LV Series Novec 1230 Brochure
LV Series Novec 1230 Brochure
LV Series Novec 1230 Brochure
in
ControlLv SERIES
Clean Agent Fire
Suppression System
for use with
3M NovecTM 1230 Fire
TM
Protection Fluid
Clean
for use with 3M TM
Fire Suppression System
Lv Series
Clean Agent
N o v e c TM F i r e P r o t e c t i o n F l u i d
Advantages
The Lv Series Clean Agent Fire Suppression 1. Agent Storage Components - Storage 3. Trim Components - Trim components
System utilizes 3M™ Novec™ 1230 Fire components consist of the cylinder complete the installation of the suppression
Protection Fluid as the extinguishing assembly(s), which contains the Novec system and consist of connection fittings,
medium. Novec 1230 fluid is a clear, 1230 fluid, and the cylinder bracket(s), pressure gauge, low-pressure supervisory
colorless and low odor liquid perfectly which holds the cylinder assembly securely switch, electric valve actuator, and manual
suited to protect high value assets in in place. valve actuator.
areas that may be normally occupied, in
locations where clean-up of other agents 2. Agent Fluid Distribution Components 4. Slave Arrangement Components -
is problematic, when storage space for - Distribution components consist of the Slave arrangement components consist of
a fire suppression agent is restricted, or discharge nozzles used to introduce the the pneumatic valve actuator(s), actuation
when an electrically non-conductive agent Novec 1230 fluid into a protected hazard check valve, vent check, actuation hose,
is required. Each system consists of the along with the associated piping system and fittings required for a multiple cylinder
following components and their associated used to connect the nozzles to the cylinder (slave) arrangement.
accessories: assembly.
5. Supplemental Components -
Supplemental components include the
discharge pressure switch and manifold
check valve. They supplement the core
TypicalAgent
Typical Clean CleanSystem
Agent System
Layout Layout equipment or complete a specific multi-
Alarm cylinder configuration.
Warning Sign
Smoke Detector
any manual release and abort stations. All
Cylinder Valve
Discharge Nozzle
Control Panel
electric or electronic devices must connect
Manual Release
to the control panel in order to function.
& Abort
1 Lv Series Novec
Cylinder Valve
Rupture Disc
Dip Tube
Nominal P/N Fill Capacity
Empty Weight Liquid Level
Cylinder P/N Minimum Maximum
Indicator
Size (CE) lb kg lb kg lb kg
600 lb 18527 18591 304 137.9 609 276.2 346 157.0
900 lb 18528 18592 455 206.4 910 412.7 471 213.6
1000 lb 18529 18593 561 254.5 1000 453.6 766 346.5
Cylinder
Equipment Description Bracket
The Novec 1230 fluid is stored as a liquid reaching a minimum concentration level of
in cylinder assemblies designed specifically 4.2%, but not exceeding 10% in normally
Cylinder
for the application and charged to a fill occupied areas.
density of between 35 lb/ft3 (561 kg/m3)
and 70 lb/ft3 (1121 kg/m3). To ensure The cylinder assembly is composed of a cylinder valve. The cylinder is designed for
optimal performance, each cylinder is cylinder, dip tube, cylinder valve, rupture mounting in a vertical position only.
Protection
The cylinder valve has five connection points: Valve Actuation
Connection
Pressure Gauge
Low-Pressure Supervisory Switch Connection: A female connection Connection
serves as the attachment point for the low-pressure supervisory switch.
An internal check valve allows for removal of the pressure switch while
the cylinder is pressurized. Safety
Pressure Gauge Anti-Recoil
Cap
Connection Safety Device
Discharge Outlet: A 3 in (80 mm) grooved connection serves as the
attachment point for discharge piping.
Wall Mount Cylinder Bracket Assembly (P/N see chart) Cylinder 4.25”
Mounting (108 mm)
Cylinder stability is ensured by the cylinder bracket assembly, consisting of one
strap and rail with accompanying bolts, nuts, and washers. The rail is slotted for
ease of mounting with fasteners provided by the installer.
H1
Cylinder Dimensions
H2
600 lb 900 lb 1000 lb
in mm in mm in mm
D2
H1 56.40 1433 72.97 1852 66.92 1700
H2 42.65 1083 59.15 1502 53.17 1351
H3 21.5 546 45.75 908 30.0 762 H3
D1 24.0 610 24.0 610 30.0 762
D2 25.9 658 25.9 658 31.9 810
P/N 18536 18536 18537
D1
D1
3 Lv Series Novec
Trim Components
Trim components are required to operate the
Manual Valve Actuator
clean agent cylinder(s). (P/N 17001)
3” Grooved Coupling
(80 mm)
(P/N 18554) Rupture Disc
Shipped with Cylinder Valve Affixed to Cylinder
Liquid Level
Indicator
Affixed to Cylinder
9.84”
(250 mm)
(P/N 18554)
(P/N 18550)
Lv Series Novec
Electric Valve Actuator (P/N 18481)
The electric valve actuator attaches to the primary cylinder at the valve actuation
connection and is utilized to automatically open the cylinder valve upon receipt of a
signal from the control panel or other source. It operates between 17 and 30 VDC and
consumes 600 mA (.6 Amps) at 24 VDC nominal with a maximum supervisory current
of 30 mA (0.03 Amps).
1/2” (15 mm)
The electric valve actuator body is steel construction with a brass knurled swivel nut Conduit Connector Knurled
and a stainless steel actuation pin that depresses the valve core when energized. with 36” (914 mm) Leads Swivel Nut
To discharge the primary cylinder manually, the ring pin is removed and the
emergency release button is depressed forcing the pin in the electric valve actuator Ring Pin
to depress the valve core of the cylinder valve. All other connected cylinders will be
opened pneumatically.
Knurled Nut
Discharge Variable Size Flex Hose (P/N Variable) 34” Flex Hose (864 mm) Discharge Manifold
Pressure Switch Manual Pilot Actuation Pneumatic (40” / 1016 mm for (Provided By Installer)
(P/N 18773) Valve Actuator Mid Line Tee Valve Actuator 1000 lb cylinder) Male NPT Adapter
(P/N 17001) (P/N 18622) (P/N 17019) (P/N 18650 or 18651) (P/N 18625)
Male NPT
Adapter
(P/N 18625) Pilot Actuation End Line
Tee (P/N 18611)
3” (80 mm) Manifold
Check Valve
(P/N 18538) Vent Check
(P/N 10173)
Electric Valve Actuator
(P/N 18481)
Pilot Actuation
Check Valve
(P/N 18560)
Primary Cylinder Slave Cylinder Slave Cylinder Slave Cylinder Slave Cylinder
5 Lv Series Novec
1/4” (8 mm) FNPT
1/4” (8 mm) 37° Male JIC Pilot Actuation Check Valve (P/N 18560)
A 1/4 in (8 mm) MNPT by 37° male JIC check valve is installed in the
pilot actuation port of the primary cylinder valve with direction of flow
OUT of the valve. When the valve opens, pressure will be directed
1/4” (8 mm) MNPT through the pilot actuation check valve to the pneumatic valve actuators
on the slave cylinders. The purpose of the pilot actuation check valve
is to ensure the pneumatic actuator(s) remain pressurized for the entire
discharge period.
Lv Series Novec
Pilot Actuation End Line Tee (P/N 18611)
A 1/4 in (8 mm) FNPT by MNPT brass branch tee mounts to the final
pneumatic valve actuator to facilitate attachment of the vent check to the
pilot actuation line.
Supplemental Components
Supplemental components complete various system arrangements.
7 Lv Series Novec
ES
ports) are used to uniformly distribute the Novec 1230 fluid. They
sure that the agent is discharged within 10 seconds and properly
tected area. Maximum nozzle height for a protected space is 18
1' [305mm]
ozzles. Additional tiers are required forMAXIMUM
heights greater than 18 ft
180° Sidewall Nozzle
39' (6 Port) 39'
[11.89m] [11.89m]
Arrangement 39'
[11.89m]
24'
[7.32m]
27.6'
[8.41m]
MAXIMUM
27.6'
[8.41m]
MAXIMUM
33.94'
45° [10.34m]
MAXIMUM
39' 24' 39'
45°
[11.89m][7.32m] [11.89m]
39' 39'
1' [305mm] 45° [11.89m] [11.89m]
MAXIMUM
5mm]
MUM
1' [305mm]
MAXIMUM Discharge Nozzles
1' [305mm]
MAXIMUM Discharge nozzles (4, 6,1'MAXIMUM
or 8 ports) are used to uniformly
[305mm]
39'
[11.89m]
ES
1' [305mm]
MAXIMUM
ports) are used to uniformly distribute the Novec 1230 fluid. They
sure that the agent 180° 180° Sidewall
is discharged Nozzle
within 10(6 seconds
Port) and properly A
Sidewall Nozzle (6 Port)
Arrangement Arrangement 39'
tected area. Maximum nozzle height for a protected space is 18 90° Corner Nozzle (4 Port)
[11.89m]
39' 39'
45°
45° [11.89m]
[11.89m] 180° Sidewall Nozzle (6 Port)
39' 39'
[11.89m] [11.89m]
1' [305mm]
MAXIMUM Discharge Nozzle Top View
1' [305mm]
MAXIMUM
1' [305mm]
MAXIMUM
5mm]
MUM 90° Corner Nozzle (4 Port)
Arrangement
Lv Series Novec 8
Nozzle Orientation
Part Number Nominal Nozzle Height (A)
Pipe
Brass Stainless Steel
Size
360° 180° 90° 360° 180° 90° in mm
19529 19522 19515 20445 20438 20431 3/8 in (10mm) 1.436 36.5
19530 19523 19516 20446 20439 20432 1/2 in (15 mm) 1.722 43.7
19531 19524 19517 20447 20440 20433 3/4 in (20 mm) 1.926 48.9
19532 19525 19518 20448 20441 20434 1 in (25 mm) 2.176 55.3
19533 19526 19519 20449 20442 20435 1 1/4 in (32 mm) 2.500 63.5
19534 19527 19520 20450 20443 20436 1 1/2 in (40 mm) 2.689 68.3
19535 19528 19521 20451 20444 20437 2 in (50 mm) 3.100 78.7
Ordering Instructions: Specify the Nozzle P/N followed by a dash and the three digits representative of the drill code as provided by the Janus Design Suite™
software. Example: 19529-XXX = Nozzle: 360°, 3/8” (10 mm), Brass (with drill code as specified)
Safety Considerations
Although the EPA Significant New Alternative Program (SNAP) seconds or less in order to minimize the amount of HF formed.
lists Novec 1230 fluid as acceptable for occupied spaces, NFPA
The Material Safety Data Sheet (MSDS) on Novec 1230 fluid
Standard 2001 and SNAP list the following guidelines for human
should be read and understood prior to working with the agent.
exposure:
A cylinder containing Novec 1230 fluid should be handled
Novec 1230 fluid has a NOAEL¹ of 10.0% v/v with no restrictions.
carefully. The anti-recoil safety device must be in place at all times
The maximum exposure time shall not exceed five (5) minutes.
when the cylinder is not connected to the discharge piping and
Avoid any exposure greater than 10% v/v (LOAEL²).
restrained.
The discharge of Novec 1230 fluid into a hazard may reduce
visibility for a brief period. ¹ NOAEL (No Observed Adverse Effect Level) - The highest concentration at
which no adverse toxicological or physiological effect has been observed.
When Novec 1230 fluid is exposed to extremely high temperatures,
² LOAEL (Lowest Observable Adverse Effect Level) - The lowest
the by-product Hydrogen Fluoride (HF) will be formed. Novec concentration at which an adverse physiological or toxicological effect has
1230 fire protection fluid systems are designed to discharge in 10 been observed.
9 Lv Series Novec
Order Review List
Nominal Ship
P/N Description
Wt. lb (kg)
205081 Cylinder Assembly, Novec 1230 Fluid, 600 lb (304 to 607 lb capacity / 137.9 to 275.3 kg) 346 (157.0)
205091 Cylinder Assembly, Novec 1230 Fluid, 900 lb (455 to 910 lb capacity / 206.4 to 412.8 kg) 471 (213.6)
20510 1
Cylinder Assembly, Novec 1230 Fluid, 1000 lb (619 to 1000 lb capacity / 280.8 to 453.6 kg) 766 (346.5)
NOVEC1230 Bulk Novec 1230 Fluid Variable
18536 Bracket Assembly, Cylinder (600 lb / 900 lb) 10.0 (4.5)
18537 Bracket Assembly, Cylinder (1000 lb) 12.0 (5.4)
18481 Electric Valve Actuator (primary cylinder) 2.0 (0.9)
17001 Manual Valve Actuator (primary cylinder) 0.6 (0.3)
20529 Gauge Assembly, Pressure, Novec 1230 Fluid (all cylinders) 0.4 (0.2)
18775 Switch Assembly, Low-Pressure Supervisory (recommended all cylinders) 0.5 (0.2)
18554 Coupling, Grooved, 3” (80 mm) 3.9 (1.8)
18550 Elbow, Grooved, 3” (80 mm) 4.7 (2.1)
17019 Pneumatic Valve Actuator (slave cylinder) 1.2 (0.5)
18560 Valve, Check, 1/4” JIC Male x 1/4” MNPT Pilot Actuation Check Valve 0.3 (0.1)
18622 Tee, 1/4” JIC Male x 1/4” MNPT, Brass Pilot Actuation Mid Line Tee 0.2 (0.1)
10173 Vent Check (connects to Pilot Actuation End Line Tee) 0.2 (0.1)
Adapter, 1/4” MNPT x 1/4” JIC Male, Brass
18625 0.2 (0.1)
Male NPT Adapter (connects to Pilot Actuation End Line Tee)
18611 Tee, 1/4” FNPT x 1/4” MNPT, Brass Pilot Actuation End Line Tee 0.3 (0.1)
18773 Switch, Discharge Pressure 1.4 (0.6)
18538 Valve, Check, Grooved, 3” (80 mm) Manifold Check Valve 25.0 (11.3)
Hose, Flex, 3/16”, 1/4” JIC Female, 34” long
18650 0.6 (0.3)
(recommended for 600 / 900 lb cylinder arrangements)
18651 Hose, Flex, 3/16”, 1/4” JIC Female, 40” long (recommended for 1000 lb cylinder arrangements) 0.6 (0.3)
Variable Nozzle, 3/8”, Novec 1230 Fluid 0.5 (0.2)
Variable Nozzle, 1/2”, Novec 1230 Fluid 0.6 (0.3)
Variable Nozzle, 3/4”, Novec 1230 Fluid 0.8 (0.4)
Variable Nozzle, 1”, Novec 1230 Fluid 1.2 (0.5)
Variable Nozzle, 1-1/4”, Novec 1230 Fluid 1.6 (0.7)
Variable Nozzle, 1-1/2”, Novec 1230 Fluid 1.7 (0.8)
Variable Nozzle, 2”, Novec 1230 Fluid 3.6 (1.6)
1
Specify the Cylinder Assembly P/N followed by a dash and the fill weight in pounds expressed in three digits
Example: 20509-815 - Cylinder Assembly, Novec 1230 Fluid, 900 lb (815 lb fill)
The seller makes no warranties, express or implied, including, but not limited to, the implied warranties of merchantability and fitness for a
particular purpose, except as expressly stated in the seller’s sales contract or sales acknowledgment form. Every attempt is made to keep our
product information up-to-date and accurate. All specific applications cannot be covered, nor can all requirements be anticipated. All specifications
are subject to change without notice.