Vat-3fd Instruction Manual
Vat-3fd Instruction Manual
Vat-3fd Instruction Manual
VAT-3FD
3ph 380V-460V System 50 to 460KVA
Constant Torque Series UADX..
Variable Torque Series UADVX..
INSTRUCTION MANUAL
3. When using this inverter in the EU, compliance with the EMC Directive (89/336/EEC) is required.
Thus, in this case, check carefully the section 7-3. For more information refer to the separate
“EMC Application Manual” (PCST-3088E), and install and wire accordingly.
GE POWER CONTROLS
PCST-3037/1E-R1
Contents
Preface ............................................................................................................................ iii
Precautions for Safety .................................................................................................. iv
1- Precautions for Transportation and Installation .................................................. iv
2- Precautions for Wiring .......................................................................................... v
3- Precautions for Operation .................................................................................... v
4- Precautions for Maintenance, Inspection and part replacement ........................ vi
5- Others.................................................................................................................... vi
<Names of each part> ................................................................................................... vii
-i-
Chapter 6 Control Functions and Parameter Settings ........................................... 6-1
6-1 Monitor Parameters ........................................................................................... 6-1
6-2 Block A Parameters ........................................................................................... 6-3
6-3 Block B Parameters ........................................................................................... 6-8
6-4 Program Ramp Function ................................................................................. 6-39
6-5 Pattern Run Function ........................................................................................ 6-40
6-6 PID Control ........................................................................................................ 6-41
- ii -
Preface
Please read this manual thoroughly before use, and keep the manual at hand for later
reference. Also make sure that this manual is delivered to the final users.
WARNING
ALWAYS READ THIS MANUAL THOROUGHLY BEFORE USING THE VAT 3FD.
• ELECTRIC SHOCK MAY OCCUR IF THE FOLLOWING POINTS ARE NOT OBSERVED.
• DO NOT OPEN THE OUTER-COVER (FRONT COVER) WHILE THE POWER IS ON.
• A CHARGE STILL REMAINS IN THE INVERTER WHILE THE INDICATOR IS LIT EVEN
IF THE POWER HAS BEEN TURNED OFF. DO NOT OPEN THE OUTER-COVER
(FRONT COVER) IN THIS CASE. WAIT AT LEAST 10 MINUTES AFTER THE
INDICATOR GOES OUT.
• DO NOT CONTACT THE ELECTRICAL CIRCUIT WHILE THE CHARGE LAMP ON THE
PCB IS LIT. PERFORM SERVICING, ETC., AFTER WAITING AT LEAST 10 MINUTES
AFTER THE LAMP GOES OUT.
• ALWAYS GROUND THE INVERTER CASE. THE GROUNDING METHOD MUST
COMPLY WITH THE LAWS OF THE COUNTRY WHERE THE INVERTER IS BEING
INSTALLED.
• THE INVERTER MAY BE DESTROYED IF THE FOLLOWING POINTS ARE NOT OBSERVED.
• BE SURE THE UNIT VOLTAGE RATING IS ADEQUATE TO THE POWER SUPPLY
• OBSERVE THE INVERTER SPECIFICATIONS.
• CONNECT ADEQUATE CABLES TO THE INPUT/OUTPUT TERMINALS.
• ALWAYS KEEP THE INVERTER INTAKE/OUTTAKE PORTS CLEAN, AND PROVIDE
ENOUGH VENTILATION.
• ALWAYS OBSERVE THE CAUTIONS LISTED IN THIS INSTRUCTION MANUAL.
CAUTION
When using this inverter in the EU, compliance with the EMC Directive (89/336/EEC) is required.
Thus, in this case, check carefully the section 7-3. For more information refer to the separate
“EMC Application Manual” (PCST-3088E), and install and wire accordingly.
- iii -
Precautions For Safety
Items to be observed to prevent physical damage and to ensure safe use of this product are noted on the
product and in this instruction manual.
• Please read this instruction manual and enclosed documents before starting operation to ensure
correct usage. Thoroughly understand the device, safety information and precautions before starting
operation. After reading, always store this manual where it can be accessed easily.
• The safety precautions are ranked as “DANGER” and “CAUTION” In this instruction manual.
Note that some items described as CAUTION may lead to major results depending on the situation. In
any case, important information that must be observed is described.
• This instruction manual is written on the premise that the user has an understanding of the inverter.
Installation, operation, maintenance and inspection of this product must be done by a qualified person.
Even qualified persons must undergo periodic training.
CAUTION
• Always transport the product with an appropriate amount according to the products weight
Failure to observe this could lead to injuries.
• Install the inverter and brake resistor on non-combustible material such as metal.
Failure to observe this could lead to fires.
• Do not place the product near inflammable items.
Failure to observe this could lead to fires.
• Do not hold the from cover while transporting the product.
Failure to observe this could lead to injuries from dropping.
• Do not led conductive materials such as screws or metal pieces and inflammable material such as oil
enter the product.
Failure to observe this could lead to fires.
• Install the product in a place that can withstand the weight of the product, and follow the instruction
manual
Failure to do so could lead to injuries from dropping.
• Do not install and operate an inverter that is damaged or that is missing parts.
Failure to observe this could lead to injuries.
• Always observe the conditions described in the instruction manual for the installation environment.
Failure observe this could lead to faults.
- iv -
2. Precautions for Wiring
DANGER
• Always turn the device’s input power OFF before starting wiring.
Failure to do so could lead to electric shocks or fires.
• Always perform class 3 or higher grounding work.
Failure to do so could lead to electric shocks or fires.
• Wiring must always be done by a qualified electrician.
Failure to observe this could lead to electric shocks or fires.
• Always install the device before starting wiring.
Failure to do so could lead to electric shocks or injuries.
• Prepare a breaker such as an MCCB that matches the capacity for the inverter’s power supply side
Failure to do so could lead to fires.
CAUTION
DANGER
• Always install the from cover before turning the input power ON. Never remove the cover while the
power is ON. There are sections in the from PCB that are charged with high voltages.
Failure to observe this could lead to electric shocks.
• Never touch the switches with wet hands.
Failure to observe this could lead to electric shocks.
• Never touch the inverter’s terminals while the inverter power is ON even if the operation is stopped
Failure to observe this could lead to electric shocks
• Selection of the retry function could lead to unexpected restarting when an alarm occurs. The machine
may start suddenly if the power is turned ON when the automatic start function is selected Do not go
near the machine.
Failure to do so could lead to injuries.
(Design the machine so that physical safety can be ensured even if the machine restarts.)
• The machine may not stop when a stop command is issued if the deceleration stop function is
selected. Prepare a separate emergency stop switch.
Failure to do so could lead to injuries.
• Resetting of an alarm while the run signal is input could lead to unexpected restarting. Always confirm
that the run signal is OFF before resetting the alarm.
Failure to do so could lead to injuries.
-v-
Continue from previous page
CAUTION
• The radiating fins and electrical discharge resistor are heated to high temperatures, so never touch
them.
Failure to observe this could lead to burns.
• Do not block the inverter’s ventilation holes.
Failure to observe this could lead to fires.
• The inverter operation can easily be set from low speeds to high speeds, so confirm that the operation
is within the tolerable range for the motor or machine before making settings.
Failure to do so could lead to injuries.
• Prepare holding brakes when necessary. Holding is not possible with the inverter’s brake functions.
Failure to do so could lead to injuries.
• Confirm the operation of the motor as a single unit before operating the machine.
Failure to do so could lead to injuries or machine damage due to unforeseen movements.
• Always prepare a safety backup device so that the machine is not placed in a hazardous situation
when an error occurs in the inverter.
Failure to do so could lead to injuries or machine damage.
DANGER
• Always wait at least ten minutes after turning the input power OFF before starting inspections.
(Check the DC voltage between the terminals P (L+) and N (L-),and confirm that it is 15V or less)
Failure to observe this could lead to electric shocks.
• Maintenance, inspections and part replacement must be done by a designated person.
(Remove all metal accessories such as watches, bracelets, etc., before starting the work.)
(Always use an insulation measure tool.)
Failure to observe this could lead to electric shocks and injuries.
• Always turn the power OFF before inspecting the motor or machine . A potential is applied on the
motor terminal even when the motor is stopped.
Failure to do so could lead to electric shocks and injuries.
• Do no use parts other than those designated for the replacement parts.
Failure to observe this could lead to fires.
CAUTION
• Vacuum the inverter with a vacuum cleaner to clean it. Do not use organic solvents.
Failure to observe this could lead to fires or damage.
5. Others
DANGER
CAUTION
- vi -
<Names of each part>
Suspension hole
Heatsink (exhaust)
- vii -
1. Delivery Inspection and storage
1) Remove the inverter from the packaging, and check the details on the rating nameplate to confirm
that the inverter is as ordered. The rating name plate is on top of the inner-cover.
2) Confirm that the product has not been damaged.
3) If the inverter is not to be used for a while after purchasing, store it in a place with no humidity or
vibration in the packaged state.
4) Always inspect the inverter before using after storing for a long period. (Refer to 8-1.)
CAUTION
UADX... are general purpose type units
UADVX.. are Variable Torque type units
(only for load as Pump / Fans)
1-1
2. Installation and Wiring
2-2 Installation
The upper installation holes are for hooks, and those on the lower side are notched. The VAT3FD
mass is approx. from 30 to 300kg, so installation by two workers with appropriate tools is
recommended.
Fig 2.2
2-1
2. Installation and Wiring
CAUTION
• Do no connect AC power supply to the output terminals (U,V,W)
Failure to do so could lead to electric shocks or fires, and damage the drive
• Confirm that the product’s rated voltage and frequency match the power supply voltage and frequency
Failure to do so could lead to injuries or fires
• Do no directly connect a resistor to the DC terminals P (L+), N (L-)
Failure to do so could lead to fires
• Tighten the terminals screws with the designated tightening torque.
Failure to do so could lead to fires
• Connect accordingly the output side (U,V,W).
Failure to do so could case the motor to rotate in reverse and the machine to be damaged
CAUTION
Risk of electric shocks
An electrolytic capacitor is built into the VAT3FD, so there will be a charge even when the inverter power
is turned OFF. Observe the following items when wiring.
• Wait 20 minutes or more before starting work after turning the power OFF. Confirm that all indicators
on the operation are out before opening the cover.
• After opening the cover, confirm that the CHARGE lamp at the positions shown below is out. Check
the DC voltage between (P2) and (L-) and start the wiring only if the voltage measured is 15V or less.
2-2
2. Installation and Wiring
2-3
2. Installation and Wiring
a) Insert a noise filter on the input side of the inverter. Refer to section 7.3 and select the
noise filter.
b) Keep the wiring length between the noise filter and inverter to 50cm or less.
c) Use a screen cable for the inverter and motor wiring, and connect the screen to the
inverter’s G terminal and motor grounding terminal.
d) When using the circuit control wiring explained in section 2-4 and the main circuit wiring in
this section in parallel, separate the wiring by 30cm or more, or pass each of the wiring
through metal conduits. If the control circuit wiring intersect, make sure that they intersect
at a right angle.
Note 7) Inverter output
a) Do not insert a power factor improvement capacitor on the output side of the inverter.
b) When inserting a magnetic contactor on the output side of the inverter, prepare a
sequence control circuit so that the magnetic contactor will open and close when the
inverter stops.
Note 8) Grounding
Always ground the inverter unit grounding terminal (G) and the ground according to the
regulations of the Country where the inverter is being used . Ground the motor grounding at
the motor installation position.
Note 9) Inverter output surge voltage (For 400V Series)
As the inverter output cable is lengthened, the surge voltage applied on the motor also
increases. If the wiring between the inverter and motor exceeds 20m, connect a surge
absorber exclusive for the inverter output.
Note 10) DCL
Always short circuit across P1 and P2 when not using DCL. (Factory setting state)
When connecting the optional DCL, connect it to P1 and P2.
Twist the wiring to the DCL, and keep the wiring length to 5m or less.
Note 11) DBR unit
When connecting the optional DBR unit, follow Fig. 2.3 and connect the P2 and L-. The DBR
unit and inverter unit will both be damaged if the connection is mistaken.
Twist the wiring to the DBR unit, and keep the wiring length to 3m or less.
Refer to section 7-2 for details.
Note 12) DRB protection
When using the optional DBR unit, insert a thermal relay (76D) to protect the DBR resistor
and inverter. Prepare a sequence control circuit to turn OFF the magnetic contactor (MC) on
the input side of the inverter or trip the wiring breaker (MCCB) with trip coil using this relay
contact.
Note 13) Installation of surge absorber
Install a surge absorber on the magnetic contactor and relay coils installed near the inverter.
2-4
2. Installation and Wiring
2-5
2. Installation and Wiring
2
1) Use a 0.13 to 0.8mm wire for connection to the control terminal block. The tightening torque must
be 4,9N.m.
2) Use shielded wires for wiring to the setter and meters, etc. (analog signal circuit).
Connect the shielded wires to the VAT3FD COM terminal. The wire length must be 30m or less.
3) The length of the contact input/output wire must be 50m or less.
4) Follow the precautions listed in "Table 5.4 Control input/output circuit".
(Notes)
1. Three COM terminals are internally connected
. 2. No connection shall be made between RY0 and COM since this section is insulated.
PSI1 PSI3 PSI5 RESET P10 COM AM COM FM COM AUX ATNE
Fig. 2.5
2-6
3. Test Operation and Adjustment
All parameter of VAT3FD have been presetted for standard values in factory. Some of them should
be changed before run.
Start
↓
Installation and wiring
↓
Initial power supply 3-2 The default settings are for standard 50Hz motors.
↓ Change it, if necessary. (B00-1), Page 6-9 and
Page 4-7
Setting of rated items
↓
Test operation with 3-3 Make test, following instructions on page 3-2
operation panel
↓
Setting of parameters
Refer to Chapter 5, and perform test operation with
compatible with
the control Input/Output from the terminal block.
external control
↓
Test operation
including external control
↓
End of test operation
<Caution>
1. Check that the wiring is correct.
2. The power supply must always be kept in the tolerable range.
3. Always check that the inverter rating and motor rating match.
4. Always correctly install the front cover and outer cover before turning the power on.
5. Be sure that the unit can be quickly disconnected if any problem happen.
6. Refer to the Chapter 6 and observe the precautions when changing the set values such as
torque boost A02-0.
3-1
3. Test Operation and Adjustment
The "LCL" and "Hz" lamps will also light. If not, please press + to select local control
(2) Refer to section 4-5, and change.
The "LCL" and "Hz" lamps will also light. If not, please press + to select local control
<Caution>
The motor will run. Confirm the safety around the motor before starting the next step.
(3) Press the key and confirm that the motor runs in reverse.
(5) Press the key. The motor will forward run at 10Hz.
(6) Press the key once. The display will alternate between " " and “ • ”
3-2
3. Test Operation and Adjustment
<Caution>
A 10-second acceleration and 20-second deceleration ramp time are set as defaults. The motor will
slowly increase its speed to the set value. Increase the speed by approx. 10Hz at a time with
the and keys.
(9) Press the key when the motor speed reaches 50Hz. The display will decrease to 0.00 in 20
seconds. The "FWD" or "REV" lamp will flicker for two seconds while the DC-brake is applied
and the motor will stop.
3-3
4. Operation Panel
4-1
4. Operation Panel
Start the drive in the reverse direction. (in Local Mode only)
Change control Modes from Local to Remote, or vice-versa. When the drive is in
+ Local Mode, LCL lamp is on. (Note)
Reset a fault, putting out FLT LED.
+
Parameter Operation Keys
Change display Modes in the following order.
(Mode) Monitor → Parameter-A → Parameter-B
Fix Parameter number or set its values.
(SET)
Increase Parameter Number or its values.
Param. Change Parameter Block for the desired Parameter. To change to the next Block
select
up, press first. For the next block down, press first.
Value Move the cursor to the desired digit to adjust. The cursor is on the flickering digit.
change
Note) The drive is default set so that a Local/Remote selection is disabled while the drive is running.
Even while the drive is at a stop, this selection cannot be made if operating commands such as
F.RUN, JOG, etc., are being received at the terminal. This lock can be released with Parameter
B06-0.
4-2
4. Operation Panel
The VAT 3FD Parameters are classified as shown in Fig. 4.2. These parameters are grouped into
Modes and Blocks according to their functions and frequency of usage.
Mode
Output frequency To
Setting frequency To
Current To
Voltage To
Sequence status To
Extended monitor To
Fault history reading
Trace Data reading
Non-Default
parameter list
•
•
•
Frequency setting To
Acceleration/deceleration times To
Key Torque Boost To
DC Brake To
Customer Parameters To
Block-B Parameter Skip
4-3
4. Operation Panel
BASIC FUNCTIONS TO
Output ratings
Control methods
Start/stop frequency
Programmable Input configuration 1 & 2
Meter output/gain and scale Multiplier
Parameter Protection/Operation Locks
Custom Parameter register
Operation Panel Initial Mode
EXTENDED FUNCTIONS TO
Program frequency setting
Acceleration/deceleration times
Frequency Skip
Ratio Interlock setting
Input Terminal function
Output Terminal function
Detect Level for sequence output
Retry/Pick-up
Overcurrent Limit
Overload
V/F Middle point
Start Interlock
SOFTWARE FUNCTIONS TO
Software Option application
Program rump-Acceleration
Program rump-deceleration
PID Control
Traverse option adjustments
Pattern run step -0~-9
4-4
4. Operation Panel
Press key to change modes. The modes will change as follows. Parameters ,
4-5
4. Operation Panel
1) Refer to Table 6.1 for the Parameters that can be read in Monitor Mode.
2) The following is an example for reading the output current as a percentage and then showing the
output frequency as Hz.
<Keys> <Display> <Explanation>
Parameter block changes to block.
4-6
4. Operation Panel
1) Refer to Tables 6.2 to 6.5 for the details of Block-A and B Parameters.
2) The following is an example for changing "Preset V/F Patterns ( )" in Block-B
Parameters, and then for changing "DC Braking Time ( )" in Block-A Parameters.
<Keys> <Display> <Explanation>
Change Parameter b00-1 (Preset V/F Patterns) from 21 (default value) to 42.
(Note 2)
The value will display and the last digit (f0=1)
will flicker indicating that it can be changed.
The present value is:
f0=1 (Ftrq=50Hz and Fmax=50Hz)
↑
f1=2 (Input voltage=200V)
f0 Note: Parameter B00-1 cannot be changed
while the inverter is running.
4-7
4. Operation Panel
11
Increase the Parameter Number.
↓↑
↓↑
The display will alternate between Parameter
Number and the present value. The operation
panel is in Parameter Number Scanning
Mode.
Note 1) When the Block Number is changed by , it will change to the next Block Number either
Note 2) If (RUN) displays while the parameter is being set in and 12 , the parameter is one
that can only be changed while the inverter is stopped. In this case, stop the drive first
4-8
4. Operation Panel
1) Monitor Parameter D05-2 is an entry into Non-Default Value Parameter Listing Mode in which the
Block-A and B parameters that have been changed can be read.
2) In Non-Default Value Parameter Listing Mode, the display will show the Block-A and B
Parameters that have different values from their default values. These Parameter values can also
be changed in this mode.
3) The following is an example for reading B05-0 (FM Output Gain) and changing its value.
<Keys> <Display> <Explanation>
6
The Parameter B05-0 (FM [Frequency Meter]
↓↑
Output Gain) will display.
4-9
4. Operation Panel
↓↑
↓↑
12
4-10
4. Operation Panel
1) Block-B Parameters can be assigned to any Block-A Parameter in the range of A04-0 to A04-7,
and can be read and changed in the Block-A Parameter Setting Mode.
2) To assign the parameters, register the desired Block-B Parameter Number in the Block-B
Parameters in the range B07-0 to B07-
4-11
4. Operation Panel
↑ ↑
f1 f0
↑ ↑
4-12
4. Operation Panel
↓↑
Note 1) If the Parameters B07-n values are either 0.0 or any other undefined values, Parameters
A04-n will be skipped during Parameter scan.
Note 2) If all the B07 Parameters are set at 0.0. all the A04 Parameter block will be skipped during
Parameter scan.
4-13
4. Operation Panel
4-14