Modbus Map VLT - R0
Modbus Map VLT - R0
Modbus Map VLT - R0
Speed Reference:
Reference % Hexadecimal value Scaled by parameters 3-02/3-03
0% 0000h Min. ref. Par. 3-02
50% 2000h ((Par. 3-03) - (Par. 3-02))/2
100% 4000h Max. ref. Par. 3-03
200% 8000h Max. ref. Par. 3-03 x 2
Holding registers
Register Number Description
00001-00006 00001-00006 Reserved
7 Last error code from an FC data object interface
8 Reserved
9 Parameter index*
00010-00999 000 parameter group (parameters 001 through 099)
01000-01999 100 parameter group (parameters 100 through 199)
02000-02999 200 parameter group (parameters 200 through 299)
03000-03999 300 parameter group (parameters 300 through 399)
04000-04999 400 parameter group (parameters 400 through 499)
... ... ... ...
49000-49999 4900 parameter group (parameters 4900 through 4999)
50000 Input data: Frequency converter control word register (CTW).
50010 Input data: Bus reference register (REF).
... ...
50200 Output data: Frequency converter status word register (STW).
50210 Output data: Frequency converter main actual value register (MAV).
Data Readouts
Par. No. # Parameter description Default value (units) 4-set-up Change during operation Conversion index Type Modbus Address
15-0* Operating Data
15-00 Operating Hours 0h All set-ups 0 74 Uint32 15000
15-01 Running Hours 0h All set-ups 0 74 Uint32 15010
15-02 kWh Counter 0 kWh All set-ups 0 75 Uint32 15020
15-03 Power Up's 0 N/A All set-ups 0 0 Uint32 15030
15-04 Over Temp's 0 N/A All set-ups 0 0 Uint16 15040
15-05 Over Volt's 0 N/A All set-ups 0 0 Uint16 15050
15-06 Reset kWh Counter [0] Do not reset All set-ups 1 - Uint8 15060
15-07 Reset Running Hours Counter [0] Do not reset All set-ups 1 - Uint8 15070
15-08 Number of Starts 0 N/A All set-ups 0 0 Uint32 15080
16-0* General Status
16-00 Control Word 0 N/A All set-ups 1 0 V2 16000
16-01 Reference [Unit] 0.000 ReferenceFeedbackUnit All set-ups 1 -3 Int32 16010
16-02 Reference [%] 0.0 % All set-ups 1 -1 Int16 16020
16-03 Status Word 0 N/A All set-ups 1 0 V2 16030
16-05 Main Actual Value [%] 0.00 % All set-ups 1 -2 N2 16050
16-09 Custom Readout 0.00 CustomReadoutUnit All set-ups 1 -2 Int32 16090
16-1* Motor Status
16-10 Power [kW] 0.00 kW All set-ups 1 1 Int32 16100
16-11 Power [hp] 0.00 hp All set-ups 1 -2 Int32 16110
16-12 Motor Voltage 0.0 V All set-ups 1 -1 Uint16 16120
16-13 Frequency 0.0 Hz All set-ups 1 -1 Uint16 16130
16-14 Motor Current 0.00 A All set-ups 1 -2 Int32 16140
16-15 Frequency [%] 0.00 % All set-ups 1 -2 N2 16150
16-16 Torque [Nm] 0.0 Nm All set-ups 1 -1 Int32 16160
16-17 Speed [RPM] 0 RPM All set-ups 1 67 Int32 16170
16-18 Motor Thermal 0% All set-ups 1 0 Uint8 16180
16-22 Torque [%] 0% All set-ups 1 0 Int16 16220
16-3* Drive Status
16-30 DC Link Voltage 0V All set-ups 1 0 Uint16 16300
16-32 Brake Energy /s 0.000 kW All set-ups 1 0 Uint32 16320
16-33 Brake Energy /2 min 0.000 kW All set-ups 1 0 Uint32 16330
16-34 Heatsink Temp. 0 °C All set-ups 1 100 Uint8 16340
16-35 Inverter Thermal 0% All set-ups 1 0 Uint8 16350
16-36 Inv. Nom. Current ExpressionLimit All set-ups 1 -2 Uint32 16360
16-37 Inv. Max. Current ExpressionLimit All set-ups 1 -2 Uint32 16370
16-38 SL Controller State 0 N/A All set-ups 1 0 Uint8 16380
16-39 Control Card Temp. 0 °C All set-ups 1 100 Uint8 16390
16-40 Logging Buffer Full [0] No All set-ups 1 - Uint8 16400
16-5* Ref. & Feedb.
16-50 External Reference 0.0 N/A All set-ups 1 -1 Int16 16500
16-52 Feedback [Unit] 0.000 ProcessCtrlUnit All set-ups 1 -3 Int32 16520
16-53 Digi Pot Reference 0.00 N/A All set-ups 1 -2 Int16 16530
16-54 Feedback 1 [Unit] 0.000 ProcessCtrlUnit All set-ups 1 -3 Int32 16540
16-55 Feedback 2 [Unit] 0.000 ProcessCtrlUnit All set-ups 1 -3 Int32 16550
16-56 Feedback 3 [Unit] 0.000 ProcessCtrlUnit All set-ups 1 -3 Int32 16560
16-58 PID Output [%] 0.0 % All set-ups 1 -1 Int16 16580
16-59 Adjusted Setpoint 0.000 ProcessCtrlUnit All set-ups 1 -3 Int32 16590
16-6* Inputs & Outputs
16-60.0 Digital Input 0 N/A All set-ups 1 0 Uint16 16600 Indexed
16-60.1 Digital Input 1 N/A All set-ups 1 0 Uint17 16600 Indexed
16-60.2 Digital Input 2 N/A All set-ups 1 0 Uint18 16600 Indexed
16-60.3 Digital Input 3 N/A All set-ups 1 0 Uint19 16600 Indexed
16-60.4 Digital Input 4 N/A All set-ups 1 0 Uint20 16600 Indexed
16-61 Terminal 53 Switch Setting [0] Current All set-ups 1 - Uint8 16610
16-62 Analog Input 53 0.000 N/A All set-ups 1 -3 Int32 16620
16-63 Terminal 54 Switch Setting [0] Current All set-ups 1 - Uint8 16630
16-64 Analog Input 54 0.000 N/A All set-ups 1 -3 Int32 16640
16-65 Analog Output 42 [mA] 0.000 N/A All set-ups 1 -3 Int16 16650
16-66 Digital Output [bin] 0 N/A All set-ups 1 0 Int16 16660
16-67 Pulse Input #29 [Hz] 0 N/A All set-ups 1 0 Int32 16670
16-68 Pulse Input #33 [Hz] 0 N/A All set-ups 1 0 Int32 16680
16-69 Pulse Output #27 [Hz] 0 N/A All set-ups 1 0 Int32 16690
16-70 Pulse Output #29 [Hz] 0 N/A All set-ups 1 0 Int32 16700
16-71.0 Relay Output [bin] 0 N/A All set-ups 1 0 Uint16 16710 Indexed
16-71.1 Relay Output [bin] 0 N/A All set-ups 1 0 Uint16 16710 Indexed
16-71.2 Relay Output [bin] 0 N/A All set-ups 1 0 Uint16 16710 Indexed
16-71.3 Relay Output [bin] 0 N/A All set-ups 1 0 Uint16 16710 Indexed
16-71.4 Relay Output [bin] 0 N/A All set-ups 1 0 Uint16 16710 Indexed
16-71.5 Relay Output [bin] 0 N/A All set-ups 1 0 Uint16 16710 Indexed
16-72 Counter A 0 N/A All set-ups 1 0 Int32 16720
16-73 Counter B 0 N/A All set-ups 1 0 Int32 16730
16-8* Fieldbus & FC Port
16-80 Fieldbus CTW 1 0 N/A All set-ups 1 0 V2 16800
16-82 Fieldbus REF 1 0 N/A All set-ups 1 0 N2 16820
16-84 Comm. Option STW 0 N/A All set-ups 1 0 V2 16840
16-85 FC Port CTW 1 0 N/A All set-ups 1 0 V2 16850
16-86 FC Port REF 1 0 N/A All set-ups 1 0 N2 16860
16-9* Diagnosis Readouts
16-90 Alarm Word 0 N/A All set-ups 1 0 Uint32 16900
16-91 Alarm Word 2 0 N/A All set-ups 1 0 Uint32 16910
16-92 Warning Word 0 N/A All set-ups 1 0 Uint32 16920
16-93 Warning Word 2 0 N/A All set-ups 1 0 Uint32 16930
16-94 Ext. Status Word 0 N/A All set-ups 1 0 Uint32 16940
16-95 Ext. Status Word 2 0 N/A All set-ups 1 0 Uint32 16950
16-96 Maintenance Word 0 N/A All set-ups 1 0 Uint32 16960
Holding registers
Register Number Description
00001-00006 00001-00006 Reserved
7 Last error code from an FC data object interface
8 Reserved
9 Parameter index*
00010-00999 000 parameter group (parameters 001 through 099)
01000-01999 100 parameter group (parameters 100 through 199)
02000-02999 200 parameter group (parameters 200 through 299)
03000-03999 300 parameter group (parameters 300 through 399)
04000-04999 400 parameter group (parameters 400 through 499)
... ... ... ...
49000-49999 4900 parameter group (parameters 4900 through 4999)
50000 Input data: Frequency converter control word register (CTW).
50010 Input data: Bus reference register (REF).
... ...
50200 Output data: Frequency converter status word register (STW).
50210 Output data: Frequency converter main actual value register (MAV).
Data Readouts
Par. No. # Parameter description Default value (units) 4-set-up Change during operation Conversion index Type Modbus Address
15-0* Operating Data
15-00 Operating Hours 0h All set-ups 0 74 Uint32 15000
15-01 Running Hours 0h All set-ups 0 74 Uint32 15010
15-02 kWh Counter 0 kWh All set-ups 0 75 Uint32 15020
15-03 Power Up's 0 N/A All set-ups 0 0 Uint32 15030
15-04 Over Temp's 0 N/A All set-ups 0 0 Uint16 15040
15-05 Over Volt's 0 N/A All set-ups 0 0 Uint16 15050
15-06 Reset kWh Counter [0] Do not reset All set-ups 1 - Uint8 15060
15-07 Reset Running Hours Counter [0] Do not reset All set-ups 1 - Uint8 15070
15-08 Number of Starts 0 N/A All set-ups 0 0 Uint32 15080
16-0* General Status
16-00 Control Word 0 N/A All set-ups 1 0 V2 16000
16-01 Reference [Unit] 0.000 ReferenceFeedbackUnit All set-ups 1 -3 Int32 16010
16-02 Reference [%] 0.0 % All set-ups 1 -1 Int16 16020
16-03 Status Word 0 N/A All set-ups 1 0 V2 16030
16-05 Main Actual Value [%] 0.00 % All set-ups 1 -2 N2 16050
16-09 Custom Readout 0.00 CustomReadoutUnit All set-ups 1 -2 Int32 16090
16-1* Motor Status
16-10 Power [kW] 0.00 kW All set-ups 1 1 Int32 16100
16-11 Power [hp] 0.00 hp All set-ups 1 -2 Int32 16110
16-12 Motor Voltage 0.0 V All set-ups 1 -1 Uint16 16120
16-13 Frequency 0.0 Hz All set-ups 1 -1 Uint16 16130
16-14 Motor Current 0.00 A All set-ups 1 -2 Int32 16140
16-15 Frequency [%] 0.00 % All set-ups 1 -2 N2 16150
16-16 Torque [Nm] 0.0 Nm All set-ups 1 -1 Int32 16160
16-17 Speed [RPM] 0 RPM All set-ups 1 67 Int32 16170
16-18 Motor Thermal 0% All set-ups 1 0 Uint8 16180
16-22 Torque [%] 0% All set-ups 1 0 Int16 16220
16-3* Drive Status
16-30 DC Link Voltage 0V All set-ups 1 0 Uint16 16300
16-32 Brake Energy /s 0.000 kW All set-ups 1 0 Uint32 16320
16-33 Brake Energy /2 min 0.000 kW All set-ups 1 0 Uint32 16330
16-34 Heatsink Temp. 0 °C All set-ups 1 100 Uint8 16340
16-35 Inverter Thermal 0% All set-ups 1 0 Uint8 16350
16-36 Inv. Nom. Current ExpressionLimit All set-ups 1 -2 Uint32 16360
16-37 Inv. Max. Current ExpressionLimit All set-ups 1 -2 Uint32 16370
16-38 SL Controller State 0 N/A All set-ups 1 0 Uint8 16380
16-39 Control Card Temp. 0 °C All set-ups 1 100 Uint8 16390
16-40 Logging Buffer Full [0] No All set-ups 1 - Uint8 16400
16-5* Ref. & Feedb.
16-50 External Reference 0.0 N/A All set-ups 1 -1 Int16 16500
16-52 Feedback [Unit] 0.000 ProcessCtrlUnit All set-ups 1 -3 Int32 16520
16-53 Digi Pot Reference 0.00 N/A All set-ups 1 -2 Int16 16530
16-54 Feedback 1 [Unit] 0.000 ProcessCtrlUnit All set-ups 1 -3 Int32 16540
16-55 Feedback 2 [Unit] 0.000 ProcessCtrlUnit All set-ups 1 -3 Int32 16550
16-56 Feedback 3 [Unit] 0.000 ProcessCtrlUnit All set-ups 1 -3 Int32 16560
16-58 PID Output [%] 0.0 % All set-ups 1 -1 Int16 16580
16-59 Adjusted Setpoint 0.000 ProcessCtrlUnit All set-ups 1 -3 Int32 16590
16-6* Inputs & Outputs
16-60 Digital Input 0 N/A All set-ups 1 0 Uint16 16600
16-61 Terminal 53 Switch Setting [0] Current All set-ups 1 - Uint8 16610
16-62 Analog Input 53 0.000 N/A All set-ups 1 -3 Int32 16620
16-63 Terminal 54 Switch Setting [0] Current All set-ups 1 - Uint8 16630
16-64 Analog Input 54 0.000 N/A All set-ups 1 -3 Int32 16640
16-65 Analog Output 42 [mA] 0.000 N/A All set-ups 1 -3 Int16 16650
16-66 Digital Output [bin] 0 N/A All set-ups 1 0 Int16 16660
16-67 Pulse Input #29 [Hz] 0 N/A All set-ups 1 0 Int32 16670
16-68 Pulse Input #33 [Hz] 0 N/A All set-ups 1 0 Int32 16680
16-69 Pulse Output #27 [Hz] 0 N/A All set-ups 1 0 Int32 16690
16-70 Pulse Output #29 [Hz] 0 N/A All set-ups 1 0 Int32 16700
16-71 Relay Output [bin] 0 N/A All set-ups 1 0 Uint16 16710
16-72 Counter A 0 N/A All set-ups 1 0 Int32 16720
16-73 Counter B 0 N/A All set-ups 1 0 Int32 16730
16-75 Analog In X30/11 0.000 N/A All set-ups 1 -3 Int32 16750
16-76 Analog In X30/12 0.000 N/A All set-ups 1 -3 Int32 16760
16-77 Analog Out X30/8 [mA] 0.000 N/A All set-ups 1 -3 Int16 16770
16-8* Fieldbus & FC Port
16-80 Fieldbus CTW 1 0 N/A All set-ups 1 0 V2 16800
16-82 Fieldbus REF 1 0 N/A All set-ups 1 0 N2 16820
16-84 Comm. Option STW 0 N/A All set-ups 1 0 V2 16840
16-85 FC Port CTW 1 0 N/A All set-ups 1 0 V2 16850
16-86 FC Port REF 1 0 N/A All set-ups 1 0 N2 16860
16-9* Diagnosis Readouts
16-90 Alarm Word 0 N/A All set-ups 1 0 Uint32 16900
16-91 Alarm Word 2 0 N/A All set-ups 1 0 Uint32 16910
16-92 Warning Word 0 N/A All set-ups 1 0 Uint32 16920
16-93 Warning Word 2 0 N/A All set-ups 1 0 Uint32 16930
16-94 Ext. Status Word 0 N/A All set-ups 1 0 Uint32 16940
16-95 Ext. Status Word 2 0 N/A All set-ups 1 0 Uint32 16950
16-96 Maintenance Word 0 N/A All set-ups 1 0 Uint32 16960
18-0* Maintenance Log
18-00 Maintenance Log: Item 0 N/A All set-ups 0 0 Uint8 18000
18-01 Maintenance Log: Action 0 N/A All set-ups 0 0 Uint8 18010
18-02 Maintenance Log: Time 0s All set-ups 0 0 Uint32 18020
18-03 Maintenance Log: Date and Time ExpressionLimit All set-ups 0 0 TimeOfDay 18030
18-3* Inputs & Outputs
18-30 Analog Input X42/1 0.000 N/A All set-ups 0 -3 Int32 18300
18-31 Analog Input X42/3 0.000 N/A All set-ups 0 -3 Int32 18310
18-32 Analog Input X42/5 0.000 N/A All set-ups 0 -3 Int32 18320
18-33 Analog Out X42/7 [V] 0.000 N/A All set-ups 0 -3 Int16 18330
18-34 Analog Out X42/9 [V] 0.000 N/A All set-ups 0 -3 Int16 18340
18-35 Analog Out X42/11 [V] 0.000 N/A All set-ups 0 -3 Int16 18350