Derating in Switchboards

The document discusses factors that affect switchboard design including temperature, ventilation, installed devices, enclosure size, and installation mode. It provides tables showing maximum current ratings for different sizes of Masterpact circuit breakers in switchboards under varying ambient temperatures and ventilation conditions.

Uploaded by

venkal_vk
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
4 views

Derating in Switchboards

The document discusses factors that affect switchboard design including temperature, ventilation, installed devices, enclosure size, and installation mode. It provides tables showing maximum current ratings for different sizes of Masterpact circuit breakers in switchboards under varying ambient temperatures and ventilation conditions.

Uploaded by

venkal_vk
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

Derating in switchboards

Factors affecting switchboard design Basis of tables


The temperature around the circuit breaker and its b switchboard dimensions
connections: b number of circuit-breakers installed
7KLVLVXVHGWRGH¿QHWKHW\SHRIFLUFXLWEUHDNHUWREH b type of breaker connections
used and its connection arrangement. b drawout versions
b ambient temperature outside of the switchboard: Ta (IEC 60439-1).
Vents at the top and bottom of the cubicles:
Vents considerably reduce the temperature inside the
switchboard, but must be designed so as to respect the
degree of protection provided by the enclosure.
For weatherproof heavy-duty cubicles, a forced
ventilation system may be required.
The heat dissipated by the devices installed in the
switchboard:
This is the heat dissipated by the circuit breakers under
normal conditions (service current).
The size of the enclosure:
This determines the volume for cooling calculations.
Switchboard installation mode:
Free-standing, against a wall, etc.
Horizontal partitions:
Partitions can obstruct air circulation within the
enclosure.

Masterpact NT06-16 H1/H2/L1 (switchboard 2000 x 400 x 400) - area of outlet vents: 150 cm2
Type NT06 H1/H2/L1 NT08 H1/H2/L1 NT10 H1/H2/L1 NT12 H1/H2 NT16 H1/H2
Switchboard composition
4
3
2
1

Connection type

Busbar dimensions (mm) 2b. 40 x 5 2b. 50 x 5 3b. 63 x 5 3b. 63 x 5 3b. 80 x 5


3b. 50 x 5 3b. 63 x 5
Ventilated switchboard 4 H1/L1 H1/L1
(➨ IP31) 3 630 630 800 800 1000/1000 1000/1000 1250 1250 1400 1520
2
DB108437.eps

Ta = 35 °C
1
4
3 630 630 800 800 1000/950 1000/1000 1250 1250 1330 1440
Ta = 45 °C
2
1
4
3 630 630 800 800 1000/890 1000/960 1200 1250 1250 1340
Ta = 55 °C
2
1

(1) Area of outlet vents: 150 cm².


(2) Area of inlet vents: 150 cm².
Non ventilated switchboard 4
(➨ IP54) 3 630 630 800 800 1000/960 1000/1000 1250 1250 1330 1400
Ta = 35 °C 2
Db101495.eps

1
4
3 630 630 800 800 1000/910 1000/980 1220 1250 1260 1330
Ta = 45 °C
2
1
4
3 630 630 800 800 1000/860 1000/930 1150 1230 1200 1260
Ta = 55 °C 2
1

Note: the values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot
replace industrial experience or a temperature rise test.
The values indicated for the cross-sectional area of the vents should be considered as general indications only given that the thermal performance of a switchboard
ZLWKQDWXUDOYHQWLODWLRQGHSHQGVRQPDQ\SDUDPHWHUVHJVKDSHSRURVLW\DQGORFDWLRQRIYHQWVDQGDLUÀRZZLWKLQWKHVZLWFKERDUG

B-15
Installation Derating in switchboards
recommendations

Masterpact NT06-08 H1/H2/L1 (switchboard 2300 x 1100 x 500) - area of outlet vents: 300 cm²
Type NT06 H1/H2/L1 NT08 H1/H2/L1
Switchboard composition
5
4
3
2
1

Connection type

Busbar dimensions (mm) 2b. 40 x 5 2b. 50 x 5

Ventilated switchboard (➨ IP31) 5 630 630 800


4 630 630 630 800 800
DB108444.eps

3 630 630 630 630 800 800 800


Ta = 35 °C
2 630 630 630 630 630 630 800 800 800 800 800
1 630
5 630 630 800
4 630 630 630 800 800
Ta = 45 °C 3 630 630 630 630 800 800 800
2 630 630 630 630 630 630 800 800 800 800 800
1 630
5 630 630 800
4 630 630 630 800 800
Ta = 55 °C 3 630 630 630 630 800 800 800
2 630 630 630 630 630 630 800 800 800 800 800
1 630
(1) Area of outlet vents: 300 cm².
(2) Area of inlet vents: 300 cm².
Non ventilated switchboard 5 630 630 800
(➨ IP54) 4 630 630 630 800 800
3 630 630 630 630 800 800 800
Db101489.eps

Ta = 35 °C
2 630 630 630 630 630 630 800 800 800 800 800
1 630
5 630 630 800
4 630 630 630 800 800
Ta = 45 °C 3 630 630 630 630 800 800 800
2 630 630 630 630 630 630 800 800 800 800 800
1 630
5 630 630 800
4 630 630 630 800 800
Ta = 55 °C 3 630 630 630 630 800 800 800
2 630 630 630 630 630 630 800 800 800 800 800
1 630

Note: the values indicated in these tables have been extrapolated from test data and theoretical
calculations. These tables are only intended as a guide and cannot replace industrial experience
or a temperature rise test.
The values indicated for the cross-sectional area of the vents should be considered as general
indications only given that the thermal performance of a switchboard with natural ventilation
GHSHQGVRQPDQ\SDUDPHWHUVHJVKDSHSRURVLW\DQGORFDWLRQRIYHQWVDQGDLUÀRZZLWKLQWKH
switchboard.

B-16
Masterpact NT10-16 H1/H2/L1 (switchboard 2300 x 1100 x 500) - area of outlet vents: 300 cm²
Type NT10 H1/H2/L1 NT12 H1/H2 NT16 H1/H2
Switchboard composition
5
4
3
2
1

Connection type

Busbar dimensions (mm) 3b. 63 x 5 3b. 63 x 5 3b. 80 x 5


2b. 63 x 5 3b. 50 x 5 3b. 63 x 5
Ventilated switchboard (➨ IP31) 5 H1/L1 H1/L1 H1/L1
H1/L1
4 1000/1000 1250
DB108444.eps

3 1000/10001000/1000 1250 1250 1500


Ta = 35 °C
2 1000/10001000/10001000/10001000/1000 1250 1250 1250 1250 1460 1600 1550
1
5
4 1000/1000 1250
Ta = 45 °C 3 1000/10001000/1000 1250 1250 1420
2 1000 /960 1000/10001000/10001000/1000 1250 1250 1250 1250 1400 1500 1480
1
5
4 1000 /920 1250
Ta = 55 °C 3 1000 /950 1000 /930 1250 1250 1330
2 1000 /900 1000/1000 1000 /970 1000 /950 1250 1250 1250 1250 1300 1400 1370
1
(1) Area of outlet vents: 300 cm².
(2) Area of inlet vents: 300 cm².
Non ventilated switchboard 5
(➨ IP54) 4 1000 /950 1250
3 1000/1000 1000 /960 1250 1250 1370
Db101489.eps

Ta = 35 °C
2 1000/10001000/10001000/1000 1000 /970 1250 1250 1250 1250 1400 1500 1400
5
4 1000 /900 1180
Ta = 45 °C
3 1000 /950 1000 /910 1250 1190 1300
2 1000 /950 1000/1000 1000 /960 1000 /930 1250 1250 1250 1220 1350 1430 1320
5
4 1000 /850 1120
Ta = 55 °C
3 1000 /900 1000 /860 1200 1130 1210
2 1000 /880 1000 /970 1000 /910 1000 /870 1210 1250 1210 1150 1250 1350 1250

Note: the values indicated in these tables have been extrapolated from test data and theoretical
calculations. These tables are only intended as a guide and cannot replace industrial experience
or a temperature rise test.
The values indicated for the cross-sectional area of the vents should be considered as general
indications only given that the thermal performance of a switchboard with natural ventilation
GHSHQGVRQPDQ\SDUDPHWHUVHJVKDSHSRURVLW\DQGORFDWLRQRIYHQWVDQGDLUÀRZZLWKLQWKH
switchboard.

B-17
Installation Derating in switchboards
recommendations

Masterpact NW08-10 N/H/L (switchboard 2300 x 800 x 900) - area of outlet vents: 350 cm²
Type NW08 N/H/L NW10 N/H/L
Switchboard composition
4
3
2
1

Connection type

Busbar dimensions (mm) 2b. 50 x 5 3b. 63 x 5


2b. 63 x 5
Ventilated switchboard (➨ IP31) 4 800
3 800 800 1000
DB108438.eps

Ta = 35 °C 2 800 800 800 1000 1000


1 800 800 800 800 800 1000 1000 1000 1000
4 800
3 800 800 1000
Ta = 45 °C
2 800 800 800 1000 1000
1 800 800 800 800 800 1000 1000 1000 1000
4 800
3 800 800 1000
Ta = 55 °C
2 800 800 800 1000 1000
1 800 800 800 800 800 1000 1000 1000 1000

(1) Area of outlet vents: 350 cm².


(2) Area of inlet vents: 350 cm².
Non ventilated switchboard 4 800
(➨ IP54) 3 800 800 1000
2 800 800 800 1000 1000
Db101491.eps

Ta = 35 °C
1 800 800 800 800 800 1000 1000 1000 1000
4 800
3 800 800 1000
Ta = 45 °C
2 800 800 800 1000 1000
1 800 800 800 800 800 1000 1000 1000 1000
4 800
3 800 800 1000
Ta = 55 °C
2 800 800 800 1000 1000
1 800 800 800 800 800 1000 1000 1000 1000

Note: the values indicated in these tables have been extrapolated from test data and theoretical
calculations. These tables are only intended as a guide and cannot replace industrial experience
or a temperature rise test.
The values indicated for the cross-sectional area of the vents should be considered as general
indications only given that the thermal performance of a switchboard with natural ventilation
GHSHQGVRQPDQ\SDUDPHWHUVHJVKDSHSRURVLW\DQGORFDWLRQRIYHQWVDQGDLUÀRZZLWKLQWKH
switchboard.

B-18
Masterpact NW12-16 N/H/L (switchboard 2300 x 800 x 900) - area of outlet vents: 350 cm²
Type NW12 N1 NW12 H/L NW16 N1 NW16 H/L
Switchboard composition
4
3
2
1

Connection type

Busbar dimensions (mm) 3b. 63 x 5 3b. 63 x 5 3b. 80 x 5 3b. 80 x 5


3b. 50 x 5 3b. 50 x 5 3b. 63 x 5 3b. 63 x 5
Ventilated switchboard (➨ IP31) 4
3 1250 1250
DB108438.eps

Ta = 35 °C 2 1250 1250 1250 1250 1600 1600


1 1250 1250 1250 1250 1250 1250 1250 1250 1550 1600 1600 1600 1600 1600
4
3 1250 1250
Ta = 45 °C
2 1250 1250 1250 1250 1500 1600
1 1250 1250 1250 1250 1250 1250 1250 1250 1470 1600 1600 1600 1600 1600
4
3 1250 1250
Ta = 55 °C
2 1250 1250 1250 1250 1380 1470
1 1250 1250 1250 1250 1250 1250 1250 1250 1380 1500 1500 1520 1600 1600

(1) Area of outlet vents: 350 cm².


(2) Area of inlet vents: 350 cm².
Non ventilated switchboard 4
(➨ IP54) 3 1240 1250
2 1250 1250 1250 1250 1425 1600
Db101491.eps

Ta = 35 °C
1 1250 1250 1250 1250 1250 1250 1250 1250 1440 1550 1550 1600 1600 1600
4
3 1170 1250
Ta = 45 °C
2 1210 1210 1250 1250 1360 1500
1 1200 1250 1250 1250 1250 1250 1250 1250 1360 1470 1470 1500 1600 1600
4
3 1100 1250
Ta = 55 °C
2 1140 1170 1250 1250 1280 1400
1 1130 1200 1200 1200 1250 1250 1250 1250 1280 1380 1380 1400 1520 1520

Note: the values indicated in these tables have been extrapolated from test data and theoretical
calculations. These tables are only intended as a guide and cannot replace industrial experience
or a temperature rise test.
The values indicated for the cross-sectional area of the vents should be considered as general
indications only given that the thermal performance of a switchboard with natural ventilation
GHSHQGVRQPDQ\SDUDPHWHUVHJVKDSHSRURVLW\DQGORFDWLRQRIYHQWVDQGDLUÀRZZLWKLQWKH
switchboard.

B-19
Installation Derating in switchboards
recommendations

Masterpact NW20-40 N/H/L (switchboard 2300 x 800 x 900) - area of outlet vents: 350 cm²
Type NW20 H1/H2/H3 NW20 L1 NW25 H1/2/3 NW32 H1/2/3 NW40 H1/2/3
Switchboard composition
4
3
2
1

Connection type

Busbar dimensions (mm) 3b. 100 x 5 3b. 100 x 5 4b. 100 x 5 3b. 100 x 10 4b. 100 x 10
Ventilated switchboard (➨ IP31) 4
3 2000 1830
DB108438.eps

Ta = 35 °C 2 2000 2000 2000 2000 2000 2000 2375 2500 3040 3200 3320 3700
1
4
3 2000 1750
Ta = 45 °C
2 2000 2000 2000 1810 1960 1920 2250 2380 2880 3100 3160 3500
1
4
3 2000 1640
Ta = 55 °C
2 2000 2000 2000 1700 1850 1800 2100 2250 2690 2900 2960 3280
1

(1) Area of outlet vents: 350 cm².


(2) Area of inlet vents: 350 cm².
Non ventilated switchboard 4
(➨ IP54) 3 2000 1750
2 2000 2000 2000 1800 1900 1890 2125 2275 2650 2850 3040 3320
Db101491.eps

Ta = 35 °C
1
4
3 1900 1660
Ta = 45 °C
2 1900 1960 1960 1680 1810 1800 2000 2150 2550 2700 2880 3120
1
4
3 1780 1550
Ta = 55 °C
2 1800 1920 1920 1590 1700 1700 1900 2020 2370 2530 2720 2960
1

Note: the values indicated in these tables have been extrapolated from test data and theoretical
calculations. These tables are only intended as a guide and cannot replace industrial experience
or a temperature rise test.
The values indicated for the cross-sectional area of the vents should be considered as general
indications only given that the thermal performance of a switchboard with natural ventilation
GHSHQGVRQPDQ\SDUDPHWHUVHJVKDSHSRURVLW\DQGORFDWLRQRIYHQWVDQGDLUÀRZZLWKLQWKH
switchboard.

B-20
Masterpact NW40b-63 H1/H2 (switchboard 2300 x 1400 x 1500) - area of outlet vents: 500 cm²
Type NW40b H1/H2 NW50 H1/H2 NW63 H1/H2
Switchboard composition
4
3
2
1

Connection type

Busbar dimensions (mm) 5b. 100 x 10 7b. 100 x 10 8b. 100 x 10


Ventilated switchboard (➨ IP31) 4
3
DB108445.eps

Ta = 35 °C 2 4000 4000 4700 5000 5850


1
4
3
Ta = 45 °C
2 4000 4000 4450 4850 5670
1
4
3
Ta = 55 °C
2 4000 4000 4200 4600 5350
1

(1) Area of outlet vents: 500 cm².


(2) Area of inlet vents: 500 cm².
Non ventilated switchboard 4
(➨ IP54) 3
2 4000 4000 4350 4650 5290
Db101492.eps

Ta = 35 °C
1
4
3
Ta = 45 °C
2 4000 4000 4100 4400 5040
1
4
3
Ta = 55 °C
2 3840 3840 3850 4150 4730
1

Note: the values indicated in these tables have been extrapolated from test data and theoretical
calculations. These tables are only intended as a guide and cannot replace industrial experience
or a temperature rise test.
The values indicated for the cross-sectional area of the vents should be considered as general
indications only given that the thermal performance of a switchboard with natural ventilation
GHSHQGVRQPDQ\SDUDPHWHUVHJVKDSHSRURVLW\DQGORFDWLRQRIYHQWVDQGDLUÀRZZLWKLQWKH
switchboard.

B-21