Anderson HA Sanitary Electronic Pressure Transmitter Instruction Manual
Anderson HA Sanitary Electronic Pressure Transmitter Instruction Manual
HA SANITARY ELECTRONIC
PRESSURE TRANSMITTER
Form Number #2005
© December 1997
Rev. 11/00
PAGE 2
Table of Contents
Page Number
SECTION 1 - INTRODUCTION 3
1.1 SPECIFICATIONS 3
SECTION 3 - INSTALLATION 5
SECTION 7 - TROUBLESHOOTING 9
7.1 VOLTAGE CHECK 9
7.2 CURRENT CHECK 9
7.3 MISCELLANEOUS TROUBLESHOOTING 9
FIGURES
1 Dimensional View 3
2 Wiring Terminal Connections 6
3 Loop Power Guidelines 7
4 Loop Diagram 7
PAGE 3
Section 1 - Introduction
This manual has been designed to assist the end-user with the installation of the Anderson
model HA Sanitary Electronic Pressure Transmitter. When followed properly, your sensor will
provide optimum performance with minimum maintenance.
1.1 SPECIFICATIONS
Excitation:
10-40 VDC (Absolute), 24 VDC Nominal regulated or unregulated.
Output:
4-20 mA DC, 2 wire with non-interrupting circuit verification test points
Loop Resistance:
0-700 ohms at 24 VDC
Wiring Connection:
16 AWG max.; Screw Terminal; Accessible via removable screw cap conduit housing
Recommended Cable:
22-24 AWG, foil shielded, and PVC coated. (3/16 - 1/4 OD insulation)
Accuracy:
± 0.5% of Full Scale
Repeatability:
± 0.3% of full scale
Hysteresis:
± 0.25% of full scale
PAGE 4
Linearity:
±0.10% of full scale
Stability:
±.25% of calibrated range/6 months
Storage Temperature:
-40° to 149°F (-40°C to 65°C)
Over-Range Rating:
2 times base range
Wetted Parts:
316L stainless steel electropolished (Ra max. = 8 microinches, .2 microns)
Housing Material:
304 Stainless Steel
Mounting:
Direct connection
Section 3 - Installation
The physical installation is the most important concern with regards to promoting sensor
reliability. Sensors must be installed in such a way that the housing and cable are not subject
to physical abuse. In addition, moisture or moist air must not be allowed to enter the sensor
housing or cable.
NOTE: The installer assumes responsibility for preventing water or water- vapor from
entering the sensor housing.
Your new HA transmitter is supplied with a conduit housing. If mounted horizontally, the
conduit connection should point downward. Also, to prevent entry of excessive moisture, it is
highly recommended that flexible conduits not be connected directly to the sensor. If conduit
is to be run to the sensor, it is preferable that the watertight connector provided with each
sensor not be removed from the sensor. Instead, run the flexible conduit as near to the
sensor as possible and utilize a seal-tight connector at the end of the conduit. Allow a short
amount of cable to run between the sensor and the flexible conduit. This isolates the sensor
housing from the conduit system and any moisture it may contain. If the conduit is connected
directly to the sensor, the chances are high that the sensor will eventually fail due to exces-
sive water or water vapor entry into the housing.
If utilizing customer supplied cable, select a round cable with 22-24 AWG wire and a shield.
In order for the Anderson provided seal-tight connector to seal on the cable, the O.D. of the
cable must be between 3/16" and 1/4". If smaller cable is utilized, a different neoprene
bushing must be used (must be customer supplied).
If an alternate seal-tight type connector is going to be used, be absolutely certain that the
rubber bushing will adequately seal on the cable. Do not use a connector intended for power
cable (large inside diameter) if the sensor cable is only 1/4". Be sure to use Teflon thread
tape when attaching the new seal-tight connector.
2. Insert the cable through the seal-tight connector, stripping back approximately 2 inches of
sheathing to expose the wires.
3. Two wires will be utilized for connections at the transmitter end of the loop. Normal color
codes being RED (Loop +) and BLACK (Loop -). Trim off all unused wires, including the
bare shield ground wire. To prevent a GROUND LOOP condition, be sure the shield
material and the shield ground wire do not touch the sensor housing. Use an insulator
such as electrical tap or heat shrink tubing if necessary.
4. Strip the tips of the remaining wires back approximately 3/8 of an inch and twist strands
(tinning is highly recommended).
5. Using Figure 2, make the proper connections to the wiring terminal strip (located inside the
conduit housing)
The Anderson HA requires loop power for operation. Ratings are as follows:
As inherent resistance associated with cable length and signal receiver input may affect
operation of the transmitter, Figure 3 shows some guidelines for loop power required.
Please consult the Installation/Service Manual that was provided with your receiver for
specific wiring instruction. Most Anderson receivers (displays, chart recorders, etc.) are
capable of supplying loop power. Typical wiring would be as follows:
If you feel that the output of the HA transmitter is not correct, calibration of the unit may be
required. Section 6.1 illustrates the procedures for calibration of the transmitter.
Equipment required:
Pressure source
Accurate reference gauge
DC Milliamp Meter (accurate to .01 mA)
Small straight blade screwdriver
Calculator
The output of a properly calibrated transmitter may be calculated by using the following
formula:
1. Expose the transmitter to a known zero reference point. If transmitter range starts at
atmospheric zero, zero adjust at atmospheric zero. If transmitter is a compound range,
you should be as close to sensor zero as possible . You must calculate the expected mA
signal (use formula proved at start of this section).
3. With your meter set to DC mA, connect the RED (Meter +) lead to the (TP +) terminal.
Connect the BLACK (Meter - ) lead to the (TP -) terminal. (See Figure 2)
4. Adjust the transmitter ZERO potentiometer as shown in Figure 2, until you either see 4.00
mA if you are at atmospheric zero, or your expected mA signal for a compound range.
PAGE 9
5. Expose the transmitter to a know process variable near the top end of the range.
7. Adjust the transmitter SPAN potentiometer, as shown in Figure 2, until you see
your expected mA output.
NOTE: For pressure transmitters with compound ranges, the ranges must first be converted
to all one type unit of measure. For example, a 30" Hg/0/30 psig unit may be considered to
have a range of -14.7 psig-0-30 psig and a span of 44.7 psig (2.036" Hg = 1 psi). Be careful
not to lose the (-) sign while performing the calculation of the proper reading.
Section 7 - Troubleshooting
7.1 VOLTAGE CHECK
Using a digital multimeter on the DC volts scale and with the sensor connected to the re-
ceiver, confirm that the sensor is being provided the correct loop power. Place the RED
(Meter +) lead on the (Loop +) terminal, and the BLACK (Meter -) lead on the (Loop -)
terminal. You should see between 10-40 VDC for a standard transmitter.
Symptom Action
Feel free to contact Anderson Technical Services Department at 1-800-833-0081 for further
assistance with troubleshooting.
PAGE 10
These products are sold by The Anderson Instrument Company (Anderson) under the
warranties set forth in the following paragraphs. Such warranties are extended only with
respect to a purchase of these products, as new merchandise, directly from Anderson or from
an Anderson distributor, representative or reseller, and are extended only to the first buyer
thereof who purchases them other than for the purpose of resale.
Warranty
These products are warranted to be free from functional defects in materials and workman-
ship at the time the products leave the Anderson factory and to conform at that time to the
specifications set forth in the relevant Anderson instruction manual or manuals, sheet or
sheets, for such products for a period of one year.
Limitations
Anderson shall not be liable for any incidental damages, consequential damages, special
damages, or any other damages, costs or expenses excepting only the cost or expense of
repair or replacement as described above.
Products must be installed and maintained in accordance with Anderson instructions. Users
are responsible for the suitability of the products to their application. There is no warranty
against damage resulting from corrosion, misapplication, improper specifications or other
operating condition beyond our control. Claims against carriers for damage in transit must be
filed by the buyer.
This warranty is void if the purchaser uses non-factory approved replacement parts and
supplies or if the purchaser attempts to repair the product themselves or through a third party
without Anderson authorization.
Returns
Anderson’s sole and exclusive obligation and buyer’s sole and exclusive remedy under the
above warranty is limited to repairing or replacing (at Anderson’s option), free of charge, the
products which are reported in writing to Anderson at its main office indicated below.
Anderson is to be advised of return requests during normal business hours and such returns
are to include a statement of the observed deficiency. The buyer shall pre-pay shipping
charges for products returned and Anderson or its representative shall pay for the return of
the products to the buyer.