Daikin Electrical Data Sheet

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 7

DAIKIN VRV-IV INDOOR UNITS

RECOMMONDED POWER SUPPLY IS 1PH + N , 240 VAC , 50Hz. WITH


EARTHING.
PROVIDE INDEPENDENT DB PANEL FOR VRV INDOOR UNITS.
EARTH LEAKAGE CKT. BRAKER 300mA PER PHASE IS
MANDATORY.
FXCQ –M CEILING MOUNTED DOUBLE FLOW
CASSETTE UNIT
SR NO MODEL VOLTAGE Watts MCB Cable size
1 FXCQ 20 MVE 77 6 Amps 3C X 1.5 sq.mm.
2 FXCQ25, 32MVE 92 6 Amps 3C X 1.5 sq.mm.
3 FXCQ40,50MVE 130 6 Amps 3C X 1.5 sq.mm.
220~240
4 FXCQ 63MVE 161 6 Amps 3C X 1.5 sq.mm.
5 FXCQ 80MVE 209 6 Amps 3C X 2.5 sq.mm.
6 FXCQ 125MVE 256 6 Amps 3C X 2.5 sq.mm.
FXFQ-M CEILING MOUNTED MULTIFLOW CASSETTE
SR NO MODEL VOLTAGE Watts MCB Cable size
1 FXFQ 25 33 6 Amps 3C X 1.5 sq.mm.
2 FXFQ 32 33 6 Amps 3C X 1.5 sq.mm.
3 FXFQ 40 47 6 Amps 3C X 1.5 sq.mm.
4 FXFQ 50 52 6 Amps 3C X 1.5 sq.mm.
220~240
5 FXFQ 63 66 6 Amps 3C X 1.5 sq.mm.
6 FXFQ 80 93 6 Amps 3C X 1.5 sq.mm.
7 FXFQ 100 187 6 Amps 3C X 2.5 sq.mm.
8 FXFQ 125 209 6 Amps 3C X 2.5 sq.mm.
FXZQ-MVE CEILING MOUNTED COMPACT CASSETTE
SR NO MODEL VOLTAGE Watts MCB Cable size
1 FXZQ20 MVE 73 6 Amps 3C X 1.5 sq.mm.
2 FXZQ25 MVE 73 6 Amps 3C X 1.5 sq.mm.
3 FXZQ32 MVE 220~240 76 6 Amps 3C X 1.5 sq.mm.
4 FXZQ40 MVE 89 6 Amps 3C X 1.5 sq.mm.
5 FXZQ50 MVE 115 6 Amps 3C X 1.5 sq.mm.
FXKQ-MA CEILING MOUNTED CASSETTE CORNER U
SR NO MODEL VOLTAGE Watts MCB Cable size
1 FXEQ20AVE 26 6 Amps 3C X 1.5 sq.mm.
2 FXEQ25AVE 27 6 Amps 3C X 1.5 sq.mm.
3 FXEQ32AVE 34 6 Amps 3C X 1.5 sq.mm.
220~240
4 FXEQ40AVE 46 6 Amps 3C X 1.5 sq.mm.
5 FXEQ50AVE 48 6 Amps 3C X 1.5 sq.mm.
6 FXEQ63AVE 67 6 Amps 3C X 1.5 sq.mm.
FXDQ-P,FXDQ-N(A) SLIM CEILING MOUNTED DUCT
SR NO MODEL VOLTAGE Watts MCB Cable size
1 FXDQ 20 86 6 Amps 3C X 1.5 sq.mm.
2 FXDQ 25 86 6 Amps 3C X 1.5 sq.mm.
3 FXDQ 32 86 6 Amps 3C X 1.5 sq.mm.
220~240
4 FXDQ 40 160 6 Amps 3C X 1.5 sq.mm.
5 FXDQ 50 165 6 Amps 3C X 1.5 sq.mm.
6 FXDQ 63 181 6 Amps 3C X 1.5 sq.mm.
FXHQ –MA CEILING SUSPENDED TYPE
SR NO MODEL VOLTAGE Watts MCB Cable size
1 FXHQ 32MAVE 111 6 Amps 3C X 2.5 sq.mm.
220~240
2 FXHQ 63MAVE 220~240 115 6 Amps 3C X 2.5 sq.mm.
3 FXHQ100MAVE 135 6 Amps 3C X 2.5 sq.mm.
FXMQ-MA CEILING MOUNTED DUCT TYPE UNIT
SR NO MODEL VOLTAGE Watts MCB Cable size
1 FXMQ 20 81 6 Amps 3C X 1.5 sq.mm.
2 FXMQ 25 81 6 Amps 3C X 1.5 sq.mm.
3 FXMQ 32 85 6 Amps 3C X 1.5 sq.mm.
4 FXMQ 40 194 6 Amps 3C X 1.5 sq.mm.
5 FXMQ 50 215 6 Amps 3C X 2.5 sq.mm.
6 FXMQ 63 230 6 Amps 3C X 2.5 sq.mm.
7 FXMQ 80 220~240 298 6 Amps 3C X 2.5 sq.mm.
8 FXMQ 100 376 6 Amps 3C X 2.5 sq.mm.
9 FXMQ 125 461 6 Amps 3C X 2.5 sq.mm.
10 FXMQ140 461 6 Amps 3C X 2.5 sq.mm.
11 FXMQ170 900 15 Amps 3C X 2.5 sq.mm.
12 FXMQ 200 1100 15 amps 3C X 2.5 sq.mm.
13 FXMQ 250 1650 15 amps 3C X 2.5 sq.mm.
FXAQ–MA WALL MOUNTED TYPE UNIT
SR NO MODEL VOLTAGE Watts MCB Cable size
1 FXAQ 20 16 6 Amps 3C X 1.5 sq.mm.
2 FXAQ 25 22 6 Amps 3C X 1.5 sq.mm.
3 FXAQ 32 27 6 Amps 3C X 1.5 sq.mm.
220~240
4 FXAQ 40 20 6 Amps 3C X 1.5 sq.mm.
5 FXAQ 50 27 6 Amps 3C X 1.5 sq.mm.
6 FXAQ 63 50 6 Amps 3C X 1.5 sq.mm.
FXLQ-MA / FXNQ–MA FLOOR & CONCELLED TYPE U
SR NO MODEL VOLTAGE Watts MCB Cable size
1 FXLQ/FXNQ 20MAVE 49 6 Amps 3C X 1.5 sq.mm.
2 FXLQ/FXNQ 25MAVE 49 6 Amps 3C X 1.5 sq.mm.
3 FXLQ/FXNQ 32MAVE 90 6 Amps 3C X 1.5 sq.mm.
220~240
4 FXLQ/FXNQ 40MAVE 90 6 Amps 3C X 1.5 sq.mm.
5 FXLQ/FXNQ 50MAVE 110 6 Amps 3C X 1.5 sq.mm.
6 FXLQ/FXNQ 63MAVE 110 6 Amps 3C X 1.5 sq.mm.
FXMQ –MFV1 OUTDOOR AIR PROCESSING UNIT
SR NO MODEL VOLTAGE Watts MCB Cable size
1 FXMQ 125MFV1 359 6 Amps 3C X 2.5 sq.mm.
2 FXMQ 200MFV1 220~240 548 15 Amps 3C X 2.5 sq.mm.
3 FXMQ 250MFV1 638 15 Amps 3C X 2.5 sq.mm.

MCA : MINIMUM CIRCUIT AMPS. FLA : FULL LOAD AMPS.


MFA : MAX FUSE AMPS.
IFM : FAN MOTOR RATED OUTPUT KW.

PLEASE NOTE THE ABOVE DATA IS IN DESIGN


CONDITIONS WITH 39 DEGREE CENTIGRADE
AMBIENT CONDITIONS & 25 DEGREE CENTIGRADE
INDOOR TEMPREATURE (CONDITIONED AREA)
NOTE:- 1. Max. allowable voltage unbalance between phases is 2%
2. MCA= 1.25 X FLA
MFA ≤ 4 X FLA
3. Select wire size based on the MCA
4. Instead of fuse, use circuit breaker based on MFA
ELECTRICAL POWER REQUIREMENT FOR DAIKIN VRV X OUTDOOR UNITS

RECOMMONDED POWER SUPPLY IS 3PH + N, 380 – 415 VAC, 50Hz. WITH EARTHING.

EARTH LEAKAGE CKT. BRAKER 300mA FOR EACH ODU IS MANDATORY.


Nominal size of Cu
MCB (Amp) ELCB (Amp)
conductor, 4core XLPE
SR. NO. MODEL 4 Pole (300mA,4-Pole)
insulated armoured cables
Amps. Amps. SQ. MM.
1 RXYQ6ARY6 20 25 6
2 RXYQ8ARY6 20 25 6
3 RXYQ10ARY6 25 25 6
4 RXYQ12ARY6 25 25 6
5 RXYQ14ARY6 32 32 10
6 RXYQ16ARY6 40 40 10
7 RXYQ18ARY6 40 40 10
8 RXYQ20ARY6 63 63 10

NOTE:-
1. RLA is based on Indoor temp. 27ºC and outdoor temp. 35ºC (ARI standards)

a) If the Ambient temp raises above 35 deg C and indoor is maintained below 27 deg C then
Power consumption would vary according to desired condition

2. Max. allowable voltage variation between phase is 2%


3. Select wire size based on the larger value of MCA or TOCA
4. MFA is used to select circuit breaker and the ground fault circuit interrupter (ELCB)
SYMBOLS:-
MCA:- Min. circuit amps.
TOCA:- Total over current amps.
MFA:- Max. fused amps.
RLA:- Rated load amps.
Safety Measures
1) Time delay of atleast 20 seconds is required in between power switchovers. In case
time delay is not possible reverse phase protection is required
2) Auto phase change over switch should be installed in main panel to automatically change the phase seq
to avoid tripping of outdoor units in case of power switchovers
PROJECT:
POWER DETAILS AND ELECTRICAL REQUIREMENTS FOR VRV UNITS

Power Supply Copper Cable size


SNO UNIT DESCRIPTION MODEL NUMBER MCB FOR EACH UNIT REQUIREMENT for each unit
Requirement (Multilead)
OUTDOOR UNITS

Single Phase Side Discharge


4 HP VRV OUTDOOR UNIT RXMQ4TVE6 1 Phase, 220-240V, 50Hz Armored 3C×4 Sq mm 2Pole 32A MCB at Panel Room 32A MCB with 300mA ELCB Near ODU
5 HP VRV OUTDOOR UNIT RXMQ5TVE6 1 Phase, 220-240V, 50Hz Armored 3C×4 Sq mm 2Pole 32A MCB at Panel Room 32A MCB with 300mA ELCB Near ODU
6 HP VRV OUTDOOR UNIT RXMQ6TVE6 1 Phase, 220-240V, 50Hz Armored 3C×4 Sq mm 2Pole 32A MCB at Panel Room 32A MCB with 300mA ELCB Near ODU

Three Phase Side Discharge


8 HP VRV OUTDOOR UNIT RXMQ8TY16 3 Phase, 380-415V, 50Hz Armored 4C×6 Sq mm 4Pole 25A MCB at Panel Room 25A MCB with 300mA ELCB Near ODU
10 HP VRV OUTDOOR UNIT RXMQ10AY16 3 Phase, 380-415V, 50Hz Armored 4C×6 Sq mm 4Pole 25A MCB at Panel Room 25A MCB with 300mA ELCB Near ODU
12 HP VRV OUTDOOR UNIT RXMQ12AY16 3 Phase, 380-415V, 50Hz Armored 4C×10 Sq mm 4Pole 32A MCB at Panel Room 32A MCB with 300mA ELCB Near ODU

ELCB Rating (A) 300mA, 4 Pole.


*1 Rated capacity MCB should be provided
*2 Rated capacity MCCB should be provided

Safety Measures
1) Time delay of atleast 20 seconds is required in between power switchovers. In case time delay is not possible reverse phase protection is required.
2) Auto phase change over switch should be installed in main panel to automatically change the phase sequence and to avoid tripping of outdoor units in case of power switchovers.