SM6
DM1‐A, DM1‐W Cubicles
Incoming or Outgoing, Fixed or Withdrawable
Single Isolation Circuit Breaker up to 24 kV DM1-A DM1-W
SM6 units meet all the following
standards and specifications:
Introduction Basic Equipment - IEC standards
- UTE standards for SM6-24
- EDF specifications for SM6-24
DM1-A & DM1W are part of SM6 product range * SF1 circuit break 630 amp - SEISMIC standards for 24 kV
and called as single section isolation circuit breaker. * Three phase busbar 630 A
* Disconnectro and earthing switch IEC standards
This modulator unit is used for MV section of MV/LV * RI circuit breaker operating mechanism 62271-200 ,62271-1, 62271-103, 62271-
substation in secondary distribution system up to 24 kV * Enlarge low voltage compartment 105, 62271-100, 62271-102, 61869-2,
* Three current transformers 61869-3, 60044-8, 62271-206, 62271-304
* Auxiliary contacts on circuit breaker
* CC earthing switch operating mechanism SEISMIC standards for 24kV
(only for DM1-W) IEEE-693 2005
EN600068-3-3 1993
Application * Downstream earthing switch
* Heater 50 W, 220V
UTE standards for 24 kV
DM1-A is single isolation circuit breaker unit with fixed * Voltage presence indicator
NFC 13.100
breaker, normally used as incoming or outgoing cubicle.
NFC 13.200
Optional LV Control DM1-A NFC 64.130
DM1-W is withdrawable single isolation circuit breaker NFC 64.160
Unit and it is also used for incoming or outgoing feeder. * DM1-A fix LV cable connection
This DM1-A or DM1-W is normally installed together in * DM1-A plug in LV cable connection EDF specifications for 24 kV
system with other parts of SM6 product reange such as
IM, IMC, QM, QMC, CM, etc, in accordance with Condition Monitoring HN 64-S-41
the design of a distribution system * Basic : thermal sensors (TH110) HN 64-S-43
* Option : humidity sensors (CL110)
Colour
White RAL 9003
MV prefabricated equipment
SM6
DM1‐A, DM1‐W Cubicles
Electrical characteristics
MV prefabricated equipment
SM6
DM1‐A, DM1‐W Cubicles
MV prefabricated equipment
SM6
DM1‐A, DM1‐W Cubicles
MV prefabricated equipment
SM6
DM1‐A, DM1‐W Cubicles
Normal operating conditions Protection index:
• Ambient air temperature: • Classes: PI (insulating partition)
1) less than or equal to 40°C • Loss of service continuity classes: LSC2A (LSC1 for metering GAM/GBM functions)
2) less than or equal to 35°C on average over 24 hours • Units in switchboard: IP3X
3) greater or equal to –5°C. • Between compartments: IP2X for SM6-24, IP2XC for SM6-36
• Altitude • Cubicle: IK08 for SM6-24, IK07 for SM6-36.
1) less than or equal to 1000 m
2) above 1000 m, a derating coefficient is applied (please consult us). Electro-magnetic compatibility:
• Solar radiation • Relays: 4 kV withstand capacity, as per recommendation IEC 60801.4
1) no solar radiation influence is permitted. • Compartments:
• Ambient air pollution electrical field:
1) no significant pollution by dust, smoke, corrosive and/or flammable gases, -- 40 dB attenuation at 100 MHz
vapours or salt. -- 20 dB attenuation at 200 MHz
• Humidity magnetic field: 20 dB attenuation below 30 MHz.
1) average relative humidity over a 24 hour period, less than or equal to 95% • According to standards IEEE-693/2005 and EN 60068-3/1993
2) average relative humidity over a 1 month period, less than or equal to 90% for 36 kV (please contact us).
3) average vapor pressure over a 24 hour period, less than or equal to 2.2 kPa
4) average vapor pressure over a 1 month period, less than or equal to 1.8 kPa. Temperatures:
For these conditions, condensation may occasionally occur. Condensation can be The cubicles must be stored and installed in a dry area
expected where sudden temperature changes occur in periods of high humidity. free from dust and with limited temperature variations.
To withstand the effects of high humidity and condensation, such as breakdown of • For stocking: from -40°C to +70°C
insulation, please pay attention on Civil Engineering recommendations for design • For working: from -5°C to +40°C
of the building or housing, by suitable ventilation and installation. • Other temperatures, consult us.
• Seismic (for 24 Kv and 36 kV): • Seismic:
1) Up to 0.5 g (horizontal) and 0.4 g (vertical) for 24 kV (option):
2) Class 2 for 24 kV and Class 1 for 36kV 1) Up to 0.5 g (horizontal) and 0.4 g (vertical)
3) According to standards IEEE-693/2005 and EN 60068-3/1993 for the 24 kV and 2) Class 2
36 kV
MV prefabricated equipment
SM6
DM1‐A, DM1‐W Cubicles
Safety of people
By internal arc protection
Standard IEC 62271-200 appendix
A indicates a method for testing
switchgear in metal enclosures
under internal arc conditions. The
aim of this test is to show that
an operator situated in front of a
switchboard would be protected
against the effects of an internal
fault.
1
Rated short‐time thermal current depend on rated primary current, accuracy class & burden
2
Rated burden depend on rated short‐time thermal current & accuracy class
MV prefabricated equipment
SM6
DM1‐A, DM1‐W Cubicles
Voltage Transformer
Service Condition Indoor
Insulation Dry epoxy resin moulded and treated under vacuum
Connection Phase to earth
Highest system voltage kV 24
Rated power‐frequency withstand voltage kV 50
Lightning impulse test voltage kV 125
Rated frequency Hz 50 or 60
Rated primary voltage kV 2.4√3 ~ 22/√3
Rated secondary voltage V 100√3 ; 110√3 ; 100/√3 ; 110/√3
Number of secondary windings 1 or 2
Rated voltage factor Un 1.2 Cont : 1.9/30 s or 1.9/8 h
Measurement : 0.2 ; 0.5 or 1
Accuracy classes
Protection : 3P or 6P
1
Rated burdens VA 10 ; 15 ; 25 ; 30 ; 50 ; 75
Approx. weights kg 24
1
Rated burden depend on accuracy class