Bs 6622 Xlpe PVC 15kv Cable
Bs 6622 Xlpe PVC 15kv Cable
Bs 6622 Xlpe PVC 15kv Cable
APPLICATION STANDARDS
Medium voltage PVC power cables for power networks, BS 6622, IEC/EN 60228
underground and in cable ducting.
Flame Retardant according to IEC/EN 60332-1-2
CHARACTERISTICS
THE CABLE LAB®
Voltage Rating Uo/U (Um)
AN ISO/IEC 17025 AND IECEE CBTL ACCREDITED FACILITY
8.7/15 (17.5) kV
Our world-class testing facility assures the quality and compliance of this cable
Temperature Rating through a continuous and rigorous testing regime.
Fixed: 0°C to +90°C
Conductor Screen
Semi-conductive XLPE (Cross-Linked Polyethylene)
Insulation
XLPE (Cross-Linked Polyethylene)
Filler
PET (Polyethylene Terephthalate) fibres
Separator
Binding tape
Bedding
PVC (Polyvinyl Chloride)
Armour
Single core: AWA (Aluminium Wire Armoured)
Multi-core: SWA (Steel Wire Armoured)
Sheath
PVC (Polyvinyl Chloride)
Sheath Colour
Red Black
DIMENSIONS
ELAND PART NO. NUMBER OF NOMINAL MINIMUM THICKNESS NOMINAL THICKNESS OF NOMINAL DIAMETER NOMINAL WEIGHT
CORES CROSS mm SEMI CONDUCTIVE LAYER mm kg/km
SECTIONAL mm
AREA
mm2
* Designates the sheath colour. For each Eland Cables part number replace with the colour code as listed below e.g. A9M15KV01050RD = 50mm² Red
COLOUR CODES
COLOUR Red Black
CODE RD BK
CONDUCTORS
Class 2 Stranded Conductors for Single Core and Multi-Core Cables
NOMINAL CROSS NOMINAL DIAMTER OF CONDUCTOR NOMINAL SHORT CIRCUIT CURRENT CONDUCTOR DC RESISTANCE AT CONDUCTOR AC RESISTANCE AT
SECTIONAL AREA AT 1 SECOND 20 °C 90 °C
mm2 kA Ω/km Ω/km
ELECTRICAL CHARACTERISTICS
Current Carrying Capacity
NUMBER OF CORES NOMINAL CROSS CURRENT CARRYING CAPACITY CONDUCTOR LOSSES IN THE GROUND
SECTIONAL AREA A kW/km
mm2
DE-RATING FACTORS
AIR TEMPERATURE °C 25 30 35 40 45 50 55
DE-RATING FACTOR 1.00 0.96 0.92 0.88 0.83 0.78 0.73
GROUND TEMPERATURE °C 10 15 20 25 30 35 40
DE-RATING FACTOR 1.03 1.00 0.97 0.93 0.89 0.86 0.82
GROUND THERMAL
RESISTIVITY km/W
0.9 1.0 1.2 1.5 2.0 2.5 3.0
The information contained within this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is
believed to be correct at the time of publication. When selecting cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.