PVC INDOOR WIRES / IEC 60227-3, BS EN 50525-2-31

CU / PVC 450 / 750 V

DIMENSIONS AND
ELECTRICAL DATA
WEIGHTS
Nominal
Max. Conductor
cross Continuous Current Ratings (@ 40° C)
Resistance
sectional
area Approx. Approx.
3 loaded conductors Cable Code
DC at AC at 2 loaded conductors overall overall
(Three-Phase circuit)
20 °C 70 °C (Single-Phase circuit) diameter weight

(a) (b) (c) (d) (e) (f) (g)


mm² Ω / km Ω / km
A A A A A A A mm kg / km
a. Solid Conductors
1.5 12.1000 14.4777 13 15 - - - - - 2.8 25 C108PB101000X000XX
2.5 7.4100 8.8661 17 21 - - - - - 3.4 35 C110PB101000X000XX
4 4.6100 5.5159 23 28 - - - - - 3.9 50 C112PB101000X000XX
6 3.0800 3.6853 30 36 - - - - - 4.4 70 C113PB101000X000XX
10 1.8300 2.1897 40 50 - - - - - 5.6 115 C114PB101000X000XX
b. Stranded Conductors
1.5 12.1000 14.4777 13 15 - - - - - 3.0 25 C208PB101000X000XX
2.5 7.4100 8.8661 17 21 - - - - - 3.6 35 C210PB101000X000XX
4 4.6100 5.5159 23 28 - - - - - 4.2 55 C212PB101000X000XX
6 3.0800 3.6853 30 36 - - - - - 4.7 70 C213PB101000X000XX
10 1.8300 2.1898 40 50 - - - - - 5.7 110 C314PB101000X000XX
16 1.1500 1.3763 53 66 - - - - - 6.7 170 C315PB101000X000XX
25 0.7270 0.8703 70 88 114 96 127 99 113 8.3 260 C316PB101000X000XX
35 0.5240 0.6276 86 109 141 119 157 124 141 9.3 350 C317PB101000X000XX
50 0.3870 0.4639 103 131 170 145 190 151 171 10.9 475 C318PB101000X000XX
70 0.2680 0.3220 131 167 218 188 244 196 221 12.5 675 C319PB101000X000XX
95 0.1930 0.2328 158 202 264 230 297 239 270 14.5 925 C345PB101000X000XX
120 0.1530 0.1856 183 234 306 268 344 279 315 15.8 1160 C346PB101000X000XX
150 0.1240 0.1514 209 - 353 310 397 323 364 17.7 1425 C347PB101000X000XX
185 0.0991 0.1224 237 - 403 356 453 371 417 19.8 1785 C348PB101000X000XX
240 0.0754 0.0952 279 - 475 422 535 441 495 22.5 2335 C349PB101000X000XX
300 0.0601 0.0780 319 - 547 488 617 510 573 25.3 2905 C350PB101000X000XX
400 0.0471 0.0638 - - 656 570 741 599 691 28.3 3745 C351PB101000X000XX
500 0.0366 0.0531 - - 755 651 854 686 800 32.1 4830 C352PB101000X000XX
630 0.0283 0.0450 - - 874 743 990 787 930 35.7 6105 C353PB101000X000XX
c. Flexible Conductors
1.5 13.3000 15.9135 13 15 - - - - - 3.0 25 C508PB101000X000XX
2.5 7.9800 9.5481 17 21 - - - - - 3.7 35 C510PB101000X000XX
4 4.9500 5.9227 23 28 - - - - - 4.1 50 C512PB101000X000XX
6 3.3000 3.9485 30 36 - - - - - 4.6 70 C513PB101000X000XX
10 1.9100 2.2855 40 50 - - - - - 6.0 120 C514PB101000X000XX
16 1.2100 1.4480 53 66 - - - - - 7.6 185 C515PB101000X000XX
25 0.7800 0.9337 70 88 114 96 127 99 113 9.5 285 C516PB101000X000XX
35 0.5540 0.6635 86 109 141 119 157 124 141 11.0 385 C517PB101000X000XX
50 0.3860 0.4628 103 131 170 145 190 151 171 12.6 550 C518PB101000X000XX
70 0.2720 0.3269 131 167 218 188 244 196 221 14.6 740 C519PB101000X000XX
95 0.2060 0.2484 158 202 264 230 297 239 270 17.0 1000 C545PB101000X000XX
120 0.1610 0.1952 183 234 306 268 344 279 315 18.9 1255 C546PB101000X000XX
150 0.1290 0.1575 209 - 353 310 397 323 364 21.2 1565 C547PB101000X000XX
185 0.1060 0.1306 237 - 403 356 453 371 417 23.4 1915 C548PB101000X000XX
240 0.0801 0.1008 279 - 475 422 535 441 495 26.9 2515 C549PB101000X000XX

Laying Conditions: Ambient air temperature of 40 ºC. In case of different laying conditions, appropriate correction (derating) factors from Annex
C have to be applied to cater for the actual installation conditions.