VSB-VMB DBL008e
VSB-VMB DBL008e
VSB-VMB DBL008e
VSB-VMB
MODEL Kvs STROKE
DN
2 WAY 3 WAY [m3/h] [mm]
VSB3 VMB3 3/4” 6,3
VSB4 VMB4 1” 10
VSB5 VMB5 1 ¼” 16
16,5
VSB6 VMB6 1 ½” 22
VSB8 VMB8 30
2”
VSB8A VMB8A 40
MANUFACTURING CHARACTERISTICS
The valve body is made of G25 cast iron. The plug is in brass with Con-
toured-type profile on direct way and V-port on angle way.
The stem is in CrNi steel with threaded M8 end and female threaded
connections. The stem packing is constituted by a EPDM O-ring with
graphited teflon scraper rings.
NOTE: The valves are also available in the stainless steel plug version
(profile and Kvs are the same of the brass plug). For further sales in-
formation, please contact our Sales Support.
INSTALLATION
TECHNICAL CHARACTERISTICS
Before valves are mounted, make sure that pipes are clean, free
from welding slags, that are perfectly lined up with valve body and
not subjected to vibrations.
Constructions: PN16 The valve can be mounted in any position except upside-down (for
Control characteristics: direct way equal-percentage MVH actuators see Fig. 3).
angle way linear (VMB) While assembling, respect the flow directions indicated by the
Leakage*: direct way 0...0,03% of Kvs letters located on the valve body (see Fig. 1 and 2) and the appli-
angle way 0...2% of Kvs (VMB) cation schemes.
Connections: female threaded
Stroke: 16,5mm (max 18,5)
Allowed fluids:
- water: max. temperature 150°C
min. temperature -10 °C
(in case of ice on stem and gasket, use
the stem-heater, see actuators data
sheets; is not applicable to V.B DN15
valves)
glycol added max 50%
- saturated steam: max. temperature 150 °C
max. pressure 250kPa (absolute value)
Weight: see dimensions
Controlli S.p.A.
16010 Sant’Olcese (GE)
Tel. 010 73 06 1
Fax. 010 73 06 870/871
www.controlli.eu
VSB and VMB are actuated by CONTROLLI MVB, MVH, MVH56EA/C, AG52 Valve linkage kit with MVE
MVE electrical actuators. AG62 Valve linkage kit with MVH
AG63 Valve linkage kit with MVE..S
GVB3 Insulation shell for DN 3/4“ valves for V.B3
MOUNTING POSITIONS GVB4 Insulation shell for DN 1“ valves for V.B4
GVB5 Insulation shell for DN 1 ¼” for V.B5
GVB6 Insulation shell for DN 1 ½” for V.B6
GVB8 Insulation shell for DN 2” for V.B8
Fig. 3 GVB8A Insulation shell for DN 2” for V.B8A
APPLICATION SCHEMES
a) Variable flow control when used c) Variable flow mixing when used
A AB
AB A
USER
B USER
b) Constant flow when used in injection circuits d) Constant flow mixing when used in injection or tapping circuits
AB A
USER USER
B
AB A
3/4” 1600 1600 1600 1560 1080 260 1600 1310 1600 1600 1600 1600 1600 1600
1” 1600 1600 1380 1030 680 170 1190 870 1600 1560 1600 1600 1600 1600
VSB
1 ¼” 1600 1370 840 650 410 110 720 540 1210 980 1600 1540 1600 1600
VMB
1 ½” 1170 990 590 470 290 80 500 390 860 710 1300 1110 1600 1600
2” 870 750 440 350 210 60 370 290 640 540 960 840 1430 1263
* with MVH.A in emergency valve closed, with MVH.C in emergency valve open.
The max regulation differential pressure, it means the pressure which can be used during the stroke, is conditioned by wear between seat
and plug and by the performance guaranteed by the actuator for the evaluated valve. So we recommend not to overcome the differential
pressure whose value corresponds to the minimum between 200kPa (maximum admitted value not to cause wear) and the one shown in
the previous table (max close-off differential pressure).
Note: The max operating pressures at different temperatures for various PN classes must correspond to the following standards: UNI 1092-02
and UNI 12516-1.
DIMENSIONS [mm]
The performances stated in this sheet can be modified without any prior notice