Hmi PIXSYS
Hmi PIXSYS
Hmi PIXSYS
410-710-810-820
HMI TOUCH SCREEN
12”
10”
7”
4,3”
L (± 0,5 mm)
H (± 0,5 mm)
Information! If additional space is needed to operate or maintain the device, this must be taken into
consideration during installation.
Caution! The spacing specifications for air circulation are based on the worst-case scenario for
operation at the maximum specified ambient temperature. The maximum specified ambient
temperature must not be exceeded!
Caution! An inclined installation reduces the convection by the HMI device and therefore the
maximum permissible ambient temperature for operation.
Connect a 24VDC 1,0A (min.) power supply, as showed into the figure.
Connect the device grounding with a conductor of 18AWG (2,5mmq)
minimum section. For the whole series it is suggested to use a 24
VDC 1,0A 24VA power supply (Pixsys code 2700.10.008).
Use Copper, Copper-Clad Aluminium or Aluminium conductors wire
for all electric connection.
5 Technical data
5.1 Main features
TD410 TD710 TD810 TD820
Power supply voltage 12 ÷ 24 VDC ± 10%
Consumption (typical
7,5 VA 13 VA 16 W 15 W
use with 2 USB devices)
Temperature range 0..50°C
Humidity range 10..90% (without condensation)
6 Communication interfaces
TD410 TD710*** - TD810 - TD820
DIP2
OFF
EXP1/CAN with termination resistor 120Ω
EXP1/CAN con terminazione 120Ω
ON
PIN5: GND (brown)
PIN6: CANH (blue)
PIN7: CANL (white)
6.2 RS232
6.2.a Using RS232 / COM1 on DB9 (No available for TD410)
6.3 RS485
6.3.a Using RS485 / COM2 on terminal M1
DIP2
RS485 MASTER:
OFF
RS485 MASTER:
OFF
RS485 SLAVE
ON
PIN3: B+ (green)
PIN4: A- (yellow)
PIN5: GND (brown)
6.3.b Using RS485 / COM2* MASTER on DB9 (No available for TD410)
DIP2
ON OFF
COM2 RS485
Pin 7 : 5Vi MASTER
9 5 1 - Input
470 Ω 2-C
Pin 8 3 A-
330 Ω 4
Pin 3 6 1 5-C
470 Ω 7 - 5V
8
B+
Pin 5 : C EARTH 9
Note: 5V Is isolated an can supply 70mA max
* Using the DB9 connector it is possible to introduce termination resistances using DIP2 as for terminal M1 or short-circuiting terminals 3-4 e 8-9, as showed
in the figure.
ON OFF
DIP2 2,3,4 to off
COM2 RS485
Pin 7 : 5Vi SLAVE
9 5 1 - Input
470 Ω 2-C
Pin 8 3-
330 Ω 4 - A-
Pin 3 6 1 5-C
470 Ω 7 - 5V
8-
Pin 5 : C EARTH 9 - B+
Note: 5V Is isolated an can supply 70mA max
Warning! Peripheral USB devices can be connected to the USB interfaces on this device. Due to the
large number of USB devices available on the market, Pixsys cannot guarantee their performance.
Caution! Because this interface is designed according to general PC specifications, extreme care
should be exercised with regard to EMC, cable routing, etc.
7 Ethernet interface
7.1 Technical data
This Ethernet controller is connected to external devices via the system unit.
Ethernet 1 interface (ETH1) TD410 - TD710 TD810 - TD820
Number of ports 1 2
Controller LAN8710A
Cabling S/STP (Cat 5e)
10/100 Mbit/s ETH1-ETH2 to CPU Link
Transfer rate 10/100 Mbit/s
10/100/1000 Mbit/s ETH1-ETH2 link
Cable length Max. 100 m (min. Cat 5e)
LED
On = Gigabit connection
Green Link
Off = 10/100 Mbit connection
On =Link
Yellow 10/100 Mbit Activity
Blink = Activity (data transfer)
9 Battery
9.1 Internal battery replacement
BIOS and clock store data also in case of power failure thanks to a CR2032 battery placed on the side.
To replace the battery it is necessary to remove the protection and pull out the extraction box using
a blade screwdriver.
Danger! KEEP OUT OF REACH OF CHILDREN. Swallowing may lead to serious injury or death in as little
as 2 hours due to chemical burns and potential perforation of the esophagus. To prevent children
from removing batteries, battery compartments is designed to be opened with a screwdriver and is
protected by a security label.
Warning! It is suggested to replace the battery every 3 years. When the battery is removed, an
internal dedicated device allows replacement without data loss if operation is completed within 1
hour since battery removal.
Using a VNC client you can view from your PC what is displayed on the PLC / HMI. Starting a browser
with active Java service it is possibile to test if the device Webserver function is active. For this function
it is necessary to use Internet Explorer.
10.b HMI_MOVICON
“START” activates manually the Movicon project (and the file upload service)
10.f WINVNC
Attention: selecting “respect capital/lowercase letters”, a variable which contains a capital letter
will be understood as different from another with the same name but with this letter lowercase. It
is recommended to keep this selection disabled, to avoid any confusion durign the drafting of the
program code.
PC requirements:
• IP address compatible with the network where it is located and with the IP address configured on
the target (see previous points)
• antivirus/firewall which allows the connection to network devices (normally already correctly
configured)
• LogicLab configured for the connection to the target to be programmed: menu “On Line” > “Select
communication” , on the window that opens press “Properties” and than enter the target IP on “IP
Address” , keeping all the rest unaltered. In case of very slow networks or of a network configuration
with different switches, it is possibile to increase the “Timeout” value (expressed in mS).
Confirm all windows pressing “OK” and save through or from the menu “file” > “SaveProject”.
To verify the correct LogicLab and Target configurations, it is possible to make the connection pressing
or form the menu “On Line” > “Connect”. If the connection is correctly done, the status bar at the
lower right side will visualize “CONNECTED” and “NO CODE” (to indicate that the target is connected
and has no code in it) or “DIFF CODE” (to indicate that the code which is being visualized does not
correspond to those who lies in the target).
Through it is possible to save, load and add an exsisting watch-list to the list of variables.
NB: If importing an array variable, it will be visualized as a structure carrying the array name.
Single array members will be accessible individually with following syntax NameMyArray:NameMyArray
_X where X is the array index (starting from 0).
Now variables are available on the Movicon project. If it is necessary to import new variables (to modify
LogicLab project), repeat only the reading and import variables procedure.
User manual - HMI Series - 17
12.c Downloading the Movicon code to the target
To downlaod the Movicon Project, use the icon:
1. Select the protocol used to transfer the code:
TCP
2. Insert the target IP address (default for HMI/
PLC: 192.168.0.100).
3. If using an HMI/PLC leave the field blank,
if using a Panel-PC insert user (or the user
name that is logged on the Panel-PC target).
4. If using an HMI/PLC leave the field blank, if
using a Panel-PC insert 123456
5. If using an HMI/PLC insert \NandFlash\
MyMoviconProjectName\, if using a Panel-PC
insert D:\MyMoviconProjectName\. In this way
Movicon will create a folder named MyMovi-
conProjectName and it will download all the
project files into it.
6. Press “Upload Project!“ to download the
project files to the target (press “Yes to All“
if a project was already downloaded to
overwrite the old files).
NB: if you need to trasfer different projects/versions to the target, you can change the destination
folder (you must mantain the first part of the address \NandFlash\).
Using the TdControlPanel is possible to select which Movicon 11 project will be executed automatically
at starting (see paragraph 10.b).
7. Once the download is completed, press “Start Deviec Project“ to launch the execution of the project
in the target (the project in execution will be closed and the new one will be executed).
Warranty terms
Pixsys srl warrants its electronic devices for 12 months from Invoice date. Pixsys liability shall be limited
to repairing (or replacing at its option) any defective product which is returned with RMA (Return
Material Authorization) priorly obtained on Pixsys website and to be clearly marked on documents.
Pixsys shall not be responsible for accident, neglect, misuse, damage to objects or people caused
using the devices outside their specifications or outside any published performance data, including
unauthorized and unqualified repairing or failure to provide proper environmental conditions. In no
event shall Pixsys liability exceed the purchase price of the product(s).
Warranty does not cover any damage arising from post-sale installation of software applications and
specifically any damage caused by malware. Technical assistance by Pixsys which should be required
to restore OS will be subject to assistance fee prevailing at time of request.