Site Inspection and Test Record: (Acceptance Test) T601 SET 1
Site Inspection and Test Record: (Acceptance Test) T601 SET 1
Site Inspection and Test Record: (Acceptance Test) T601 SET 1
1. GENERAL INFORMATION.
Item Description
1 Inspect for physical damage / defects. Yes N/A
2 Verify connections as per approved drawing. Yes N/A
3 Check tightness of all connections. Yes N/A
3. TRANSFORMER DATA:
Rated Current Prim HV: 251A Rated Current Prim LV: 2092A
Rated Current Sec HV: 0.418A Rated Current Sec LV: 0.523A
4. Electrical Checks:
Item Description
1 Human Machine Interface [ HMI ] checked. Yes N/A
2 Test switch checked for correct function. Yes N/A
3 Case earthling checked. Yes N/A
4 Indications checked. Yes N/A
5 Binary Input checked Yes N/A
6 Checked all binary output configured as per scheme Yes N/A
7 Disturbance Report Function checked Yes N/A
8 Reset of indications checked. Yes N/A
5. Secondary Injection
5.1. Measurements:
Note:
Zero Sequence is depend on The Type of Fault & The Vector Group i.e. when Zero Sequence
Subtraction is ON:
STAR DELTA
ZS = 1.5 (for 1PH faults) ; ZS = 1.732 (for PH-PH faults )
ZS = 1 (for 3PH faults) ; ZS = 1.0 (for 3-PH faults)
Operating
Input Set Calculated Measured Value
Phase Time @ Remarks
Wdg - CT Value value
Pick up Drop out 2X I set
W1 0.3 In -- -- -- --
R
W2 0.3 In 0.235 0.239 0.228 31.0
W1 0.3 In -- -- -- --
Y
W2 0.3 In 0.235 0.239 0.228 29.0
OK
W1 0.3 In -- -- -- --
B
W2 0.3 In 0.235 0.239 0.228 30.0
W1 0.3 In -- -- -- --
RYB
W2 0.3 In 0.157 0.157 0.150 32.0
Limit: ±2.0%Ir, Reset ratio>95% MANUAL- IMRK504048 PAGE#121
Operating
Input Set Calculated Measured Value
Phase Time @ Remarks
Wdg - CT Value value
Pick up Drop out 2X I set
W1 0.3 In 0.217 0.218 0.207 29.0
R
W2 0.3 In -- -- -- --
W1 0.3 In 0.217 0.218 0.208 27.1
Y
W2 0.3 In -- -- -- --
OK
W1 0.3 In 0.217 0.218 0.208 29.1
B
W2 0.3 In -- -- -- --
W1 0.3 In 0.126 0.126 0.120 30.0
RYB
W2 0.3 In -- -- -- --
Limit: ±2.0%Ir, Reset ratio>95% MANUAL- IMRK504048 PAGE#121
Operating
Input Set Calculated Measured
Phase Time @ 2X Remarks
Wdg - CT Value value Value
I set
W1 10 In -- -- --
R
W2 10 In 7.844 7.80 18
W1 10 In -- -- --
Y
W2 10 In 7.844 7.81 17
OK
W1 10 In -- -- --
B
W2 10 In 7.844 7.79 18
W1 10 In -- -- --
RYB
W2 10 In 5.23 5.19 21.0
Limit: ±2.0%Ir, Reset ratio>95% MANUAL- IMRK504048 PAGE#121
Operating
Input Set Calculated Measured
Phase Time @ 2X Remarks
Wdg - CT Value value Value
I set
W1 10 In 7.246 7.22 18
R
W2 10 In -- -- --
W1 10 In 7.246 7.24 19
Y
W2 10 In -- -- --
OK
W1 10 In 7.246 7.24 19
B
W2 10 In -- -- --
W1 10 In 4.184 4.18 19
RYB
W2 10 In -- -- --
Limit: ±2.0%Ir, Reset ratio>95% MANUAL- IMRK504048 PAGE#121
HV SIDE LV SIDE
PHASE Setting
Inject I Inject I % Inject I Inject I %
60 Hz 120 Hz Meas. 60 Hz 120 Hz Meas.
R 1.00 0.149 14.9 1.00 0.149 14.9
Y 15% 1.00 0.149 14.9 1.00 0.149 14.9
B 1.00 0.149 14.9 1.00 0.149 14.9
Limit: ±2.0%Ir MANUAL- IMRK504048 PAGE#122
HV SIDE LV SIDE
PHASE Setting Inject I Inject I % Inject I Inject I %
60 Hz 300 Hz Meas. 60 Hz 300 Hz Meas.
R 1.00 0.307 30.7 1.00 0.307 30.7
Y 30% 1.00 0.309 30.9 1.00 0.307 30.7
B 1.00 0.309 30.9 1.00 0.308 30.8
Limit: ±5.0%Ir MANUAL- IMRK504048 PAGE#122
5.2.9. Id ALARM:
Operating
Input Set Calculated Measured
Phase Time @ Remarks
Wdg - CT Value value Value
2X I set
W1 0.2 In 0.084 0.085 10.022
RYB OK
W2 0.2 In 0.105 0.106 10.023
Limit: ±2.0%Ir, Reset ratio>95% MANUAL- IMRK504048 PAGE#121
NOTE: Id Alarm is always three phase as described in logicdiagram of manual no. 504113
(TRM) page no 137.
Slope %
IBIAS BALANCE(A) TRIP (A) (A)
Calculated
Idiff I bias Idiff Ibias
HV LV HV LV
MEAS. MEAS. CALC. CALC.
L1
L3
3 phase HV calculated current was injected. While yellow and blue phases were reversed.
A little less than calculated LV 3 phase current was injected at an angle of zero degree with
respect to HV winding. While yellow and blue phases were reversed.
LV current was increased slowly until NEG SEQ SENS and TRIP LEDs appeared at the same
time.
3 phase HV/ LV calculated current was injected keeping phase difference between HV and
LV equal to zero. While yellow and blue phases were reversed.
Now change angle for LV 3 phases together to get operating angle boundaries.
Where
1. is Differential Current
2. is Differential Current Contribution from W1 side
3. is Differential Current Contribution from W2 side
4. is Differential Current Contribution from W3 side
A, B, C is a coefficients depended on vector group; refer to Manual to get exact value.
Time @ 2X Is
Phase Setting (A) Pick Up Remarks
(mSec)
R 2.002 33.0
Y 2 In 2.001 29.9
B 2.002 38.4
Limit: ±1.0%Ir, Reset ratio>95% MANUAL- IMRK504048 PAGE#183
TMS=1.0
Cal. time Measured time (sec)
Curve
@ 3* IS Phase Stage 1
ANSI ext. Inverse 3.646 A 03.61
ANSI very inverse 2.942 B 02.93
ANSI Normal inverse 0.405 C 00.43
ANSI Moderately inverse 2.432 A 02.43
IEC normal inverse 6.3 C 06.31
IEC very inverse 6.75 A 06.79
IEC ext. Inverse 10 B 10.03
IEC short time inverse 1.112 C 01.16
IEC Long time inverse 60 A 60.04
IEC Definite time 1.0 B 01.03
Limit: ±10 ms MANUAL- IMRK504048 PAGE#183
Time @ 2X Is
Phase Setting (A) Pick Up Remarks
(mSec)
IN1> 0.5 In 0.501 37.7
Limit: ±1.0%Ir, Reset ratio>95% MANUAL- IMRK504048 PAGE#199
7.2. IDMT.
Current
I K Value Value
2XIs
1 In 1.0 2.000 10.02 10.04
R
1 In 0.5 2.000 05.01 05.04
1 In 1.0 2.000 10.02 10.04
Y
1 In 0.5 2.000 05.01 05.03
1 In 1.0 2.000 10.02 10.05
B
1 In 0.5 2.000 05.01 05.05
Limit: time clas5+40ms MANUAL- IMRK504048 PAGE#714