VALVES

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Fig.

8230
RESILIENT SEATED GATE VALVE,OS&Y
FLANGED ENDS,300PSI

Features &Benefits
● Fire Protection Valve.UL listed.FM approved.
●Valves comply with AWWA C515.
● Working pressure 300PSI.Cold water pressure (Max.temp 63°C).
● Flanged ends to ANSI B16.1 Class 125.Other flange types available.
● Application:Fire protection /Air condition /Plumbing.
● Epoxy coated interior and exterior to AWWA C550.

Material List
Part Name Material ASTM SPEC.
Body Ductile Iron A53665-45-12
Wedge Ductile Iron coated with EPDM
Wedge Nut Stainless Steel AISI 201
Bonnet Ductile Iron A53665-45-12
Packing Graphite Packing
Bonnet Bolt Stainless Steel AISI 304
Gland Flange Ductile Iron A53665-45-12
Square Head Bolt Stainless Steel AISI 304
Stainless Steel AISI 304
Stem
Brass ASTM B16
Yoke Sleeve Cast Bronze ASTM B62
Hand Wheel Cast Iron ASTM A126-B
Wheel Nut Ductile Iron A53665-45-12
Rubber Gasket EPDM Commercial
Hexagon Nut Stainless Steel AlSI 304

APPROVED LISTED

Dimensions (mm/Inch)
Valve 65mm/2-1/2" 80mm/3" 100mm/4" 150mm/6" 200mm/8" 250mm/10" 300mm/12"
Size mm Inch mm nch mm Inch mm Inch mm Inch mm Inch mm Inch
A 190.5 7-1/2 203.2 8 228.6 9 266.7 10-1/2 292.1 11-1/2 330.2 13 355.6 14
B(Open) 395 15-1/2 496 19-1/2 553 21-3/4 750 29-1/2 946 37-1/4 1118 44 1327 52-1/4
B(Close) 330 13 406 16 448 17-3/4 590 24-1/4 736 29 857 33-3/4 1016 40
C 178 7 203 8 254 10 304.8 12 355.6 14 406.4 16 457.2 18
Note:Design and materials are subject to change without notice.
2014-01-13.
HYFLO
Alarm Check Valve,Vertical Trim
R
Flange End,300PSI
Specifications Material Specifications
·Valve must be installed in vertical position with the trim as shown. No. Part Name Material ASTM Spec.
Anyde ia o n m ay affe ct the roper e ation of t h e valve.
· Fl a n ge e igned to EN10 92- PN 1 p16 A N SI B16 1 Class 125 or 1 Body Ductile Iron A53665-45-12
BS10 Table D/E(Other types available on request). 2 Cover Ductile Iron A53665-45-12
·UL/ULC list e an GOST Certifie d 3 Gasket Rubber EPDM
·F M A p proved siz s through 6°/150
4 Bolt Carbon Steel A307B
5 Stem Stainless Steel AISI 304
Working Pressure 6 Spring Stainless Steel AISI 304
7 Disc Ductile Iron A53665-45-12
·4°C-70*℃ .
8 Disc Ring Rubber EPDM
Working Temperature 9 Seat Bronze B62 C83600
·Cold water,300PSI, 10 Retaine Brass B16 C36000
·200PSI or 250PSI available on request. 11 Bolt Stainless Steel A2-70

Note:
Corrosion Protection Design and material are subject to change without notice.
·Internally and externally fusion bonded epoxy powder coated(FBE).

Dimensions(mm)

Size 80 100 150 200


L 257 270 340 432

HYFLO Fire Protection Valves -US


WFD Series
Waterflow Detector

The System Sensor WFD series is compatible

with schedule 10 through 40 steel pipe,sizes

2"through 8",and can be mounted in a vertical

or horizontal position.

RobustConstruction.TheWFDseriesconsistsofarugged,
Features
NEMA 4-rated enclosure.Designed for both indoor and outdoor
·Two-inch mounting hole provided in newWFD30-2 models use,the WFD series operates across a wide temperature range,from

·UL-listed models are NEMA 4 rated 32F to 120°F.

·Sealed retard mechanism immune to dust and other contaminants Reliable Performance.UL-listed models areequippedwith
·Visual switch activation tamper-resistant cover screws to prevent unauthorized entry.Inside,
two sets of SPDT (Form C)synchronized switches are enclosed in a
·Field-replaceable retard mechanism and SPDT switches durable terminal block to assure reliable performance.

·Rugged,dual SPDT switches enclosed in a durable terminal block False Alarm Immunity. The WFD series incorporates a mechanical

·Accommodates up to 12 AWG wire retard feature,which minimizes the risk of false alarm due to

pressure surges or air trapped in the sprinkler system.In addition,


·Designed for both indoor and outdoor use the mechanical retard's unique sealed design is immune to dust and

·100 percent synchronization activates both alarm panel and other contaminants.
local bell
Simplified Operation.The WFD series isdesigned tosimplify
·Tamper-resistant cover screws
installation.Two conduit openings permit easy attachment to the
local alarm system.The retard mechanism and dual SPDT switches
are field-replaceable.

Agency Listings

MEA
approved
5739 C5169 7770-1652:114 167-93-E 3006195
Waterflow Detector Specifications
Engineering Specifications
Vane-type waterflow detectors shall be installed on system piping as designated on the drawing and/or as specified herein.Detectors shall mount on any
clear pipe span of the appropriate nominal size,either a vertical upflow or horizontal run,at least 6"from any fittings that may change water direction,
flow rate,or pipe diameter or no closer than 24"from a valve or drain.Detectors shall have a sensitivity in the range of 4 to 10 gallons per minute and a
static pressure rating of 450 psi*for 2"-8"pipes.The detectorshall respond to waterflow in the specified direction after a preset time delay that is field
adjustable.The delay mechanismshall be a sealed mechanical pneumatic unit with visual indication of actuation.The actuation mechanismshall include
a polyethylene vane inserted through a hole in the pipe and connected by a mechanical linkage to the delay mechanism.Outputs shall consist of dual
SPDT switches (Form C contacts).Two conduit entrances for standard fittings of commonly used electrical conduitshall be provided on the detectors.
A grounding provision is provided.Unless noted,enclosures shall be NEMA 4 listed by Underwriters Laboratories Inc.All detectors shall be listed by
Underwriters Laboratories Inc.for indoor or outdoor use.

Standard Specifications
Static Pressure Rating 450 PSI* Operating Temperature Range 32F to 120F(0℃to 49℃)
Maximum Surge 18 Feet Per Second (FPS) Enclosure Rating" NEMA 4-suitable for indoor/outdoor use
Triggering Threshold 4-10 GPM Cover Tamper Switch Standard with ULC models,optional for UL
Bandwidth (Flow Rate) models,part no.546-7000
Conduit Entrances Two openings for Vz"conduit Service Use Automatic Sprinkler:NFPA-13
One open,one knock-out type One or Two Family Dwelling:NFPA 13D
Residential Occupancies up to 4 Stories:NFPA 13R
National Fire Alarm Code:NFPA-72
Contact Ratings Two sets of SPDT(Form C) U.S.Patent Numbers 5,213,205
10.0 A,bHP@125/250VAC
2.5A@6/12/24VDC
Compatible Pipe Steel water pipe,schedule 10 through 40 Warranty 3 Years

WFD Field Wiring Diagram Delay Adjustment Dial Overall Dimensions,Installed


SSM24X
dene ouNEWP
SSv ERRE1EBHSGB,
RHWN bUa
POWMER
PPL ASHICNE TG BE COWINED
P

e
CONTACTF RATNGB
]suge
T
oF

HCHNFLOW
配 QmS
BREAKWR AS

o
9H8

BEYON[D SWIT!

^F toa0PW wnE ”

Ordering Information
UL Mode ULC Model Pipe Size Hole Size Shipping Weight
WFD20 WFD20A 2” 11 4 ” 4.2Ibs
WFD25 WFD25A 2V 2 ” 11 4 ” 43Ibs
WFD30-2 WFD30-2A 3” 2” 45Ibs
WFD35 WFD35A 3V2“ 13 4 ” 4.7Ibs
WFD40 WFD40A 4” 2” 5.2 Ibs.
WFD50 WFD50A 5° 2” 63Ib5
WFD60* WFD60A 6” 2” 6.8 |bs
WFD80* WFD80A 8” 2” 75Ibs
Accessories
A3008-00 Retard mechanism
A77-01-02 Terminal block

546-7000 Tamper-proof switch kit


WFDW Tamper-proof wrench for cover
WFDN4 Gasket kit
*Maximum pressure rating 400 psi as approved by Factory Mutual.
Test And Drain Valve

BH-7 (614)

TEST AND DRAIN VALVE LISTED 37 XL APPROVED

The test and drain valve com-


plies with NFPAl3 sprinkler sys-
CERTIFICATIONS a INLET b OUTLET
tems.
UL FM 1"NPT 1"NPT
Standard equipment: UL FM 1Y”NPT 1V”NPT
Inspector's test anf drain unit w/
on-off unit with brass sight glass. - 2"NPT 2"NPT
Female NPT inlet and outlet cast
brass valve. K-Factor
(mm) 1" 1" 2 ” gpm/(psi)"
BRASS ASTM C85710 (L/min(kpa)

A 261.5 275 371 5.6(8.0)


Working pressure 175PSI
H 60 60 90 5.6(8.0)
Optional Finishes:
RB-Rough Brass
I 61 64 79 5.6(8.0)
J 110 110 134 5.6(8.0)
K 22.5 13 13.5 5.6(8.0)
L 130 130 155 5.6(8.0)

You might also like