Nedap vp1801
Nedap vp1801
Nedap vp1801
The VP1801 is a Velos component that is used to identify animals for feeding, weighing, milking,
heat detection etc. The VP1801 is equipped with an internal switch to support a double Ethernet
connection (web interface ready) and the existing VC3 interface. The Ethernet channel is used
for the main functionality and communication like software updates and service. An extra
communication channel is available for the VC3 systems. The function is the same as the existing
Single Feeder.
The VP1801 can be installed in a V-box.
1. Shielded cable
Switch
2. Shielded cable,
VPU
shield not connected
Power + to VP1801.
supply -
When connecting the Ethernet cable, the VP1801 automatically detects TX/RX , plus and minus
connections, and switches to the correct connection.
The SYNC connection is necessary for HDX ISO synchronization between other readers. For FDX
a SYNC connection is possible, but not necessary if only one antenna is used. When two
antennas are used the SYNC connection is always needed, even when FDX-only (no ISO) mode is
enabled. The switching between the two antennas uses the ISO timing.
The F SYNC connection is necessary when the distance between two antennas is ≤ 3 m. Connect
the F SYNC as shown in the picture below.
2
Installation steps Ethernet
Step 1 Install the VP1801 in the V-box (or other box). See the manual of the relevant
equipment (feeding station, separation unit etc.) where is indicated how to install
the V-box.
Step 2 Connect all required wiring. See the manual of the relevant equipment and the
manual of the required behaviour component.
Step 3 Power up and check the LED indicators, see also the overview on page 9.
Step 4 When the system is equipped with the auto-addressing function, the host
computer requires the address. Select “Sp > y” in the display menu of the VP1801,
see page 6. Go to Step 8.
Step 5 When auto-addressing is not available, set the required address manually via “Ad”
in the display menu, see page 6.
Step 6 Check the ip settings via “IP” in the display menu, see page 6. Default DHCP is on.
When DHCP must be switched off, set the required ip address settings via “IP” in
the display menu. When DHCP is switched off, the default IP address is
192.168.1.100.
Step 7 Check the antenna tuning. Select “HF > H1 > tu” in the display menu to start and
enable autotune, see page 7. If external manual adjustment is used (e.g. adjustable
antenna-trafo), select “AA” in the display menu, see page 7.
Step 8 Test the functioning. See manual of the behaviour component. In case of
malfunctioning the connected devices like sensors, motors, valves can be checked
with options from menu option “It”, see page 7.
Step 2 Connect all required wiring. See the manual of the relevant VC3 application.
Step 3 Power up and check the LED indicators, see also overview on page 9.
Step 4 Set the required VC3 address via “CO > SA” in the display menu, see page 8.
Step 5 Select the VC3 application and other relevant VC3 settings via “CO > AP”, see page
8.
Step 5 Check the antenna tuning. Select “HF > H1 > tu” in the display menu to start and
enable autotune, see page 7. If external manual adjustment is used (e.g. adjustable
antenna-trafo), select “AA” in the display menu, see page 7.
Step 6 Test the functioning. See the manual of the VC3 application. In case of
malfunctioning of the connected devices like sensors, motors, valves execute a
test with options from menu option “It”, see page 7.
Connections
See the manual of the concerning behaviour component for a detailed overview of the
connections. O5 is default controlled by the identification process of the VP1801 itself, and can
be overruled by the behaviour component. If the V-box has a signal light, connect it default to
O5.
When connecting the Ethernet cable, the VP1801 automatically detects TX/RX , plus and minus
connections, and switches to the correct connection.
4
Antennas
The VP1801 has two antenna connections and one internal reader. When two antennas are
connected, the used application determines if the second antenna is used or not. In case the
reader has to control both antennas, the reader switches fast between the two antennas in a
smart way. That means the identification time is divided over the two antennas with a switching
time that can vary between 24ms and 120ms in case both antennas have the same priority.
Priority is controlled by Ethernet control like a behaviour component.
Autotune
The VP1801 is equipped with the autotune function. This means it can tune an antenna by itself
due to an integrated internal tuning-circuit on board. Tuning can be started with the display
menu “HF > H1 > tu”, remote from an external command over Ethernet or with the web-interface
of the VP1801.
Important!
Autotune works with all Nedap antennas. In case external antenna adjustment is used
(e.g. adjustable antenna-trafo), the autotune function must be switched off to achieve
the maximum reading distance. This can be done via “HF > HI > AA” in the menu
display of the VP1801, see page 6. Then the autotune function is disabled until it is
started again with the display menu “HF > H1 > tu”.
Display menu
1. Display
2. Push button
SERIAL NUMBER
Shows last four digits of serial number
SYSTEM PING
Send system ping
PROGRAM VERSION
Shows program version
DISPLAY ADDRESS
Shows the actual address
SET ADDRESS
Change the address
DISPLAY SECTION
Show section (Default 0, enter 0 to have access to IP address settings)
SET SECTION
Change section
SETTINGS TO DEFAULT
All address settings back to factory settings
DHCP IS ON
Press long until blinking to turn on DHCP
DHCP IS OFF
Press long until blinking to turn off DHCP
DISPLAY IP ADDRESS
Shows actual IP address (one by one)
SET IP ADDRESS
6
SET NETWORK MASK (only shown in case of DHCP OFF)
Changes network mask (8=255.0.0.0, 16=255.255.0.0, 24=255.255.255.0)
SETTINGS TO DEFAULT
All address settings back to factory settings
AUTOTUNE MODE
Starts antenna tuning
ADJUST ANTENNA
Antenna tuning level will be shown (sets autotuning
position off)
ANTENNA POWER
Min/max 10 / 99. Normally set to 25 (=25% of maximum
power).
TEST IDENTIFICATION
Shows last 2 digits of a tag number
SEE H1 MENU
SETTINGS TO DEFAULT
All antenna settings to default
DISPLAY ERROR
Safeguard error
DISPLAY ERROR
Output error
DISPLAY ERROR
Other system errors
NO VC3 APPLICATION
Select no VC3 application
ETHERNET IDENTIFICATION
ILS PROGRAM
Select Identification Lon Standard
WHS PROGRAM
Select Walk through herringbone or side-by-side
FSS PROGRAM
Select Feed Station
2 HOURS DATA
Do not send 2 hours data over VC3 channel
2 HOURS DATA
Send 2 hours data over VC3 channel
8
VC3 COMMUNICATION SPEED 4800 BAUD
Set communication speed to 4800 Baud
DEFAULT
Enter value 99 to return to factory defaults
LED indicators
= OK
= not OK
10
Specifications VP 1801
Dimensions 143 x 120 x 68 mm LxWxH (excluding mounting rail) Weight: ± 430 gr
Power Input voltage 25 VDC, +20% -20%
Max current consumption without connected I/O = 300 mA
Maximum (total) motor output current 3,5 A
Protected against reverse connection power supply
Software Check for available updates
Inputs I1 – I4 0V – 35V DC
Suitable for NPN sensors
Outputs O1 – O4 In total max. 3.5 Amp continue, short-circuiting and overload protected
O5 Max. 400mA continue, short-circuiting and overload protected
V out Max. 4A continue, short-circuiting and overload protected
Synchronization Synchronization according to ISO 11785
Environment Temperature: Operating: -10 – 50 °C, Storage: -25 – 50 °C
Relative humidity: 10 – 93% non condensing
Maximum noise level: 10 dBµA/m quasi peak, according CISPR 16-1-1
Conducted noise: according EN55022
IP class IP 30. When installed in V-box IP 65 (cover and cables installed correctly !)
Always use a NEDAP power supply. The Nedap guarantee-regulations are only valid when is installed as indicated in this manual. Install data cables at
a safe distance from (high) powered cables. For more detailed information contact your local Nedap supplier or check the internet site.
Declaration of Conformity
FCC ID : CGDVP1801
IC : 1444A-VP1801
Changes or modifications not expressly approved by the party responsible for compliance could void the
user’s authority to operate the equipment.
Cet appareil se conforme aux normes RSS 210 exemptés de license du Industry Canada. L’opération est soumis aux deux
conditions suivantes:
(1) cet appareil ne doit causer aucune interférence, et
(2) cet appareil doit accepter n’importe quelle interférence, y inclus interférence qui peut causer une opération non pas voulu
de cet appareil.
Les changements ou modifications n’ayant pas été expressément approuvés par la partie responsable de la conformité
peuvent faire perdre à l’utilisateur l’autorisation de faire fonctionner le matériel.
Cet équipement est conforme a RSS-102 limites énoncées pour un environne- ment non contrôlé. Cet équipement doit être
installé et utilisé avec une distance minimale de 20 cm entre le radiateur et votre corps.
This information is furnished for guidance, and with no guarantee as to its accuracy or completeness; its publication conveys no licence under
any patent or other right, nor does the publisher assume liability for any consequence of its use; specifications and availability of goods
mentioned in it are subject to change without notice; it is not to be reproduced in any way, in whole or in part, without the written consent of the
publisher.
© Nedap N.V., Livestock management P.O. Box 104 NL-7140 AC GROENLO The Netherlands.
12