Next you must select your Drive Series, Drive Model and Motor from the pop-up dialog.
At this point the Motion Toolbar should be active and we can activate the terminal window or run
the Motion Expert wizard.
Clicking the Terminal Window Button will cause the Terminal Window page to be displayed and
the terminal communications settings will appear in the Inspector window as shown below.
The default communication settings should be correct for the S2K amplifier and not require any
changes. Make sure that the Port assignment agrees with the physical COM port to which you
connected your serial cable. If you need to change the Port setting you must do the following:
In the Navigator, right-click the Target1 entry and choose Properties from the shortcut
menu.
The Inspector window should now display the settings shown in the example below and
you can select a new Com Port by clicking on the entry to display the drop-down list box.
At this point, assuming your serial cable connections and port assignment are correct, you are ready
to communicate with the amplifier.
Place the mouse cursor anywhere in the terminal window and click once to place the Windows
focus on the terminal, and then press the Enter key on your keyboard several times. The “*GE
Fanuc S2K Series” prompt should eventually be displayed as shown below.
Next, try to query the contents of the Fault Code register (FC) using the query command (Q or ?).
In the terminal window, type FC? and then the <Enter> key. The Lost Enable and Power Failure
messages should be displayed as shown below. This is normal since the Enable digital input is not
yet connected and the power failure fault is present each time the amplifier is energized.
Congratulations, you have successfully established communications with the amplifier and are
ready to move on to Configuring the Operating Mode.
Velocity control mode In velocity mode, the analog command input (AI1) tells the amplifier
how much velocity to generate as a function of the command input
voltage. This mode requires an external controller to handle position
control with the S2K amplifier.
Position (follower) mode Position mode makes use of the auxiliary encoder input (IN_A and
IN_B) when using a pulse input from an external source such as a
pulse generator card, a quadrature encoder, or a handwheel.
You must first decide which mode is appropriate for your application and then wire the Auxiliary
I/O connections and configure the amplifier for that mode. The Motion Type (MT) parameter is
used to select which of these control modes the amplifier will use. Motion Developer includes a
Motion Expert wizard that will guide you through the various steps required to configure an S2K
amplifier for each of the control modes. The following sections describe the configuration process
for each operating mode.
You can change the mode by typing “MT=” followed by the desired mode keyword.
In torque mode the differential command input is intended to be used as a ± 10Vdc torque
command interface to a host motion. The Analog Input Deadband (AIB1) and Analog Input Offset
(AIO1) parameters are used to configure the deadband and voltage offset for this input if necessary
for your application. See Chapter 5 for detailed descriptions of these parameters.
Usually, it is necessary to scale the analog torque command input based on the application
requirements. In the S2K amplifier the gearing ratio parameters (GRN and GRD) can be used to
scale the command to represent a specific motor torque at a given voltage input. The base scaling
of the torque command input for the default ratio of 1 (GRN/GRD = 1) is as follows:
1 Volt Command = 10% Amplifier Peak Current
The process for rescaling the torque command input is shown in the example below. Keep in mind
that servo amplifiers control motor torque by regulating the current delivered to the motor. When
we refer to torque scaling or limiting we are really scaling or limiting the current output from the
amplifier. The constant of proportionality that relates these two factors is the Torque Constant of
the motor. The motor specifications in Chapter 2 show the nominal value for each motor. The
actual value can vary from this nominal value by as much as ± 10% from one motor to the next. It
is important to understand these limits when trying to precisely control motor torque. Applications
that require greater precision must use an in-line torque transducer and separate torque regulator.
There is an OK digital output available on the S2K amplifier that can be wired back to the host
controller to indicate amplifier status. See Chapter 3 for more details on the Auxiliary I/O
connections.
100% / 5Volts
= =2
10% / Volt
The differential command input is intended to be used as a ± 10Vdc velocity command interface to
a host motion controller. The Analog Input Deadband (AIB1) and Analog Input Offset (AIO1)
parameters are used to configure the deadband and voltage offset for this input if necessary for your
application. See Chapter 5 for detailed descriptions of these parameters.
Usually, it is necessary to scale the analog torque command input based on the application
requirements. In the S2K amplifier the gearing ratio parameters (GRN and GRD) can be used to
scale the command to represent a specific motor velocity at a given voltage input. The base scaling
of the velocity command input for the default ratio of 1 (GRN/GRD = 1) is as follows:
1 Volt Command = 1228.8 Motor RPM
The Motion Developer Motion Expert wizard can be used to configure this scaling or you can set
the parameters manually. The process for rescaling the velocity command input is shown in the
example below.
There is an OK digital output available on the S2K amplifier that can be wired back to the host
controller to indicate amplifier status. See Chapter 3 for more details on the Auxiliary I/O
connections.
300
= = 0.2441406
1228.8
1000
=
4096
Next, you must configure the type of pulse input that will be used to control the amplifier. The
Auxiliary Encoder Type (QTX) parameter is used to select the required pulse command signal type
from the following options:
Q4 (quadrature x4) Sets the input for two pulse waveforms in quadrature with a pulse multiplier
of 4. Use this option for a master encoder interface.(Default)
PD (pulse/direction) Sets the input for a pulse input on channel A and a direction input on
channel B.
CW (CW/CCW) Sets the input for a pulse input on channel A for CW motion and a pulse
input on channel B for CCW motion.
To change the input type enter “QTX=” followed by one of the 2-letter options above and then
press <Enter>.
Next, you must configure the pulse-scaling ratio that determines how far the motor will move for
each input pulse. This ratio is set using the Gearing Numerator (GRN) and Gearing Denominator
(GRD) registers. Together they form the scaling ratio as GRN/GRD and relate the input pulses to
motor pulses as shown in the following formula:
Motor Pulses = Gearing Input Pulses * GRN/GRD
See the example below for more detail on how to determine the proper ratio.
The Gearing Enable register must then be set (GRE=1) to enable the gearing mode and the Gearing
Bound (GRB) register sets a limit, if required, on the maximum velocity (pulses/second) that the
electronic gearing mode can command. There is also a smoothing algorithm included in the S2K
amplifier for electronic gearing applications that are too sensitive. The Gearing Filter Constant
(GRF) parameter configures the level of filtering based on the application requirements. Finally,
the Gearing Input Source Selection (GRI) parameter provides a way to run the motor at a fixed
speed (jog) using an internal pulse generator, which runs at a fixed 2048 pulses/second. This
function may be useful during machine start-up. See Chapter 5 for more detail on using these
parameters.
Make sure your pulse source is properly connected to the Auxiliary I/O connector or Pulse Input
connector (SSD216 and SSD228) on the amplifier as shown in Chapter 3 – Auxiliary I/O Wiring.
MTR-Series Motors:
4096 motor pulses/rev * (motor rev/encoder rev) = (4000 gearing pulses/rev) * GRN/GRD
Solving for the gearing ratio we have:
GRN/GRD = 4096/4000
Therefore, by setting GRN = 4096 and GRD = 4000 the motor will make one revolution for each
revolution of the master encoder.
If instead, we wanted the motor to make ¼ revolution for each encoder revolution, the following
ratio would be required:
S-Series Motors:
10,000 motor pulses/rev * (0.25 motor rev/encoder rev) = (4000 gearing pulses/rev) * GRN/GRD
Again, solving for the gearing ratio we have:
GRN/GRD = (10,000)(0.25)/4000 = 2500/4000
Therefore, by setting GRN = 2500 and GRD = 4000, the motor will make ¼ revolution for each
revolution of the master encoder.
MTR-Series Motors:
4096 motor pulses/rev * (0.25 motor rev/encoder rev) = (4000 gearing pulses/rev) * GRN/GRD
Again, solving for the gearing ratio we have:
GRN/GRD = (4096)(0.25)/4000 = 1024/4000
Therefore, by setting GRN = 1024 and GRD = 4000, the motor will make ¼ revolution for each
revolution of the master encoder.
• When EOT=0 (default) the encoder output buffers the auxiliary encoder input pulse-for-
pulse. If the auxiliary input is a quadrature encoder the output will be quadrature. If the
auxiliary input is CW/CCW pulses, the output will be in this same format.
• When EOT is non-zero the output tracks the motor feedback (up to the full resolution of
2500 or 1024 lines/rev based on feedback type), and the setting of the EOT register
determines the output resolution. The allowed values for this resolution are 500, 625, 1000,
1250, 2000, and 2500 lines/revolution for encoder-based models and 250, 256, 500, 512,
1000, and 1024 lines/revolution for resolver-based models. The quadrature resolution would
be four times greater than the EOT setting.
The marker pulse width is fixed at 1/5000th of the source encoder revolution (auxiliary encoder or
motor feedback based on setting of EOT). This implies that the marker pulse output width will vary
with encoder speed and the smallest width will occur at the highest speed. For example, if the
source device is rotating at 1000 RPM or 16.667 rev/sec then the encoder takes 0.06 seconds per
revolution. Therefore, 1/5000th of this value, or 12 µS, represents the marker pulse width at that
speed. The encoder output is connected on the Auxiliary I/O connector. Addition details can be
found in Chapter 3 – Auxiliary I/O Wiring-Encoder Output.
Note
When both DIR = CCW and GRD is negative the two factors cancel and the
motor will rotate in the clockwise direction for a positive command input.
The Fault Code register (FC) can be queried in the terminal window to examine the current state of
the Direction parameter.
If your application requirements dictate limiting the peak torque of the motor to a value less than its
full rating, you must set the CURP parameter to a lower value. Since the CURP values shown in
Chapter 5 correspond to the full peak torque for each motor, you can use this value as a baseline
from which to scale the required CURP value. For example, if you wanted to limit the SLM040
motor which has a peak torque rating of 33.6 in-lb (from S-Series Motor Specifications Table in
Chapter 2) to a peak torque of 25 in-lb you can calculate the CURP value as follows:
1. Determine ratio of required peak torque to rated peak torque
Ratio = (required peak torque/rated peak torque)
= (25 in-lb/33.6 in-lb)
= 0.744
4.7 Tuning
If you have completed all of the previous sections and have verified your wiring connections you
are now ready to run the motor and set the tuning parameters.
Caution
For the initial test we recommend that you disconnect the motor from any
load in order to ensure that the system is under control before trying to
move the machine.
Warning
When the AUTOTUNE function runs, it will automatically turn the motor
shaft a few turns in each direction. You must insure that the motor shaft can
be turned safely before starting the AUTOTUNE function. Also, you should
have a way to stop the motor quickly, should it be required. All personnel
working in the area should be alerted that the motor will be run, and any
machinery or mechanism connected to the motor should be secured and in
safe running condition. All safety equipment and guarding should be
installed and functional. Failure to heed this warning could result in injury
to personnel and damage to equipment.
The Autotune function can be run from the Autotune wizard in Motion Developer or manually
from the terminal window.
To initiate the Autotune function from the terminal window follow the procedure below:
1. Set the Enable input to false
2. Type AUTOTUNE <Enter> in the terminal window
3. Within 10 seconds activate the Enable input
4. When complete, autotune will disable the drive and display the Lost Enable (LE) fault code on
the LED display. An asterisk will be displayed in the terminal window.
5. If AUTOTUNE fails an error message preceded by a question mark will be displayed in the
terminal window.
• Increase KI until the motor becomes unstable, and then reduce KI to 75 – 85% of this
value.
Command
Analog Input Mnemonic
Syntax: AIp1
The Motion Developer terminal window or other VT100-compliant terminal emulator can be used
to set or query the values of the amplifier registers as well as execute commands such as
AUTOTUNE. To set a register value, simply type the register name followed by the equal sign and
the desired value. Hitting the Enter key will load the new value into amplifier memory (examples:
TLE=1, DIR=CW). To query the current value of a register, type the command followed by a
question mark (examples: FC?, TLC?, GRN?) or the letter Q (FCQ, TLCQ, GRNQ) followed by
pressing the Enter key.
5-1
5
Related Commands: Q
AI Analog Input
Class: Input/Output Register
Syntax: AIp1
Range:
units volts
minimum -10.00
maximum 10.00
Examples:
AI1? (* report value of analog input one from the terminal window)
AI2? (* report value of analog input two from the terminal window)
Related Registers: AO
Use: Defines a range over which the analog input remains constant
at zero volts. Deadband reduces hunting around the zero
command level. When the analog input AI1 is less than or
equal to AIB1, the analog input is set to 0. When the analog
input AI2 is less than or equal to AIB2, the analog input is set
to 0. The deadband resolution is in 10 mV increments.
Examples:
AIB2=1.5 (* set analog input deadband for AI2 equal to 1.5 V)
AIB2? (* report value of analog input deadband from the terminal
window)
Range:
units volts
default 0
minimum -10.00
maximum 10.00
Use: The analog input offset one, AIO1, is used to add a voltage
offset to analog input one, AI1. Analog input offset two,
AIO2, is used to add a voltage offset to analog input two, AI2.
Often the analog command output from a host controller will
generate a small voltage even at zero command. The offset
should be adjusted to counteract this voltage to eliminate drift.
If the host controller is closing a position loop, the controller
should be run open loop, if possible, while making the offset
adjustment. The offset resolution is in 10mV increments.
Examples:
AIO1=2.5 (* set analog input offset for AI1 equal to 2.5 V)
AIO1? (* report offset value of analog input 1 from Terminal window)
Related Registers: AI
AO Analog Output
Syntax: AO
Range:
units volts
default 0
allowed values -10.000 through 10.000
VLA (actual velocity of axis motor)
CMD (instantaneous value of amplifier output current)
FE (following error)
Related Registers: AI
Syntax: AUTOTUNE
Remarks: This command can only be initiated when the amplifier is not
enabled. Servo tuning is dependent on the connected load and
friction. It is often necessary to tune the system initially with
no load connected to verify proper operation of the servo.
Then, once the machine is operational and the normal running
load is connected, it is necessary to repeat the tuning process.
For final tuning on the machine, the motor should be connected
to the load when using this command. When executed, it
causes the axis to move half a revolution in the forward
direction. Be sure that the axis is free to move this far before
executing this command.
Syntax: CLM
Syntax: CMD
Range:
units %
minimum -20,000.0
maximum 20,000.0
Use: The command output is used to control the current to the axis
motor. It is a percentage of the controller continuous current
setting, CURC.
Syntax: CMO
Range:
units degrees
default Encoder Feedback: -90.0
Resolver Feedback: 90.0
minimum -180.0
maximum 180.0
Syntax: CMR
Range:
units degrees
default Encoder Feedback: 1
Resolver Feedback: 3
minimum 1
maximum 16
Use: Limits the current that the drive will continuously supply to the
motor. It is a percentage of the maximum continuous current
rating of the amplifier.
Remarks: The Terminal window can be used to set CURC manually or the
Motion Expert Wizard in Motion Developer will set CURC
automatically when you select your GE Fanuc motor and amplifier
model from the selection lists. The values for a specific motor can
be calculated as follows:
Syntax: CURP
Range:
units %
default 100.0
minimum 1.0
maximum 100.0
Use: The peak current setting limits the peak value of the current
that the drive will supply to the motor. It is a percentage of the
maximum peak current rating of the drive.
Remarks: The terminal window can be used to set CURP manually or the
Motion Expert Wizard in Motion Developer will set CURP
automatically when you select your GE Fanuc motor and
amplifier model from the selection lists. The values for a
specific motor can be calculated as follows:
Syntax: DIR
Range:
default CW
allowed values CW, CCW
Type: Integer
Syntax: EOT
Range:
units lines per revolution
default 0
allowed values Encoder Feedback: 0; 500; 625; 1,000; 1,250; 2,000, 2,500
Resolver Feedback: 0; 250; 256; 500; 512; 1,000; 1024
Use: This register sets the output type for the encoder output. When
this register is set to zero, the encoder output buffers the
auxiliary encoder input pulse for pulse. If the input is a
quadrature encoder the output will be quadrature. If the input
is CW/CCW pulses the output will be the same format. When
the EOT register is non-zero, the encoder output tracks the
motor feedback (encoder or resolver) at the resolution set by
the EOT value. For encoder-based models the lines per
revolution of the motor encoder is 2500 (10,000
counts/revolution) while for the resolver-based models the
maximum resolution is 1024 lines per revolution (4096
counts/revolution). The encoder output can use the maximum
resolution or divide down this resolution based on the allowed
values shown above.
The encoder output marker pulse width is fixed at 1/5000th of a
revolution of the source encoder. This implies that the marker
pulse output width will vary with encoder speed and the
smallest width will occur at the highest speed. For example, if
the source encoder is rotating at 1000 RPM or 16.667 rev/sec
then the encoder takes 0.06 seconds per revolution. Therefore,
1/5000th of this value, or 12 µS, represents the marker pulse
width at that speed.
There is a 40 nanosecond delay between the encoder input and
encoder output signals when EOT=0.
Examples:
EOT=0 (* encoder output uses the auxiliary encoder input)
EOT=1000 (* encoder output provides 1,000 lines per revolution of the
motor)
FC Fault Code
Syntax: FC
Use: The fault code register is used to identify the type of fault that has
occurred.
Remarks: When the FC? command is executed in the terminal window the text
message as shown in the table below will be displayed for any active
fault codes. If more than one fault code is active, then multiple
messages will be displayed. If no fault has occurred, the message
given is Controller functional.
FE Following Error
Class: Axis Register
Syntax: FE
Range:
units pulses
minimum 0 pulses
maximum 16,000 pulses
Syntax: FEB
Range:
units pulses
defaults Encoder Feedback: 1,000 pulses
Resolver Feedback: 400 pulses
minimum 0 pulses
maximum 16,000 pulses
Use: The following error bound is a limit set on the following error.
If this limit is exceeded, the amplifier will fault and display the
FE code on the LED display and in the fault code (FC) register.
Examples:
FEB=0.5 (* set following error bound)
FEB? (* report value of following error bound)
Related Registers: FE
FI Fault Input
Class: System Register
Syntax: FI
Use: The fault input register is used to identify what type of faults are
currently active.
Remarks: When the FI? command is executed from the terminal window, the
fault input register value will be given as an English statement as
shown in the message column in the table below. If no faults are
active, the message given is No fault input is active.
bit message
0 Feedback lost input active (resolver feedback only)
1 Motor power over-voltage input active
2 Motor power clamp input active
3 Reserved
4 Reserved
5 Motor over-temperature input active
6 Drive over-temperature input active
7–15 Reserved
FR Feedback Resolution
Syntax: FR
Range:
units pulses/revolution
default Encoder Feedback: 10,000
Resolver Feedback: 4,096
minimum 500
maximum 1,000,000
Syntax: GRB
Range:
units pulses/sec
default 0 pulses/sec
minimum 0 pulses/sec
maximum 16,000,000 pulses/sec
Syntax: GRD
Range:
default 1
minimum 1
maximum 10,000
300
= = 0.2441406
1228.8
1000
=
4096
100% / 5Volts
= =2
10% / Volt
Syntax: GRE
Range:
default 0
allowed values 0, 1
Use: The gearing enable is used to enable the use of the GRN/GRD
scaling ratio for either electronic gearing (if MT=POS) or for
the analog command input AI1 (if MT=TORQ or VEL). If
GRE is set to 1, electronic gearing or command scaling is
enabled. If GRE is set to 0, it is disabled.
Syntax: GRF
Range:
default 0
minimum 0
maximum 8
Syntax: GRI
Range:
default PSX
allowed values FREQ 2048 pulses/sec
PSX auxiliary encoder input
Use: The gearing input is used when the electronic gearing mode is
enabled (GRE=1) to define the command source for the gearing
input. When set to PSX, the gearing function will follow
pulses input on the auxiliary encoder input. When set to
FREQ, the gearing function will follow a fixed frequency
internal oscillator. This mode is useful for jogging the motor
during start-up and system validation. By changing the gearing
ratio (GRN/GRD) from the terminal window, you can vary the
motor speed.
Syntax: GRN
Range:
default 1
minimum -10,000
maximum 10,000
300
= = 0.2441406
1228.8
1000
=
4096
100% / 5Volts
= =2
10% / Volt
IO General I/O
Class: Input/Output Register
Syntax: IO
Use: The general I/O register is used to identify what inputs and
outputs are active.
Remarks: When the IO? command is executed, the general I/O register
will be given as an English statement that says what inputs or
outputs, if any, are active. If none of the inputs or outputs are
active, the message given is No I/O is active.
bit message
0 Reserved
1 Reserved
2 Reserved
3 Reserved
4 Auxiliary channel A input active
5 Auxiliary channel B input active
6 Reserved
7 Marker input active
8 Reserved
9 Reserved
10 Reserved
11 Enable input active
12 Reserved
13 Reserved
14 Reserved
15 OK output active
Syntax: KD
Range:
default Encoder Feedback: 200
Resolver Feedback: 500
minimum 0
maximum 8,000
316,022,860 1
KD = ×
FR torque
inertia
Syntax: KI
Range:
default 0
minimum 0
maximum 64,000
Use: The integral control gain is used to multiply the time integral of the
following error to control the position of the axis. The equation for
setting KI based on the torque to inertia ratio and the axis feedback
resolution (FR) is:
686,310 torque
KI = ×
FR inertia
where torque is the continuous torque of the motor in in-lbs and inertia
is the system inertia in in-lb-sec2. This value along with the values of
all the other tuning parameters can be set automatically by the
AUTOTUNE command.
Related Registers: FR
KL Motor Inductance
Syntax: KL
Range:
units mH
default 4 mH
minimum 1 mH
maximum 100 mH
Use: The motor inductance is used to tune the digital current controller to
the attached motor. S2K drives are designed to operate with a
minimum line-line inductance of 2 mH. This register should be set to
the motor’s line-line inductance in mH—use the following table for
your KL values:
Syntax: KP
Range:
default 10
minimum 0
maximum 8,000
327,680
KP =
FR
Since FR is 10,000 for the S-Series motor encoders, KP should
be set to 32. For MTR-Series motors FR=4096 and Kp should
be set to 80. This value, along with the values of all the other
tuning gains, can be set automatically by the AUTOTUNE
command.
Syntax: KT
Range:
default Encoder Feedback: 3
Resolver Feedback: 1
minimum 0
maximum 5
280
KT = + 0.5
torque
inertia
Resolver Feedback:
120
KT = + 0.5
torque
inertia
Syntax: MOTORSET
Remarks: This command will execute only when the controller is faulted,
the axis Enable input is true, and no programs or motion blocks
are executing. The motor must not be connected to a load
when you use this command.
MT Motion Type
Syntax: MT
Range:
default TORQ
allowed values VEL (velocity mode)
POS (position mode)
TORQ (torque mode)
Use: The motion type register is used to define the operating mode
of the amplifier. In torque mode the amplifier uses the
command analog input (AI1) to control the amount of torque
the motor will generate. In position mode the amplifier uses
the auxiliary encoder input (IN_A and IN_B) to control the
position of the motor shaft using electronic gearing (following).
In velocity mode the analog command input (AI1) is used to
control the velocity of the motor.
Related Commands: ?
Syntax: QTX
Range:
default Q4
allowed values Q4 (quadrature x4)
PD (pulse/direction)
CW (clockwise/counterclockwise)
Use: This register is used to define the signal type for the auxiliary encoder
input. The possibilities are listed below:
Q4 (quadrature x4) Sets the input for two pulse waveforms in quadrature with a pulse
multiplier of 4.
PD (pulse/direction) Sets the input for a pulse input on channel A and a direction input on
channel B.
CW (CW/CCW) Sets the input for a pulse input on channel A for CW motion and a
pulse input on channel B for CCW motion.
Remarks: With DIR=CW the auxiliary encoder output will cause the motor to
move in the clockwise direction (viewing into the shaft) when:
Syntax: REVISION
Syntax: SRA
Use: The axis status register is used to determine the status of the
axis.
Bit Message
0 Axis moving
1 Gearing enabled
2 Reserved
3 Reserved
4 Reserved
5 Reserved
6 Reserved
7 Axis direction forward
8 Reserved
9 Axis at torque limit
10 Reserved
11 Reserved
12 Reserved
13 AXIS FAULT
14 Reserved
15 Reserved
Remarks: The step input cannot be larger than the following error bound,
FEB or a following error fault will occur when the command is
executed.
Syntax: TLC
Range:
units %
default 100.0
minimum 1.0
maximum 100.0
Syntax: TLE
Range:
default 0
allowed values 0, 1, 2
Use: This command is used to enable the torque limit. If TLE is set
to 1, then the torque limit is enabled and the amplifier current
will be restricted based on the set value for the Torque Limit
Command (TLC). If TLE is set to 0, the torque limit is
disabled. When TLE = 2 the torque limit is set by the absolute
value of analog input 2 (AI2) with a scale factor as follows:
For example, if the drive is faulted due to FE and LE, the unit will alternately display FE, LE… FE,
LE… etc.
Faults are reset using the Enable input. When a fault occurs, the Enable input must make a logic
low to logic high transition to clear the faults.
6-1
6
The contents of any status register can be queried using either the terminal window in the Motion
Developer software or other VT100-compliant terminal emulation program such as Windows
Hyper Terminal. The following tables show the contents of each status register. Also, see Chapter
5 for descriptions of the register commands.
yes
Is the LED no
displaying the O.K.
code?
yes
yes
Does the
Is the terminal no LED display decimal no
communicating with the point flicker when you type
drive? on the terminal?
yes
yes
The S2K is receiving characters,
but is not transmitting them back
Is the Enable input yes
to the terminal
functional?
no
Check if the PC serial port baud rate is
Make sure that the voltages set to 9600. Also, check that the serial
across the inputs are OK. cable is plugged into the Serial Port
connector and that the cable is wired
correctly.
yes
If problems persist, check the serial port
cable by disconnecting the terminal
cable from the display or controller.
no Connect a jumper wire from pin 2
(receive) to pin 3 (transmit) and type on
Make sure the analog output value is the terminal. The characters you type in
set to your satisfaction, if in use. should be echoed back to the terminal.
(next page)
yes
Make sure that the CURC and CURP
no values are set correctly.
Is there torque on
the motor?
If torque limiting is enabled (TLE=1) make
yes
sure torque limit current (TLC) is a
sufficient non-zero value.
yes
Make sure Following Error Bound is a
sufficient non-zero value (FEB ≠ 0)
END
A-1
A
Temperature Conversion
Formulas
°C = 5/9(°F – 32)
°F = (9/5 x °C) + 32
Table
Miscellaneous Equivalents
1 ounce (weight) = 28.35 grams
Fraction-Decimal-Metric Equivalents
Fraction Decimal Metric Fraction Decimal Metric
(Inch) (Inch) (mm) (Inch) (Inch) (mm)
1/64 0.01562 0.397 33/64 0.51562 13.097
1/32 0.03125 0.794 17/32 0.53125 13.494
3/64 0.04688 1.191 35/64 0.54688 13.891
1/16 0.06250 1.588 9/16 0.56250 14.288
5/64 0.07812 1.984 37/64 0.57812 14.684
3/32 0.09375 2.381 19/32 0.59375 15.081
7/64 0.10938 2.778 39/64 0.60938 15.478
1/8 0.12500 3.175 5/8 0.62500 15.875
9/64 0.14062 3.572 41/64 0.64062 16.272
5/32 0.15625 3.969 21/32 0.65625 16.669
11/64 0.17188 4.366 43/64 0.67188 17.066
3/16 0.18750 4.763 11/16 0.68750 17.463
13/64 0.20312 5.159 45/64 0.70312 17.859
7/32 0.21875 5.556 23/32 0.71875 18.256
15/64 0.23438 5.953 47/64 0.73438 18.653
1/4 0.25000 6.350 3/4 0.75000 19.050
17/64 0.26562 6.747 49/64 0.76562 19.447
9/32 0.28125 7.144 25/32 0.78125 19.844
19/64 0.29688 7.541 51/64 0.79688 20.241
5/16 0.31250 7.938 13/16 0.81250 20.638
21/64 0.32812 8.334 53/64 0.82812 21.034
11/32 0.34375 8.731 27/32 0.84375 21.431
23/64 0.35938 9.128 55/64 0.85938 21.828
3/8 0.37500 9.525 7/8 0.87500 22.225
25/64 0.39062 9.922 57/64 0.89062 22.622
13/32 0.40625 10.319 29/32 0.90625 23.019
27/64 0.42188 10.716 59/64 0.92188 23.416
7/16 0.43750 11.113 15/16 0.93750 23.813
29/64 0.45312 11.509 61/64 0.95312 24.209
15/32 0.46875 11.906 31/32 0.96875 24.606
31/64 0.48438 12.303 63/64 0.98438 25.003
1/2 0.50000 12.700 1 1.00000 25.400
1 cubic centimeter = 0.061 023 74 0.000 035 314 67 0.000 001 307 951
1 cubic Inch = 16.387 064 0.016 387 064 0.000 016 387 064
1 cubic foot = 28,316.846 592 28.316 846 592 0.028 316 846 592
1 cubic yard = 764,554.857 984 764.554 857 984 0.764 554 857 984
Hardware
200 MHz Pentium-based workstation
64 MB RAM
200 MB free hard disk space
CD ROM drive or access to one via parallel port or network
800 by 600 resolution, 256 color display and video adapter
Software
Windows ® NT operating system version 4.0 with service pack 4 or later
Windows 98, Windows ME, Windows 2000 & Windows XP operating system
B.1.2 Installation
B-1
B
5. Click Authorize by disk. At this point, you need to go to the source computer that has the
authorized software, and move the authorization to a disk.
6. From the source computer, run the Product Authorization program and click Software.
7. Click Move, and then click OK. Enter the target site code that you wrote down from Step 3 and
click Next. Verify that the site code is correct and click OK.
8. Insert a blank formatted floppy disk into the floppy drive and click Next. The authorization
code will be moved to the disk and a dialog box should appear telling you it was successful.
Click OK.
9. Go back to the computer to which you are moving the authorization and insert the floppy disk.
(The screen that is asking for an authorization disk should be displayed.) Click Next.
10. Click Finish. A screen should appear telling you the move was successful. Click OK. The
authorization has now been moved to the new computer.
Contact Choices
You have several contact choices if you need help with your GE Fanuc products:
• Fax. Send a message via the Technical Support Fax number at (780) 420 - 2049
• Internet. Use the address www.gefanuc.com to reach the GE Fanuc home page, then click
the Support link to reach the main Support page. The Support pages allow you to look up
technical information, download useful files, register software, or send a question to our
support experts.
• Telephone. Call 1-800 GEFANUC (1-800 433-2682)
• e-mail. Address your message to support@gefanuc.com
S2K Motor and Controller Help. When contacting us about an S2K hardware problem, include
the information listed below in your fax or message. If telephoning, call from a telephone near
your installation, if practical, and have the following information available to help us assist you as
quickly as possible:
The S2K model and serial number for controller and motor
The circumstances leading up to the problem occurrence.
a45113
B
A
C-1
C
supply the wiring between the S2K Auxiliary I/O connector and terminal block screw terminals.
Figure C-2 below shows the typical wiring between the APM terminal block and the S2K
amplifier. For complete wiring details for the APM modules please refer to the APM User’s
Manuals, publication GFK-0781 for follower mode, or GFK-0840 for standard mode.
S2K Amplifier
Auxiliary I/O Connector
APM300 Aux TB
SSD104
SSD104, SSD107 SSD216
SSD216, SSD228
Connector Terminal SSD407 SSD420
VEL + SSD107 SSD228
A8 4 (1) AI1+ (1) AI1+
VEL COM
B7 17 (14) AI1 - (2) AI1 -
EN +
A7 3 (7) +12 Vdc (19) +12 Vdc
EN -
B6 16 (24) Enable + (15) Enable +
{
(25) OK + (16) OK +
No Connection
(13) OK - (18) Output Com
SHIELD
B12 13
A+
B11 18 (8) Out_A+ (8) Out_A+
A-
A12 5 (21) Out_A- (9) Out_A-
B+
B10 19 (9) Out_B+ (10) Out_B+
B-
A11 6 (22) Out_B- (11) Out_B-
Z+
B9 20 (10) Index + (12) Out_Index +
Z-
A10 7 (23) Index - (13) Out_Index -
Figure C-2. APM300 to S2K Amplifier Connections Using Terminal Block 44A726268-001
S
S
19
1
20
2
21
3
22
DSM Module Fwd/Rev
23
5
24
6
25
STA Serial
7
Port
T
26
O Flying Lead Cables
8
K
27
CF IC800SKCFLY010 (1M)
9
G
28
IC800SKCFLY030 (3M)
10
29
EN 3 EN 1 Auxiliary
11
I/O
30
EN 4 EN 2
12
31
C A
13
ANALOG
32
14
SERVO
33
15
AXIS 1 Position
34
Feedback
16
35
17
36
18
DSM to Terminal
Board Cables:
IC693ACC336 SSD216SSD228
SSD216, or SSD228
or SSD420
IC693CBL324 (1M)
D B Auxiliary Terminal Board Amplifier
Amplifier
IC693CBL325 (3M)
Code
S
S
19
1
20
2
21
3
ANALOG Fwd/Rev
22
4
SERVO
23
5
AXIS 2
24
Serial
Port
6
25
7
26
8
Customer
27
9
Supplied Cable
28
10
29
Auxiliary
11
I/O
30
12
31
13
32
14
33
15
34
Position
16
Feedback
35
17
36
18
Note: The DSM314 supports axis-3 and axis-4 connections on the C and D faceplate connectors using an identical wiring interface
Figure C-3. DSM Terminal Boards and Cables for S2K Amplifier Interface
Appendix C Interfacing With GE Fanuc APM or DSM Series Motion Controllers C-3
C
Caution
The maximum voltage that should be applied to I/O terminals 16-18 and 34-36 is 30
VDC. The maximum voltage for any other input terminal is 5 VDC.
Six 130V MOVs are installed between selected I/O points and the shield (frame
ground) for noise suppression. The I/O terminal points so connected are 16, 17, 18,
34, 35, and 36.
The I/O terminals support a wire gauge of 14-28 AWG. Maximum screw torque that
may be applied is 5 inch-pounds.
Two of the screw terminals are labeled S for Shield. A short earth ground wire should be connected
from one of the S terminals directly to a panel earth ground. The cable shields for any shielded
cables from user devices should connect to either of the S terminals.
1.8" (45mm)
18
36
17
35
16
34
15
33
14
32
13
31
Height
12
30
1.95" (48mm)
9
27
Panel Mount
8
26
1.65" (42mm)
6
24
5
23
4
22
3
21
2
20
1
19
S
S
IC693ACC336
Auxiliary Terminal Board
105.25 +0.25
UM 45-SEFE UM 45-SES
10 11
6
45 45
21 21
Appendix C Interfacing With GE Fanuc APM or DSM Series Motion Controllers C-5
C
Table C-2. Terminal Block Pin Assignments for DSM300 Analog Servo Axes
Circuit Type Circuit Function DSM Analog DSM Aux Term
Axis Signal Faceplate Board
Name Connector Terminal
Pin
Encoder Chan A (+) IN1P_x 1 1
Encoder Chan A (-) IN1M_x 19 19
Single Ended Or
Encoder Chan B (+) IN2P_x 2 2
Differential
Encoder Chan B (-) IN2M_x 20 20
5V Inputs
Encoder Marker (+) IN3P_x 3 3
Encoder Marker (-) IN3M_x 21 21
5V Power 5v Encoder Power P5V_x 4 4
0V 0V 0V_x 22,23 22,23
Single ended 5V input Servo Ready Input IN4_x 5 5
Strobe 1 Input IO5_x 9 9
Single Ended Strobe 2 Input IO6_x 10 10
5V Inputs /Outputs Not Used IO7_x 11 11
Not Used IO8_x 12 12
0V 0v 0V_x 27-30 27-30
Overtravel (+) IN9_x 16 16
24v Optically
Overtravel (-) IN10_x 34 34
Isolated Inputs
Home Switch IN11_x 17 17
24v Input Common 24v Input Common INCOM_x 35 35
24 v, 125 ma PLC 24v Output (+) OUT1P_ x 18 18
DC SSR Output PLC 24v Output (-) OUT1M_x 36 36
Not Used OUT2P_x 13 13
Differential Not Used OUT2M_x 31 31
5V Outputs PLC 5v Output (+) OUT3P_x 14 14
PLC 5v Output (-) OUT3M_x 32 32
24v, 30 ma Servo Enable (+) ENBL1_x 15 15
SSR Output Servo Enable (-) ENBL2_x 33 33
PLC Analog In (+) AIN1P_x 7 7
Differential
PLC Analog In (-) AIN1M_x 25 25
+/- 10v
PLC Analog In (+) AIN2P_x 8 8
Analog Inputs
PLC Analog In (-) AIN2M_x 26 26
+/- 10v Analog Out Servo Vel Cmd (+) AOUT_x 6 6
Analog Out com Servo Vel Cmd Com ACOM_x 24 24
Cable Shield Cable Shield SHIELD_x S
Figures C-7 and C-8 show typical connections between the DSM module and the S2K amplifier for
each analog servo axis. Since the position feedback from the servo motor must be connected to the
S2K amplifier to ensure proper commutation, the signals from the S2K amplifier encoder output
are connected to the terminal board. This provides position feedback to close the loop so the DSM
module can control the position of the motor.
Appendix C Interfacing With GE Fanuc APM or DSM Series Motion Controllers C-7
C
Figure C-7. DSM Analog Interface to SSD104, SSD107, and SSD407 Amplifier (With external Enable)
CMD+ 6 1 AI1+
CMD- 24 2 AI1-
Rdy In 5 16 OK
0 Vdc 22 14 common
S 18 Out Com
A+ 1 8 Out A+
A- 19 9 Out A-
B+ 2 10 Out B+
B- 20 11 Out B-
Mkr + 3 12 Index+
Mkr - 21 13 Index-
20 Common
E-Stop
17 IN Com
EN Out 15 15 Enab
EN Com 33 19 12Vdc+
Figure C-8. DSM Analog Interface to SSD216, SSD228, and SSD420 Amplifier (With external Enable)
C
? Cables, 3-45
?, 5-3 APM terminal block interface, C-1
CE agency approvals, 1-7
A Clear user memory, 5-7
CLM, 5-7
AC Supply, 2-2 CMD, 5-7
Agency approvals, 1-7 CMO, 5-8
AI, 5-3 CMR, 5-9
AIB, 5-4 Command
AIO, 5-4 input scaling, 3-33, 4-14, 4-15
Altitude, 2-2, 3-2 step input, 5-34
Ambient temperature, 2-2, 3-1 Command input, 3-33, 4-14, 4-15
motor derating, 2-15 Command output, 5-7
Amplifier Communications
Installation, 3-2 establishing with amplifier, 4-1
Analog input serial, specifications, 2-3
command input description, 3-33, 4-14, 4-15 Commutation angle offset, 5-8
deadband adjustment, 5-4 Commutation poles ratio, 5-9
offset, 5-4 Compatibility
scaling, 3-33, 4-14, 4-15 motor and amplifier combinations, 1-5
software register, 5-3 Computer requirements
specifications, 2-3 for Motion Developer, B-1
torque limit input description, 3-33 Configuration parameters, 4-21
Analog output, 3-34, 5-5 Connection diagrams
specifications, 2-3 SSD104 model, 3-37
AO, 3-34, 5-5 SSD216 &SSD228 models, 3-44
APM300, connection to, C-1 to APM motion controller, C-2
ASCII codes, A-1 to DSM motion controller, C-7
Atmosphere, 3-1 Connections
Authorization motor brake, 3-26, 3-27
Motion Developer, B-2 motor encoder, 3-25, 3-28
AUTOTUNE, 4-23, 5-6 motor power, 3-26, 3-27
CURC, 5-6 S2K amplifier to APM300, C-1
FR, 5-6 S2K amplifier to DSM300, C-2
KD, 5-6 serial port, 3-30
KI, 5-6 Connector mates, 3-45
KP, 5-6 Conversion table
KT, 5-6 English to Metric, A-4
Auxiliary encoder CUL/CUR agency approvals, 1-7
input type selection, 5-32 CURC, 5-10
using single ended inputs, 3-35 CURC, 4-21
Auxiliary Terminal Board CURP, 5-11
Assembly Drawings, C-5 CURP, 4-21
description and mounting dimensions, C-4 Current
Axis Status Register, 5-33 amplifier ratings, 2-2
continuous limit, 5-10
B peak limit, 5-11
GFK-1866A Index-1
Index
E G
EC fault code, 5-14
Gain
EI fault code, 5-14 manual adjustment, 4-24
Electrical specifications, 2-1 setting parameters, 4-23
Enable Gearing
digital input, 3-36 bound, 5-17
reset faults using, 3-36, 4-20, 6-1 enable register, 5-20
torque limit, 5-36 filter constant, 5-20
Encoder input source selection, 5-21
auxiliary encoder input specifications, 2-4 ratio used to scale analog command input, 3-33,
auxiliary input type, 5-32 4-14, 4-15
cables, 3-45 ratio, numerator register, 5-18, 5-22
encoder output specifications, 2-4 General IO register, 5-24
motor encoder input specifications, 2-4 GRB, 3-34, 4-17, 5-17
motor feedback specifications, 2-4
GRD, 3-34, 4-17, 5-18
Encoder output, 3-35, 4-18
GRE, 3-33, 3-34, 4-14, 4-16, 4-17, 5-20
functional description, 4-18
marker pulse width, 4-19, 5-13 GRF, 5-20
type assignment (EOT), 5-13 GRI, 5-21
Environmental specifications, 3-1 GRN, 3-34, 4-17, 5-22
amplifier, 2-2 Ground fault breaker, 3-3
EOT, 5-13
selecting encoder output, 4-18
Equivalent units
H
English and Metric, A-6 Hardware resources, 2-1
fraction, decimal, mm, A-5 Humidity, 2-2, 3-2
Hyper Terminal
F using to configure amplifier, 4-2
Index-2 S2K Series Brushless Servo Amplifier User's Manual–September 2002 GFK-1866A
Index
Regenerative resistor
part numbers, 1-4 T
selection, 3-48
Tables and formulas
wiring, 3-48
appendix, A-1
Register Technical support
query value of, 5-31
Motion Developer, B-4
Reset Temperature conversion
faults, 3-36, 4-20, 6-1
formulas and table, A-3
Resolver Terminal block assemblies
specifications, 2-4
part numbers, 1-4
REVISION, 5-32 Terminal board assemblies
components, C-5
S converting from DIN rail to panel mounting, C-
5
Scaling S2K to APM300, C-1
position command input, 4-17 S2K to DSM300, C-4
torque command input, 4-14 Terminal window
velocity command input, 4-16 emulation software, 4-1
Sealing, motor, 2-16 Motion Developer toolbar button, 4-10
Serial communications Tie terminal, 3-35
cable, 3-45, 4-1 TLC, 5-35
establishing with amplifier, 4-1 TLE, 4-20, 5-36
specifications, 2-3 Toolbars, Motion Developer
Serial number Motion, 4-10
Motion Developer, B-2 Torque command
Servo motor scaling the input, 4-14
performance curves, 2-12 Torque derating, 2-15
Shaft Seal, 2-16 Torque limit
Software enable, 5-36
Hyper Terminal, 4-2 setting, 4-20, 5-35
Motion Developer, 4-6 Torque limit input, 3-33
terminal emulation, 4-1 Torque mode
Specifications configuring, 4-13
amplifier power, 2-2 operation, 4-13
analog inputs, 2-3 Transformer, 2-2
analog outputs, 2-3
Troubleshooting flowchart, 6-7
auxiliary encoder input, 2-4
digital inputs, 2-3
Tuning, 4-23
digital outputs, 2-3 autotune, 4-23, 5-6
electrical, 2-1 derivative gain register, 5-25
encoder output, 2-4 filter time constant, 5-29
environmental, 3-1 integral gain register, 5-26
environmental, amplifier, 2-2 manual gain adjustment, 4-24
motor encoder input, 2-4 motor inductance register, 5-27
motor resolver input, 2-4 proportional gain register, 5-28
serial communications, 2-3
Speed/torque curves
servo motors, 2-12
U
Speed/Torque curves, 2-12 UL/UR agency approvals, 1-7
SRA, 5-33 Unpacking, 1-2
STEP, 5-34
Step input, 5-34
Storage, 1-2
V
System components, 1-5 Velocity command
System overview, 1-1 scaling the input, 4-16
Index-4 S2K Series Brushless Servo Amplifier User's Manual–September 2002 GFK-1866A
Index
Velocity mode
configuring, 4-13
operation, 4-15
Ventilation, 3-2
W
Wire size
English to Metric, A-2
Wiring
AC supply, 3-22
analog output, 3-34
auxiliary encoder input, 3-34
auxiliary I/O, 3-30
command input (AI1), 3-33, 4-14
dynamic brake function, 3-55
enable input, 3-36
encoder output, 3-35, 4-18
grounding, 3-22
motor brake, 3-26, 3-27
motor encoder feedback, 3-25, 3-28
motor power, 3-22, 3-26, 3-27
OK output, 3-36
S2K amplifier to APM300, C-1
S2K amplifier to DSM300, C-2
serial port, 3-30
torque limit input (AI2), 3-33