Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

C 304

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

February 15, 2001

DF-51339 E-300

Addressable Modules
www.firelite.com
Section: Addressable Devices California State Fire Marshal 7300-0075:159 (M300, M301, I300, C304) 7300-0075:162 (M302)

MS-9200

MEA
3-94-E (M300, M301, I300) 16-94-E (M302) 326-94-E (C304)

CS68 (non "A" suffix)

CS68 ("A" suffix only)

C304

CONTROL MODULE

I300

FAULT ISOLATOR MODULE

This module has been replaced with modules CMF-300 and CRF300, detailed in data sheet DF-52130.

The FireLite C304 Control Module is used with the MS-9200 to provide a Style D (Class A) or Style B (Class B) Notification Appliance (Signal) Circuit (NAC). Alternately, the C304 may be converted to an addressable Form-C relay by removing a break off tab. The C304 may be programmed to operate dry contacts for door holders, Air Handling Unit shutdown, etc.

The FireLite I300 Fault Isolator Module is used with the MS-9200 to protect the system against wire-to-wire short circuits on the SLC loop. The I300 should be placed between each device on the SLC loop, to isolate a short-circuit problem between the modules. It is required for true Style 7 operation so that other devices can continue to operate normally in the event of a short-circuit on the SLC.

FEATURES
Internal circuitry and relay powered directly by two-wire SLC loop. NAC configuration requires second loop for notification appliance power. Integral LED blinks each time it communicates with the MS-9200. Mounts in standard 4" square (2-1/8" deep) junction box. Direct-dial entry of Decade address (01-99).

FEATURES
Powered by SLC loop directly, no external power required. Mounts in standard 4-inch square (2-1/8" deep) junction boxes. Integral LED blinks to indicate normal condition. Illuminates steady when short circuit condition is detected. High noise (EMF/RFI) immunity.

SPECIFICATIONS
Operating voltage: 15-28 VDC (Peak). Maximum current in alarm: refer to the MS-9200 Technical Manual. Standby current: 400 A maximum. Contact rating: 2.0 amps @ 30 VDC (resistive) 0.6 amp @ 30 VDC (inductive, 0.35 PF) 0.3 amps @ 110 VAC (0.35 PF) 0.6 amps @ 30 VDC (inductive, 0.35 PF) Temperature range: 32F to 120F (0C to 49C). Relative humidity: 10% to 93%. Weight: 150 grams (5 oz.).

SPECIFICATIONS
Operating voltage: 15-28 VDC (peak). Maximum current upon activation due to short circuit: refer to the MS-9200 Technical Manual. Standby current: 450 A maximum; I300 is not isolating relay closed. Temperature range: 32F to 120F (0C to 49C). Relative humidity: 10% to 93%. Weight: 150 grams (5 oz.).

PRODUCT LINE INFORMATION


I300 I300A SMB500 Isolator Module. Isolator Module, ULC listed. Optional surface-mount backbox.

PRODUCT LINE INFORMATION


C304 C304A SMB500 Addressable Control Module. Addressable Control Module, ULC listed. Optional surface-mount backbox.

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact FireLite Alarms, One Fire-Lite Place, Northford, Connecticut 06472. Phone: (800) 627-3473, Toll Free FAX: (877) 699-4105, FAX Back:(888) 388-3299.

Made in the U.S.A.


DF-51339 Page 1 of 2

COMMON FEATURES
High noise (EMI/RFI) immunity.

MS-9200 Monitor Modules


LED flashes during normal operation and latches on in alarm. NOTE: M301 Mini-Monitor Module does not include LED. Two rotary switches for direct-dial entry of Decade address (01-99).

Built-in type identification automatically identifies device as a monitor module to the control panel.

NOTE: The M300, M301 and M302 modules have been replaced with modules MMF-300, MMF-301 and MMF-302 respectively. Please see data sheet DF-52121 for a description of the MMF-300 series modules.

M300

M301

M302

Monitor Module
The FireLite M300 Monitor Module is used with the MS-9200 to monitor a single Initiating Device Circuit (IDC) of normallyopen contact devices. It can be used to monitor a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally open dry-contact alarm activation devices. The monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class D) Initiating Device Circuit.

Mini-Monitor Module
Though the FireLite M301 can be used to monitor an entire Class B initiating circuit, it is ideally suited for monitoring single N/O contact devices. The M301 is small enough to fit inside a single-gang junction box behind the device being monitored. Its small size and light weight allow it to be installed without the need to be rigidly mounted. It can be used to monitor a single device or a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices (per local authority) or other normally-open, dry-contact devices. It may also be used to monitor normally-open supervisory devices with special supervisory indication at the control panel. The monitored circuit/device is wired as an NFPA Style B (Class B) Initiating Device Circuit.

Two-wire Conventional Smoke Detector Monitor Module


The FireLite M302 Monitor Module is used with the MS-9200 to monitor a single Initiating Device Circuit (IDC) of compatible two-wire smoke detectors. The monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. Requires auxilliary/ external resettable 24VDC power.

FEATURES
Terminals with SEMS screws and clamping plates for ease of wiring. Built-in magnetic alarm test switch. Mounts in standard 4" square (2-1/8" deep) junction boxes.

FEATURES
Supports compatible two-wire smoke detectors. Supervises IDC wiring and connection of external power source. Built-in magnetic alarm test switch. Mounts in standard 4" square (2-1/8" deep) junction boxes.

PRODUCT LINE
M300 M300A M02-04-00 SMB500 Contact device monitor module. Contact device monitor module, ULC listed. Alarm Test Magnet. Optional surface-mount backbox.

FEATURES
Compact size; only 2.75" [70 mm] high x 1.30" [33 mm] wide x 0.50" [12.7 mm] deep. Tinned, stripped leads for wiring ease. Class B (Style B) IDC only. Capable of mounting behind monitored device in single-gang box.

PRODUCT LINE
M302 M302A M02-04-00 SMB500 Two-wire detector monitor module. Two-wire detector monitor module, ULC listed. Alarm Test Magnet. Optional surface-mount backbox.

PRODUCT LINE
M301 M301A Contact device mini-monitor module. Contact device mini-monitor module, ULC listed.

Face plate for M300, M302, C300, and I300

To a 2-wire Class-B initiating circuit

Specifications
Operating voltage: Maximum current in alarm: Standby current: Temperature range: Relative humidity: Weight: EOL resistor value: IDC loop length: IDC loop resistance:
Page 2 of 2 DF-51339

M300
15 - 28VDC (peak) see MS-9200 Technical Manual 400 A maximum 32 F to 120 F (0 C to 49 C) 10% to 93% 150 grams (5 oz.) 47 K ohm 2,500 feet (7.62 km) maximum 40 ohms maximum

To MS-9200 Addressable Loop M301


15 - 28VDC (peak) see MS-9200 Technical Manual 400 A maximum 32 F to 120 F (0 C to 49 C) 10% to 93% 150 grams (5 oz.) 47 K ohm 2,500 feet (7.62 km) maximum 20 ohms maximum

M300 and M302


M302
15 - 28VDC (peak) 90 mA 300 A max. (Style D, 1.3 mA) 32 F to 120 F (0 C to 49 C) 10% to 93% 150 grams (5 oz.) 3.9 K ohm 2,500 feet (7.62 km) maximum 25 ohms maximum

You might also like