FMDS0401N
FMDS0401N
FMDS0401N
Table of Contents
Page
List of Figures
Fig. FM-1.
Nozzle and piping arrangement for open tank of flammable liquids. ......................................... 5
Fig. FM-2.
Nozzle and piping arrangement for transformer, using nozzles of ordinary capacity. ............... 7
Fig. FM-3.
Nozzle and piping arrangement for transformer, using large-capacity nozzles. ........................ 8
Fig. FM-4.
Typical water-spray nozzles for fixed systems, illustrating various methods of producing
spray. ......................................................................................................................................... 10
Fig. FM-5. Typical nozzle-discharge patterns. ............................................................................................ 11
List of Tables
Table FM-1. FM Global Data Sheets and Standards of the National Fire Protection Association. .............. 3
Table FM-2. Nozzle Location, Size, and Discharge Pressures for Open Tank Protection. ........................... 6
©2010 Factory Mutual Insurance Company. All rights reserved. No part of this document may be reproduced,
stored in a retrieval system, or transmitted, in whole or in part, in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without written permission of Factory Mutual Insurance Company.
4-1N Fixed Water Spray Systems For Fire Protection
Page 2 FM Global Property Loss Prevention Data Sheets
1.0 SCOPE
FM Global has accepted and adopted NFPA Standard 15, Standard for Water Spray Fixed Systems for Fire
Protection, 2001 Edition.
This data sheet addresses design and installation of fixed water spray systems as it pertains to the
conservation and protection of property.
1.1 Changes
May 2010. Replaced all references to Data Sheet 2-8N, Installation of Sprinkler Systems (NFPA), with
references to Data Sheet 2-0, Installation Guidelines for Automatic Sprinklers.
2.1 Introduction
Design and install fixed water spray systems for fire protection in accordance with the requirement of NFPA
15, Standard for Water Spray Fixed Systems for Fire Protection, 2001 Edition, and the interpretations
included in this data sheet.
2.2.1 Protection
2.2.1.1 Treat ‘‘Appendix A’’ material in NFPA 15 as recommended practice applicable to FM Global insured
locations.
2.2.1.2 Use of Water Spray. In addition to the uses and applications provided in NFPA 15, fixed water spray
systems may be used to prevent the spread of fire, hot gases and smoke through wall or floor openings.
Certain nozzles are specifically Approved for this use at openings in important walls where it is not possible
to install automatically closing fire doors. Where fixed water spray systems are used to protect openings,
design the system in accordance with FM Global Data Sheet 1-23, Protection of Openings in Fire
Subdivisions, to discharge directly into the opening at 2.0 to 4.0 gpm/ft2 (81.5 to 163 mm/min), depending
on the height of the opening above the floor level. The use of fixed water spray systems is not considered
equivalent protection or fire cut off as physical barriers. Methods of providing water spray protection for
conveyor belt openings are described in Data Sheet 1-23.
2.2.1.3 Automatic vs. Manual Operation. Use automatic systems with control valves locked or supervised
in the open position. Manually operated systems can be accepted under limited hazard conditions and where
failure to turn on the system would not result in serious consequences. Where manually operated systems
become acceptable, use preferentially quick-opening valves of small diameter, instead of OS&Y valves, and
provide the system with automatic fire detection and alarm.
2.2.1.4 Pipe having wall thickness conforming with Schedule 10 (10S) can be used in sizes 4, 5 and 6 inches
(100, 150 and 200 mm) when joined by welding or Approved joints.
2.2.1.5 The interior of piping used in open-nozzle water spray systems is subject to the same extent of
corrosion as the exterior of the pipe. If galvanizing is considered not suitable protection against corrosion
on the exterior, similarly it is unsuitable on the interior of the pipe. Do not use galvanized pipe for systems
intended for extinguishment, where one obstructed nozzle by scale or other corrosion by-product can result
in failure to achieve extinguishment.
2.2.1.6 Design water spray systems to conform to the applicable requirements of the following FM Global
Data Sheets and Standards of the National Fire Protection Association.
Table FM-1. FM Global Data Sheets and Standards of the National Fire Protection Association.
Title FM Global Data Sheet (NFPA Standard)
Installation of Sprinkler Systems Data Sheet 2-0
Installation of Standpipe and Hose Systems Data Sheet 4-4N (NFPA 14)
Deluge-Foam Sprinkler and Spray Systems Data Sheet 4-12
Fire Protection Pumps Data Sheet 3-7
Water Tanks For Private Fire Protection Data Sheet 3-1 & 3-2 (NFPA 22)
Outside Protection Data Sheet 3-10 (NFPA 24)
Inspection and System Maintenance Data Sheet 2-81
National Electrical Code NFPA 70
National Fire Alarm Code NFPA 72
Protection From Exposure Fires Data Sheet 1-20 (NFPA 80A)
Protection of Openings in Fire Subdivisions Data Sheet 1-23
Cooling Towers Data Sheet 1-6 (NFPA 214)
Transformers Data Sheet 5-4
Conveyors Data Sheet 7-11
Cable Runs and Bus Bars Data Sheet 5-31
Industrial Ovens and Dryers Data Sheet 6-9
Fire & Explosion Protection for Flammable Liquid, Flammable Gas & Data Sheet 7-14
Liquefied Flammable Gas Processing Equipment & Supporting Structures
2.2.1.7 For flammable liquid and liquefied flammable gas processing equipment and supporting structures
located indoors, design water supply assuming discharge from all nozzles within the building ground floor
areas up to 10,000 ft2 (930 m2).
2.2.1.8 Provide automatic starting water supplies, i.e., water supplies which are available to the system without
the need for manual operation of valves or pumps, and which are as reliable as the supplies used for
automatic sprinkler systems. In very large systems (2000 gpm or higher) supplied principally by pumps,
provide additional or reserve capacity so that the system can function effectively in case one of the water
supply pumps is out of service for repair or maintenance.
2.2.1.9 Where water spray systems are used for protection of remotely located transformers, provide water
supply (pressure tanks or other source of supply in accordance with NFPA 15) with at least 60 minute
duration, in accordance with Data Sheet 5-4, Transformers.
2.2.1.10 Density and Application. Provide a minimum nozzle discharge pressure of at least 20 psi (138 kPa)
(1.4 bar) so that the system can maintain a good distribution pattern. Outdoor installations with nozzles less
than 1⁄2 in. (12 mm) nominal diameter provide 30 psi (207 kPa) (2.2 bar) for proper discharge pattern and
spray protection against moderately intense wind. Outdoor systems with nozzles 1⁄2 in (12 mm) and larger
require at least 20 psi (138 kPa) (1.4 bar) discharge pressure for proper discharge pattern against moderately
intense wind.
For indoor installations, 20 psi (138 kPa) (1.4 bar) discharge pressure is adequate for spray nozzles properly
located over open tanks containing high flashpoint liquids, such as quench oil. For liquids similar to Kerosene,
30 to 100 psi (207 to 689 kPa) (2.1 to 6.9 bar) discharge pressure is required, depending upon the spacing
and the discharge characteristics of the nozzle.
2.2.1.11 Open Tank Protection. For protection of dip tanks, flow coaters and roll coaters use the
recommendations in Data Sheet 7-9, Dip Tanks, Flow Coaters and Roll Coaters, in addition to requirements
of NFPA 15.
Fixed water-spray systems designed in accordance with NFPA 15 are suitable for protection of fires in open
tanks of flammable liquids with flash points above 140°F (60°C) (hazards equivalent to or less than kerosene,
quench oil and transil oil). The design should be based on spacing and discharge pressure as specified for
the particular nozzles in Table FM-2.
Arrange nozzles to provide an adequate amount of water at sufficient velocity to penetrate through fire and
updraft and contact the liquid surface without creating excessive turbulence. An example of the arrangement
of nozzles and piping for open tank protection is given in Figure FM-1.
To protect against spread of fire from boilover, extend spray-nozzle protection a distance of 10 to 20 ft (3
to 6 m) beyond tanks containing liquids that are or may become heated to 212°F (100°C) or above in
production operations.
Fig. FM-1. Nozzle and piping arrangement for open tank of flammable liquids.
Table FM-2. Nozzle Location, Size, and Discharge Pressures for Open Tank Protection.
Recommended distance,
Nozzle to hazard, ft (m) Spacing, ft (m), and discharge pressure to extinguish, psi (bar)*
Nominal For liquids similar to quench and
orifice Indoors Outdoors For liquids similar to kerosene transil oil
size and 4x4 6x6 8x8 4x4 6x6 8x8
discharge
(1.2 x (1.8 x (2.4 x (1.2 x (1.8 x (2.4 x
rate at 50 Cone
psi (3.4 angle of 1.2) 1.8) 2.4) 1.2) 1.8) 2.4)
bar) spray, ° Minimum Maximum Maximum spacing spacing spacing spacing spacing spacing
1⁄2in. 160-180 5 (1.5) 14 (4.3) 7 (2.1) 35 (2.4) 40 (2.8) 20 (1.4) 20 (1.4)
(12.7 6 (1.8) 14 (4.3) 7 (2.1) 45 (3.1) 50 (3.4) 20 (1.4) 20 (1.4)
mm) 7 (2.1) 16 (4.9) 8 (2.4) 60 (4.1) 65 (4.5) 30 (2.1) 30 (2.1)
37-42 125-140 9 (2.7) 18 (5.5) 12 (3.7) 75 (5.2) 75 (5.2) 30 (2.1) 30 (2.1)
gpm
(140-159 90-110
dm3/min) 60-80
3⁄8 in. 160-180 4 (1.2) 12 (3.7) 6 (1.8) 30 (2.1) 40 (2.8) 50 (3.4) 20 (1.4) 20 (1.4) 20 (1.4)
(9.5 mm) 5 (1.5) 13 (4.0) 6.5 (2.0) 40 (2.8) 50 (3.4) 50 (3.4) 20 (1.4) 20 (1.4) 20 (1.4)
20-24 125-140 6 (1.8) 14 (4.3) 7 (2.1) 50 (3.4) 65 (4.5) 75 (5.2) 20 (1.4) 30 (2.1) 30 (2.1)
gpm 8 (2.4) 16 (4.9) 11 (3.4) 65 (4.5) 75 (5.2) 90 (6.2) 30 (2.1) 30 (2.1) 30 (2.1)
(76-91 90-110
dm3/min) 60-80
1⁄4 in. 160-180 2 (0.6) 8 (2.4) 4 (1.2) 40 (2.8) 60 (4.1) 75 (5.2) 20 (1.4) 30 (2.1) 30 (2.1)
(6.4 mm) 3 (0.9) 8 (2.4) 4 (1.2) 50 (3.4) 70 (4.8) 90 (6.2) 30 (2.1) 30 (2.1) 30 (2.1)
8-12 125-140 5 (1.5) 10 (3.0) 5 (1.5) 75 (5.2) 80 (5.6) 30 (2.1) 30 (2.1)
gpm 6 (1.8) 12 (3.7) 8 (2.4) 90 (6.2) 30 (2.1)
(30-45 90-110
dm3/min) 60-80
*1 bar = 100 kPa
2.2.1.12 Exposure Protection of Transformers. For exposure protection of transformers use the
recommendations in Data Sheet 5-4, Transformers, in addition to requirements of NFPA 15.
Weatherproof any indoor-type transformers and associated electrical devices protected by water spray. This
is needed to prevent electrical breakdown, unless individual transformers are in separate curbed and drained
areas with baffles extending from the ceiling to below the lowest spray nozzles and a separate spray system
is provided at each transformer. Use carbon dioxide (or other applicable gaseous suppression systems)
instead of fixed water spray systems where transformers have openings in the top (as some used with
electric-arc furnaces) and/or where it is impractical to make the transformers watertight.
Water-spray systems using nozzles of various patterns are suitable for protection of oil-filled transformers
and for exposure protection of adjacent transformers and associated equipment (Fig. FM-2). Large
transformers are more easily protected by large-capacity nozzles because their greater discharge and range
permit simpler piping arrangements. Also, the large-capacity nozzles better overcome the effects of wind
currents (Fig. FM-3). To extinguish fire in transil oil flowing over a transformer case, over cooling radiators,
and the surrounding pit area locate and direct nozzles to cover the entire surface with water spray.
2.2.1.13 Protection of Cable Trays and Cable Runs. For protection of cable trays and cable runs use the
recommendations in Data Sheet 5-31, Cables and Bus Bars, in addition to requirements of NFPA 15.
2.2.1.14 Protection of Belt Conveyors. For protection of conveyor belts use the recommendations in Data
Sheet 7-11, Conveyors, in addition to requirements of NFPA 15.
2.2.1.15 Protection of Cooling Towers. For protection of Cooling Towers use the recommendations in
FM Global Loss Prevention Data Sheet 1-6, Cooling Towers, in addition to requirements of NFPA 15.
2.2.1.16 Protection of Ovens & Dryers. Spray nozzles with a flat fan-shaped discharge are suitable for
horizontal multipass dryers handling large sheets of combustible stock, such as wallboard, where space
limitations and the arrangement of racks and rolls would interfere with proper spacing and distribution of
automatic sprinklers. This spray nozzle discharges a small quantity of water over a large horizontal area. For
further details on fire protection in ovens and dryers refer to Data Sheet 6-9, Industrial Ovens and Dryers.
Fig. FM-2. Nozzle and piping arrangement for transformer, using nozzles of ordinary capacity. Upper-level nozzle piping
shown by full line, lower-level by dash line. Both levels same distance from transformer.
Fig. FM-3. Nozzle and piping arrangement for transformer, using large-capacity nozzles. Upper-level nozzle piping shown
by line, lower level by dash line. Both levels same distance from transformer.
2.2.1.17 Protection of Engine Test Cells. Solid-cone, narrow-angle spray nozzles are suitable for test cells
for jet engines and other highspeed, high-fuel-demand engines, where it is necessary to project the spray
through rapidly moving air and to provide for rapid absorption of heat liberated by the burning fuel. Spilled
flammable liquid acquires little depth, and water spray successfully prevents damage to cells and test
structures.
2.2.1.18 Protection of Chemical Process Areas. Protect chemical process areas and other flammable material
processing areas in accordance with Data Sheet 7-14, Fire & Explosion Protection for Flammable Liquid,
Flammable Gas & Liquefied Flammable Gas Processing Equipment & Supporting Structures.
Fig. FM-4. Typical water-spray nozzles for fixed systems, illustrating various methods of producing spray.
liquids of low viscosity, emulsification is probably temporary, existing only during the application of the spray.
With materials of higher viscosity, the emulsion will last longer and provide some protection against
re-flashing.
Dilution of water-soluble liquids is usually a minor factor in extinguishing a fire because of the high degree
of dilution required.
4.0 REFERENCES
4.1 FM Global
Data Sheet 2-0, Installation Guidelines for Automatic Sprinklers.
Data Sheet 2-8, Earthquake Protection for Water-Based Fire Protection Systems.
Data Sheet 3-2, Water Tanks for Fire Protection.
Data Sheet 3-7, Fire Protection Pumps.
Data Sheet 4-12, Foam Extinguishing Systems
Data Sheet 6-9, Industrial Ovens and Dryers.