AMP-TRAP®–Form 101

A100P SEMICONDUCTOR PROTECTION FUSES

A100P Amp-trap Form 101 Semiconductor


®

Protection fuses are rated 1000V, extending the


range of protection for UPS systems, AC and DC
drives, reduced voltage motor starters and similar
applications where lower l2t and superior reliability
are needed. With ratings from 15 through 1000
amperes, a wide range of high voltage applications
can be served.

Features/Benefits
➤ Low l t minimizes damage to protected components on
2

short circuit
➤ Controlled arc voltage reduces stress to circuit
components during fuse clearing
➤ Wide range of ampere ratings

Ratings Approvals
➤ AC: 15-30A1000VAC, ➤ UL Recognized
100kA I.R. Component
35-1000A
➤ AC: UL Guide No.
1000VAC, 100kA I.R.
JFHR2 (60-800A)
➤ DC: 15-1000A
➤ DC: Ferraz Shawmut
750VDC, 100kA I.R.
HIGHLIGHTS: APPLICATIONS: Certified

➤ Fast Acting ➤ Protection of UPS


➤ Current Limiting systems AC/DC drives,
➤ Low l t 2 reduced voltage motor
starters and other 1000V
Catalog Numbering System
➤ Optional Trigger or less semiconductor
A 100 P 80 - 4 TI
Indicator devices Amp-trap Fuse
®
A

Rated Volts - 1000 100

Style P

Amperes * 80

Mounting Types* 1
Ferrule 4
Single Pole Fuse Blocks for A100P Fuses Blades, bolt-in

Integral Blown-Fuse
FUSE FUSE BLOCK Indicator TI
AMPERE CATALOG Trigger Indicator
RATING NUMBER
35-100 P266G
125-400 P266L
* For ampere ratings and types not listed, consult the factory.

D 40
AMP-TRAP®–Form 101

A100P SEMICONDUCTOR PROTECTION FUSES


Standard Fuse Ampere Ratings, Catalog Numbers
AMPERE CATALOG OUTLINE AMPERE CATALOG OUTLINE AMPERE CATALOG OUTLINE
RATING NUMBER FIG. RATING NUMBER FIG. RATING NUMBER FIG.
15 A100P15-1 1 100 A100P100-4 2 350 A100P350-4TI 2
20 A100P20-1 1 100 A100P100-4TI 2 400 A100P400-4 2
25 A100P25-1 1 125 A100P125-4 2 400 A100P400-4TI 2
30 A100P30-1 1 125 A100P125-4TI 2 500 A100P500-4 3
35 A100P35-4 2 150 A100P150-4 2 500 A100P500-4TI 3
40 A100P40-4 2 150 A100P150-4TI 2 600 A100P600-4 3
50 A100P50-4 2 200 A100P200-4 2 600 A100P600-4TI 3
50 A100P50-4TI 2 200 A100P200-4TI 2 650 A100P650-4 4
60 A100P60-4 2 225 A100P225-4 2 700 A100P700-4 4
60 A100P60-4TI 2 250 A100P250-4 2 800 A100P800-4 4
70 A100P70-4TI 2 300 A100P300-4 2 800 A100P800-4TI 4

D
80 A100P80-4 2 300 A100P300-4TI 2 1000 A100P1000-4 5
80 A100P80-4TI 2 350 A100P350-4 2

For ampere ratings and styles not listed, call Technical Services.

Figure 1

Figure 2 Figure 3

Figure 4 Figure 5

Dimensions

OUTLINE MOUNTING FIG. DIMENSIONS - INCHES (mm)


REF. TYPE A B C D E F G H J

A100P15 to 30 1 1 2.63 0.56 - - - - - - -


(66.8) (14.2) - - - - - - -
A100P35 to 60 4, 4TI 2 5.00 1.00 3.50 4.31 4.19 0.31 0.75 0.13 -
(127) (25.4) (173) (109) (106) (7.9) (19.1) (3.3) -
A100P65 to 100 4, 4TI 2 5.00 1.22 3.50 4.31 4.19 0.31 1.00 0.19 -
(127) (31.0) (173) (109) (106) (7.9) (25.4) (4.8) -
A100P125 to 200 4, 4TI 2 5.72 2.00 3.47 4.78 4.16 0.41 1.00 0.25 -
(145) (38.1) (88.1) (121) (106) (10.4) (25.4) (6.4) -
A100P225 to 400 4, 4TI 2 5.72 2.00 3.47 4.78 4.16 0.41 1.50 0.25 -
(145) (50.8) (88.1) (121) (106) (10.4) (25.4) (6.4) -
A100P500 to 600 4, 4TI 3 7.72 2.50 3.47 5.88 5.56 0.53 2.00 0.38 -
(196) (63.5) (88.1) (149) (141) (13.5) (50.8) (9.7) -
A100P650 to 800 4, 4TI 4 7.44 2.88 3.94 5.94 - 0.63 2.00 0.38 -
(189) (73.2) (100) (151) - (16.0) (50.8) (9.7) -
A100P1000 4 5 8.22 3.50 4.47 6.59 5.84 0.63 2.75 0.50 1.38
(209) (88.9) (114) (167) (148) (16.0) (69.9) (12.7) (35.1)

D 41
AMP-TRAP®–Form 101

A100P SEMICONDUCTOR PROTECTION FUSES


A100P15 to 1000
Melting Time – Current Data, 1000V Fuses

Current in Amperes
Time in Seconds

Peak Let-Thru Current Data ­– A100P30 to 1000, 1000 Volts AC


Maximum Instantaneous Peak Let-Thru Amperes

Available Current in RMS Symmetrical Amperes


D 42
AMP-TRAP®–Form 101

A100P SEMICONDUCTOR PROTECTION FUSES

1000 VAC Fault Load

Fig. A

I t Data ­– 1000 Volts AC, 100kA


2

I2t DATA
FUSE CLEARING
AMPERE MELTING @ 1000VAC
RATING FIG. A Clearing I t vs. AC Operating Voltage
2

(A2s x 103) (A2s x 103)


15 .023 .6
20 .03 .8

D
25 .047 1.3
30 .057 1.5
35 .29 2.2

Correction Factor for I t


2
40 .38 2.9
50 .60 4.5
60 .86 6.5
65 1.0 7.6
70 1.2 8.8
80 1.5 12
100 2.4 18
125 3.8 28
150 5.4 41
200 9.6 72
225 12 91
250 15 110
300 22 160
350 29 220
Operating Voltage (AC RMS Volts)
400 38 290
500 60 450
600 86 650
650 100 760
700 120 880
800 150 1,200
1,000 240 1,900

Watts Loss vs. % Rated Current


Watts Loss at Rated Current
AMPERE WATTS AMPERE WATTS
RATING LOSS RATING LOSS
Correction Factor for Watts Loss

15 3.4 225 40
20 5.9 250 45
25 9 300 55
30 12.8 350 65
35 7.3 400 70
40 8.3 500 90
50 11 600 110
60 13 650 120
70 13 700 125
80 14 800 140
100 18 1000 190
125 23
150 28
200 36
Percent Rated Current