Manual Unidades Manejadoras
Manual Unidades Manejadoras
Manual Unidades Manejadoras
s
e n e w al Part
R P1
o r m 1 02.20-R rts
F
t a c t B alt. Pa
/N con
With P 9 3 2-1701
(8 0 0 ) arts
s p e c ialty p 14
d or 5-78
a n u f acture ide (800) 54
M t Airs
contac
LD09624
Indoor unit
LD09688
Outdoor unit
IMPORTANT!
Read BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
This equipment is a relatively complicated apparatus. This document is intended for use by owner-authorized
During installation, operation, maintenance or service, operating/service personnel. It is expected that this
individuals may be exposed to certain components or individual possesses independent training that will
conditions including, but not limited to: refrigerants, enable them to perform their assigned tasks properly
oils, and materials under pressure, rotating components, and safely. It is essential that, prior to performing any
and both high and low voltage. Each of these items task on this equipment, this individual shall have read
has the potential, if misused or handled improperly, and understood this document and any referenced
to cause bodily injury or death. It is the obligation materials. This individual shall also be familiar with
and responsibility of operating/service personnel to and comply with all applicable governmental standards
identify and recognize these inherent hazards, protect and regulations pertaining to the task in question.
themselves, and proceed safely in completing their
tasks. Failure to comply with any of these requirements
could result in serious damage to the equipment and
the property in which it is situated, as well as severe
personal injury or death to themselves and people at
the site.
Safety symbols
The following symbols are used in this document to alert the reader to areas of concern:
IAQ
• Protect this equipment from damage, construction – Start-up will be performed according to that
dirt, debris and water. outlined in Section 3 of the Installation and
Start-up Instructions provided.
DO NOT OPERATE DOORS WHEN
UNIT IS NOT ON A FLAT SURFACE. • Temporary use of air handler requires startup
performed according to that outlined in Section
• Isolate this equipment from pressure testing of 3 of the Installation and Start-up Instructions
water, steam, gas and air piping. provided.
• Do not test, clean and flush piping through coils • A qualified startup technician must complete
in this equipment. the “AIR HANDLING UNITS START-UP
• Isolate this equipment from temporary building CHECK LIST” Form 100.00-CL1 and file a
power. copy at the local YORK Service Office. ► This
form is provided in the information package with
• Contact local Johnson Controls Service for each air handler.
purchase of Startup Service with two weeks
advance notice. Provide current job site • Rotate fans every four (4) weeks beginning upon
contact. arrival.
It is the responsibility of operating/service personnel to verify the applicability of these documents to the equipment
in question. If there is any question in the mind of operating/service personnel as to the applicability of these
documents, then prior to working on the equipment, they should verify with the owner whether the equipment has
been modified and if current literature is available.
johnson controls 3
FORM 102.20-NOM1 (909)
Table of contents
GENERAL SAFETY GUIDELINES.......................................................................................................................2
CHANGEABILITY OF THIS DOCUMENT............................................................................................................3
Table of contents........................................................................................................................................4
list of figures..............................................................................................................................................16
list of TABLES................................................................................................................................................25
service task reference...........................................................................................................................26
introduction.................................................................................................................................................29
GENERAL....................................................................................................................................................29
TYPICAL YORK SOLUTION OPERATION IN “HVAC” SYSTEM...............................................................29
VENTILATION SYSTEM...........................................................................................................................29
ECONOMIZER SYSTEM - TYPICAL.......................................................................................................30
HEATING OPERATION............................................................................................................................30
COOLING OPERATION...........................................................................................................................30
HAND IDENTIFICATION..............................................................................................................................30
SEGMENT IDENTIFICATION.......................................................................................................................31
UNIT IDENTIFICATION............................................................................................................................33
UNIT ID LABEL...................................................................................................................................33
SKID ID LABEL...................................................................................................................................33
SEGMENT IDENTIFICATION BOX.....................................................................................................33
FILTER ID LABEL...............................................................................................................................34
LOOSE COMPONENT ID LABEL......................................................................................................34
DIRECTION OF AIRFLOW.......................................................................................................................34
1.0 pre-installation...................................................................................................................................1-1
RECEIVING.................................................................................................................................................1-1
RIGGING OF INDOOR AND OUTDOOR UNITS........................................................................................1-1
OFF-LOADING........................................................................................................................................1-2
CRANE AND SPREADER BARS...........................................................................................................1-2
FORK LIFT..............................................................................................................................................1-2
COME-A-LONGS OR POWER PULL.....................................................................................................1-2
SHACKLES.............................................................................................................................................1-3
INSPECTION...............................................................................................................................................1-4
CHECK FOR DAMAGE...........................................................................................................................1-4
RECEIVER RESPONSIBILITY...........................................................................................................1-4
INDOOR UNITS..................................................................................................................................1-4
OUTDOOR UNITS..............................................................................................................................1-4
CHECKING FOR NON MOUNTED PARTS............................................................................................1-4
STORAGE...................................................................................................................................................1-4
SHORT-TERM STORAGE.......................................................................................................................1-4
LONG-TERM STORAGE.........................................................................................................................1-5
PREVENTIVE MAINTENANCE PRIOR TO LONG TERM STORAGE..............................................1-5
PERIODIC FAN CHECK.....................................................................................................................1-5
4 johnson controls
FORM 102.20-NOM1 (909)
johnson controls 5
FORM 102.20-NOM1 (909)
6 johnson controls
FORM 102.20-NOM1 (909)
johnson controls 7
FORM 102.20-NOM1 (909)
8 johnson controls
FORM 102.20-NOM1 (909)
johnson controls 9
FORM 102.20-NOM1 (909)
10 johnson controls
FORM 102.20-NOM1 (909)
johnson controls 11
FORM 102.20-NOM1 (909)
johnson controls 13
FORM 102.20-NOM1 (909)
14 johnson controls
FORM 102.20-NOM1 (909)
johnson controls 15
FORM 102.20-NOM1 (909)
list of figures
FIG. 1 – CUTAWAY OF YORK Solution SHOWING VARIOUS SEGMENTS.........................................29
FIG. 2 – UNIT AND COIL HAND IDENTIFICATION.....................................................................................30
FIG. 3 – UNIT ID LABEL..............................................................................................................................33
FIG. 4 – SKID ID LABEL..............................................................................................................................33
FIG. 5 – SEGMENT ID BOX EXAMPLE......................................................................................................33
FIG. 6 – LOOSE COMPONENT ID LABELS...............................................................................................34
FIG. 7 – filter LABELS............................................................................................................................34
FIG. 1-1 – RECOMMENDED LIFTING WITH FOUR LIFTING POINTS.....................................................1-1
FIG. 1-2 – RECOMMENDED LIFTING WITH MULTIPLE POINTS.............................................................1-1
FIG. 1-3 – TYPICAL COME-A-LONG TYPES............................................................................................1-2
FIG. 1-4 – P
ROPER LIFTING WITH SHACKLE AT CORNER...................................................................1-3
FIG. 1-5 – P
ROPER LIFTING WITH SHACKLE AT LIFTING LUG............................................................1-3
FIG. 1-6 – R
ECOMMENDED LIFTING WITH BASERAIL..........................................................................1-3
FIG. 2-1 – MINIMUM SERVICE CLEARANCES.........................................................................................2-1
FIG. 2-2 – TYPICAL CURB ASSEMBLY.....................................................................................................2-4
FIG. 2-3 – NO BASERAIL – HOUSEKEEPING PAD REQUIRED TO ACCOMMODATE TRAP HEIGHT........2-5
FIG. 2-4 – NO HOUSEKEEPING PAD – BASERAIL REQUIRED TO ACCOMMODATE TRAP HEIGHT.......2-5
FIG. 2-5 – W
ITH BASERAIL AND HOUSEKEEPING PAD .......................................................................2-5
FIG. 2-6 – CEILING SUSPENDED UNIT....................................................................................................2-6
FIG. 2-7 – TOOLS TYPICALLY USED FOR ASSEMBLY OF SHIPPING SPLITS.....................................2-7
FIG. 2-8 – S
ECOND TIER TIE-DOWN FASTENER PACK P/n 386-03419-000........................................2-8
FIG. 2-9 – BOTTOM RACEWAY SHIPPING SPLIT FASTENER PACKP/n 386-03418-000.....................2-8
FIG. 2-10 – B
ASERAIL SHIPPING SPLIT FASTENER PACK P/n 386-03417-000 .................................2-8
FIG. 2-11 – TOP RACEWAY SPLIT FASTENER PACK.............................................................................2-8
FIG. 2-12 – PIPE CHASE, HOODS & SEAM CAPS...................................................................................2-9
FIG. 2-13 – Miscellaneous parts for Options..........................................................................2-10
FIG. 2-14 – HARDWARE, GASKETING, CAULK, PAINT AND TAPE.....................................................2-11
FIG. 2-15 – SHIPPING SPLIT EXAMPLES...............................................................................................2-12
FIG. 2-16 – SHIPPING SPLIT EXAMPLES FOR EXPANDED CABINET................................................2-12
FIG. 2-17 – APPLYING GASKET..............................................................................................................2-14
FIG. 2-18 – ELECTRICAL CONNECTIONS.............................................................................................2-14
FIG. 2-19 – R
EMOVE AND REPOSITION SHIPPING SPLIT ANGLE....................................................2-15
FIG. 2-20 – BRINGING SECTIONS TOGETHER.....................................................................................2-16
FIG. 2-21 – APPLYING GASKET TO SHIPPINGSPLIT............................................................................2-17
FIG. 2-22 – APPLYING GASKET TO DOOR FRAMEWHEN AT SHIPPING SPLIT.................................2-17
FIG. 2-23 – ASSEMBLY OF END CHANNEL SHIPPING SPLIT ((EXPANDED CABINET)....................2-18
FIG. 2-24 – R
EMOVE AND REPOSITION SHIPPING SPLIT ANGLE....................................................2-18
FIG. 2-25 – P
lacing & anchoring first section and attaching come-a-longs.............2-19
FIG. 2-26 – R
EMOVE LIFTING LUGS AND SAVE HARDWARE.............................................................2-19
FIG. 2-27 – ELECTRICAL CONNECTIONS.............................................................................................2-19
FIG. 2-28 – installing bolts after pulling units tight together...................................2-20
FIG. 2-29 – TIERED UNIT.........................................................................................................................2-21
FIG. 2-30 – TIERED UNIT SECURED WITH BRACKETS.......................................................................2-21
16 johnson controls
FORM 102.20-NOM1 (909)
johnson controls 17
FORM 102.20-NOM1 (909)
18 johnson controls
FORM 102.20-NOM1 (909)
johnson controls 19
FORM 102.20-NOM1 (909)
20 johnson controls
FORM 102.20-NOM1 (909)
johnson controls 21
FORM 102.20-NOM1 (909)
22 johnson controls
FORM 102.20-NOM1 (909)
johnson controls 23
FORM 102.20-NOM1 (909)
24 johnson controls
FORM 102.20-NOM1 (909)
list of TABLES
TABLE 1 – SEGMENT IDENTIFICATION....................................................................................................31
TABLE 2 – UNIT NOMENCLATURE............................................................................................................32
TABLE 1-1 - SPACING REQUIREMENTS FOR OFFLOADING LONG UNITS.........................................1-2
TABLE 3-1 – TORQUE FOR TIGHTENING SETSCREWS........................................................................3-3
TABLE 3-2 – NATURAL GAS PRESSURE REQUIREMENTS (INCHES WC)........................................3-18
TABLE 3-3 – P
IPE SIZE REQUIRED........................................................................................................3-19
Table 3-4 – B
URNER TEPERATURE RISE...........................................................................................3-23
TABLE 3-5 – INSPECTION REQUIREMENTS.........................................................................................3-29
TABLE 4-1 – MINIMUM MAINTENANCE ACTIVITY AND FREQUENCY
(ASHRAE STANDARD 62-2001 FOR INDOOR AIR QUALITY)...........................................4-2
TABLE 4-2 – FAN BEARING – LUBRICATION INTERVALS - BALL BEARING PILLOW BLOCKS.....4-12
TABLE 4-3 – F
AN BEARING – LUBRICATION INTERVALS - SPHERICAL ROLLER BEARING
SOLID PILLOW BLOCKS....................................................................................................4-12
TABLE 4-4 – F
AN BEARING – LUBRICATION INTERVALS - SPHERICAL ROLLER
BEARING-SPLIT PILLOW BLOCKS..................................................................................4-12
TABLE 4-5 – MOTOR BEARING – LUBRICATION INTERVALS.............................................................4-14
TABLE 4-6 – MOTOR BEARING – SERVICE CONDITIONS...................................................................4-14
TABLE 4-7 – MOTOR BEARING – LUBRICATION INTERVAL MULTIPLIER.........................................4-14
TABLE 5-1 – TORQUE FOR TIGHTENING SET SCREWS.......................................................................5-8
TABLE 5-2 – RECOMMENDED CLEARANCE REDUCTION VALUES OF SKF TAPERED
BORE BEARINGS (IN INCHES).........................................................................................5-17
TABLE 5-3 – RECOMMENDED CAP BOLT TORQUE VALUES FOR SPLIT PILLOW BLOCK.............5-17
TABLE 5-4 – C
APSCREW TORQUE VALUES FOR FIXED PITCH SHEAVES......................................5-19
TABLE 5-5 – CONNECTORS & SLEEVES WITH STRIP LENGTHS......................................................5-24
TABLE 5-6 – TORQUE CHART - TIGHTENING TORQUE IN INCH POUNDS........................................5-24
TABLE 5-7 – CROSS REFERENCE; CONTINUOUS TO SINGLE LINK BELT/BELT PULLEY KITS....5-69
TABLE 5-8 – TROUBLESHOOTING TIPS...............................................................................................5-79
johnson controls 25
FORM 102.20-NOM1 (909)
26 johnson controls
FORM 102.20-NOM1 (909)
johnson controls 27
FORM 102.20-NOM1 (909)
28 johnson controls
FORM 102.20-NOM1 (909)
introduction
LD13764
johnson controls 29
FORM 102.20-NOM1 (909)
Right
ReAR
rIGht hAND (rh)
cOIL cONNEctION
OUtSIDE AIr
leFt
INLEt SEctION
DrIVE hAND AND cOIL hAND DEtErMINED
By FAcING thE INLEt SEctION
FROnt
LD08004
30 johnson controls
FORM 102.20-NOM1 (909)
SEGMENT IDENTIFICATION
Refer to Tables 1 and 2 for segment identification and nomenclature.
johnson controls 31
32
Solution Unit Model Number.
PRIMARY
IDENTIFIER
ENVIRONMENT
NOMINAL
HEIGHT
NOMINAL
WIDTH
SUPPLY FAN
OPTIONS
RETURN FAN
OPTIONS
SUPPLY FAN
MOTOR HP
RETURN FAN
MOTOR HP
FACTORY
MOUNTED END
DEVICES
PRIMARY
VOLTAGE
CODE
DESIGN
SERIES
XT I - 048 X 075 - D C M K 0 46 A
DESIGN DEFINITION
A ORIGINAL UNIT DESIGN
XT
CODE NAMEPLATE VOLTAGE
TABLE 2 – UNIT NOMENCLATURE
12 120 - 1 - 60
17 200 or 208 - 3 - 60
I INDOOR UNIT 27 277 - 1 - 60
O OUTDOOR UNIT 28 230 or 240 - 3 - 60
40 380 - 3 - 60
44 440-3-50
46 460 - 3 - 60
50 380 or 415 - 3 - 50
58 575 - 3 - 60
63 220 - 3 - 50
LD13350
johnson controls
FORM 102.20-NOM1 (909)
FORM 102.20-NOM1 (909)
AHU 9-10
HP FLA M.C.A. MAX. O.C. PROT.
25 38 47.5 80
HEAT RECOVERY WHEEL MOTOR RATING (INDIVIDUAL LOAD)
HP FLA M.C.A. MAX. O.C. PROT.
N/A N/A N/A N/A
ELECTRIC HEAT RATINGS GAS HEAT RATINGS Estimated Weight:
4,100
N/A N/A
LIGHTS & OUTLETS
VOLTS / PH / HZ M.C.A. MAX. O.C. PROT.
120/1/60 20 20
pounds
COIL DATA
HOT WATER COIL MAX. INLET WATER TEMP. 200 F (FR) Bolded indicates skid 1 of 5 is a Return
STEAM COIL MAX. OPERATING PRESSURE. 50 Fan and is placed first in the direction of airflow.
See Segment ID box example.
EVAPORATOR COIL DESIGN PRESSURE. 325 PSI LD11729A
FIG. 4 – SKID ID LABEL
EVAPORATOR COIL REFRIGERANT USED. _____
EVAPORATOR COIL REFRIGERANT OIL USED. _____ SEGMENT IDENTIFICATION BOX
SUITABLE FOR USE WITH REMOTE CONDENSER; AIR-COOLED, WATER-COOLED, OR
VAPORATIVE. THE DESIGN PRESSURE MARKED ABOVE SHALL NOT BE LESS THAN THE
DESIGN PRESSURE MARKED ON THE REMOTE CONDENSING UNIT. The Segment Identification box indicates the skids and
MANUFACTURING LOCATION segments* used on a multi piece unit. The contents of
YORK INTERNATIONAL - East York FACILITY
each skid are indicated by segment(s) surrounded by
1499 E PHILADELPHIA ST
parenthesis (see Fig. 5 below).
YORK PA 17403
USE COPPER WIRES ONLY. CLEARANCE FROM COMBUSTIBLE SURFACE: UNIT IS 0 INCHES,
DUCT IS 0 INCHES. MAXIMUM INLET TEMPERATURE; 100^ F / MAXIMUM OUTLET (Skid 5 of 5) (Skid 3 of 5) (Skid 1 of 5)
TEMPERATURE; 200^ F. EXTERNAL STATIC PRESSURE RANGE OF 0.25'' - 5.00'' WG. CONFORMS
TO UL STD 1995 AND CERTIFIED TO CSA STD C22.2 NO 236
(Skid 4 of 5) (Skid 2 of 5)
(FS)(CC-HM)(XA-IC-XA-RF)(EE)(FR)
johnson controls 33
FORM 102.20-NOM1 (909)
Filter
UNIT TAG
AHU 9-10
JOB NAME SKID OVERALL SIZE
Owens Corning BLDG-21 116 H x 156 W x 76 L
Filters
026-32406-001 FLTR,PERFPLT,30%EFF,12W_24H_2D Qty: 4
026-32406-003 FLTR,PERFPLT,30%EFF,24W_24H_2D Qty: 16
026-32404-009 FLTR,VCL_SH,12W_24H_12D,80-85% Qty: 4
026-32404-010 FLTR,VCL_SH,24W_24H_12D,80-85% Qty: 16
Spare Filters
026-32406-001 FLTR,PERFPLT,30%EFF,12W_24H_2D Qty: 8
026-32406-003 FLTR,PERFPLT,30%EFF,24W_24H_2D Qty: 32
OA Moisture Eliminator installed on (EE) skid/segment. 026-32404-009 FLTR,VCL_SH,12W_24H_12D,80-85% Qty: 4
LD11730 026-32404-010 FLTR,VCL_SH,24W_24H_12D,80-85% Qty: 16
LD13942
FIG. 7 – filter LABELS
Bird Screen
MODEL # COM : 117817
DIRECTION OF AIRFLOW
XTO-108X120-JJRN046A
SERIAL # / DATE CODE JOB IDENTIFICATION #
The direction of airflow is always read from right to
CHTM XT0085 08-179121-01-01 left.
SEGMENT IDENTIFICATION *Ship Loose*
Outside Air 386-60000-938 Hood - EE
UNIT TAG
Hood 1 of 6 AHU 9-10
JOB NAME SKID OVERALL SIZE
Owens Corning BLDG-21 116 H x 180 W x 85 L
AHU 9-10
One of six hoods installed on (EE) skid/segment.
LD11751A
FIG. 6 – LOOSE COMPONENT ID LABELS
34 johnson controls
FORM 102.20-NOM1 (909)
1.0 pre-installation
LD13769
RIGGING INSTRUCTIONS
FOR LIFTING AIR HANDLERS WITH LIFTING LUGS, USE 60°min.
SPREADER BARS AND CABLES AS INDICATED. DO NOT USE
A FORKLIFT. ALL LIFTING LUGS MUST BE USED TO AVOID
DAMAGE. LD13765B
LD09613
SHACKLES
Refer to Fig. 1-4 for proper lifting with hook and
shackle at corners. Refer to Fig. 1-5 for proper lifting
with hook and shackle at lifting lugs.
LD13768
FIG. 1-5 – P
ROPER LIFTING WITH SHACKLE
AT LIFTING LUG
LD13767
FIG. 1-4 – P
ROPER LIFTING WITH SHACKLE AT
CORNER
LD13766
FIG. 1-6 – R
ECOMMENDED LIFTING WITH
BASERAIL
INSPECTION STORAGE
CHECK FOR DAMAGE SHORT-TERM STORAGE
RECEIVER RESPONSIBILITY Indoor Units:
Receiver is solely responsible for noting freight bill and Under no circumstances should out-
filling freight claims IMMEDIATLY (see “Receiving” door storage be used
in this section).
Outdoor Units:
Visible damage should be noted on the signed and
Be sure all shipping covers are re-
dated bill of lading with a request that the carrier
inspect the damage within 72 HRS. of notification. The
applied after inspection, or tarps are
shipping wrapper must be removed and replaced with used during storage.
a tarp or similar protective covering. Any concealed
damaged reported after 15 days will compromise a Short-term storage is considered six (6) months or less
claim settlement. Inspection requests may be done from date of shipment. Storage maintenance during
by telephone or in person, but should be confirmed in this time is usually limited to the following.
writing. If assistance is needed with the claim process,
contact your Johnson Controls Sales representative.
• Rotate fans every four (4) weeks beginning
INDOOR UNITS upon arrival to prevent moisture from damaging
bearing.
It is Johnson Controls intention that a shipping wrapper
be applied to unpainted indoor units for protection • If the units are to be stored out-of-doors, prior
from weather, road dirt, etc. during inland transit and to installation, special care must be taken to
that the wrapper be removed at the time of delivery to cover and protect the units from dust, rain, snow
allow for a thorough inspection, both inside and out. and rodents. The units must be protected from
constant exposure to rain and snow.
OUTDOOR UNITS • Store on a firm, flat surface to prevent distortion.
Outdoor units are not fully wrapped. Exposed openings Block the unit off the ground to protect
are covered for protection from weather, road dirt, etc. components from water.
during inland transit. A thorough inspection, both
inside and out, should be done at the time of delivery.
Protect all parts and porous materials
from rain and other sources of mois-
CHECKING FOR NON MOUNTED PARTS
ture. Decontaminate or replace as
• Check the packing list for non-mounted ship needed to ensure microbial growth is
loose parts. (Check inside all segments.) IAQ not introduced to the air handler.
• Packing list will note how many and type of
parts.
• The unit must also be protected from damage
• Shortages must be reported within 10 days after to the exterior of the cabinet or coil connections
receipt of order. by construction vehicles and personnel.
See Ship Loose Parts, Fig 2-8 thru 2-14
LONG-TERM STORAGE
requirement - field preparation
AIR HANDLING UNITS
SERVICE POLICY & PROCEDURES Supersedes 50.20-NM3 (307 ) Form 50.20-NM3 (909)
I. Supplementary Documentation
The following documentation is required to FULLY COMPLY with the Long-Term Storage requirements.
A. Long-Term Storage Requirements – GENERAL (refer to Form 50.20-NM1)
B. Long-Term Storage – PERIODIC CHECKLIST AND LOGS,
AIR HANDLING UNITS (refer to Form 50.20-CL3).
Indoor Units
It is Johnson Controls' intention that a shipping wrapper be applied to unpainted indoor units for protection
from weather, road dirt, etc. during inland transit and that the wrapper be removed at the time of delivery
to allow for a thorough inspection, both inside and out. Visible damage should be noted on the signed
and dated bill of lading with a request that the carrier inspect the damage within 72 hrs of notification.
The shipping wrapper must be removed and replaced with a tarp or similar protective covering. Any
concealed damaged reported after 15 days will compromise a claim settlement. Inspection requests
may be done by telephone or in person, but should be confirmed in writing. If assistance is needed with
the claim process, contact your Johnson Controls Sales person.
Outdoor Units
Outdoor units are not fully wrapped. Exposed openings are covered for protection from weather, road
dirt, etc. during inland transit. A thorough inspection, both inside and out, should be done at the time of
delivery. Visible damage should be noted on the signed and dated bill of lading with a request that the
carrier inspect the damage within 72 hrs of notification. Concealed damage must be reported within 15
days of delivery with a request that the carrier inspect the damage within 72 hrs of notification. Any
concealed damaged reported after 15 days will compromise a claim settlement. Inspection requests
may be done by telephone or in person, but should be confirmed in writing. If assistance is needed with
the claim process, contact your Johnson Controls Sales person.
3. Touch up any paint that has worn or chipped off using paint supplied in ship loose items. Prepare the
surface as required using a wire brush.
4. Verify that all ship loose items are present. Note any missing items on the Periodic Check List and Log
Sheet (50.20-CL3).
5. Locate unit(s) so that passing traffic will not damage shafts, coil connections, damper linkages or unit 1
panels.
6. Refrigerant coils must be evacuated and pre-charged with 5 PSIG nitrogen holding charge. DO NOT
damage or disturb these coils and connections.
7. Water coils must have all inlet and outlet connections capped or closed tight to prevent foreign materials
and liquids from gaining entrance during the storage period.
1. Electrical Equipment and Components shall not be stored or left in an outdoor environment.
2. Electrical Equipment and Components shall not be stored or left in a wet or damp environment.
Components sealed in plastic shrink-wrap are not exempt from this requirement. Moisture will collect
inside the plastic, resulting in corrosion of the cabinet, the electronic components and/or copper bus
bars.
3. Cortec® spray (Part VpCL-248) shall be applied to all components in the motor terminal box. The
spray shall be applied to all exposed areas of concern.
4. YORK Vapor Emitter(s) shall be installed inside each electrical and electronic components cabinet(s)
to protect against corrosion. Openings in cabinets shall be taped closed to minimize air infiltration
during the storage period. The quantity of emitters is determined by measuring the gross volume of the
component space occupied. YORK Part Number 026-37705-000 will protect a volume up to 5 cubic
feet. YORK Part Number 026-37706-000 will protect a volume up to 11 cubic ft. Both emitters have a
service life of 12 months.
5. A Vapor Type Corrosion inhibitor must be installed in the following equipment and components:
a. Place one corrosion inhibitor, YORK part number 026-37706-000, inside the power panel.
b. Place one corrosion inhibitor, YORK part number 026-37705-000, inside the control panel.
c. Place one corrosion inhibitor, YORK part number 026-37705-000, inside each VFD panel.
C. MECHANICAL
1. Spray all exposed shafts and sheaves with anti-corrosion spray, YORK part number 026-37707-007.
2. Disconnect belts and wrap all motors and sheaves in plastic with a YORK vapor emitter, part number
026-37705-000.
©2009 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53203 Printed in USA 50.23-NM3 (909)
www.johnsoncontrols.com Supersedes 50.23-NM3 (307)
LONG-TERM STORAGE
periodic checklist and logs
AIR HANDLING UNITS
SERVICE POLICY & PROCEDURES Supersedes: 50.20-CL3 (507) Form 50.20-CL3 (909)
I. Supplementary Documentation
The following documentation is required to FULLY COMPLY with the long term storage requirements.
II. Checks
1.2 Refrigerant Coils - Check holding charge pressure monthly to be sure that the pressure has not
dropped. If pressure has dropped, the unit should be inspected for signs of visible damage which may
have caused the loss of pressure. If pressure drops more than 2 psi, the unit should be pressure tested to
locate the leak, the leak repaired, and the unit recharged with nitrogen to 5 psig pressure. Note this in the
comments section of the monthly log sheet (see page 2 of this document).
2.2 Grease bearings every three months. The greasing procedure is explained in the product service
manual. 1
3.0 Semi Annual Checks
3.1 None
4.2 Re-spray all exposed shafts and sheaves with anti-corrosion spray, YORK P/N 026-37707-007.
1.0 Monthly
Motor Belts &
Rotate 5 PSI Coil
Drives Protected Comments
Shafts Pressure
and Dry
Date
Initial
Date
Initial
Date
Initial
Date
Initial
Date
Initial
Date
Initial
Date
Initial
Date
Initial
Date
Initial
Date
Initial
Date
Initial
Date
Initial
2.0 Quarterly
Grease Inspect Protective
Bearings Covering
Comments
Date
Initial
Date
Initial
Date
Initial
Date
Initial
4.0 Annual
Re-spray
Install New
Vapor Emitters
Exposed Shafts Comments
and Sheaves
Date
Initial
2.0 INSTALLATION
Do not weld or use torches on the ex- Never use silicone caulk/sealant or
terior or interior of the unit housing. caulk/sealant containing silicone in or
The housing contains polyurethane on any air handling equipment. [Only
insulation, which under combustion exception is when provided (high tem-
will produce harmful, toxic gases re- perature) with gas heat venting].
sulting in personal injury or death.
SITE PREPARATION
This instruction is written to provide
general information. The product OUTDOOR UNITS (SITE PREP)
line allows many variations and the Location of unit(s) should be away from building
installer is fully responsible for ad- flue stacks or exhaust ventilators to prevent possible
justing his actions as needed. If any introduction of contaminated air through the outside 2
questions regarding the content of air intakes (see Fig. 2-1 for service clearances).
this manual, or if any information is
not covered, contact local Johnson Allow sufficient space around the unit
Controls Service. for removing the access panels and
various parts of the unit. A minimum
Surface must be level on all installa- clearance equal to the width of the unit
tions. must be provided on one side of the
unit for removing the coil or fan as-
sembly. Add dimension of pipe chase,
air hoods, ducts, control/electrical
panels, etc. to minimum clearances.
If your unit has HEPA filters the fil- Allow additional clearance as required
ter frames, filter bulkheads and filter by local and national codes. Consider
segment panels are factory sealed Coil Access Panel for coil removal on
and must remain sealed for NO air outdoor units.
bypass.
A Fan Section
36"
H B Coil Section
36" C Face and Bypass Damper Section
D Filter Section - Door should open 180°
36" A B C D E F
E Inlet Section
F Rain Hood (add to unit width or length)
G
UNIT WIDTH G Pipe Chase Enclosure (add to unit width)
LD6328-4
MOUNTING CURB
Units must be installed in such a manner as to provide The curb, which supports the unit, will be shipped
enough elevation for properly designed condensate unassembled. It will be necessary to assemble the curb
traps (see Section 2 “Drain - Condensate Drain parts on the job site. Assembly drawing and a hardware
Trap”). ► package are shipped with each curb package. It is
important the curb be installed square. If applicable,
Installation Site: Area of roof on which ensure pitch orientation is correct.
curb is to be installed must be structur-
ally adequate to support the combined This “Curb Assembly & Installation Instruction” is
weight of curb, unit and system fluids. typical. Use it in conjunction with the specific drawing
supplied with each curb.
With these combined weights in place,
the resting surface for the unit MUST
Should there be any questions as to
be flat and level.
the number of pieces of curb parts or
assembling of the curb, notify Johnson
Concrete pads often are not as flat
Controls immediately.
as they should be. Shimming and/or
grouting may be necessary. Whether
Curb, nailer, and gasket are supplied.
under the unit base or under the curb,
All other parts such as wood or fiber
this is to ensure the unit base is on a
cant strips, roofing felts, roofing mate-
perfectly flat plane.
rial, caulking and curb-to-roof fasten-
ers are to be field supplied.
Curb Assembly & Installation Instructions When unit is shipped in sections, the
See Fig. 2-2 curb gasket is to be replaced with caulk
provided by contractor.
1. Unpack shipping package, layout pieces and
parts according to the exploded views and check
against Bill of Materials.
5. After verifying curb is square and level, tighten
2. Layout all channel pieces as shown. Make certain all bolts and then anchor as appropriate.
that all channel tabs are located on inside of mat- If bolts are tightened after anchoring,
ing channel curb will be pulled, twisted and torqued
Make certain that all curb walls ac- out of square.
2
cessories and flanges, which may
have been distorted in handling, are
straightened before assembly.
6. Pipe Chase Curb Assembly - once curb is square
and level mark the exact location for the pipe
chase curb. Drill and assemble.
3. Attach curb walls together to form rectangular
perimeter as shown, leaving bolts loose. Pipe Chase Curb Location:
Unit submittal drawing package has
After the curb is set in place, ensure a Johnson Controls curb drawing
proper consideration has been given showing dimensions of curb and pipe
to the air duct openings through the chase..
roof.
7. The curb should be insulated and roofed as re-
quired. Refer to SMACNA for counter flash.
4. The curb installation drawing (see Fig. 2-2)
shows a gasket that is mounted between the curb
and the unit. This gasket is shipped with the curb STEEL FRAME
parts. Install the curb gasket before setting the
unit on the curb. The gasket forms an air seal When a steel frame is used to support the unit, it must
between the unit and the curb and serves as a be level, flat without uneven steel frame joints, and
dampener, preventing metal-to-metal contact support the unit around the full perimeter. As a general
between the unit and curb. However, the gasket rule, cross members should be placed every 96" in
should not be used as a vibration isolator where addition to every shipping split.
the prevention of noise and vibration transmis-
sion into the building is critical.
CURB SUPPORTS
D
UNIT WALL as required
RIGHT HAND
A PIPE CHASE
UNIT RACEWAY B
B C
1-7/8" Note 1
CURB REST
1-7/8" 1-1/2"
CURB GASKET "A"
2" x 4" NAILER
Note 1
DETAIL B
PIPE CHASE CURB CONNECTION
TO UNIT CURB
WALL PANEL
Notes:
1. Curbs available in 14", 18", 22", 26", 30" & 34" heights 3. Curb material is galvanized steel, unpainted, and may vary in gage
2. Outdoor Base Rails are available in 6", 8" & 10" heights. based on the unit load and the Qty. of cross bracing provided.
Contractor is responsible for providing ductwork to include Base Rail height. 4. If curb space used as plenum, Seal all joints and seams with suitable sealer
such as urethane caulk (YORK P/N 013-02966-011)
LD09616G
CLEARANCE
Allow sufficient space around the unit
for removing the access panels and
various parts of the unit. A minimum
clearance equal to the width of the
unit must be provided on one side of 0 LD05373
2
the unit for removing the coil or fan
assembly. FIG. 2-4 – NO HOUSEKEEPING PAD – BASERAIL
REQUIRED TO ACCOMMODATE TRAP
HEIGHT
MOUNTING
FLOOR
Units must be installed in such a manner as to provide
enough elevation for properly designed condensate The floor must be flat and level.
traps.
HOUSEKEEPING PAD
See Section 2 “Piping Connections - Condensate The housekeeping pad must be flat and level (see Fig's
Drain Trap.” ► 2-3, 2-4 & 2-5).
LD05372
BDW COOLING
BDW COOLING
FAN SECTION FS
MC RF CC RF
MB MB
FAN SECTION FS
LD09619a
ELEVATION VIEW ELEVATION VIEW
General Requirements
Johnson Controls recommends that ceiling suspen-
sion of units be accomplished in the field with the Structure Positioned In the Direction of Airflow
following: The unit base must be supported continuously, on both
sides of the unit.
Structure Positioned Perpendicular to Airflow
UNIT INSTALLATION
LD09613
Material not provided by YORK.
FIG. 2-7 – TOOLS TYPICALLY USED FOR When unit is shipped in sections, the
ASSEMBLY OF SHIPPING SPLITS gasket provided with the curb is to
be replaced with caulk provided by
contractor. Gaskets on curbs can
pose a problem when sliding sections
together for the final connection of
each shipping split.
3/8" Flat
Washer
Size = 3/16" 3/8" Lock Washer
Allen Wrench
LD11029A
Bracket p/n 086-11146-001
FIG. 2-8 – S
ECOND TIER TIE-DOWN FASTENER PACK
P/n 386-03419-000 (4 each per pack) 1/2" Flat
1/2" Nut
Washer
1/2" Lock
Washer
LD11032A
FIG. 2-10 – B
ASERAIL SHIPPING SPLIT FASTENER PACK
P/n 386-03417-000 (4 each per pack)
1/2" x 5-1/2"
Hex Cap
Screw (2)
.56" ID x 1.38"
Raceway Lifting Lugs 1/2" Hex OD Flat
(assembled) 3/8" Flat Nut Lock Washer (2) Washer (2)
Washer LD13349
3/8" Lock
FIG. 2-11 – TOP RACEWAY SPLIT FASTENER PACK
Washer LD11030A
P/n 386-04747-000 (2 each per pack)
FIG. 2-9 – B
OTTOM RACEWAY SHIPPING
SPLIT FASTENER PACK
P/n 386-03418-000 (4 each per pack)
2-8 johnson controls
FORM 102.20-NOM1 (909)
SEAM CAP
• 1/4" x 2" Neoprene Gasket, P/N 028-15954-010
• 1/4"-14 x 1" Phillips Pan Head Tek Screw, P/N 021-19560-000
• 1/4"-14 x 1" Hex Head w/ Washer & Gasket Tek Screw 2
P/N 021-30530-052 for Outdoor Wall.
ROOF SEAM CAP
• 1/4" x 2" Neoprene Gasket, P/N 028-15954-010
Apply 2" Gasket • 1/4"-14 x 1" Hex Head w/ Washer & Gasket Tek Screw
& Caulk P/N 021-30530-052 for Outdoor Roof.
PIPE CHASE
• 1/4" x 2" Neoprene Gasket, P/N 028-15954-010
• 1/4"-14 x 1" Hex Head w/ Washer & Gasket Tek Screw
P/N 021-30530-052
Apply Caulk
Apply Caulk
PIPE CHASE BASERAIL COVER HOOD
P/N 086-23998-001
• 1/4"-14 x 1" Hex Head w/ Washer & Gasket Tek Screw
• 3/16" x 3/4" Butyl Tape
LD13770A
HUMIDIFIERS
Optional Steam humidifiers, when selected are provided
with dispersion equipment factory mounted inside the
air handling unit. The steam injection or generating
equipment, metering devices & sundries are shipped
loose.
FLUE CAP
CONTAINMENT
BAND
UV
UV
LIGHT
LIGHT
TUBE
TUBE
1/4”-14 X 1”
PHILLIPS PAN HEAD
SELF DRILLING SCREW
P/N 021-19560-000
1/4”-14 X 1”
SPARE FAN BELT HEX HEAD
(Attached to Fan)
SELF DRILLING SCREW
W/ EDPM WASHER
P/N 021-30530-052
LD13771
TOP SPLIT
CURB REST
BASE CHANNEL
e) Make sure all wiring and/or control tubing 6. Place the next section on the curb about 4" from
connection pig tails are secured out of the path the section already placed.
of the shipping split mating surfaces to prevent
7. At this time feed the electrical and control
damage.
connections from section to section and ensure
f) Apply 3.5" x 3.5" separate gasket squares, that they will be accessible after the sections
placing one square at each corner of the face are joined. Assemble the electrical connectors
of one section. Apply 1/4" x 2" foam gasket and/or pneumatic tubes each according to their
to face perimeter from 3.5" square to 3.5" labels. Do this before joining sections if access
square. Apply this gasket 1/4" from outside will be a problem later. Refer to Fig. 2-18.
edge of mating surface (nearest to exterior of
air handler). This is to allow for a 1/4" bead
of caulk. Refer to Fig. 2-17. Connectors
Butt joints to raceway gasket.
Caulked at joints.
0.25 thk
neoprene at
raceway split.
After wiring connections are made Ensure chain does not apply pressure
and before proceeding with assembly, to drain connection. Improper posi-
the top shipping split angle will need tioning of chain may cause damage
to be removed and repositioned (see to unit.
Fig. 2-19).
LD13775 LD13777
LD13776 LD13778
13. Apply a 1/4" bead of caulking to the exterior If a roof seam cap has a tab on one
of the seam. Trowel the bead level with the air end only, the end without the tab goes
handler exterior. This is to be done on roof and above the pipe chase location.
both sides (see Fig. 2-20).
14. Apply 1/4" bead of caulking to the seam inside
the unit on the floor.
15. Apply 1/4" x 2" foam gasket to the underside of 16. Repeat this procedure for each additional section
the seam caps and install them over the joints to be placed in making up the complete unit.
using 1/4"-14 x 1" hex head screws provided. 17. Install 1-1/2" Corner Connector Plugs on bottom
Painted seam caps are applied over the joints on raceway corners.
the sides and roof of the exterior and galvanized
seam caps are applied on the floor of the interior
only. Only needed on units or sections with-
out baserails.
REMOVE SHIPPING
BRACKETS
LD14262
Remove ShippingSplit
Remove Shipping SplitAngle
Angle
after completion
after completion ofofwiring
wiringand
and
tubing placement
tubing placement and
and
reposition before
reposition before proceeding
proceeding
with assembly
with assembly of shipping
of shipping
splits.
splits.
LD14097
FIG. 2-24 – R
EMOVE AND REPOSITION SHIPPING
SPLIT ANGLE
LD13782
2
LD13773A
FIG. 2-25 – P
lacing & anchoring first
section and attaching come-a-
longs
BASE CHANNEL
LD13374
7. Start pulling the sections together. Pull evenly 10. Fasten top raceway brackets with 1/2" x 5-1/2"
on both sides. bolts.
a) Be sure all of the electrical or control wires or 11. Apply 1/4" x 2" foam gasket to the underside of
tubes are clear. the seam caps and install them over the joints
using 1/4"-14 x 1" hex head screws provided.
b) Guide the top raceways together by placing
Seam caps are provided for sides, top and
rods or drift pins through the holes in the top
floors.
guide angles. When the raceways are together,
install the long bolts provided. 12. Repeat previous steps for each additional section
to be placed in making up the complete unit.
c) Guide the bottom raceway/baserails together
using rods or drift pins through the holes in the 13. Install 1-1/2" Corner Connector Plugs in bottom
lifting lugs on opposing sections. Do this on raceway corners.
each side of the unit simultaneously.
d) If any difficulty aligning due to racking of one Only needed on units or sections with-
section or the other, use another come-a-long
out baserails.
diagonally on the inside of that section at the
shipping split or across the tops of opposing
sections..
e) If any difficulty aligning due to top and bottom
not pulling together simultaneously, apply
shims under the unit sections as needed to
compensate for uneven placement area.
8. Complete pulling the sections together.
9. Fasten bottom, lifting lugs together with 1/2" x
4" bolts provided. See Fig. 2-28.
LD13781
Be sure all of the electrical or control 7. Lower the top tier onto bottom tier so that
wires or tubes in both tiers are clear. mounting brackets mate. Guide brackets
together using rods or drift pins through the bolt
holes (see Fig. 2-32).
LD09626
See “Ship Loose Parts” to identify 5. Apply 1/4" x 2" neoprene gasket to all raceway
gaskets and hardware items. mating surfaces of one mating section. Include
two gaskets side by side on intermediate raceway
surfaces (large units).
6. Ensure that the sections are not racked and will
line up properly.
ASSEMBLY OF END CHANNEL SHIPPING SPLIT
Attach sections as follows:
The assembly is the same regardless of 1. Make sure assembly surface is clean and level
what sections are being connected to- to allow the sections to slide freely. If surface
gether. The vertical Energy Recovery is irregular, use metal shims under sections as
Wheel shown in Fig. 2-33 is a common necessary to align mating surfaces.
example 2. Pull sections together using a come along,
drawing the base together. 2
Prior to pulling sections together:
3. Attach the sides of the sections. Beginning at the
1. Remove baserail support plate (large units).
bottom of the sections secure the end channel
2. Remove shipping brackets in corners. assembly brackets together using 3/8" x 3/4"
Allen head bolts, lock washers & hex nuts
3. Remove screws in raceway corners at ends of all
at each bracket . Continue securing the end
segments joining together (as shown in Detail A
channel assembly brackets together, working
of Fig. 2-33).
from bottom to top, pulling the sections tight.
4. Clean the metal surface where gasket is to
4. After the sides are secured, secure the brackets
be applied with mineral spirits or rubbing
on top of the unit with the same hardware
alcohol.
mentioned in step 3.
FIG. 2-33 – ASSEMBLY OF END CHANNEL SHIPPING SPLIT (ENERGY RECOVERY WHEEL SHOWN)
Apply Butyl
Apply Caulk
Clip
Mist Eliminator LD13783
or Filter
FIG. 2-34 – HOOD INSTALLATION WITH OPTIONAL MIST ELIMINATORS
HOOD INSTALLATION WITH OPTIONAL 7. Each hood is to be centered over the width
MIST ELIMINATORS of the opening. All hoods, especially those
containing barometric dampers, MUST be
See “Ship Loose Parts” for identifica- installed square.
tion of gaskets and hardware.
8. Seal each hood gutter to the unit panel with
Polyurethane Caulk provided.
9. When multiple hoods are installed in a stack
space the hoods approx. 1.5" apart so the bottom
1. Identify correct hood and respective location hood will extend 6" below the bottom of the
(see example on Fig 5 “Loose Component ID opening.
Labels” found in the Unit Identification section
10. Install optional mist eliminators.
of this Manual). Each hood is labeled for easy
identification. • Remove the clip(s) from the leading edge of
the hood.
2. Correct orientation is with the tracks or bird
screens to the bottom. The mounting flanges • Insert the proper size mist eliminator or filter
are predrilled. into the tracks.
3. Each hood is fitted with a factory installed • Reinstall the clip(s) on the leading edge of the
bird screen unless mist eliminator option is hood.
selected.
OUTDOOR AIR TEMPERATURE AND/OR
4. Apply provided 3/16" x ¾" Butyl tape to the HUMIDITY SENSORS
predrilled hood flanges and back wall angle that
contact the unit panels. When Outside Air Hoods are shipped loose on units
that include Factory Packaged Controls, these sensors
5. Use ¼"-14 x 1" Hex Head Self Drilling Screws will be dismounted and pulled back into the air handler.
w/EPDM washer provided. The contractor is to find them secured with tape inside
6. Each damper opening in the unit panels should be and put them through their respective penetration to
completely covered by its respective hood. The the exterior and mount them to the bracket provided.
bottom of the hood should extend approximately
6" below the opening in the unit panel.
JACKSHAFT TO
BLADE LINKAGE
DAMPER
ACTUATOR SELF
ACTUATOR DRILLING
SHAFT CLAMP SCREWS
BEARING PLATE
EDGE CLIP
025-39067-002
ROTATION
SELECTOR
ccw
cw
MOUNTING
GROOVES
MOUNTING BKT
JACKSHAFT
ACTUATOR
MANUAL
CRANK
SPRING HOSE
CLAMP(S)
LD12144
ACTUATOR
ACTUATOR EXTENSION PIN
025-39032-002
025-39032-002
MOUNTING
FLANGES COLD DECK
DAMPER
FACTORY
ACTUATOR P/N TORQUE BRACKET
INSTALLED SMALL 025-39032-002 35 IN LBS 086-03474-516
COUPLER
086-03474-516 (Top Disch.)
LARGE 025-30958-008 133 IN LBS
086-03474-517 (Rear Disch.)
COLD DECK
DAMPER
LD12029A
• Calculate the torque by number and size of • Direct coupled actuators are recommended.
blades in each individual zone. Remember there • Duct connections are to be made at the zone
are hot deck blades directly connected to cold dividers without damper blade restriction.
deck blades.
• Blades per zone are to be determined by 2
system CFM and static pressure requirements INERTIA FAN BASE FILL INSTRUCTION
for each zone by the Engineer’s construction
Inertia fan bases are pre-engineered according to fan
documents.
& motor size. Each cavity having a pre-installed
• The blade linkage (flat rods) connecting corrugated bottom is to be filled to the top with wet
all blades of each deck are to be cut at the concrete. The contractor must take care not to get
appropriate places to divide the decks into concrete mix on the bolts and adjusting parts of the
correct size zones. These blade linkage rods are adjustable motor base, sheaves, belts or on the floor
mounted externally on the assembly. Be sure to under the edges of the isolated fan base. The amount
cut a section of the flat connecting rod out. This of concrete can be calculated by measuring the overall
is to prevent interference when zones modulate length and width of the fan base assembly cavities
in opposite directions. that have the corrugated metal bottoms. The standard
depth of the cavity is 4".
• One Damper Shaft Extension Kit is provided for
each zone per the Factory Order Form (see Fig.
2-37). HUMIDIFIERS
Optional Steam humidifiers, when selected are
provided with dispersion equipment factory mounted
inside the air handling unit. The steam injection or
generating equipment, metering devices & sundries are
shipped loose with the unit. Humidifier manufacturer’s
installation, operation and maintenance information
is packaged with the respective humidifier. It is the
responsibility of the installing contractor(s) to make
use of the instructions and preserve same for turn-
over to the end user. All required steam supply piping,
condensate piping & wiring are the responsibility of
the installing contractor(s).
UVC EMITTER LIGHTS V-Ray lamps (tubes) have all four contact prongs on
one end of the lamp (tube). The lamp fits into clamps
When UV Lights are provided, the contractor is mounted in the air handler UV segment where a pre-
responsible for installing UV Lamps (tubes) and wired pig tail is installed. Simply engage the plug on
connecting a 120 volt power supply. The YORK the pig tail with the prongs on the end of the lamp.
Solution factory provides internal wiring with a
magnetic door safety switch, a lockable disconnect
switch with “Press to Test” pilot light and a latching
circuit that has to be manually re-energized on the
air handler exterior after a door has been opened and
closed. This is all pre-wired. The UV Lamps (tubes)
are shipped loose, but in protective packaging for
installation by the contractor.
See “Ship Loose Parts” to identify • Pinpoint the exact location to attach the pipe
gaskets and hardware items. chase.
• Ensure enough space will remain to apply
pipe fittings with insulation, inside the pipe
chase.
Pipe chase should be installed before • The pipe chase height should align with the
piping is connected. unit height.
2. Apply Gaskets
• Apply provided 1/4" x 2" neoprene gasket to
the underside of the air handler roof overhang
(see Fig. 2-41).
TOOLS REQUIRED
• Screw Gun
• Complete set of mechanics hand tools.
MATERIALS REQUIRED
• Shipped loose package containing 1/4"-14 x 1"
Self-drilling Screws w/gasket, Caulking, 1/4" x
2" Neoprene Gasket.
AIR HANDLER
AIR HANDLER
Apply gasket
Apply gasket
• When unit purchased with Baserail: Pipe Chase
Baserail Covers, 3/8"-16 x 1-1/2" Bolts and
Lock Washers.
LD11564
PROCEDURE
FIG. 2-41 – INSTALL GASKET UNDER ROOF
Never use silicone caulk/sealant or OVERHANG
caulk/sealant containing silicone in or
on any air handling equipment. [Only
• Apply gasket provided by curb vendor to top
exception is when provided (high tem-
of curb.
perature) with gas heat venting]
• Apply 1/4" x 2" neoprene gasket to the pipe
The top and bottom flanges are inside chase (vertical gaskets first, then horizontal
pipe chase. Separate cover angles are gaskets). Keep the gasket aligned with the
outside edges of the pipe chase housing (see
used on external vertical seams.
Fig. 2-42).
3 gaskets
Horizontal gaskets
completely overlap
overlap
vertical gaskets
vertical gaskets in
in
PIPE
PIPE CHASE
CHASE all four
all four corners
corners
RIVET NUT
(installed by factory)
PIPE CHASE
CHASE
3
3 with self
Install with self drilling
drilling screws.
screws. Insert
Insert screws
screws
LD12560A
into, and
into, and between,
between,all allpre-punched
pre-punchedholes
holes in
in
flange. Typical for both top and bottom
flange. bottom
FIG. 2-42 – APPLY GASKET TO PIPE CHASE
flanges.
flanges.
AIR HANDLER
AIR HANDLER
Caulk
Caulk as
as shown
shown byby PIPE CHASE
PIPE CHASE
dotted
dotted line
line (visible)
(visible)
and
and
dashed
dashed line
line (hidden).
(hidden).
Apply caulk between
Pipe Chase and Air
Handler
AIR HANDLER
PIPE CHASE
LD12565
FIG. 2-47 – P
IPE CHASE TO AIR HANDLER CAULK
LD12035A
APPLICATION
FIG. 2-45 – BASERAIL CAULK APPLICATION
AIR HANDLER
5
3
1
2
4 Install self-drilling
screws starting in • Apply 1/4" x 2" neoprene gasket to contact
middle and working
towards ends.
side of cover angle.
PIPE CHASE
• Remove top and bottom self-drilling screws
FIG. 2-46 – P
IPE CHASE TO ROOF INSTALLATION from pipe chase and set aside for later use.
• Place cover angles in vertical corners of pipe
• Add a small bead of caulking to the exterior chase and unit wall.
vertical seam between the air handler and
the pipe chase to insure complete seal. Pay
special attention to the top & bottom corners,
raceway & baserail engagements and under
the roof overhang (see Fig.'s 2-45 & 2-47).
AIR HANDLER
• Starting at the center, and working toward PIPE CHASE
each end, run 1/4"-14 x 1" hex head self-
drilling screws down through the air handler
overhang into the top of the pipe chase
through the gasket. Use caution not to strip Install Cover
Angle between
the 20-gage housing with the screws. Line Cover Angle Air Handler and
up self-drilling screws with double row of shown with Pipe Chase
screws on top of unit raceway, plus one gasket side before caulk
out dries LD12564
spaced evenly between each (see Fig. 2-46)
(No caulking required here.) FIG. 2-48 – INSTALL COVER ANGLE
PIPE CHASE
AIR HANDLER
FIG. 2-49 – P
ROPER POSITIONING OF COVER
Alternating between Air
ANGLE WITH NOTCH ON AIR Handler and Pipe Chase,
HANDLER SIDE install remaining self-drilling
screws starting at the top and
2
working toward the bottom.
• Attach the cover angle to the air handler and
pipe chase panels. Install self drilling screws
removed earlier to top and bottom holes on
cover angle.
• Starting at the top and alternating between
the air handler and pipe chase, continue
installing self drilling screws until reaching
the bottom. Use caution not to strip the LD12562
2-34
STEP 1 FLUE CAP STEP 2
42"L VSI PIPE SPLIT CLAMP
SPLIT PLATE (NOT INSULATED)
(Factory Installed)
Installation
PIPE CHASE
CURB
PIECE
RACEWAY
IVSI PIPE
SIDE (INSULATED PIPE)
PANEL
CONTAINMENT
BAND SET &
GASKET, 1" THK X 3"W X LG,
6"L SLIP INSULATION FIBER STEP 4
JOINT
0.43" CLEARANCE
GAS FURNACE WITH CASING 7.75
TRANSITION
PIECE
12" ID
EXT. FAN
STORM
COLLAR
LD13326
NOTES:
HAT 1. On outdoor Air Handling units the external flue/vent piping parts above the pipe chase are factory installed on units
CHANNEL having an overall height of less than 102”, including the vent piping.
2. Outdoor Air Handling units over 102” high will have the external vent piping parts shipped loose for field mount-
5.50 ing.
FIG. 2-52 – GAS FURNACE FUEL VENTING SYSTEM 3. On all outdoor Air Handling units the vent piping parts internal to the pipe chase will be factory mounted.
johnson controls
FORM 102.20-NOM1 (909)
FORM 102.20-NOM1 (909)
BURNER
ASSY
ID
MOTOR
FLOW 2
1
3
4
2
3 2
PITCH
4 Foot
LD12912
1
ELECTRICAL - GENERAL
All field wiring must conform to the DO NOT PENETRATE any main or
National Electrical Code (N.E.C.) and auxiliary drain pan.
possible local codes that may be in DO NOT PENETRATE roof of out-
addition to N.E.C. door unit.
POWER CONNECTIONS
LD11591
00495VIP
Panel locations and sizes vary based upon unit size and
burner configurations.
or side wall panels. Any penetration will have to FIG. 2-57 – MAIN POWER AND CONTROL PANEL
be drilled and must be properly sealed to keep out W/ COVER OPEN
moisture. Refer to IOM Section 5 “Field Penetrations
for Piping & Electrical Connections”. ►
Safety Limits
ID Fan
ID Fan Motor
LD11596B
FIG. 2-56 – GAS BURNER COMPONENT LOCATIONS
LD11595
ELECTRIC HEAT DISCONNECT SWITCH OPTIONS
• Fused Disconnect. LD11595
Staging
All accessible electrical connections
Contactors must be checked for tightness prior to
the actual startup. Many of the con-
nections contain several strands of
wire, and while they were tightened at
the time of assembly, they should be
checked and re-tightened if needed.
Knockouts
The danger of a poor connection is
overheating and component failure.
AVAILABLE CONTROL OPTIONS 2. The maximum air inlet temperature for open coil
heaters is 100° F, and for finned tubular heaters,
• Staging - No controller, but contactors are
80° F.
energized by providing control power to each
contactor from external BMS source. 3. Sufficient working space must be provided per
paragraph 110-26 of the NEC.
• Step Controller - device to receive a 0- to 10 VDC
or 4 to 20 mA signal and step on heat stages. 4. This electric heater is not designed for or intended
Mechanical/electrical device. to be used for temporary heat prior to system
startup / balancing.
• Vernier SCR - completely electronically con-
trolled by varying signal and varying output
between stages. Increases power to a stage by MECHANICAL INSTALLATION
modulation until another stage is needed. Ener- 1. All heaters will contain an adjustable airflow
gizes another stage and modulates power until switch in the heater control panel. This switch
another stage is needed. 0 to 10 VDC or 4 TO will be preset to close at a differential pressure of
20 mA. Less expensive than Full SCR. This approximately 0.3" W.C. In all cases the switch
system utilizes a step controller and one SCR will be connected to a pressure probe positioned
that modulates and resets for each stage. in the airstream. This probe has an arrow stamped
• Full SCR - completely electronically controlled on it that is viewable from inside of the control
by varying signal and varying output of a control- panel. When the heater is located upstream of the
ler. Like a VFD for electric heat. 0 to 10 VDC or fan this arrow will point away from the fan. When
4 to 20 mA. The controller modulates a separate the heater is located on the downstream side of the
SCR for each stage. fan the arrow will again point away from the fan or
with airflow. If it is incorrectly installed, remove
the (2) screws holding the pressure probe in place
INSTALLATION
and rotate 180° and reinstall. The airflow switch
pressure port that is not connected to this pressure
Rotating parts and electrical shock probe will be run to the exterior of the air handling
hazards exist. Lock out and tag out unit to source a reference differential pressure. In
the fan motor(s) and heat power some situations it may be necessary to adjust this
disconnects before servicing. FOL- airflow switch setting to allow for proper operation.
Precautions must be made at this time to make sure
LOW THE LATEST “LOCKOUT
that the airflow switch does not provide a false indi-
TAGOUT” PROCEDURE. Failure to
cation of airflow. Failure to meet this requirement
follow proper safety precautions may may result in serious damage or nuisance thermal
result in serious injury or death cutout tripping (see Fig. 2-60 and 2-61).
2. A visual inspection of the heater elements should
APPLICATION INFORMATION
be made prior to use of the heater. If physical
1. Follow the procedure given in this instruction to damage is evident, a Megohm test should be used
find the minimum air velocity for safe operation to validate the heater elements are safe for use. If
(see Fig. 3-25) . At least this minimum velocity a minimum value of 10 megohms is not achieved
must be provided at all points over the heater face then any damaged elements or ceramic insulators
area. Failure to meet this requirement may result must be replaced prior to operation.
in serious damage or nuisance thermal cutout trip-
ping.
BLOWER HEATER
AIRFLOW
BLOWER
HEATER
AIRFLOW
FIG. 2-60 – P
RESSURE PROBE DIRECTION
MOUNTING C
BRACKET
NO
NC
LD14270
ELECTRICAL INSTALLATION 7. When connecting heaters with more than one stage,
wire stage No. 1 so that it is the first stage on and
1. Follow the wiring diagram on the inside of the
the last stage off.
terminal box.
8. The heater must be wired so that it cannot operate
2. Supply connections must be made with copper
unless air is flowing over it. This can be accom-
wiring rated for 75° C minimum.
plished by using a built-in airflow switch and a
3. If supply connections are for 250 volts or greater, remote interlock. See the accompanying wiring
all wiring must be insulated for 600 volts. diagram for the method used with this heater and
4. When making line connections to heater element provide appropriate interlock wiring as illustrated.
terminals FOR FINNED TUBULAR HEATERS This diagram will be located inside of the electric
ONLY, apply a 1/4" wrench to flat section of termi- heater control panel.
nal immediately below threads. Otherwise damage 9. If not supplied as part of this heater, install a
to terminal may result. line disconnect switch or main circuit breaker in
5. Supply conductors for heaters rated less than 50 accordance with the National Electrical Code.
KW, must be sized at 125% of rated load. On heat- Depending upon the heater’s location and acces-
ers rated 50 KW and more, the supply conductors sibility, a built-in disconnect switch may meet this
may be sized at 100% of rated load, if indicated requirement.
on the wiring diagram. The line current for either 10. All electrical connections in the heater, including
a single or three phase load is calculated as fol- both field and factory made connections, should be
lows: checked for tightness before operating the heater.
In addition, after a short period of operation, all
KW x 1000
Single Phase Line Current = connections should again be checked for tight-
Voltage
ness.
11. If heater is wired to a heating / cooling thermostat,
KW x 1000
Three Phase Line Current = use a thermostat with isolating circuits to prevent
Voltage x 1.73
possible interconnection of Class 2 outputs.
6. The following table shows the maximum current 12. If the heating elements are divided into several
for 75 °C copper wire with not more than 3 con- sections with resistance wire between two or more
ductors in a raceway. It is based on the National sections, maximum KW per sq. ft. should be cal-
Electrical Code Table 310-16. The amperages culated as follows:
shown are for 125% and 100% wire sizing. If there
are more than 3 conductors in a raceway, derate Heater nameplate KW
these amperages per Table 310-15(b)(2)(a).
Number of heated sections x
area of one heated section
AMPS WIRE AMPS WIRE AMPS WIRE
SIZE SIZE SIZE
125% 100% AWG/ 125% 100% AWG/ 125% 100% AWG/
MCM MCM MCM
12 14 80 100 3 184 230 4/0
16 12 92 115 2 204 255 250
24 10 104 130 1 228 285 300
40 8 120 150 0 248 310 350
52 65 6 140 175 2/0 268 335 400
68 85 4 160 200 3/0 304 380 500
HUMIDIFIER OPTION
Control wiring diagrams are located in the humidifier
manufacturer's IOM found inside control panel or
attached. Factory package control drawings may not
include humidifier points.
LD11726
LD11725
FIG. 2-62 – TYPICAL HUMIDIFIER PANEL LAYOUT FIG. 2-64 – HUMIDIFIER POINTS
LD06340-1
COIL PIPING piping the torque is not transmitted to the coil header,
Do not test, clean and flush piping thus damaging the coil connection.
through this equipment.
Application Notes - All connections are male piping
thread except DX coils, which are solder. Drain and vent
Isolate this equipment from pressure taps on water coils are pipe thread shipped with plugs
testing of water, steam gas and air installed. These taps are installed approximately two
piping. inches back from the end of the threaded connections.
WATER
WATER COILS - HOT WATER & CHILLED WATER HOT AND CHILLED WATER COIL
PERFORMANCE
Connect the water supply to the header connection on
the leaving air side of the coil to achieve the counter The temperature rise of the air (hot water coil) or
flow of water and air. The return pipe will be connected temperature fall of the air (chilled water coil) leaving
to the remaining coil connection. the coil is dependent on the airflow across the coil, the
gallons of water flow through the coil and the entering
Install an air vent in place of the top pipe plug on the water temperature into the coil. Consult the submittal
return header. In order to provide for drainage, install for each job for the specific information.
a drain line and shutoff valve in the supply near the coil
or in place of the plug in the supply connection. See
Figs 2-68, 2-69 & 2-70 for typical piping diagrams.
ECCENTRIC CHILLED
RETURN REDUCER WATER
UNION RETURN
COIL
SUPPLY
STRAINER
CHILLED
DRAIN REDUCING WATER
TEE SUPPLY
GLOBE
UNION VALVE
RETURN
COIL
SUPPLY
PT GATE
PLUG VALVE
FIG. 2-68 – CHILLED WATER COIL CONNECTIONS Example - NOT for construction
ECCENTRIC HOT
RETURN REDUCER WATER
RETURN
COIL
SUPPLY
STRAINER
HOT
DRAIN WATER
SUPPLY
GLOBE
UNION VALVE
RETURN 2
COIL
SUPPLY
PT GATE
PLUG VALVE
FIG. 2-69 – HOT WATER PIPING - 2 WAY VALVE Example - NOT for construction
HOT
RETURN WATER
RETURN
UNION
COIL
ECCENTRIC
SUPPLY
REDUCER STRAINER
HOT
DRAIN 3 WAY CONTROL WATER
DIVERTING VALVE SUPPLY
GLOBE 1 Inlet, 2 Outlets
UNION VALVE
RETURN
COIL
SUPPLY
PT GATE
PLUG VALVE
GATE VALVE W/
HOSE BIB LD13792
FIG. 2-70 – HOT WATER PIPING WITH DIVERTING VALVE Example - NOT for construction
Any copper tube coils may be attacked by acid Do not bush or reduce the coil return pipe size. Use a
condensate. The practice of boiler water treatment full size return pipe to the bottom of a dirt pocket. The
should include CO2 removal to assure longer tube supply pipe may be reduced at the coil connection if
life. necessary. Install the coil casing level with the return
down. A coil must be sufficiently elevated to allow a
Freeze Protection 12 inch minimum drop between the return connection
Chilled water, hot water and steam coils can be on the coil and the trap. A greater than 2 inch drop is
damaged during freezing weather. Precautionary required for protection from freezing. The return main
measures must be taken to prevent freezing such as: should be located below the trap. Refer to Fig. 2-71.
STEAM CONTROL
• Positive coil freeze protection must be used in
installations where any part of the water coil is Continuous steam supply ensures long coil life and
subjected to temperatures of 32 degrees or lower. minimizes potential trapping, venting and freezing
This may be accomplished by using a suitable problems. A rapid cycling of the modulating steam
antifreeze solution. If the coil is not in use, it is supply or a frequent on-off steam supply control
recommended that the coil be completely drained results in repeated thermal and piping stresses which
and the inside of the tubes blown dry with com- will shorten the coil life. Modulating steam control
pressed air. valves must not be oversized but must be carefully
• After draining, flush coils with an antifreeze so- selected. A substantial variation in the supply pressure
lution such as glycol. A solution of 50% glycol will require the installation of a pressure-reducing
and 50% water will protect from freezing to ap- valve ahead of the automatic control valve.
proximately 35 degrees F below zero at sea level.
Also refer to ASHRAE and ARI guidelines. Light load operation with a modulated steam supply
• During winter operation due to the possibility of can be improved by the installation of a vacuum breaker
check valve. An open relief line to the atmosphere
shutdowns such as power failure, night shutdown from the return line near the coil is desirable, except
and weekend shutdown, the controls should be on vacuum systems.
installed so the return air dampers will go to the
full open position, and all fresh air dampers go With a modulated steam supply, it is not practical to
to the full closed position. A source of auxiliary lift the condensate to an overhead return. Locate the
heat must be maintained inside the unit cabi- coil well above the return, or provide condensate unit,
net. or a boiler return trap below the coil.
• Other means of protection such as various
electro-mechanical switches and the full constant Individual control valves are required on each coil
flow of water can be used; however, Johnson installed in series with respect to airflow. When a
Controls will not be responsible for any coils modulating steam valve supplies two or more coils
damaged by freezing. in parallel, with respect to airflow, the piping must be
designed to provide for uniform steam distribution to
STEAM each of the coils.
Refer to Fig. 2-71 “Steam Coil Piping
Arrangements.”
STEAM COILS
STEAM TRAPS
Float and Thermostatic (F. & T.) traps are recommended It is preferable to provide an individual trap for each
for all low or medium pressure applications. Use coil but a single trap may be used for coils operating in
thermostatic traps only for air venting, for outdoor parallel with respect to the airflow. Coils in series with
applications where an F. & T. trap might be subject to respect to airflow must be supplied with individual traps.
freezing. Use bucket traps only for a non-modulated Locate the trap at least 12 inches below the coil return
steam supply. Size the steam traps in accordance with connection and even lower when freeze protection is
the manufacturer's recommendations (usually several required. Do not attempt to lift condensate modulated
times the steady state steam flow). Use the actual steam supply.
operating conditions (coil pressure vs. return pressure)
for the selection of a trap.
SU
P PL
YM
DRIP TRAP
STEAM COIL
BREAKER
1/2" CHECK
GATE VALVE
2
FOR END VALVE
PITCHED IN (OPTIONAL)
OR LOW CASIN G
VENT TO POINT OF
ATMOSPHERE SUPPLY
CLOSE TO MAIN DIRT
UNIT POCKET
(NOT ON (FULL STRAINER
VACUUM SIZE OF
SYSTEMS) RN COIL
TU N
RE MAI 12" MIN. CONN.)
DIRT POCKET
SINGLE COIL (FULL SIZE OF
VERTICAL AIR FLOW COIL CONN.) IN FLOAT AND
MA
RN THERMOSTATIC
U
R ET TRAP
AIN
YM
PLY PPL
SUP IN SU
MA
W
FLO
AIR FLO
W
AIR 12" MIN.
12" MIN.
12" MIN.
COILS IN SERIES
AIR FLOW MUST HAVE
COILS IN PARALLEL AIR FLOW INDIVIDUAL TRAPS AND
MAY HAVE COMMON SUPPLY CONTROL VALVES IN
AND SINGLE TRAP MA
IN RN
(INDIVIDUAL COIL TRAP PREFERRED) MA U
RN RET
TU
RE
LD04887A
STEAM IN
ACTUATOR
FACE
DAMPERS
CLOSED
BYPASS
OPEN
STEAM OUT
LD09630
FIG. 2-72 – INTEGRAL FACE & BYPASS COIL (HORIZONTAL; TUBES, STEAM SHOWN)
A complete IOM is provided with each Below 35°, the Vertical Tube Integral Face & Bypass
IFB or VIFB coil unit. (VIFB) or Integral Face & Bypass (IFB) operates with
full steam pressure or full water flow at all times. This
prevents freeze-up and temperature stratification.
Internal steam manifolds and piping should be The outside air and return air must be thoroughly
insulated. mixed before passing over the coil. When freezing air
enters only part of the coil, it creates a greater hazard
Steam traps should be sized for three times the than when the airflow entering the coil is of a uniform
calculated condensate loading at the coil design temperature.
conditions, based on the pressure differential across
the trap, not the boiler pressure. Traps should be of Coils used in series with respect to the airflow must
types that pass condensate and air at saturated steam have individual controls with ample space between the
temperature. Inverted bucket traps should incorporate coils for sensing devices, when required. Coils with
thermostatic air vents. two or more rows are more sensitive to freezing than
single row coils.
Make return connection full size as required and
reduce only at trap. Do not use reducing bushing on On 100% O.A. capable applications, locate low limit
coil return connection. at least 24" downstream of leaving edge of VIFB/IFB
casing. Low limit element must cross both face and
bypass areas, parallel to headers.
3/4" (19.1mm)
AUTOMATIC AIR
VENT IN TOP
HEADER
VIFB AIR
COIL FLOW
HOT WATER
SUPPLY
HOT WATER
RETURN
FLEXIBLE
CONNECTOR
DRAINS
LD09632
3/4" (19.1)
AUTOMATIC AIR
VENT IN TOP
HEADER
R
AI W
O
FL
HOT WATER RETURN
LD09633
T
VIFB AIR
STRAINER COIL FLOW
AIR VENT TO ATMOSPHERE ON OPEN
GRAVITY RETURN SYSTEM ONLY.
MINIMUM 1" (25.4) PIPE
8" (203.2) MINIMUM
T
8" (203.2) 2
CHECK STRAINER
VALVE
FLEXIBLE CONNECTOR INSTALLED
COMBINATION FLOAT AND PARALLEL TO COIL HEADER AND
RETURN MAIN
THERMOSTATIC TRAP AS CLOSE AS POSSIBLE TO COIL
CONDENSATE CONNECTION.
Non-venting Traps
(Steam Pressure Below 15 PSIG Or 103.4 KPa)
CONDENSATE CONDENSATE
FLOW FLOW
T
VIFB AIR
1/4" (6.4) 12" MIN. COIL FLOW
PETCOCK CRACKED (304.8)
OPEN FOR
STRAINER CONTINUOUS AIR
VENTING
8" (203.2) MINIMUM
T
8" (203.2)
CHECK STRAINER
VALVE
FLEXIBLE CONNECTOR INSTALLED
INVERTED PARALLEL TO COIL HEADER AND
RETURN MAIN AS CLOSE AS POSSIBLE TO COIL
BUCKET
TRAP CONDENSATE CONNECTION.
NOTE : DIMENSIONS ARE IN INCHES.
DIMENSIONS IN PARENTHESIS ARE IN MILLIMETERS.
LD09634
REFRIGERATION
DIRECT EXPANSION COILS (DX)
DX coils are divided into splits depending upon the Do not leave piping open to the atmosphere
unit size and coil circuiting. Each split requires its own unnecessarily. Water and water vapor are detrimental
distributor nozzle, expansion valve and suction piping. to the refrigerant system. Until the piping is complete,
Suction headers are on the air entering side with suction recap the system and charge with nitrogen at the end
connection at bottom end of headers when the coil is of each workday. Clean all piping connections before
properly installed. Matching distributor connections brazing joints.
for each coil refrigeration circuit are on the air leaving
side. See certified drawing and/or connection labeling The orientation of the refrigerant distributor is not
to ensure correct matching of suction and distributor critical but the distributor tubes must not be kinked
connections. or bent in a non-uniform configuration. For this and
other piping & sundry tips, refer to Fig. 2-77.
Direct-expansion coils are shipped
charged with nitrogen. The orientation of the refrigerant distributor is not
critical but the distributor tubes must not be kinked
or bent in a non-uniform configuration. For this and
other piping & sundry tips, refer to Fig. 2-77.
TO INSULATED SUCTION
LINE CONDENSING UNIT
INSULATED HOT GAS LINE FROM CONDENSING UNIT PITCH 1/2" PER 10' IN
PITCH 1/2" PER 10' IN DIRECTION OF FLOW DIRECTION OF FLOW
LIQUID
LINE DRIER LIQUID LINE FROM
CONDENSING UNIT
SPORLAN
ASC HOT GAS CHECK THERMAL
FITTING VALVES EXPANSION
VALVE
LIQUID LINE
SIGHT GLASS SOLENOID VALVE
TXV Equalizer
Line
SIGHT GLASS
TXV Equalizer
Line
SUCTION LINE
1-7/8"
45°
LD05171A
REFRIGERANT IN
LEGEND
LD13319B
FIG. 2-78 – DX COIL CIRCUITING TYPES
johnson controls 2-55
Installation
FORM 102.20-NOM1 (909)
H2
H1
D2 H2
D1 D2
D1 H1
2 Distributor 2 Distributor
Circuits Face Split Circuits Row Split
SQ Required SQ Required
H6 H5 H2 H1
D2 D2 H3 H1 D6 D2
H2 H1
D4 D5 D1
D2
D3 D1
D4 H8 H7 H4 H3
D8 D4
D1 H4 H3 D3 D1
D7 D3
D3 H4 H2
D2 2
H2 H1 2
D1 4
D4 1
H4 H3 1
D3 3
FIG. 2-81 – STACKED COIL DESIGN - STANDARD FIG. 2-83 – STACKED COIL CIRCUITING
H2
Single H2 Single
HDR H1
HDR H1 D2 H2 Body
Body D2
D1 H1 Single D1 D2
HDR
Body
D1 D1 H1
H6 H2 H1 H6 H5 H2 H1
Single D2 H3 H1 D6 D2
HDR D2
Body D6 D5 D1
D4 D2 D1
D3
Single
HDR
Body H5 H4 H3 H8 H7 H4 H3
D4 D8 D4
D1 D3 D1 D5
D3 D7 D3
H4 H2
compressor #1
100% capacity
tXV LLSV
compressor #3
Feeds both circuits
FIG. 2-85 – TWO COIL CIRCUITS PER The first three compressors (see Fig. 2-89) would
REFRIGERANT CIRCUIT
be tied into LLSV1, TXV1 and TXV2. This would
compressor #1 provide full-face control of the coil at even the lowest
cooling loads. Both distributors on each of the coil
tXV LLSV
circuits would include auxiliary side connectors for
HGBP.
tXV LLSV
compressor #2 condensing Unit
The second set of 3 compressors would be tied into
DX coil LLSV2, TXV3 and TXV4 to maintain full-face control
LD09150
at higher loads. Reference Form 050.40-ES3 Section 9
FIG. 2-86 – DO NOT USE THE ABOVE for compressor staging solutions.
CONFIGURATION.
When the condensing unit has three compressors The more control stages used, the more precise
per circuit, two coil circuits should be used for each the control of the air temperature will be. Smaller
refrigerant circuit (Fig. 2-87). Each coil circuit must incremental changes in capacity will result in a more
have a dedicated TXV and distributor to handle one coil consistent DX coil leaving air temperature. This will
circuit and the LLSV should be sized to handle the full eliminate temperature swings in the conditioned space
capacity of the refrigerant circuit. The hot gas bypass and improve the comfort level, but more importantly, a
line should be connected to all of the distributors in the consistent space temperature is crucial to many process
coil circuit. applications. The smaller changes in capacity that
Compressor #1
result from using a greater number of control stages
will also extend equipment life. The most important
TXV
thing to remember is to maintain full-face control of
Compressor #3 the coil at all cooling loads. When row split coils are
Feeds both Circuits LLSV used, make sure that the first LLSV is energized with
the last coil circuit in the leaving air stream. This is
TXV
Compressor #2 Condensing Unit
always the last one de-energized too.
DX Coil LD09151
There are four basic components in a VAV system - In the air-handling unit a decrease in airflow through
an air-handling unit with airflow control (i.e. variable- the DX coil will result in a corresponding decrease in
speed drives), VAV boxes, zone thermostats and duct the suction gas pressure while an increase in airflow
static pressure sensors. All of these components must will result in an increase in the suction gas pressure.
work together to provide good temperature control and a Since the system is designed to maintain a constant
comfortable environment. The zone thermostats control suction gas pressure, the compressors will be staged
the VAV boxes. As the zone temperature increases, the on or off as needed to meet the increase or decrease
VAV boxes open to allow greater airflow into the space in load demand. The system should be designed to
and as the zone temperature decreases, the VAV boxes operate smoothly avoiding transients that could upset
close to decrease the airflow to the space. system balance and cause liquid flood back.
As the VAV boxes in the system open and close the Problems can arise if the airflow
static pressure in the ductwork changes. When a box decreases more quickly than the
opens, the duct static pressure decreases, and when a compressor control can respond to
box closes, the duct static pressure increases. The duct
the load change. Therefore, airflow
static pressure sensor controls the air handling unit
should never change at a rate faster
supply fan. Since an increase in duct pressure relates
to a decrease in the zone airflow required, the supply than 3% per minute on VAV systems.
fan volume decreases in response. Conversely, a lower
duct static pressure indicates a need for increased zone This limitation will promote stable control of the
airflow; therefore, the supply fan volume increases system and minimize fluctuations in zone temperature.
in response. The change in supply air volume is Under any circumstances, a minimum of 350 FPM
accomplished using a Variable Frequency Drive or face velocity across the coil must be maintained for
similar device. DX split systems.
DRAIN
PAN TRAP
"H" must be at least
DRAIN
NIPPLE 1 inch plus fan total Drain
Connection
NO.1 - FAN OFF
static pressure
DRAIN
PAN
H
NO. 2 - TRAP CONDITION WHEN FAN STARTS
DRAIN
PAN
COOLING COIL
DRAIN PAN Top of trap must be equal to or
lower than bottom of unit drain
NO. 3 - FAN RUNNING AND CONDENSATE LD06342-1 connection. LD05371-2
Two or more drains on same side of unit must be trapped DUCT CONNECTION GUIDELINES
individually before drain lines can be combined and See Fig. 2-94.
routed to a suitable drain (see Fig. 2-93).
Duct connections to the unit may be made directly
except when the unit has external isolation. Then duct
connections should be flexible material and should be
installed so they are sufficiently loose. Duct connections
should be designed and installed according to AMCA
Standards 200 & 201 as a minimum. Duct turns and
TRAPS transitions must be made carefully to hold friction loss
to a minimum. Avoid short turns. Duct elbows should
LD06345-1 contain splitters or turning vanes.
FIG. 2-93 – COMBINING DRAIN LINES The Effective Duct Length connected to the fan or
unit discharge should run in a straight line for at least
If distance from drain pan outlet to trap exceeds 10', 2.5 Equivalent Discharge Diameters* for up to 2500
install additional clean outs for each 10' segment FPM fan outlet velocity and one additional diameter
of horizontal drain line (min. 1/4 in. per foot fall for each additional 1000 FPM fan outlet velocity. This
required). ductwork should be no greater than 105.5% or no less
than 85.5% of the discharge area. In addition, the
On initial startup, it may be necessary to fill the trap slope of the transition elements should not be greater
manually. than 15% for converging elements, or greater than 7%
for diverging elements.
ELEVATING UNIT FOR GRAVITY FLOOR DRAIN
CONNECTIONS * To find the Equivalent Discharge Diameter:
DUCT CONNECTIONS
Duct must have positive seal to unit
openings. Outdoor baserails are
available in 3", 6", 8" & 10" heights.
Contractor is responsible for providing
ductwork to include baserail height. Effective Duct Length
LD06335-2
FIG. 2-94 – R
ECOMMENDED DISCHARGE DUCT
ARRANGEMENT WHEN TURNS ARE
REQUIRED
DUCT CONNECTIONS
Ducts must have positive seal to unit openings.
Installer is responsible for providing ductwork to include base rail height for curb mounted
units.
All duct work is to be supported independent of the connection to the unit.
If the entire unit is mounted on isolation, the duct connection is to be flexible.
This instruction is suitable for bottom, end, side and top connections. Top connections on
Outdoor units are not recommended.
Flanged ducts can be connected with self drilling screws directly to the unit with gasket or sealant between unit and
duct flange.
2
A flanged sleeve may be dropped through the opening, provided there is access to seal & fasten the flange to the
unit interior surface.
:
RAW OR STRAIGHT EDGE DUCTS OR SLEEVES
The duct opening on the unit is located in a panel that is approximately 2” thick. The inside of the opening (2”
surface) is suitable for attaching ducts.
If access is not available from inside the unit, access may have to be from inside the duct or sleeve.
Raw or straight edge ducts can be connected with self drilling screws directly to the unit with gasket or sealant
between unit and duct.
DETAIL A
GASKET OR
SEALANT
GASKET OR SEALANT
FLANGED DUCT
FIG. 2-95 – R
ECOMMENDED DISCHARGE DUCT ARRANGEMENT WHEN TURNS ARE REQUIRED
The performance ratings of coils will be met only if UPPER DUCT SECTION NOT
the airflow is uniform over the face of the coils. High CONTINUOUS THROUGH ROOF
air velocity spots on the coil may cause the carry-over SEALANT UPPER SECTION
EXTENDS 3" TO 4"
of moisture from the coil. High or low air velocity WOOD NAILER BELOW TOP OF CURB.
NOMINAL 2 X 4
areas of the coil will not deliver the published ratings.
FLASHING RECEIVER
The duct connections must be designed to provide for
uniform flow of air across the face of the coil. The LOWER DUCT SECTION
DECK
CANT STRIP
SOUND AND VIBRATION TRANSMISSION
All roof mounted air-handling units generate some
sound and vibration that may or may not require some LD06494A
FILTER LATCHES
NOTE: Typically when filters are by others, so are the filter clips.
P/N - 026-35778-000
Used with 2" (C86) & 4" (C89)” Amair 300 X Pleated Prefilter
in combination with a Single Header Final Filter.
P/N - 026-35778.007
P/N - 026-35778-006
2-13/16"
P/N - 026-36339-000
LD13303C
NOTE: Typically when filters are by others, so are the filter clips.
LD010174
LD010171
Fig. 2-99 – C
orrectly installed latch P/N
026-35778-000.
These instructions are for installing a four (4)” filter 4. Insert the filter into the frame.
(typically AmAir 300X pleated filter) into 16 ga. 5. After the filter has been placed into the frame,
galvanized holding frames. grasp the loose end of the latch and place it over
• Latches needed for these applications are four the filter frame, so that the latch secures the filter
(4) P/N 026-35778-007, as shown in Fig. 2-98. into the frame (see Fig.2-102).
• A single latch should be installed at each of the Repeat for the remaining latches.
four (4) corners of the frame.
• The latch fits into the set of knockouts, which
consists of two (2) rows of three (3) knockouts.
The row of knockouts closest to the gasketing
should be used for filters with a 13/16” single
header in combination with a nominal 2” prefilter.
2
The second set of knockouts should be used for
nominal 4” filters.
LD010177
Fig. 2-101 – C
orrectly installed latch P/N
026-35778-007
LD010160
LD010148
Fig. 2-105 – installed CARTRIGE W/PLEATS
Fig. 2-103 – installed CARTRIDGE filter
2-70 johnson controls
FORM 102.20-NOM1 (909)
INSTALLATION OF A VARICEL DH DOUBLE 4. Repeat the latch installation with the remaining
HEADERED FILTER latches. Note the orientation of the latch to the
knockouts in Fig.2-107.
These instructions are for the installation of a VariCel
After the latches have been installed, the frame
DH filter (nominal 12” deep double header) into 16 ga.
should be configured like that shown in Fig.2-
galvanized holding frames.
108.
• The latches needed for this application are four
(4) spring latches, P/N 026-35778-006 (as shown
in Fig.2-98.
• Two latches should be attached on each side of
the filter frame.
• The latches should only be installed, two (2) per
side of the frame. There should be no latches
used on the top or bottom. This is done to match
the holes in the filter frame, used to secure the 2
latch to the filter. See Fig.2-106 for the sets of
knockouts that should be used for the latches.
LD010183
Installation of Spring Latches 5 Insert the VariCel DH filter into the frame. While
holding the filter in the frame, grasp the loop on
1. Insert the straight end of the latch between the the end of the latch and pull it until it stretches
knockouts furthest from the corner. over the header and rests into the pre-drilled hole
2. Using a moderate amount of pressure, force the in the header of the filter (see Fig.2-109). Repeat
latch over the third knockout. this with the remaining latches.
3. The latch installation should now be complete. The 6. The filter should now be securely installed into the
latch should now be “trapped” within the three (3) frame.
knockouts.
LD010184
INSTALLATION OF A 2” & 4" PREFILTER IN 4. Repeat the latch installation with the remaining
COMBINATION WITH A DOUBLE HEADER FINAL latches; note the orientation of the latch to the
FILTER knockouts on Fig.2-110.
These instructions are for installing either a 2” or 4" 5. Insert the VariCel DH filter into the frame. While
prefilter (typically PerfectPleat, Premium or Premium holding the filter in the frame, grasp the loop on
HM pleated filters) used in combination with a the end of the latch and pull it until it stretches
VariCel DH (nominal 12” deep) final filter into 16 ga. over the header and rests into the pre-drilled hole
galvanized holding frames. in the header of the filter (see Fig.2-111). Repeat
this with the remaining latches.
• Two sets of latches are needed for these applica-
tions. Four (4) spring latches, P/N 026-35778-
006 are used to hold the VariCel DH into the
frame. In addition, four (4) prefilter latches, P/N
026-36339-001 are used to hold the 2” and P/N
026-36339-000 are used to hold the 4” prefilter
onto the face of the VariCel DH filter.
• For the spring latches, two (2) latches should be
attached on each side of the filter frame.
• The latches should only be installed, two (2) per
side of the frame. There should be no latches
used on the top or bottom. This is done to match
the holes in the filter frame, used to secure the
latch to the filter. LD010156
1. Insert the straight end of the latch between the Installation of Prefilter Latches
knockouts furthest from the corner.
6. To install the prefilter latches, slide the end of
2. Using a moderate amount of pressure, force the the latch with the 180 ° turn, over the edge of the
latch over the third knockout. header, as shown in Fig.2-112. The latch should be
3. The latch installation should now be complete. installed at the approximate midpoint of the filter
The latch should now be “trapped” within the 3 leg.
knockouts (see Fig.2-110). The prefilter latch should be slid over the header
as shown in Fig.2-112.
LD010163
LD010165
LD010190
Application: Holds one Astrocel I 11.5" D filter along frame sides. (See Fig. 2-117, 2-118 & 2-119 for application)
029-22082 Latch, HEPA Double 11-1/2"
Application: Holds one Astrocel I 11.5" D filter along frame middle. (See Fig. 2-117, 2-118 & 2-119 for application)
The Bevel Seal frame is a factory welded, extruded Visual Control clamps are designed for use with any
aluminum frame developed specifically for High conventional gasketed HEPA filter. Located at midpoint
Efficiency Particulate Air (HEPA) filter installations. of each filter edge, the calibrated spring-loaded clamps
Standard Bevel Seal frames accommodate multiple maintain up to 100 pounds pressure against the filter at
sizes of gasketed HEPA filters 11-1/2" deep. (See Fig. each clamping point. Four clamps are used per filter to
2-116, 2-118 & 2-119.) assure uniform pressure against the gasket. The clamps
have a 1-1/2" wide bearing surface.
Two Stage Gasket Compression Prevents Leakage
Easy Clamp Installation
The Bevel Seal frame features a two level sealing
surface connected by a bevel. This causes the filter No special tools are required for proper clamp
gasket to be compressed in two stages as clamping installation. Just tighten the bolt head until it is
pressure is applied. The outer edge of the gasket is flush with the clamp face to achieve the prescribed
compressed to a greater degree than the inner portion of compression. Proper clamping pressure is created
the gasket. (See Fig. 2-119.) indefinitely by the calibrated spring.
In the event excessive clamping pres- Single filter clamps are used around the perimeter of the
frame bank. Double clamps are used along main runners
sure is applied, the individual cells in
to secure a filter on either side of the T-section. (See
the gasket material can be fractured
Fig. 2-117, 2-118 & 2-119.)
causing the gasket to relax, allowing
leakage.
11-1/2"
ASTROCEL
MAIN RUNNER PERIMETER EXTRUSION HCX
SINGLE
FILTER RED
2"
CLAMPS
(PERIMETER)
2" 2"
T-SECTION PERIMETER SECTION -
TYPE H
LD06647A DOUBLE SILVER
FILTER
FIG. 2-116 – HEPA FILTER FRAME CROSS CLAMPS
SECTION VIEW (T. SECTION)
LD06648-1
DOUBLE T-SECTIONS
FILTER
CLAMP
2
DOUBLE PERIMETER
FILTER SECTION
CLAMPS
T-SECTION
LD09657
SPRING
DUCTWORK
AIRFLOW
BEVEL SEAL
CELL SIDE
FRAME
(PERIMETER
EXTRUSION)
MEDIA PACK
BEVEL SEAL FRAME
GASKET BEVEL
RECESSED SEALING
CELL SIDE SURFACE
LD06646A
3.0 STARTUP
Rotating parts and electrical shock While it is a common practice to oper-
hazards exist. Lock out and tag out ate the fan as soon as possible (air
the fan motor(s) and heat power movement during construction is al-
disconnects before servicing. FOL- ways preferred by contractors) on the
LOW THE LATEST "LOCKOUT job site, the incomplete ductwork and
TAGOUT" PROCEDURE. Failure missing diffuser grilles will greatly
to follow proper safety precautions reduce air resistance and will allow the
may result in serious injury or death. fan to operate beyond design param-
Refer to general safety guidelines and eters. This practice may result in water
safety symbols located at the front of carry over and flooding of the unit.
this Manual. ► Also, the motor may over Amp and
become damaged.
Always replace metal tab on access Fan manufacturer's describe the rota-
doors that provide access to moving tion of the fan impeller as being
parts. This mechanical protection “clockwise” or “counterclockwise” for
from moving parts is required by UL- centrifugal fans when viewing the
1995. drive side (see AMCA Standard
When internal safety catch is not used, 2406).
always replace metal tab on access 3
doors that provide access to pressur- If your unit has HEPA filters the filter
ized areas. This mechanical protection frames, filter bulkheads and filter seg-
is to prevent accidental release of ac- ment panels are factory sealed and
cess doors under positive pressure. must remain sealed for NO air by-
pass.
Serious damage to the AHU and/or
system is eminent if the AHU is oper-
ated under any of the following condi- Never use silicone caulk/sealant or
tions: caulk/sealant containing silicone in or
• Wi t h o u t p r o p e r c o n t r o l o f on any air handling equipment. [Only
dampers. exception is when provided (high tem-
perature) with gas heat venting].
• With smoke dampers closed.
• During a fire alarm or smoke
purge test.
• Any airflow restriction greater
than normal.
• Fluctuating or incorrect voltage
power supply
PRE START UP FAN ASSEMBLY In small units the tie down bolts may
INSPECTION only be applied to three corners of
the fan base since one corner is not
When the unit is removed from long-
accessible.
term storage moisture laden bearing
grease should be purged and replen-
ished with fresh grease per lubrication
TIE DOWN BOLTS
decal. The motor should be meggered
to verify that the resistance is still at
a satisfactory level compared to the
value recorded prior to storage.
See Fig. 3-4 for TEFC. • Fig. 3-6 shows isolator with seismic snubber
restraint option.
Grommet
Snubber,
Seismic
LDO9639 LDO9636
FIG. 3-4 – TEFC (TOTALLY ENCLOSED FAN COOLED) FIG. 3-6 – SEISMIC SNUBBER
ISOLATORS
Check fan base isolators and thrust restraints for proper Preparing Fan Isolators for operation:
adjustment. 1. After tie down bolts are removed from the inter-
nal fan assembly check blower/motor frame for
• Standard fan isolation consists of spring isolators correct height and that the frame is level.
(see Fig. 3-5) mounted under the internal fan as- 2. To adjust isolators (see Fig. 3-5): First loosen
sembly. cap screws on top of adjustment bolt. Then turn
adjusting bolt. Next, check operational height
Cap Screw and level of frame. Repeat this procedure until
operational height and frame is level. Finally,
Adjusting Bolt tighten cap screws. (See IOM Section 5, “Isolator
Adjustment” for additional instructions). ►
3. Verify the fan is aligned with unit discharge.
4. Re-adjust as necessary with isolators.
LDO9637
TYPICAL ACTUATORS LOCATIONS With the actuator shaft clamp tightened to the damper
Johnson Controls standard actuators are direct coupled jackshaft, and the damper shaft is completely rotated
on damper jackshaft. to its proper position, manually operate the actuator to
its fully actuated position using the crank arm provided
BASIC ACTUATORS INSTALLATION
with the actuator. Then release the spring to allow the
damper to go back to its original position. This will
A basic procedure for installing Johnson Controls verify the actuators spring rotation and stroke.
actuators is included in Section 2"Installation". Set the damper actuators rotation selector switch to the
proper rotation required to actuate the damper.
DAMPER BLADE ORIENTATION
Return Air and Mixing Dampers with Power Off Damper actuator will always be op-
posite the spring return rotation.
Position the blades so that they will be open once the
actuator is installed. This will be the dampers spring
return position. Note whether the damper shaft is
rotated fully clockwise or counter clockwise.
FILTER
ELEVATION VIEW
COOLING HEATING
COIL COIL
ENERGY R/A DAMPER
WHEEL
O/A
BYPASS
SUPPLY FAN
EXHAUST FAN
ACCESS
WHEEL
ROTATION
BEARING SUPPORT
BEAM - PULLEY SIDE
BALL
BEARINGS (2)
BEARING ACCESS
COVER (2)
2. Before applying power to drive motor, confirm 4. If wheel has difficulty starting, turn power off and
wheel segments are fully engaged in wheel inspect for excessive interference between the
frame and segment retainers are completely wheel surface and each of the four (4) diameter
fastened (see Fig. 3-12). seals. To correct, loosen diameter seal adjusting
screws and back adjustable diameter seals away
3. With hands and objects away from moving
from surface of wheel. Apply power to confirm
parts, activate unit and confirm wheel rotation.
wheel is free to rotate, then re-adjust and tighten
Wheel rotates clockwise (as viewed from the
hub and diameter seals (see Fig. 3-13).
pulley side).
SEGMENT RETAINER
CATCH
2 ROTATE AWAY
FROM WHEEL RIM
ROTATION
TO REMOVE
SPOKE
DIAMETER
SEAL
1 PUSH
TOWARD
CENTER
TO ADJUST
WHEEL RIM
CENTER
OF
WHEEL
DIAMETER SEAL
ADJUSTING SCREWS FEELER
LD09643 GAGE
LD09644
INDIRECT FIRED GAS HEAT START UP - ECLIPSE GAS BURNER START UP 10:1 - 25:1
TURNDOWN & POWERFLAME GAS BURNER START UP 3:1 - 10:1 TURNDOWN
For your safety and satisfaction, this Your gas burner has been carefully
product requires check, test and start- inspected and tested at the factory;
up adjustment by a qualified HVAC however, different conditions at the
technician. Do not use for temporary jobsite, including controls that have
heat prior to start-up. been added at time of installation,
require careful testing and final ad-
justment for satisfactory operation.
Review burner control literature, in- The Burner Test Report / Factory
cluding wiring, piping, cut sheets and Specification Sheet in each unit shows
drawings before attempting to start the general data recorded during the
this unit. operation and safety tests at the fac-
tory. This data should be used as a
general guide; with final data recorded
on the start-up form. Do not exceed
All factory test start up burner speci- 550°F flue temperature at the ID fan
fications are located on a laminated inlet. Do not exceed 200°F supply air
“Factory Specification Sheet" located temperature.
on the inside of the control panel
door”. 3
INTRODUCTION IDENTIFY THE UNIT TYPE
This guideline describes the basic steps a technician Two types of Indirect Fired gas burners are used on
would take in starting an Indirect Fired gas heat system YORK Solution Air Handlers: The Powerflame series
on a YORK Solution Air Handler for the first time. and the Eclipse series. The Powerflame series offers
a turndown (modulating ratio) of 3:1 or 10:1. The
Each gas burner has been test run and inspected at Powerflame is easily identifiable by the motorized gas
the factory. Adjustments to component settings are valve with external linkage connecting the air dampers
typically not required. However, measurements of on the burner air inlet.
system parameters should be taken and compared to the
measurements recorded on the “Burner Test Report” to The Eclipse series uses an air/gas ratio regulator with
ensure safe and reliable operation. The “Burner Test no external linkage, and has a turndown range of 10:1
Report” is laminated to the inside of the burner control to 25:1 (sometimes greater). A visible external plastic
door. tube is used to transmit gas pressure from the burner to
the regulator. No external linkage is used.
7. The flue (stack) damper is located at the discharge 10. Visually check that the high temperature safety
of the ID blower and closed for shipping. Release limit is set for a 200-230°F range. The limit switch
the locking mechanism and set the damper to match is typically mounted behind the burner control
the position indicated by the scribed markings. panel.
Lock in place (see Fig. 3-15).
11. Connect a 0-15" gas pressure gauge or other suit-
Check Draft Test Port able instrument to the gas manifold port. The gas
ID fan
rotation pressure will be measured when running (refer to
step 4 of Burner Start-up Procedure).
Damper
Adjustment and
Indicator Plate On Powerflame burners this test port
BURNER PANEL
is downstream of the main regulator,
typically on a standard tee fitting in the
main gas line.
gram).
3. Turn burner panel off-on switch to on. FIG. 3-17 – DRAFT OVER FIRE test port
Once there is a call for heat, a 30 5. Observe the gas manifold pressure and compare to
data on the “Burner Test Report” under both High
second pre-purge period is initiated
Fire and Low Fire conditions.
to remove any gases from the heat
exchanger. The burner will then go 6. Check the flue (stack) combustion temperature at
through a second purge before igni- the ID Blower Housing Test Port. Make sure the
tion. test probe is inserted half way into the ID Inlet Tube
(see Fig. 3-18). Compare results to the “Burner
4. The burner will automatically go to Low Fire Test Report”.
at start up. After proof of Low Fire, the burner
will modulate up to High Fire. This may take 15
seconds for a Powerflame burner and 90 to 180
seconds for the Eclipse burner. After the burner
operates at High Fire use the manometer connected
to the Heat Exchanger Draft Port (see Fig. 3-17),
observe the reading. A negative pressure of about
-.03" WC is expected for draft overfire. Read-
ings may differ slightly from those shown on the
ID Fan Housing Test
“Burner Test Report”. Port
7. Using the signal generator, cycle the burner to Do not change set up of factory preset
check capacity modulation. Observe valve/damper air inlet dampers on Power Flame
actuator operation. burner.
Damper
Actuator
Any questions should be directed to
your local Service office or Johnson
Controls Product Tech Support, before
contacting the burner manufacturer.
Marked by factory,
future reference for
actuator set up.
LD12909
BURNER
ASSY
ID
MOTOR
FLOW 2
1
3
4
2
3
PITCH
4 Foot
LD12912
1
Failure to follow these guidelines may 5. Condensate drain and trap discharge should be
cause excessive condensation build up pitched away from the equipment at a slope of 1/4”
resulting in water damage to the facil- per linear foot or as local code dictates.
ity and/or a cracked heat exchanger.
6. For outdoor or unconditioned space installations
local climate may dictate the need to heat trace
1. Observe local jurisdiction codes for gravity con-
and/or insulate the exposed drain lines and trap.
densate drainage requirements.
Frozen drain lines and/or trap will cause build up
of condensate inside the heat exchanger resulting
2. Be sure the air handler is installed at an elevation
in leakage and damage to the air handler and pos-
that enables proper condensate drainage and trap-
sibly to the facility.
ping dimensions as provided in Fig. 3-21. Mini-
mum trap dimensions MUST be accommodated. 7. Provide unions in drain lines to allow removal of
trap for periodic cleaning of drain lines as well
3. Condensate drain line size must be the full line size as the trap. When the burner is operated at low
of the heat exchanger drain connection. capacity for extended periods, more condensate
is generated and with it deposits of solids in the
4. Drain lines, fittings and supports should conform condensate drainage system.
to local codes and be suitable for the application. 8. Provide the ability to prime the trap. During initial
and seasonal start up, trap inspection and priming
is required. Condensate in the trap will evaporate
during long periods of non-use.
3-16 johnson controls
GAS HEAT SEGMENT MODEL NUMBER NOMENCLATURE
B 100 U 3 L G G A A
REV DF SIZE/ CODE BURNER UNIT HAND ID FAN UNIT CONTROL BURNER
LEVEL CAPACITY COMPLIANCE TDR YORK HOUSING VOLTAGE VOLTAGE MOD
MBH DESIGNATION (T'STAT VOLTAGE) CONTROL
johnson controls
A 15 150 A ANSI 3 3:1 L Left G Galvanized A 120/1/60 A 24 A 2-10 vdc
200 or
B 20 200 U UL 10 10:1 R Right S Stainless B B 120 B 4-20 mA
208/3/60
0-135
C 25 250 F FM 25 25:1 C 277/1/60 C
Ohms
230 or
30 300 R IRI D
240/3/60
35 350 E 380/3/60
40 400 F 440/3/50
45 450 G 460/3/60
380 or
50 500 H
415/3/50
60 600 J 575/3/60
75 750 K 220/3/50
85 850
100 1000
125 1250
150 1500
175 1750
200 2000
225 2250
250 2500
275 2750
300 3000
325 3250
350 3500
375 3750
400 4000
3-17
FORM 102.20-NOM1 (909)
3
3-18
Startup
johnson controls
FORM 102.20-NOM1 (909)
FORM 102.20-NOM1 (909)
TABLE 3-3 – P
IPE SIZE REQUIRED
CONTAINMENT FURNACE A
GAS FURNACE WITH CASING OUTPUT
BAND SET &
GASKET, 1" THK X 3"W X LG, 15 21.83
INSULATION FIBER 20 21.83
25 21.83
6"L SLIP JOINT 40 23.66
7.75 0.43" CLEARANCE 50 23.65
H
75 28.15
100 28.14
TRANSITION
PIECE 125 35.12
12" ID
EXT. FAN 150 35.12
175 35.12
200 35.12
A 250 41.36
300 41.36
350 47.36
400 47.36
HAT CHANNEL
NOTES:
1. SEE SECTION 026-004 TO
5.50 DETERMINE LENGTH OF IVSI PIPES.
FLOOR PANEL
W
LD13304
FIG. 3-22 – GAS FURNACE FUEL VENTING SYSTEM
johnson controls
FORM 102.20-NOM1 (909)
STEP 3
STEP 1 FLUE CAP
STEP 2
42"L VSI PIPE SPLIT CLAMP
SPLIT PLATE (NOT INSULATED)
johnson controls
PIPE CHASE
CURB PIECE
RACEWAY
IVSI PIPE
SIDE PANEL (INSULATED PIPE)
SEE NOTE 1
CONTAINMENT
BAND SET &
GASKET, 1" THK X 3"W X LG,
INSULATION FIBER STEP 4
6"L SLIP
JOINT
12" ID
EXT. FAN TRANSITION
PIECE
STORM COLLAR
HAT CHANNEL
5.50
NOTES:
3-21
FORM 102.20-NOM1 (909)
3
Startup
FORM 102.20-NOM1 (909)
Connect Signal
Generator here for test
and start up
Jumper may be
required here for test
and start up
LD13315
INTERNAL INTERNAL
PRESSURE PRESSURE
CFM Temperature Rise (°F) CFM Temperature Rise (°F)
DROP “ DROP “
WC WC
INTERNAL INTERNAL
PRESSURE PRESSURE
CFM Temperature Rise (°F) CFM Temperature Rise (°F)
DROP “ DROP “
WC WC
3
AIRFLOW REQUIREMENTS
Calculate KW per square foot of duct area as: heater namplate KW (see step 12)
duct area (Sq.Ft.)
16 32
30
14 28
26
12 24
A ir
let
22
° In
80
10 20
r
Ai
low
let
Be
In
18
0°
KW PER SQ. FT. FACE AREA
r
Ai
-9
et
KW PER SQ. FT. FACE AREA
8 16
81
nl
°I
00
-1
14
91
6 12
10
4 8
FINNED
6
TUBULAR OPEN COIL
2 CONSTRUCTION 4 CONSTRUCTION
0 0
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 0 100 200 300 400 500 600 700 800 900 1000 1100 1200
MINIMUM AIR VELOCITY REQUIRED
MINIMUM AIR VELOCITY REQUIRED
(FEET PER MINUTE)
(FEET PER MINUTE)
BLOWER HEATER
AIRFLOW
BLOWER
HEATER
AIRFLOW
MOUNTING C
BRACKET
NO
NC
LD14270
IMPORTANT SAFETY REQUIREMENT: FOLLOW THE LATEST “LOCK OUT TAG OUT” PROCEDURE.
pre start-up
GENERAL UNIT INSPECTION
Identify and perform appropriate “lock out/tag out” and safety rules. For details on points below see appropriate
section of the Installation Instruction provided with each air handler.
For VFD equipped air handlers, refer to the VFD forms for additional requirements.
Serious damage to the AHU and/ • With smoke dampers closed.
or system is eminent if the AHU is • During a fire alarm or smoke purge test. 3
operated under any of the following • Any airflow restriction greater than normal.
conditions:
• Without proper control of dampers.
□ Equipment received as ordered. □ Verify all ductwork is complete and available for full air flow.
□ Unit checked for damage to interior and exterior. □ Unit installed with proper clearances.
□ Unit installed on flat and level surface. Outdoor unit □ Visually inspect roof curb for tight seal around unit.
mounted within roof slope limitations where applicable.
□ Terminal screws and wiring connections secure □ Clean air filters installed properly and secured.
in control, electric and Air Modulator panels.
□ Air hoods installed properly. □ Filter gauge set to zero.
□ Condensate drain properly trapped. □ All field wiring complete and inspected.
□ All wiring and tubing connections made at shipping splits. □ All shipping splits sealed and secured properly.
□ All field piping connections complete. □ Pipe chase floor sealed at penetrations.
□ All shipped loose parts installed. □ All shipping bolts and other material have been removed.
(Fan, VIFB, Energy Recovery Wheel, Damper).
□ Installer has cleaned out interior. □ Damper linkage is tight and in correct “power off” position.
□ Verify all plug-ins and wire connections are tight on UV □ Controls installation complete.
equipment.
□ Verify Energy Recovery Wheel turns freely and wheel □ Verify correct piping of split system. Reference Section 2 of
segments are fully engaged. Solution IOM & Split System Application Guide (050.40-ES3).
Fan INSPECTION
□ Check bearings and locking collars for properly tightened □ Fan wheel properly aligned, tight on shaft and freely
setscrews, bolts and nuts. moving.
□ Sheaves properly aligned and tight on shaft. □ Check fan base isolators and thrust restraints for proper
adjustment. Note: Do not remove functional bolts
□ Belt tension adjusted properly per drive pkg. label on fan. from seismic isolators.
□ Check fan alignment with unit discharge. Adjust with □ Fan bearings have been re-lubricated properly.
isolation.
start-up
Perform the following steps in order:
Refer to safety standards. Ensure all door latches are secured before starting.
□ 1. With all Electric Power off, all disconnect switches open and □ 8. Immediately check current draw of each leg of each motor.
fuses removed, check each circuit with an Ohm meter to
ground observing no continuity. Reinstall fuses.
□ 2. Energize power to the unit disconnect switch. □ 9. VFD, refer to manufactures start up guide
□ 3. Verify correct voltage, phase and cycles. □ 10. Check doors and latches for air leaks.
□ 4. Energize fan motor(s) briefly (bump) and check for correct fan □ 11. Check for obvious audible leaks.
rotation.
□ 5. Check operation of dampers. Insure unit will not operate with □ 12. Apply steam to cold coils slowly to prevent damage.
all dampers closed.
□ 6. Energize fan motor(s). Observe fan(s) for smooth operation. □ 13. Observe energy recovery wheel rotation.
□ 7. Check motor nameplate Full Load Amp rating.
RECORD DATA
POWER SUPPLY: Unit Nameplate V___ PH___ CYC, ____ Verify V __________/ _ _________ / ___________
DATA
SUPPLY FAN MOTOR EXHAUST/RETURN FAN MOTOR
Nameplate Volts_ ____________ Amps________________ Volts_ _______________ Amps_ ____________
Run Amps ____________ / _____________/ ___________ _ ___________ / ____________ / _ ___________
Catalog Number ______________________________________ _ ______________________________________
Spec Number ______________________________________ _ ______________________________________
Horse Power ______________________________________ _ ______________________________________
RPM Nameplate_ __________ Actual_____________ Nameplate___________ Actual_____________
Frame size ______________________________________ _ ______________________________________
Service Factor __________________________________ _ _________________________________
Jump (Skip) Frequencies ____________ / _____________/ ___________ _ ___________ / ____________ / _ ___________
other utilities
MAINTENANCE
Upon completion of start-up the customer assumes responsibility for periodic maintenance of this equipment in order to
continue warranty. Refer to the Installation Operation and Maintenance Manual (Form 102.20-NOM1).
Customer’s agent signature:_ __________________________________ Date: _____________________
©2009 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53203 Printed in USA 100.00-CL1 (909)
www.johnsoncontrols.com Supersedes 100.00-CL1 (309)
Refer to ASHRAE 62-2001 for startup and maintenance practices related to achieving ac-
ceptable indoor air quality. ASHRAE standard 62-2001 is under continuous maintenance
by a Standing Standard Project Committee (SSPC) for which the Standards Committee has
established a documented program for regular publication of addenda or revisions, including
IAQ procedures for timely, documented, consensus action on requests for change to any part of
the standard (see Table 4-1).
IAQ
Refer to Fig. 4-32 - “Maintenance Requirements for YORK Solution Air Handler (includes suggested IAQ minimums
for ASHRAE STD. 62-2001 Compliance”.
IAQ
Motor amperage should be checked again after the AIR HANDLER CABINET
connecting ductwork is installed and an air balance
performed on the air distribution system (see Section 4 Clean exterior with a mild, environ-
for Air Balancing Requirements). ► If motor operates mental safe detergent and high-pres-
at amperage levels above nameplate, discontinue sure water (2000 PSI max.).
operation and correct cause, or refer to Section 5.0, 4
“Service and Repair”. ► IAQ
PANELS
Inspect panels for damage. If panels show signs of
excessive pressure change, they will appear to bulge
inward or outward.
See Troubleshooting Guide regarding excessive
static pressure. ►
See Section 5 for “Panel Replacement” guide.
►
johnson controls 4-3
Operation & Maintenance
FORM 102.20-NOM1 (909)
Clip
Mist Eliminator FIG. 4-2 – TYPICAL DRIVE KIT DATA TAG
FIG. 4-1 – MIST ELIMINATOR REMOVAL
See Fig.4-4 for procedure to adjust motor base. FIG. 4-3 – ADJUSTABLE MOTOR BASE
(STANDARD)
4-6
SHEAVE
MOTOR
MOTOR BASE
MOUNTING HARDWARE MOTOR
KEYWAY
NOTE 3
DRIVE SIDE
(FIG. 1) FAN'S SHEAVE
Operation & Maintenance
KEYWAY
FAN'S BEARING
DRIVE SIDE
(FIG. 2)
MOTOR BASE
SUPPORT RAILS
MOTOR
MOUNTING/ADJUSTMENT
HARDWARE
MOTOR BASE
ADJUSTMENT SCREWS
(OPP-DRIVE SIDE)
NOTES:
1. THE SHEAVES SHOULD BE CENTERED ON THE SHAFT'S KEYWAY. SHEAVE CAN BE CLOSER TO THE BEARING,
AS LONG AS THE SHEAVES HUB IS ABLE TO FULLY ENGAGE WITH THE KEY.
2. CHECK FOR PARALLEL MISALIGNMENT BY PLACING A STRAIGHT EDGE ACROSS THE OUTER FACE OF THE
SHEAVES (FIG. 5). STRAIGHT EDGE IS TO BE LONG ENOUGH THAT IT EXTENDS PAST BOTH SHEAVES.
3. IF THE SHEAVES ARE MISALIGNED (FIG. 4), LOOSEN THE MOTOR'S MOUNTING HARDWARE AND SLIDE THE MOTOR
FORWARD (OR BACK) TO BRING THE SHEAVES INTO ALIGNMENT (FIG. 5), THEN RE-TIGHTEN HARDWARE.
MOTOR BASE
MOUNTING HARDWARE
johnson controls
FORM 102.20-NOM1 (909)
FORM 102.20-NOM1 (909)
30
Deflection
Force
25
Scale
20
15
the center of the belt span. Apply a force on the Small
“O”
Ring
plunger and perpendicular to the belt span until
the bottom of the large “O” ring is even with
the top of the next belt or with the bottom of a
straight edge laid across the sheaves.
5. Remove the tension gauge and read the force
applied from the bottom of the small “O” ring
on the deflection force scale.
150
6. Compare the force you have applied with the
value given on the Drive Kit Data Tag (see Fig. Span
4
100
SPAN
4-2). Large
“O”
Scale
Ring
of
50
INCHES
BELT SPAN
TI TH
EC NG
N
O
FL LE
DE AN
LD05628A
SP
SHEAVES ALIGNMENT
MOTOR
johnson controls
BELT
PLENUM
FAN
FAN'S
SHEAVE
NOTES:
1. TO REMOVE THE OLD BELT LOOSEN THE MOTOR BASE'S MOUNTING HARDWARE (DRIVE SIDE ONLY).
NOTE: THE DRIVE SIDE HAS 2 ADJ. SCREWS. TRY NOT TO INCREASE THE LEFT SIDE MORE THAN 1/2 AN INCH BEFORE INCREASING THE RIGHT SIDE.
2. LOWER DRIVE SIDE, USING THE ADJUSTMENT SCREWS (FIG. 3).
3. ONCE THE TENSION HAS BEEN REMOVED FROM THE BELT, THE MOTOR BASE'S (OPP-DRIVE SIDE) MOUNTING HARDWARE CAN BE LOOSENED.
4. CONTINUE LOWERING BOTH ENDS OF THE BASE UNTIL THE BELT(S) CAN BE REMOVED (FIG. 1).
5. ONCE THE SHEAVES HAVE BEEN CHECKED FOR PARALLEL ALIGNMENT (SEE SHEET 1), THE NEW BELT(S) CAN BE PLACED ON THE SHEAVES.
6. START RAISING THE BASE, TO TAKE THE SLACK OUT OF THE BELT(S), USING TH E ADJUSTMENT SCREWS ON BOTH ENDS. USE 1/2 INCH INCREMENTS.
7. AS THE BELT(S) START TO TIGHTEN, CHECK FOR PARALLEL MISALIGNMENT BY PLACING A STRAIGHT EDGE ACROSS THE OUTER FACE OF THE
SHEAVES (FIG. 4). STRAIGHT EDGE IS TO BE LONG ENOUGH THAT IT EXTENDS PAST BOTH SHEAVES.
8. IF THE SHEAVES ARE MISALIGNED AS SHOWN IN FIG. 2, THEN THE OPP-DRIVE SIDE NEEDS TO BE RAISED MORE.
9. IF THE SHEAVES ARE MISALIGNED AS SHOWN IN FIG. 3, THEN THE DRIVE SIDE NEEDS TO BE RAISED MORE.
***WARNING: AS THEN TENSION ON THE BELT INCREASES, IT IS LIKELY THAT THE OPP-DRIVE SIDE OF THE BASE WILL LIFT UP. IT IS ADVISABLE THAT
WHEN THE BELT STARTS TO GET TIGHT, THAT THE BASE'S OPP-DRIVE SIDE MOUNTING HARDWARE IS SECURED.
10. CONTINUE TIGHTENING THE BELT(S) US ING THE DRIVE SIDE ADJ. SCREWS ONLY.
11. IF THE SHEAVES ARE STILL ALIGNED (FIG 4), AFTER REACHING THE BELT'S SPECIFIED TENSION, SECURE THE BASE'S DRIVE SIDE MOUNTING
HARDWARE (YOU ARE FINISHED)..
12. IF THE SHEAVES ARE MISALIGNED (AS SHOWN IN FIG. 2 & 3), AFTER REACHI NG THE BELT(S) SPECIFIED TENSION, THEN LOWER THE DRIVE SIDE OF
THE BASE (TO REMOVE BELT TENSION). LOOSEN THE BASE'S (OPP-DRIVE SIDE) MOUNTING HARDWARE AND RAISE OR LOWER ACCORDINGLY A ND
REPEAT STEPS 6 THROUGH 11.
***NOTE: YOU MAY WANT TO MARK THE POSITION OF THE BASE'S OPP-DRIVE SIDE MOUNTING HARDWARE, BEFORE LOWER THE BASE. THIS MAY
HELP IN DETERMINING WHERE TO SECURE THE HARDWARE NEXT TIME AROUND.
4-9
FORM 102.20-NOM1 (909)
4
Operation & Maintenance
FORM 102.20-NOM1 (909)
LUBRICATION
SEAL ASSEMBLY
OUTER RING RECESSED CAM OR SELF-
VERIFY TYPES OF BEARINGS LOCKING COLLAR
Sealed (not to be re-lubricated in the field)
INNER RING
See Fig. 4-9
SELF LOCKING COLLAR
LD06357
8
1
LD09647
6
44
FIG. 4-9 – SEALED BEARING
5
9
Standard Pillow Block
See Fig. 4-10 & 4-11
Set
Screws
Lube
Fitting 7
Seal Lock
Ring
2 8
5
1
Pillow
Inner Block
Race 3 7
Outer 4 LD09648
00418VIP
Race
FIG. 4-12 – SPLIT BEARING
FIG. 4-10 – B
EARING WITH SETSCREW TYPE
1. Seal (4) 6. Lock Washer
LOCKING DEVICE
2. Housing Cap 7. Tapered Sleeve
3. Cap Bolts (2) 8. Bearing
4. Locating Ring (2) 9. Housing Base
5. Lock Nut
If fans will be down four (4) weeks or Re-lubrication is generally accompanied by a temporary
more, properly apply correct grease rise in operating temperature. Excess grease will be
and rotate monthly to prevent moisture purged at seals. Always wipe away purged grease
from damaging bearings. after several hours of operation.
FIG. 4-13 – LUBRICATION LINES (Optional) Bearing on fan split pillow blocks is
For specific fan bearing lubrication, 1/3 full when only one side of bearing
check the instruction packet attached is completely full of grease.
to the fan housing. Some forward
curved fans are permanently lubri-
cated.
TABLE 4-2 – FAN BEARING – LUBRICATION INTERVALS - BALL BEARING PILLOW BLOCKS
Re-lubrication schedule (months)
Speed (rpm) 500 1000 1500 2000 2500 3000 3500 4000 4500
Shaft dia.
1/2" thru 1-11/16" 6 6 5 3 3 2 2 2 1
1-15/16" thru 2-7/16" 6 5 4 2 2 1 1 1 1
2-11/16" thru 2-15/16" 5 4 3 2 1 1 1
3-7/16" thru 3-15/16" 4 3 2 1 1 1
TABLE 4-3 – FAN BEARING – LUBRICATION INTERVALS - SPHERICAL ROLLER BEARING SOLID
PILLOW BLOCKS
Re-lubrication schedule (months)
Speed (rpm) 500 1000 1500 2000 2500 3000 3500 4000 4500
Shaft dia
1-3/16" thru 1-7/16" 6 4 4 2 1 1 1 1 ½
1-11/16" thru 2-3/16" 4 2 1½ 1 ½ ½ ½ ½ ½
2-7/16" thru 3-7/16" 3 1½ 1 ½ ½ ½ ½
3-15/16" thru 4-15/16" 2½ 1 ½ ¼
TABLE 4-4 – FAN BEARING – LUBRICATION INTERVALS - SPHERICAL ROLLER BEARING- Grease to
Speed (rpm) 500 750 1000 15000 2000 2500 3000 3500 4000 interval
Shaft dia
1-7/16" thru 1-15/16" 6 4½ 4 4 3½ 2½ 2½ 1 1 0.50 oz.
2-3/16" thru 2-11/16" 5 4½ 4 2½ 2½ 1½ ½ ¼ ¼ 0.75 oz.
2-15/16" thru 3-15/16" 4½ 4 3½ 2½ 1½ 1 ½ 2.00 oz.
4-7/16" thru 4-15/16" 4 4 2½ 1 ½ 4.00 oz.
5-7/16" thru 5-15/16" 4 2½ 1½ 1 7.00 oz.
• Proper Interval
Lubrication Intervals – Recommended lubrication
intervals are shown in Table 4-5. It is important to
realize that the recommended intervals of Table
4-5 are based on average use. Refer to additional
information contained in Tables 4-6 & 4-7.
Over 360 to 5800 incl. (180) *2200 HRS.. 3500 HRS.. 7400 HRS.. 10500 HRS.
* Lubrication intervals are for ball bearings. For roller bearings, divide the listed lubrication interval by 2.
** For 6205 and 6806 bearings. For 6807 bearings, consult oil mist lubrication (MN410).
Re lubrication interval for 6205 bearing is 1550 HRS. (Using grease lubrication).
Re lubrication interval for 6806 bearing is 720 HRS. (Using grease lubrication).
* Special high temperature grease is recommended. Note that high temperature grease may not mix with other grease types. Thoroughly
clean bearing and cavity before adding grease.
** Special low temperature grease is recommended.
LD06352A
FILTER SEGMENTS (PRE FILTER AND INSERTING FILTERS INTO SIDE LOAD FILTER
FINAL FILTER) TRACKS FOR ANGLE AND FLAT FILTER
SEGMENTS.
A list of filter part numbers, sizes and
quantities are shown on a label lo- 1. Check filter sizes and quantities. See filter label
located on each filter segment.
cated on each filter segment of each
air handler. 2. Remove filter frame end cover (see Fig's 4-18
and 4-16).
3. Remove old filters if present.
If your unit has HEPA filters the filter
frames, filter bulkheads and filter seg- 4. Make sure gaskets at both ends of Side Load
filter tracks are in place. The gaskets are
ment panels are factory sealed and
normally found on inside of filter frame end
must remain sealed for NO air by- covers.
pass.
5. Slide the correct size new filters into tracks.
Bag Filter 12" Cartridge
6. On bag filters (in FF segments) leave banding
in place until filters are installed; then remove.
Install bag filters so that pocket dividers are
vertical if filters are over 12" high.
Cartridge 7. Airflow arrows must point downstream (in
direction of airflow).
4" High 8. All pleated filters must be installed with pleats
Efficiency 2" Pleated
Varicel II Filter vertical.
9. Re-install filter frame end cover.
Cleanable Filter
LD09650
RIGID PRE-
FILTER FILTERS
FILTER
FRAME END
COVER
LD09652
LD09652
Filter LATCHES
NOTE: Typically when filters are by others, so are the filter clips.
AAF 315-004-003
YORK P/N - 026-35778-000
AAF 315-004-000
Used with 2" (C86) & 4" (C89)” Amair 300 X Pleated Prefilter
in combination with a Single Header Final Filter.
AAF 315-004-001
YORK P/N - 026-35778-006
SPRING
DUCTWORK
LD13303A
NOTE: Typically when filters are by others, so are the filter clips.
LD010174
LD010171
Fig. 4-21 – C
orrectly installed latch
P/N 315-004-003.
Fig. 4-24 – P
lace the end of the latch
over the filter frame, securing 4
the filter to the frame.
LD010177
Fig. 4-23 – C
orrectly installed latch
P/N 315-004-000
Installation of Latches
Installation of Latches
LD010160
4
Fig. 4-27 – Fully installed filters
LD010496
LD010154
Fig. 4-29 – C
orrect latch/knockout
configuration.
LD010183
The frame contains 2 latches per side, INSTALLATION OF A 2" & 4" PREFILTER IN
none on the top or bottom. COMBINATION WITH A DOUBLE HEADER FINAL
FILTER
These instructions are for installing either a 2" or 4"
prefilter (typically AAF PerfectPleat, Premium or
Premium HM pleated filters) used in combination with
an AAF VariCel DH (nominal 12" deep) final filter into
5 Insert the VariCel DH filter into the frame. While AAF 16 ga. galvanized holding frames.
holding the filter in the frame, grasp the loop on • Two sets of latches are needed for these
the end of the latch and pull it until it stretches applications. Four (4) spring latches, AAF P/N
over the header and rests into the pre-drilled 315-004-001 are used to hold the VariCel DH
hole in the header of the filter (see Fig. 4-31). into the frame. In addition, four (4) prefilter
Repeat this with the remaining latches. latches, AAF P/N 315-003-002 are used to hold
the 2" and P/N 315-003-004 are used to hold
6. The filter should now be securely installed into
the 4" prefilter onto the face of the VariCel DH
the frame.
filter.
• For the spring latches, two (2) latches should be
attached on each side of the filter frame.
• The latches should only be installed, two (2) per
side of the frame. There should be no latches
used on the top or bottom. This is done to match
the holes in the filter frame, used to secure the
latch to the filter.
LD010154
Fig. 4-32 – C
orrect latch/knockout
configuration. P/N 315-004-001
LD010163
Fig. 4-34 – P
refilter latch after
Installation onto filter
header.
Fig. 4-35 – P
osition prefilter in front of
the final filter.
(2" w/315-003-002 latch shown)
LD010190 LD010167
Fig. 4-36 – S
pring the end of the latch so Fig. 4-37 – Completed assembly
that it fits over the edge of
the Prefilter. (4" w/315-003-004
latch shown)
Application: Holds one Astrocel I 11.5" D filter along frame sides. (See Fig. 4-26, 4-27 and 4-28 for application)
029-22082 Latch, HEPA Double 11-1/2"
Application: Holds one Astrocel I 11.5" D filter along frame middle. (See Fig. 4-39, 4-40 and 4-41 for application)
The Bevel Seal frame is a factory welded, extruded Visual Control clamps are designed for use with any
aluminum frame developed specifically for High conventional gasketed HEPA filter. Located at midpoint
Efficiency Particulate Air (HEPA) filter installations. of each filter edge, the calibrated spring-loaded clamps
Standard Bevel Seal frames accommodate multiple maintain up to 100 pounds pressure against the filter at
sizes of gasketed HEPA filters 11-1/2" deep. (See Fig. each clamping point. Four clamps are used per filter to
4-38, 4-40, & 4-41.) assure uniform pressure against the gasket. The clamps
have a 1-1/2" wide bearing surface.
TWO STAGE GASKET COMPRESSION
PREVENTS LEAKAGE EASY CLAMP INSTALLATION
The Bevel Seal frame features a two level sealing No special tools are required for proper clamp
surface connected by a bevel. This causes the filter installation. Just tighten the bolt head until it is
gasket to be compressed in two stages as clamping flush with the clamp face to achieve the prescribed
pressure is applied. The outer edge of the gasket is compression. Proper clamping pressure is created
compressed to a greater degree than the inner portion of indefinitely by the calibrated spring.
the gasket. (See Fig. 4-41.)
Single filter clamps are used around the perimeter of the
In the event excessive clamping pres- frame bank. Double clamps are used along main runners
to secure a filter on either side of the T-section. (See
sure is applied, the individual cells in
Fig. 4-38, 4-39 & 4-40.)
the gasket material can be fractured
causing the gasket to relax, allowing 11-1/2"
ASTROCEL
leakage. HCX
SINGLE
MAIN RUNNER PERIMETER EXTRUSION FILTER RED
CLAMPS
(PERIMETER)
2"
DOUBLE SILVER
FILTER
2" 2" CLAMPS
T-SECTION PERIMETER SECTION - (T. SECTION)
TYPE H LD06647A
DOUBLE T-SECTIONS
FILTER
CLAMP
DOUBLE PERIMETER
FILTER SECTION
CLAMPS
T-SECTION
LD09657
SPRING
DUCTWORK
AIRFLOW
BEVEL SEAL
CELL SIDE
FRAME
(PERIMETER
EXTRUSION)
MEDIA PACK
BEVEL SEAL FRAME
GASKET BEVEL
RECESSED SEALING
CELL SIDE SURFACE
COIL SEGMENT
COIL CLEANING PROCEDURE
SUGGESTED TOOLS, EQUIPMENT & MATERIALS LIST
3. When possible, remove dirt lodged in the depth
• Pressure washer that does not exceed 2000 of the coil by using clean oil-free air under
PSI. pressure. Caution should be taken not to use
extreme high-pressure air as this may cause fin
• Sprayer (utility garden, etc.) applicator. surface damage. Direct the air straight at the
• Plastic sheeting. openings between the fins and never at an angle,
which may bend the fins against one another.
• Duct tape. Always apply the air from the air leaving side
• Screening. of the coil.
• Coil cleaner (safe, commercial grade, 4. On heavily soiled coils, use a safe commercial
disinfecting). grade coil cleaner.
• Garden hose.
Follow the safety and mixing instruc-
• Garden hose spray nozzle.
tions as noted on or with the cleaning
• Rags. agent.
• Pail.
• Trash bags.
• Power cords.
• Four inch paintbrush.
4-28 johnson controls
FORM 102.20-NOM1 (909)
5. Spray the cleaning agent on both sides of the CONDENSATE DRAIN PAN, TRAP AND DRAIN
coil to be cleaned. Allow the cleaning agent LINE CLEANING PROCEDURE
to remain in contact with the dirty surface for
about 5 minutes or as recommended by the agent Clean condensate drain pan, trap,
instructions. Then flush the coil with clean water drain line and adjacent wetted sur-
from a hose (with spray nozzle or from pressure faces at least once per year or as often
washer). Flush from the air leaving side of
as required to retard growth of micro-
the coil. Caution should be taken, as extreme IAQ bial substances.
water pressure may result in fin surface damage.
Direct the water straight at the openings between
Testing of Drain Pans - To minimize
the fins and never at an angle, which may bend
the fins against one another. This process will conditions of water stagnation that
wash away surface dirt on the air entering side may result in microbial growth, drain
of the coil, and prevent it from loading within pans shall be field-tested under normal
IAQ operating conditions to ensure proper
the depth of the coil.
drainage.
6. Most cleaners are concentrated detergents and
can be diluted with up to 10 parts of water.
Exception: Field testing of drain pans
Dilute as per cleaning agent instructions and coil is not required if units with factory-
condition. Re-spray both sides of the coil with installed drain pans have been certi-
cleaner. Allow to stand 5 minutes and flush as fied (attested in writing) by the manu-
described previously. Finish flushing from both facturer for proper drainage when
sides of the coil. installed as recommended.
7. Apply cleaner to ALL surfaces including: • Draining each coil and related piping such as
underside of coil, header and return bends if in traps and making sure that all low areas also
air stream, coil supports, coil wall or bulkhead, drain.
auxiliary drain pans, splash guards, any other • After draining, flush coils with an antifreeze
surfaces subject to wetting by condensation solution such as propylene glycol. A solution
dripping or carried by normal airflow, drain pan of 50% glycol and 50% water will protect from
and outlet. freezing to approximately 35°F below zero at sea
8. Add ample amount of cleaning agent to drain level. Use adequate mixture for the geographic
line and trap. area of the installation.
MATERIALS
• Acti-Klean, Granger stock # 5W402. or alkaline
LD09659
WHEEL
ROTATION
BEARING SUPPORT
BEAM - PULLEY SIDE
BALL
BEARINGS (2)
BEARING ACCESS
COVER (2)
• To adjust diameter seals, loosen diameter seal • The wheel drive pulley is secured to the drive
adjusting screws and move diameter seal away motor shaft by a combination of either a key or
from wheel surface. D slot and setscrew. The setscrew is secured
with removable locktite to prevent loosening.
• Rotate wheel clockwise until two opposing
Annually confirm setscrew is secure.
spokes are hidden behind the bearing support
beam (see Fig. 4-44). • The wheel drive belt is a urethane stretch belt
designed to provide constant tension through
• Using a folded piece of paper as a feeler gage,
the life of the belt. No adjustment is required.
position paper between the wheel surface and
Inspect the drive belt annually for proper
diameter seals. Adjust seals towards wheel
tracking and tension. A properly tensioned belt
surface until a slight friction on the feeler gage
will turn the wheel immediately after power is
(paper) is detected when gauge is moved along
applied with no visible slippage during start-
the length of the spoke.
up.
• Retighten adjusting screws and recheck
clearance with “feeler” gage.
If slippage is detected, replace wheel
drive belt as soon as possible. A non-
WHEEL DRIVE COMPONENTS rotating wheel in the active air stream
• The wheel drive motor bearings are pre- is likely to become clogged. Contact
lubricated and no further lubrication is local Johnson Controls Service to
necessary. order replacement belt. See Section 5
“Belt Replacement” for Energy Re-
covery Wheel drive belt replacement
procedure. ►
johnson controls
Clean exterior of air handler cabinet. As Needed
Inspect doors, handles, latches and hinges for proper operation. X
Inspect door gaskets for damage and proper seal. X
Inspect panels for damage. X
Inspect air hoods and air louvers for damage and debris. 6 months
Inspect bird screens for damage and debris. 6 months
Inspect bird screens for damage, dirt and debris. 6 months
Clean fan segment and fan assembly (supply, return, exhaust). X
Check fan housing, wheel, shaft, frame, inlet vanes and bearings for damage, wear, loose parts, dirt and debris. X
Check fan base, vibration isolators and thrust restraints for damage, wear, loose parts, dirt and debris. X
Check flex connector for damage and wear. X
Check the cleanliness of the filters and replace or clean as required. X See IOM Tables
Check filter frames (filter tracks) for residual contaminates and clean as necessary. X
Verify filter gauge and/or switch function properly. X
Check drive kit for damage, loose parts, wear, dirt, alignment and belt tension. X
Check belt tension. X
Lubricate fan bearings. (Ball Bearing-Table 4-2, Roller Bearing-Table 4-3, Split Pillow Block-Table 4-4) See IOM Tables
Check condition of extended lubrication lines when present. X
Clean variable inlet vanes. X
Check adjustable fan motor base and mounting hardware for loose parts. X
Check adjustable fan motor base for damage. X
4-33
FORM 102.20-NOM1 (909)
SERVICE INFORMATION
All necessary tags and decals to aid in service or to While differences in temperature and humidity may
indicate caution areas are provided. Electrical wiring cause air movement, it may be considered very slight
diagrams are attached to the control panel access door. in comparison to the positive circulation required in
Installation, operation and maintenance manuals are an air conditioning system. To accomplish this air
supplied with each unit. movement, a fan has two functions to perform:
The YORK Solution offers unlimited unit access with • Produce sufficient pressure or head to accelerate
completely removable panels. All of the unit panels, the mass of air from a state of rest to the required
including the top panels can be completely removed. velocity.
The removal of top panels allows the use of overhead • Produce sufficient pressure to overcome any
cranes and gantries in removing and servicing of resistances to the flow of air.
components. Fan and filter segments come equipped
with doors as a standard feature. The determination of these pressures is a very important
part of troubleshooting an air conditioning system. The
TROUBLESHOOTING generally accepted standard instrument for measuring
these unit pressures is the Pitot Tube (see Fig's 5-1 &
An HVAC air system includes the air handling unit and 5-2). The Pitot Tube is used in conjunction with an
the entire air circuitry through which airflows. Included Inclined Manometer, Magnehelic Gauge, or a Tube
in the system are such components as ductwork, fittings, Manometer.
branch ducts, dampers, heat exchangers, filters, sound
traps, coils, elbows, diffusers, grilles, VAV's, MIT's When the Pitot Tube is used in conjunction with these
and other items through which airflows or which offer instruments, one is able to read velocity pressure (Vp),
obstruction to airflow. static pressure (SP), and total pressure (Tp) within the
system.
STATIC TUBE
0.02" DIAMETER HOLES
DRILLED THRU OUTSIDE IMPACT
TUBE INTO ANNULAR TUBE
SPACE.
D
LD06362-1
SOLDER
27926B
27928B
PRESSURE VACUUM
4 4 4
3 3 3
2 2 2
1 1 1
0 0 0
1 1 h 1 h
2 2 2
3 3 3
4 4 4
LD06364-1
Vp = TP – SP
The manometer does not sense the actual velocity INTERNAL STATIC
pressure directly but by using the Pitot Tube hook-up PRESSURE
with the static opening connected to the low pressure LD06365-1
side of the gauge, and the total pressure opening
connected to the high pressure side of the gauge, the
FIG. 5-7 – STATIC PRESSURE - AIR SYSTEM
manometer will read the difference between the two,
or the velocity pressure.
At a given flow rate the internal pressure losses plus • The most important item is to provide a detailed
the external static pressure losses equal the system explanation of the problem.
static pressure or the summation static pressure.
• An orifice is the best method of measuring flow
in piping. This is also true in an air system.
These pressures are of great importance when
troubleshooting for causes of reduced capacity,
vibration and noise. Changes in the cross sectional area
of a duct (contractions or enlargements) cause changes COMPONENT REPLACEMENT,
in the velocity of the air flowing through the duct. ADJUSTMENT & REPAIR
MARK ON
CLAMP AND FAN HUB
ROTATION
SHAFT
SETSCREW
KEY
5
LD09661
FIG. 5-9 – FC FAN SHAFT AND WHEEL MARKING
BACKWARD FORWARD
1. Disconnect all ductwork or guards attached
CURVED CURVED to the blower housing to permit unobstructed
LD6350-2
access.
2. Remove the cut off plate attached at the discharge
FIG. 5-8 – TYPES OF CENTRIFUGAL FAN IMPELLERS
or blast area of the blower housing.
3. Thoroughly clean the shaft of all grease and c) Reassemble in reverse order, center the
rust inhibitor. Be careful not to contaminate the wheel between the edges of the inlet cones.
bearing grease. Use emery cloth to remove all If bearings were removed or replaced, be
rust or the wheel may become “locked” to the sure to reuse any shim stock found between
shaft. the mounting support/plate and bearing
housings.
4. Loosen and remove setscrews on both bearing
locking collars. Inspect and, if necessary, d) Torque all hardware (see table 5-1).
replace.
9. Dynamic rebalancing the fan assembly is
5. Loosen and remove setscrews from both sides recommended.
of the wheel hub. Inspect and, if necessary,
replace.
Refer to AMCA Publication 410-90
6. Using a rubber mallet or brass bar, slowly drive
“Recommended Safety Practices” for
the shaft in one direction until the setscrew
users and installers of industrial and
marks on the shaft are fully exposed. File the
marks completely smooth. Drive the shaft in the commercial fans.
opposite direction and file smooth the setscrew
marks. Continue to clean the shaft of all dirt and These procedures must be followed
residuals. to protect personnel and include
isolating the fan from any electrical
7. To remove the key, use a rubber mallet or brass
bar to drive the shaft and wheel in one direction. supply.
Drive the key in the opposite direction using a
nail set or smaller size key stock until the key is Service should only be performed by
completely free of the wheel. Be sure that key experienced and trained personnel.
does not get bent by allowing it to ride up the key
way edge. The slightest bend will prevent quick AIRFOIL FAN WHEEL REPLACEMENT
assembly. Should this occur, replace the key The airfoil wheels can be removed from the side of
stock with a key of the same size and length. the fan housing by removing one or both unit side
8. Remove the shaft, supporting the weight of the panels. It is possible to remove the fan wheel through
wheel, particularly for larger diameter wheels. the fan discharge opening.
Do not allow the weight of the shaft to be
supported by one bearing as you disassemble.
a) Remove the wheel through the discharge or
outlet area of the blower housing.
b) File the setscrew marks on the key until
smooth.
the inlet cones must be removed from the side of the SET SCREWS (2)
housing since the cones nest inside the blower wheel
NUTS (3 or 4)
(see Fig. 5-10). The remaining steps for removing
the assembly are the same as those provided in the
instructions for removing the forward curved fans. BOLTS
LOCKING (3 or 4)
COLLAR
Dynamic rebalancing the fan assembly is SEALED BEARING
recommended.
RUBBER
FAN BEARING REPLACEMENT MOUNTING
GROMMET
SEALED BEARINGS
LD09662
TOOLS REQUIRED FIG. 5-11 – SEALED BEARING
• Standard mechanic’s hand tools. 4. Clean shaft until it is shiny from bearings to ends
• Medium flat file. of shaft.
• Torque wrench, 0 to 250 in.-lb. range. 5. File any burrs or set screw impressions from
shaft.
• Hex (Allen) socket set for torque wrench.
6. Partially disassemble the bearing support
• Plastic or brass hammer. brackets by removing the bolts closest to the
• Brass bar or pipe of proper size. bearings on the bearing support brackets.
Depending on fan size, there are either 3 or 4
• Slings or jack to support larger wheels/shafts. bolts with nuts and “ Locktite”.
7. Remove the setscrews from the bearing locking
MATERIAL REQUIRED collars (two on one side of each bearing,
90 degrees apart). Inspect and, if necessary,
• Exact replacement bearings (always in pairs). replace.
• Steel wool, fine sanding cloth or fine emery 8. Pull each bearing with its rubber mounting
cloth. grommet, out of the bearing support brackets
• Blocking or temporary support for fan wheel/ as much as possible.
shaft. 9. Remove bearings. If a bearing will not move,
• Red “Locktite” or equivalent. shine the shaft behind the bearing and bump
the bearing toward the fan wheel. Use plastic 5
hammer, brass bar or brass pipe. Then de-burr
PROCEDURE and shine the shaft where the bearing was
previously located. Finally, pull the bearing
See Fig. 5-11 off.
1. Remove belts (see Section 4, “Adjustable Motor
10. If the bearing sticks while pulling it off, don’t
Base Operation”). ►
force it. Clean, shine and de-burr the shaft where
2. Remove sheave and key (see Section 5, “Sheave ever necessary.
Replacement and Adjustment”). ►
11. Make sure the shaft is straight and not worn at
3. Support fan wheel/shaft with cribbing, slings or the bearing location.
jacks.
12. With the shaft and bearings clean, slide the new
bearings onto the shaft with the setscrews facing
away from the fan wheel.
13. Reassemble the new bearings with rubber • Slings or jack to support larger wheels/shafts.
mounting grommets gently into the support
• Quarter inch drill bit.
brackets.
14. Remove any temporary supports or blocking of MATERIAL REQUIRED
fan wheel/shaft.
• Exact replacement bearings (always in pairs).
15. Apply red “Locktite” or similar product to bolts
and re-install them with nuts in the bearing • Steel wool, fine sanding cloth or fine emery
support brackets. Be sure the bearings are cloth.
seated in the brackets and not twisted. Tighten • Blocking or temporary support for fan wheel/
to appropriate torque rating. shaft.
16. Slide the shaft in or out of the new bearings to • Grease (see Section 4 or paperwork supplied
center the wheel between the inlet cones on both with new bearings). ►
sides of the fan. This is not critical, however
should be adjusted as close as possible by feeling • Quarter inch roll pins (1 on each small bearing,
the gaps with the fingertips. 2 on each large bearing).
17. Install the setscrews in the drive side bearing but Our standard is to use standard pil-
only tighten lightly. low block bearings with setscrew type
18. Spin the fan wheel by hand to insure no rubbing locking collars. If the fan bearings
will occur. Readjust if necessary. have separate eccentric type lock-
ing collars (see Fig. 5-13), refer to
19. Install setscrews in opposite side bearing and
tighten all setscrews to correct torque rating (see special instruction “FAN BEARING
Table 5-1). ► REPLACEMENT-ECCENTRIC
LOCKING COLLAR” elsewhere in
Alternate tightening of setscrews: this section. ►
Step 1. Tighten “A” to ½ recom-
mended torque value. ABOUT THIS DEVICE
Step 2. Tighten “B” to recom- These bearings can be found mounted in various
mended torque value. positions, over or under a horizontal support or on
Step 3. Tighten “A” to recom- either side of a vertical support.
mended torque value.
20. Re-install sheave and belts (see related Set
instructions in Sections 4 ► ► and 5 ► as Screws
Lube
needed). Fitting
PROCEDURE 16. Install the setscrews in the drive side bearing but
only tighten lightly.
See Fig. 5-12
1. Remove belts (see Section 4, “Adjustable Motor 17. Spin the fan wheel by hand to insure no rubbing
Base Operation”). ► will occur. Readjust if necessary. If the wheel
rubs even though it is centered between the inlet
2. Remove sheave and key. cones, adjust by sliding bearing housing(s) on
3. Support fan wheel/shaft with cribbing, slings or bearing support(s) until the wheel is spaced evenly
jacks. at both inlet cones all around its circumference.
4. Clean shaft until it is shiny from bearings to ends 18. Install setscrews in opposite side bearing and
of shaft. tighten all setscrews to correct torque rating (see
Table 5-1). ►
5. File any burrs or set screw impressions from
shaft. 19. Drill and pin the bearings to the bearing supports.
Use ¼" drill bit and ¼" roll pins. Apply in the area
6. Remove bolts holding bearings to bearing of the bolting flange on the housing base.
supports. Be sure to save any shims found
between bearing housing and bearing support for
re-use. Alternate tightening of setscrews:
7. Remove setscrews from bearing locking collars Step 1. Tighten “A” to ½ recom-
(two on one side of each bearing, 90 degrees mended torque value.
apart). Inspect and, if necessary, replace. Step 2. Tighten “B” to recommended
8. Remove bearings. If a bearing will not move, torque value.
shine the shaft behind the bearing and bump Step 3. Tighten “A” to recommended
the bearing toward the fan wheel. Use plastic torque value.
hammer, brass bar or brass pipe. Then de-burr and
shine the shaft where the bearing was previously
located. Finally, pull the bearing off. 20. Re-install sheave and belts (see related instructions
in Sections 4 ► ►and 5 ► as needed).
9. If the bearing sticks while pulling it off, don’t force
it. Clean, shine and de-burr the shaft where ever 21. Ensure bearings are properly lubricated (see
necessary. Section 4). ►
10. Make sure the shaft is straight and not worn at the 22. Dynamically rebalancing the fan assembly is
bearing location. recommended.
11. With the shaft and bearings clean, slide the new
bearings onto the shaft with the setscrews facing A lock pin is inserted through the lubri-
away from the fan wheel. cation port on the “Sealmaster” brand
12. Reassemble bolts, flat washers, lock washers, bearing housing to prevent the bearing
nuts and any shims found exactly as they were from spinning inside the housing. If a 5
originally installed. There should be a flat washer grease fitting (lube fitting) must be
under the bolt head and under the lock washer. added or changed on bearings that
13. Lightly tighten each bolt so bearing position can utilize a lock pin under the fitting, it is
be adjusted at each bearing. important that the lock pin is in place
when the fitting is installed. If an
14. Remove any temporary supports or blocking of
adapter or grease fitting of improper
fan wheel/shaft.
style or length is used, the lock pin may
15. Slide the shaft in or out of the new bearings to be either too tight or loose and can af-
center the wheel between the inlet cones on both fect the alignment and re-lubrication
sides of the fan. This is not critical, however it of the bearing.
should be adjusted as close as possible by feeling
the gaps between the cones and the edge of the
wheel with the fingertips.
johnson controls 5-11
Service & Repair
FORM 102.20-NOM1 (909)
INNER RING
LD06357
MATERIAL REQUIRED
3. Support fan wheel/shaft with cribbing, slings or 17. Slide the shaft in or out of the new bearings to
jacks. center the fan wheel between the inlet cones on
both sides of the fan housing. This is not critical,
4. Clean shaft until it is shiny from the bearings to
however should be adjusted as close as possible
ends of shaft.
by feeling the gaps between the cones and the
5. File any burrs or other impressions from the edge of the fan wheel with the fingertips.
shaft.
18. Spin the fan wheel by hand to insure no rubbing
6. Remove the setscrew from each eccentric locking will occur. Readjust if necessary. If the fan
collar. Inspect and, if necessary, replace. wheel rubs even though it is centered between
the inlet cones, adjust by sliding bearing
7. To remove the eccentric locking collars
housing(s) on bearing support(s) until the wheel
(self-locking collar). Hold a center punch in
is spaced evenly at both inlet cones all around
the drilled recess on the outer surface of the
its circumference.
eccentric locking collar. Position the punch to
drive the eccentric locking collar in the opposite 19. Tighten all bearing mounting bolts at this
direction of normal shaft rotation. time.
8. Give a sharp blow to the punch and the collar 20. Place each eccentric locking collar (self-locking
will release. Remove each eccentric locking collar) on the shaft with its cam adjacent to the
collar in the same manner. machined cam of the bearing inner ring. Rotate
the eccentric locking collar until it fits over
9. Remove bolts holding bearings to bearing
the machined cam of the inner ring (see Fig.
supports. Be sure to save any shims found
5-14).
between bearing housing and bearing support
for re-use. 21. Holding the eccentric locking collar against the
shoulder of the machined inner ring, rotate the
10. Remove old bearings. If a bearing will not
eccentric locking collar in the normal direction
move, shine the shaft behind the bearing and
of shaft rotation. The eccentric locking collar
bump the bearing toward the fan wheel. Use
will grip the shaft as the cams engage. Rotate
plastic hammer, brass bar or brass pipe. Then
until firmly hand tight.
de-burr and shine the shaft where the bearing
was previously located. Finally pull the bearing 22. Hold a center punch in the drilled recess on the
off. outer surface of the eccentric locking collar.
Position the punch to drive the eccentric locking
11. If a bearing sticks while pulling it off, don’t force
collar in the same direction as normal shaft
it. Clean, shine and de-burr the shaft where ever
rotation.
necessary.
23. Lightly tap the center punch to lock the eccentric
12. Make sure the shaft is straight and not worn at
locking collar in the same direction as shaft
the bearing location.
rotation.
13. With the shaft and bearings clean, slide the new
24. Install the setscrew in each eccentric locking
bearings onto the shaft with the machined cam of
collar and tighten to the correct torque rating
5
the inner ring facing away from the fan wheel.
(see Table 5-1). ►
14. Reassemble bolts, flat washers, lock washers,
25. Drill and pin the bearings to the bearing supports.
nuts and any shims found exactly as they were
Use ¼" drill bit and ¼” roll pins. Apply in the
originally installed. There should be a flat
area of the bolting flange on the housing base
washer under the bolt head and under the lock
washer. Replace the lock washers if they have 26. Re-install sheave and belts (see related
taken a set making them nearly flat. instructions in Sections 4 ► ►and 5 ► as
needed).
15. Lightly tighten each bolt so bearing position can
be adjusted at each bearing. 27. Ensure bearings are properly lubricated (see
Section 4). ►
16. Remove any temporary supports or blocking of
fan wheel/shaft. 28 Dynamically rebalancing the fan assembly is
recommended.
johnson controls 5-13
Service & Repair
FORM 102.20-NOM1 (909)
MATERIAL REQUIRED
2 8
• Exact replacement bearings (always in pairs).
• Steel wool, fine sanding cloth or fine emery 6
cloth.
• Blocking or temporary support for fan wheel/ 1
5
shaft.
• Rags or paper shop towels. 3 7 LD09648
4
• Grease (see Section 4 or paperwork supplied
with new bearings). ► FIG. 5-15 – SPLIT BEARING
• Quarter inch roll pins (1 on each small bearing, 1. Seal (4) 6. Lock Washer
2. Housing Cap 7. Tapered Sleeve
2 on each large bearing).
3. Cap Bolts (2) 8. Bearing
4. Locating Ring (2) 9. Housing Base
5. Lock Nut
2. Remove sheave and key. 5. File any burrs or impressions from shaft.
Wipe the preservative from the bearing and then Lock the nut by bending one of the locking
oil the surface lightly. Use a thin mineral oil. washer tabs down into one of the slots in the
nut. Do not bend it to the bottom of the slot.
5
LD09663
6. Remove the cap bolts from the split bearing Light oil applied to the sleeve out-
housing. side surface results in easier bearing
7. Remove bearing housing cap. Tapping side- mounting and removal.
ways with hammer may be necessary.
8. Move the supported wheel/shaft/bearing
assembly out of the housing base.
22. Mount the bearing on the tapered sleeve with
9. Remove bolts holding the housing base to the the large bore side first to match the taper of the
bearing support. Remove the housing. If the sleeve. Push the bearing on hand tight and as
housing is drilled and pinned to the support, pry straight as possible.
the pin from the support. Be sure to save any
shims found between the housing and bearing 23. With the bearing hanging freely on the shaft,
support for re-use. measure the UNMOUNTED, UNLOADED
radial clearance by inserting progressively larger
10. Install the new housing base to the bearing feeler blades the full length of the roller between
support with bolt, flat washers, new lock washer the bottom most unloaded roller and the outer
and nut. There should be a flat washer under the ring. RECORD THIS NUMBER.
bolt head and the lock washer. Make these hand
tight so bearing position can be adjusted at each 24. Apply the spacer, if provided, then the lock
bearing later in this process. washer as illustrated. Fit the tab on the inside
of the lock washer into a matching notch in the
11. Remove the bulk of the grease from the bearing tapered sleeve.
and parts remaining on the shaft.
25. Apply the locknut with the chamfered face
12. Find the bent lock washer tab inside one of the toward the lock washer. TIGHTEN BY HAND
slots in the lock nut. Bend it perpendicular to ONLY.
the shaft, in line with the other tabs of the lock
washer.
Apply lubricant on the face of the lock-
13. Hook proper size spanner wrench onto a slot in nut where it contacts the lock washer
the lock nut for counterclockwise rotation. for easier mounting and removal.
14. Strike the spanner handle sharply with a hammer
to break the nut free and remove the lock nut.
15. Remove the lock washer and spacer (if spacer
present). 26. Apply grease to the rubber seals and place one
in each new housing base already mounted.
16. Using a brass bar and hammer bump the bearing
off the tapered sleeve. 27. Insert the locating rings into the housing base
of the DRIVE SIDE BEARING HOUSING
17. Open the sleeve by inserting a screwdriver in ONLY. Leave these rings out of the opposite
the slit, and then slip it off the shaft. side bearing to allow for shaft thermal expansion
18. Make sure the shaft is straight and not worn at under load.
the bearing location. 28. At this time, bring the status of both inboard and
19. De-burr, shine and clean the shaft. outboard bearing assemblies to this same level
of completion.
20. Wipe preservative from tapered sleeve and
bearing bore. 29. Install the wheel/shaft/bearing assembly to the
new housing base. It may be necessary to slide
21. Place the tapered sleeve on the shaft with the bearing assemblies on the shaft to get both to
threaded end facing away from the fan wheel. line up with the proper cavity in the housings.
Position the tapered sleeve for approximate
location with respect to the required bearing 30. Center the wheel between the inlet cones on
centerline. both sides of the fan. This should be adjusted
as close as possible by feeling the gaps between
the cones and the edges of the wheel with your
fingertips.
5-16 johnson controls
FORM 102.20-NOM1 (909)
31. Spin the fan wheel slowly by hand to insure no 36. Lock the nut by bending one of the lock washer
rubbing will occur. Readjust if necessary. If the tabs downward into one of the slots in the
wheel rubs even though it is centered between locknut. Do not bend more than a 45° angle.
the inlet cones, adjust by sliding or shimming If one of the tabs does not line up with one of
bearing housing(s) on bearing support(s) until the slots, tighten the locknut until one does line
the wheel is spaced evenly at both inlet cones up. DO NOT LOOSEN THE LOCKNUT.
all around its circumference.
37. Using your fingers, pack each bearing with
32. Tighten the mounting bolts of the housing grease by pressing measures of grease into the
bases. rollers. Rotate the bearing and shaft to access
its entire circumference. Be sure to apply grease
33. Begin tightening the locknuts of each bearing
in this manner to both sides of each bearing so
assembly using spanner wrench and hammer.
that all of the rollers are embedded in grease
Stop to check that the wheel is still centered.
over their entire length.
34. While further tightening the locknuts, periodically
38. Insert the remaining, greased seals into the
stop to check the UNLOADED radial clearance.
groove in the housing caps and fill the space
Since the bearing is mounted and now resting
between the seal lips with grease.
in the housing, insert the feeler blades between
the TOP MOST UNLOADED ROLLER and 39. Install each housing cap onto its respective
the outer ring. Spin the wheel before each housing base. Apply cap bolts and tighten to
measurement to ensure the rollers are positioned correct torque value per Table 5-3.
properly. It may be necessary to lift the wheel/
TABLE 5-3 – RECOMMENDED CAP BOLT
shaft/bearing assembly off the housing to TORQUE VALUES FOR SPLIT
complete the tightening process. PILLOW BLOCK.
35. Continue tightening the lock nut until the CAP SCREW SIZE TORQUE VALUES
UNLOADED RADIAL CLEARANCE 10 mm 37
REDUCTION (difference between clearance 12 mm 59
measured in step #34 and step #23) is within 16 mm 110
the specifications listed in Table 5-2. 20 mm 148
TABLE 5-2 – RECOMMENDED CLEARANCE 24 mm 258
REDUCTION VALUES OF SKF
TAPERED BORE BEARINGS (IN
40. Drill and pin the bearings to the bearing supports.
INCHES)
Use ¼" drill bit and ¼" roll pins. Apply in the
REDUCTION IN RADIAL
BORE DIAMETER area of the bolting flange on the housing base.
INTERNAL CLEARANCE
D(MM)
(IN.) 41. Re-install sheave and belts (see related
Over Incl. Min. Max (1) instructions in Sections 4 ► ►and 5 ► as
24 30 0.0006 0.0008 needed).
30 40 0.0008 0.0010 42. Ensure bearings are properly lubricated (see 5
40 50 0.0010 0.0012 Section 4). ►
50 65 0.0012 0.0015
43. Dynamically rebalancing the fan assembly is
65 80 0.0015 0.0020 recommended.
80 100 0.0018 0.0025
• Torque wrench, 0 to 250 in.-lb. range. 6. Pull bushing off shaft. If the bushing will not
come off, insert a screwdriver into the slit in the
• Hex (Allen) socket set for torque wrench. bushing.
• Torque wrench, 0 to 150 ft.-lb. range. 7. Remove key from keyway.
• Standard 3/8" or ½" socket set
SHEAVE INSTALLATION
• Hammer
See Fig. 5-17
MATERIAL REQUIRED
Do not use lubricants in this installa-
• Fine emery cloth. tion. Bushing and sheave mating
• Contact cleaner or mineral spirits surfaces must be clean and oil free.
SETSCREW
(Not Shown) CAPSCREWS
TAPER
FLANGE
BUSHING SHEAVE
LD09664
LD05630 LD05631
b) Install bushing on clean shaft, flange end c) If using the setscrew, tighten it enough to
first. If bushing will not freely slide on the prevent the bushing from sliding on the
shaft, insert a screwdriver or similar object shaft.
into the flange sawcut to act as a wedge to
open bushings bore.
Do not tighten the setscrew to standard
torque values at this time.
Excessive wedging will split the bush-
ing.
KEYWAY
3. Adjust the sheave to the approximate pitch
diameter desired. One turn of the adjusting
screw will vary the pitch diameter .2 inches.
Seven turns are required to adjust the sheave
from minimum to maximum pitch diameter.
4. Align the sheave with the companion sheave T.B. WOODS MODEL FHP.
(see Section 4). ►
Tools Required
STATIONARY FLANGE
LD09666
Sheave Installation
See Fig. 5-21
1. Loosen setscrews on adjustable flange(s) of new 8. Secure the adjustable sheave to the shaft by
sheave (Allen wrench). tightening the setscrew over the key to the proper
torque value (see table 5-1). ►
2. Screw the adjustable flange(s) open to expose
and loosen the mounting setscrew in the central 9. Adjust the sheave flange(s) to the desired pitch
sleeve over the keyway. diameter. Each turn of the flange changes the
pitch diameter approximately .2 inches. Six turns
3. Inspect the shaft and key for any nicks and burrs.
are required to adjust the sheave from minimum
Remove same and clean shaft.
to maximum for “A” or “B” belts and seven turns
4. Insert key in keyway. for 5V belts.
5. Slide the new sheave onto the shaft with the
mounting setscrew over the key and toward the Both flanges of a 2-groove sheave
motor. MUST be adjusted evenly.
On adjustable sheaves of two or more 11. Install belts and properly tension (see Section 4).
grooves, if there is a difference of more ►
than 1/8" between the width of the
12. Recheck alignment and speed.
companion sheave and any adjustable
pitch sheave, align per steps 7 through
10. Sheave Adjustment
1. Remove belts. (See Section 4, “Adjustable
7. Alignment procedure for multiple groove Motor Base Operation”.) ►
adjustable sheaves:
2. To adjust pitch diameter loosen setscrew(s) on
a) Use a square and straight edge to align the adjustable flange(s) of sheave.
center or stationary flange of the adjustable
sheave with the center flange of the companion 3. Follow steps 9 through 12 above.
sheave.
b) Insure the shaft of the motor is parallel to the
shaft of the fan.
MATERIAL REQUIRED
Wire insulation must be stripped in accordance with
• Correct size and quantity of insulated wire Table 5-5 for standard connectors. The wire insulation
connectors. on a properly installed wire must be inside the insulated
connector conductor port no less than 3/8". Apply the
• Correct size and quantity of flexible cable
flexible cable sleeves only to the motor wires and not
sleeves.
the power feed wires. Refer to Table 5-5 for sleeve
and connector part numbers and cable strip lengths.
PROCEDURE
Pressure screws must be secured at the torque value
1. Shut off motor power and lock out. corresponding to the wire size and connector size
shown in Table 5-6. The UL listing is for stranded
2. Disconnect and tag power wires at motor wire only, AL/CU 600V max.
terminals.
3. Loosen motor base-to-mounting-rail attaching
bolts.
4. Remove and set aside belts.
5. Remove motor bracket hold down bolts.
6. Remove motor pulley and set aside.
7. Remove motor.
LD13793
Connection box may have to be re-
moved from motor body in order to fit FIG. 5-22 – ASSEMBLY OF CONNECTORS
motor through doorway. Some ex- 5
treme cases may require removal of
door and frame as well (see Section 5,
“Door Replacement”). ►
9. Reconnect motor leads and restore power. FIG. 5-23 – MOTOR WIRE CONNECTIONS
FAN SEctION
Right
ReAR
rIGht hAND (rh)
cOIL cONNEctION
OUtSIDE AIr
leFt
LD08004
INLEt SEctION
DrIVE hAND AND cOIL hAND DEtErMINED
By FAcING thE INLEt SEctION
FROnt LD08004
• Lifting lugs for large coils or difficult work 5. DO NOT STAND INSIDE DRAIN
locations. Lifting lugs can be ordered from PAN. IAQ EFFECTIVENESS WILL
Baltimore Parts. Contact BPC-Airside for part BE COMPROMISED.
number. Must provide number of rows deep in
order to obtain correct size lugs. IAQ
MATERIALS REQUIRED
6. Remove content of coil(s) safely in regard to
• Roof or floor protection materials. personnel and environment. Usually refrigerant
• Replacement gasket for coil mounting P/N 010- can be pumped into condenser, however if
02917-000. refrigerant remains in the coil being replaced,
reclaim it per procedures and licenses according
• Replacement screws for coil mounting P/N 021- to current, applicable laws.
12917-000.
7. Disconnect piping from coil(s).
• Replacement gasket for coil access panel P/N
028-11778-000. 8. Remove coil access panel.
• Replacement screws for coil access panel P/N • On outdoor units a removable panel is usually
021-17722-000. on opposite side of unit from pipe connections.
This panel is installed with a dry gasket in
• Replacement gasket for indoor coil panel P/N order to be removable. If other panels are to be
028-11960-000. removed, see Section 5 “Panel Replacement”
• Piping needs as required for specific for specific tools, material and procedures.
connections. ►
• Caulk, P/N 013-03317-050 or 013-03317-040 • On indoor units all panels are installed with a
for outdoor units with champagne paint. dry gasket in order to be removable.
• Heavy cardboard covering for coil fin surface. • If the panel on the piping side is to be removed
to access the coil, piping will have to be
• Duct tape. removed instead of just disconnected. The
reassembly procedure will also be slightly
different (see step 25 of this procedure).
•Cleaning materials including micro-
bial disinfectant. 9. Remove any components, devices or sensors
attached to coil, frame or intermediate drain pan.
This may include another coil.
IAQ
10. Remove any components, devices, sensors,
filters or frames as needed to access coil
mounting screws in bulkhead on air entering
PROCEDURE side of coil.
1. Shut down and lock out unit fan(s). 11. Remove coil mounting screws found securing
2. Shut off and lock out piping to coil(s). coil frame to bulkhead. Be sure coil will not tip
over.
3. For DX coils pump refrigerant into condenser,
valve off and lock out associated condenser 12. Remove and save rubber grommets from coil
components. connectors.
4. Lay down roof or floor protection material at 13. Remove any extended coil drain and vent piping
work areas. or fixtures.
14. Large coils can be separated top and bottom by 27. Guide coil connectors through holes in panel
removing bolts from splice piece on coil end on piping side of unit. Stop short of the final
sheets and intermediate drain pan from coil air position.
leaving side.
28. Install rubber grommets onto coil connectors.
15. Large coils may be handled best with addition
29. Proceed to move coil guiding connectors and
of lifting lugs.
until coil is in final location.
16. Slide coil out of unit to cribbing, dolly, forklift,
30. Work the grommets into the holes around the
roof cart, etc.
coil connectors.
17. Install coil lifting lugs if applicable.
31. Make sure the coil is in the proper mounting
18. For crane lift use professionals who will rig coils position against the gasket on coil bulkhead.
without damage to coil frames or surfaces.
32. Reinstall screws to attach coil frame to
19. Take necessary precautions in moving heavy bulkhead.
objects across roof or flight over people and
33. Be sure coil and bulkhead will not allow air to
property.
bypass coil. Seal with caulk if necessary. This
20. Remove coil from workspace. material requires 3 hours to set.
34. Reinstall all components, sensors, frames, pans,
21. C
lean drain pan, all panels and filters, etc., which were removed previously
inside unit.
parts adjacent to coil area and
areas wetted by condensation. 35. Check alignment of coil connectors to existing
Use a microbial disinfectant and pipe connections. Coil connectors on copper
IAQ headers may be adjusted slightly by moving
cleaner or in combination (see
also Section 4 “Coil Cleaning carefully and gradually without causing damage
Procedure”). ► or leaks. This may be necessary because the
connectors may get bumped, pushed or pulled
slightly out of position.
22. Check gasket for coil mounting on coil bulkhead.
Replace if damaged. 36. Reconnect all piping, test for leaks and charge
systems.
23. Cover new coil fin surface on both sides of coil
with heavy cardboard or similar material to 37. Remove heavy cardboard or other material
protect from damage. previously installed on new coil as protection
for fins. Inspect fins for deformation and repair
24. Locate replacement coil at workspace. with a fin comb or fin straightener.
25. Slide coil into unit using caution not to damage 38. Check gasket for coil access panel, replaced if
coil supports, coil bulkhead, drain pan, etc. damaged.
26. If the panel on the piping side was removed to 39. Reinstall coil access panel. 5
access the coil, the procedure is the same except
reassembly will be in a slightly different order 40. Clean up inside and outside of unit. Especially
in regards to the panel. The coil will be placed check for screws or other sharp objects left on
in its final position and anchored; then the panel roof surface.
will be put on over the coil connectors. Before 41. Put unit back into operation per facility
fastening the panel in place, work the grommets requirements. Be sure if caulk was used, that
into the holes around the coil connectors. Then it has had time to set up to avoid creating air
fasten the panel in place. leaks.
DOOR REPLACEMENT
TOOLS REQUIRED 2. Before installing Door/Frame Assembly, remove
old gasket material from raceways and panels at
• Standard mechanic’s hand tools. mounting areas.
• Scraper. 3. Apply new gasket material to back of frame
• Spacers. along the outer edge. Use neoprene gasket, P/N
028-11873-010.
MATERIALS REQUIRED
• Correct parts for the application (see Form New door assemblies are provided with
102.20-RP1). ► plastic spacers to maintain proper
• Neoprene Gasket, P/N 028-11873-010 alignment.
PROCEDURE
See Fig. 5-25
1. To prevent damage during removal, close and
4. Install new door assembly with door closed and
latch doors. Remove as complete Door/Frame
latched with spacers in place.
Assemblies. On outdoor units, allow butyl tape
to properly release by removing Door/Frame 5 Then, install screws in hinge side of
Assembly slowly. Failure to do so may result doorframe.
in damage to frame.
6. Finally, install screws in top, bottom and latch
sides of doorframe. Once door assembly is
installed, remove plastic shipping spacers from
between door and doorframe.
7. Check operation of door with unit off.
8. Check for obvious air leakage with air unit in
operation.
LD14264
TOOLS REQUIRED
• Standard mechanic’s hand tools.
• Scraper.
• Caulk gun.
MATERIALS REQUIRED
• Door gasket material (order by measuring exact
size of door panel height and width).
• One tube caulk (sealant), P/N 013-03317-050
aluminum gray or 013-03317-040 for outdoor
units with champagne paint.
LD09668
PROCEDURE GASKET
Using fingers or pliers, grasp the old gasket at a point INSTALL NEW MITERED GASKET (BEFORE JAN
near the center of any horizontal or vertical frame 2006)
component, and pull straight out of the frame, working 1. Cut the end of the gasket at an angle of 40°
from the center toward the corners. Repeat on each of through the top of foam to the stem (see Fig.
the four sides of the gasket. 5-27).
Do not start at a corner! Starting at a 2. Cut the stem back slightly so that the top of the
corner may cause a portion of the stem is flush with the base of the gasket, and the
gasket to tear away and remain inside barb end of the stem is cut back at a slight angle
(see Fig. 5-27).
the narrow groove in the aluminum
doorframe. Any such material must Cut the
the stem
stem back
backso so
be removed before the new gasket is that the
that the top
top of
of the
the stem
is flush
flush with
with the
the base
baseof of
installed. The old gasket MUST be the gasket, and and the
the barb
barb
COMPLETELY REMOVED. end ofof the
the stem
stem isiscut
cut 5
back at at aaslight
slightangle.
angle.
LD12131A
6 inches
inches
• Turn the gasket over, open the notch, and cut
back the stem on both ends (see Fig. 5-31).
When starting,
starting, cut the end
end angle
anglefirst.
first.
Cut the
the first
first notch next.
next. TheThelength
lengthfrom
from
the top of the splice
splice to
to the
the first
first notch
notch
should be
be about
about6"
6"(+
(+/-/-1.0").
1.0").
LD12038A
FIG. 5-28 – MARKING GASKET FOR FIRST CUT Gasket stemcutback.
Gasket stem cutback.
Note: The
The stem
stemmust
must
be cut
cut back
backtotoallow
allow
• The first cut is about 2/3 to 3/4 of the way for a good
good corner
corner
through the gasket. The cut should be about
40 degrees (see Fig. 5-29).
LD12132A
Making the initial
initialcut
cutin
inthe
thegasket.
gasket.
location line
Using the location line as aa guide,
guide, FIG. 5-31 – CUT BACK STEM
cut about
about 2/3 to 3/4 of the way through
through the
the gasket.
gasket.
The cut should be
be about
about 4040 degrees.
degrees. 4. Apply the sealant to the area on the latch side
where the overlapping splice will be.
• The sealant must be in the groove and
surrounding area on the perimeter.
• The length of the sealant area is about 2" (see
Fig. 5-32).
LD12039A
5. Apply sealant to the corner. 9. Fold the joint together and press the gasket into
place.
• Sealant needs to fill the gasket grooves 1 to
1-1/2" out from the corner.
• Sealant is also applied to the edge outside the Ensure that the mitered joint is com-
grooves. pletely closed, the two pieces are not
• A liberal amount is also applied on the inside offset, and it lays flat.
of the corner (see Fig. 5-33).
16. Mark the bottom of the gasket about 1 to 2 mm Flush joints or gaps between pieces
longer than the base of the “in place” gasket (see are not acceptable (see Fig. 5-38 for
Fig. 5-36). correct overlap).
Gasket overlap --
Gasket must overlap
11 to
to 2 mm step
step
LD12137A
FIG. 5-38 – O
VERLAP CUT PIECE WITH “IN
17. Cut the gasket at an angle using the two marks
PLACE” GASKET
as a guide.
18. Apply sealant to the splice area. 21. Apply sealant to the inside of the splice and
along the bottom of the gasket in the splice area
• Completely cover the cut edge of the “in (minimum of 1" to both sides of splice at the
place” gasket end. base). See Fig. 5-39.
• Fill the gasket groove on the perimeter and
surrounding area about 1" out from the base
of the “in place” gasket (see Fig. 5-37).
sure that
Make sure that sealant is
is applied
applied
to the
to the inside
inside of
of the
the splice and along
bottomof
bottom ofthe
thegasket
gasketin inthe
thesplice
splice area
area
(min of 1" to both
both sides splice at
sides of splice at base).
base).
Applying sealant
Applying sealant to
tosplice
splice area.
area. LD12140A
Note: Application
Note: Applicationtotosurface
surfacearea
area FIG. 5-39 – APPLY SEALANT TO SPLICE BASE
ofofgasket
gasketand
andextrusion.
extrusion.
LD12138A
Note: rounded
appearance.
Corner of gasket
should be within
1/16" of the corner
of the door.
Gasket cannot overlap
the edge of the door.
cornermust
Inside corner must
have sealant
sealantshowing.
showing.
LD12141A
Gasket Corner
Good Foam Gasket Corner
5
Gasket must
Gasket must not
not overlap
overlap
the edges of the
edges of the perimeter,
perimeter,
and point of gasket should
should extend
extend
out within
within 1/16"
1/16" (2mm) of point of
door perimeter.
LD12142A
FIG. 5-41 – C
ORRECT MITERED FOAM GASKET
CORNER
1/8”
Turn the
the shears
shearsandand
snip off
off the
the hard
hard
portion of
portion of the
the gasket
LD12248A
LD12251A
Vertical anti-compression
anti-compressionleg
leg Make sure that the gasket is completely
snapped in place or leakage will occur.
The horizontal gasket should extend
the entire width of the opening (+0,
LD12250A
-2 mm).
LD12253
LD12255A
10. Rough cut the gasket to approximately the same FIG. 5-52 – APPLY SEALANT END OF FIRST
length as the opening between the horizontal VERTICAL GASKET
frame pieces.
14. Place the vertical gasket about 1/4 to 1/2" from
11. Trim one end of the gasket to 90 degrees, per the horizontal gasket, align the attachment
step 8. pocket of the gasket over the gasket attachment
leg of the extrusion, and snap the last inch of
12. Apply sealant down the edge of the horizontal
the gasket into place. Push the vertical into the
gasket and fill the area out 1" between the anti-
side of the horizontal 1 to 2 mm. Sealant should
compression leg and the wall of the vertical (see
ooze from the joint (see Fig's 5-53 and 5-54).
Fig. 5-51).
1”
Apply
Apply sealant
down
down the
the edge
edge of
Fill area
areaout
out 1”
1”between
between Push the vertical
Push the verticalinto
into
the horizontal
the anti-compression
anti-compression leg
leg the side of
of the
the
gasket.
and the
the wall
wall of
of the
the horizontal 1 to
horizontal to 22 mm.
mm.
vertical
LD12256A
LD12254A
Sealant should
shouldooze
ooze
from the joint.
joint.
LD12257A
15. Roll the gasket in place to within 5 to 6" from 16. Trim enough of the gasket off in order to allow
the opposite end. the tail end to fit inside the frame (see Fig.
5-56).
Trim enough
enough of of the
the
gasket end
endtoto allow
allow
the tail
tail end to fit
fit
inside the
the frame.
frame.
LD12259A
11 to
to 2 mm.
LD12260A
LD12258A
FIG. 5-57 – MARK VERTICAL GASKET
FIG. 5-55 – R
OLL GASKET TO WITHIN 5 TO 6" OF
OPPOSITE END 18. Trim the end of the gasket to 90 degrees, per 5
step 8.
19. Apply sealant down the edge of the horizontal
gasket and fill the area out 1" between the anti-
compression leg and the wall of the vertical (see
Fig. 5-51).
Roll gasket
gasketinto
into place.
place.
LD12263A
FIG. 5-60 – R
OLL VERTICAL GASKET INTO
PLACE AND SECURE
Place thevertical
Place the verticalgasket
gasketabout
about1/4”
1/4”from
from the horizontal
the horizontal gasket.
gasket. Align Align
the the
attachment pocket of the gasket
attachment gasket over
over
the gasket attachment
attachment leg
leg of
of the
the
extrusion and snap
snapthe
thelast
lastinch
inchofofthe
the
gasket into
into place.
place.
LD12261A
After securing
After cornerroll
securing corner roll
Sealant
Sealantshould
should ooze towards the opposite corner.
corner.
from the
from the joint.
joint.
LD12264A
FIG. 5-61 – R
OLL TOWARDS OPPOSITE END OF
VERTICAL GASKET
Push
Push the
the vertical gasket into
into 22. Using either a dry towel or one moistened in
the
the side of the horizontal mineral spirits; wipe the excess sealant from the
gasket
gasket11 to
to 2 mm. gasket and anti-compression leg area (see Fig.
LD12262A
5-62).
FIG. 5-59 – P
ROPER PLACEMENT OF VERTICAL
TO HORIZONTAL GASKET
21. Roll the gasket into place. Secure the corner first
as in Fig. 5-60 (roll into the corner). Once the
corner is secured, roll out towards the opposite
corner per Fig. 5-61.
Wipe away
away excess
excess
sealant from
from gasket.
gasket.
Wipe away
away excess
excesssealant
sealantfrom
from
anti-compression legarea.
anti-compression leg area.
LD12265A
LD12267A
When clamping
clampinggasket
gasketjoint,
joint,
the clamp must
must rest
reston
onthe
the
Note Step-off
Step-off is
is good.
good. Vertical
Vertical
anti-compression legs.
anti-compression legs. LD12266A needsto
gasket needs tobe
bepushed
pushed
farther into
farther into horizontal
horizontal gasket.
gasket.
FIG. 5-63 – APPLY CLAMP TO CORNER AS
NECESSARY
LD12268A
25. See Fig's 5-64 and 5-65 for examples of
unacceptable gasket joints. FIG. 5-65 – UNACCEPTABLE BUT JOINT,
VERTICAL GASKET NOT PUSHED IN
FAR ENOUGH
GASKET INSTALLATION
1. Cut gasket and then peel red backer plastic back
12 to 18 inches (see Fig. 5-67).
FIG. 5-66 – S
TEEL FRAME DOOR WITH BUT
CORNER JOINT GASKET (Units
Produced AFTER oct 2008)
Cut gasket
and then peel
INSTALL NEW GASKET ON DOOR PRODUCED red backer
plastic back
AFTER OCT 2008 12 to 18
inches.
This procedure describes the method of installing the
self-adhesive gasket in frames to eliminate air/water
infiltration.
PREPARATION
1. Ensure that the frame has been cleaned and Ensure that cut is as close to 90 degrees as pos-
sible, both vertically and horizontally to ensure a
sealed. proper fit.
LD14271
Be extremely careful when handling The notch on the gasket is to the out-
frames as serious cuts may occur from side of the frame.
all exposed edges. Be extra careful
when sliding fingers down the gasket
to secure, as the exposed edges of the
anticompression leg are extremely
sharp.
LD14274
FIG. 5-68 – P
LACE GASKET ON LATCH SIDE OF
FRAME FIG. 5-70 – start corner
3. Lay the gasket to the corner, lift the loose side of the Examples of a Good Gasket Corner
gasket up, and begin the corner (see Fig. 5-69).
Entire anticompression leg is visible
and the gasket is tight with it (see Fig.
5-71).
The entire
anticompression leg is
visible and the gasket is
tight with it.
Lay the gasket to the
corner, lift the loose
side of the gasket up
and begin the corner. LD14273
Gasket must be +0
/ -1mm from the
UNACCEPTABLE anticompression
leg.
LD14278
UNACCEPTABLE
UNACCEPTABLE
Gasket needs to be +0 / -1 mm
from the anticompression leg. This
gap is too big.
LD14279
UNACCEPTABLE
FIG. 5-78 – P
OSITION GASKET FOR SECURING
Gasket cannot 8. Push the gasket into the secured portion (see Fig.
overhang onto the 5-79).
anticompression leg.
LD14280
FIG. 5-76 – UNACCEPTABLE gasket
fit - GASKET OVERHANGS
ANTICOMPRESSION LEG.
1/8" to 1/4"
LD14283
9. Push the gasket down onto the gasket leg (see Fig. Examples of Unacceptable Joints
5-80).
For examples of unacceptable joints see Fig 5-82
through 5-85.
Finished joint will not have any gaps;
it will be a perfect seal.
UNACCEPTABLE
Open Joint
LD14286
LD14284 UNACCEPTABLE
FIG. 5-80 – F
INAL POSITIONING
LD14287
LD14285
Offset Joint
FIG. 5-81 – EXAMPLE OF A GOOD FINISHED
JOINT
LD14288
SPLICING
UNACCEPTABLE If the joint of the gasket is too short, and does not
make a perfect seal, a splice may be used rather than
replacing the entire gasket (see Fig. 5-86).
10. With fingers press entire gasket down flat onto the
gasket leg, ensuring it makes a seal all the way
around the frame.
LD14291
MATERIALS REQUIRED Correct parts for the application (see Form 102.20-
RP1). ►
Correct parts for the application (see Form 102.20-
RP1). ►
PROCEDURE
2. Remove existing door latch assembly. 3. Insert shafts of each of the individual latching
mechanisms through holes in door from outside
3. Insert shaft of latching mechanism through hole to inside.
in door from outside to inside.
4. Thread flanged retainers of latching mechanisms
4. Thread flanged retainer of latching mechanism onto each mechanism shaft until firmly against
onto mechanism shaft until firmly against inside inside of door.
of door.
5. Install one handle (without offset roller) to the
5. Thread 3/8" flat jam nut onto mechanism shaft mechanism designated to be the “operator” on
and tighten against retainer. outside of door using slotted screw to secure.
6. Install handle (without offset roller) to mechanism 6. Tighten slotted screw in handle and apply plastic
on outside of door using slotted screw to screw cover.
secure.
7. To the other mechanism(s), apply push on
7. Tighten slotted screw in handle and apply plastic cover(s) in place of handle(s).
screw cover.
8. Place the designated mechanism handle in a
8. Add two 3/8" flat washers. downward position.
9. Add cam roller (Detail B) so that roller will 9. Place the other mechanism(s) so the square
engage doorframe when handle is in the shaft(s) is/are positioned the same as that of the
downward position. designated mechanism shaft.
10. Add inside handle (if applicable) to mechanism 10. Apply a linkage adapter to each mechanism
shaft. shaft. Be sure the peg is downward and at an
11. Thread 3/8" lock nut w/nylon washer onto angle away from the edge of the door. Also, be
mechanism shaft and tighten. sure the smooth side of the linkage adapter is
toward the door.
12. Repeat these steps for each individual handle on
the door. 11. Install the connecting rod by engaging its
holes with the respective peg on each linkage
13. Check operation of door latch with unit off and adapter.
with unit in operation to check for leakage.
12. Secure the connecting rod by placing an “E” ring
14. If adjustment is required, add or take away 3/8" (snap ring) in the groove on each peg.
flat washers.
13. Add two 3/8" flat washers.
Latching
Mechanism Rod
Inside Handle (In Swing
Handle Handle (In Swing Offset Shown)
Offset Shown) (See Detail A)
Cam Roller, Snub (See Detail A) Cam Roller, Snub
Nose (Out Swing Nose (Out Swing
Only) (See Detail B) Only) (See Detail B)
Inside Handle
DETAIL A DETAIL B
HANDLE W/OFFSET ROLLER CAM ROLLER SNUB NOSE
(In Swing Only) (Out Swing Only) LD09669
FIG. 5-87 – STANDARD DOOR LATCHES, IN SWING, OUT SWING & MULTI PT. LATCH
14. Add cam rollers (Detail B) to each mechanism 11. Check operation of door latch with unit off and
shaft so that rollers will engage doorframe when with unit in operation to check for leakage. If
handle is in the downward position. leakage occurs, check door gasket (see “Door
Gasket Replacement” in this section). ►
15. Add one inside handle (if applicable) to the
mechanism shaft most convenient to operate 12. If adjustment is required, add or take away 3/8"
from inside unit. flat washers.
16. Thread 3/8" lock nuts w/nylon washer onto each
mechanism shaft and tighten. STANDARD IN SWING DOOR WITH MULTI-POINT
17. Check operation of multi-point latching LATCH
assembly with unit off and with unit in operation TOOLS REQUIRED
to check for leakage.
Standard mechanics tool kit.
If adjustment is required, add or take away 3/8"
flat washers. MATERIALS REQUIRED
STANDARD IN SWING DOOR Correct parts for the application (see Form 102.20-
RP1). ►
TOOLS REQUIRED
13. Add three 3/8" flat washers. 2. Remove isolator spring(s) being replaced.
14. Ensure offset on door handle engages door frame 3. Place replacement spring(s) in existing rubber
when handle is in the downward position. Isolator Cup.
15. Add one inside handle (if applicable) to the 4. Lower fan base assembly guiding the existing
mechanism shaft most convenient to operate Isolator Cap over the spring(s).
from inside unit. 5. Install washer and cap screw into top of
16. Thread 3/8" lock nuts w/nylon washer onto each adjustment bolt. Do not tighten cap screw at
mechanism shaft and tighten. this time.
ISOLATOR ADJUSTMENT (LEVEL WITH PROPER
17. Check operation of multi-point latching assembly
CLEARANCES)
with unit off and with unit in operation to check
for leakage (see “Door Gasket Replacement” in 1. With cap screw loose, turn adjustment bolts
this section). ► counter clockwise to raise or clockwise to lower
the fan base assembly.
ISOLATOR SPRING REPLACEMENT AND 2. Repeat the procedure one isolator at a time until
the required distance of 5/8" is reached between
ADJUSTMENT
the top of the isolator rail and the bottom of the
TOOLS REQUIRED spring rail.
• Mechanics tool kit 3. Make sure the spring is not collapsed. Minimum
• Pry bar (large fan base) and maximum tolerances shown in the table in
Fig. 5-88 should be followed.
• Lumber blocking/cribbing (large fan base)
4. Make sure the flex connector at the fan discharge
is not folded inward or pinched between the
MATERIAL REQUIRED floating fan assembly and the stationery segment
• Correctly sized replacement isolator spring(s) discharge.
5. Once the fan base assembly is adjusted, tighten
CAP SCREW the cap screws to lock the assembly in place.
ADJUSTMENT BOLT
A 5
ACCESS SLOT
SPRING TOLERANCE
ISOLATOR CAP
DEFLECTION LIMIT (A)
SPRING RAIL TYPE
1/2" TO 5/8" MIN MAX
1.00 1.50 2.75
2.00 1.00 3.00
LD08592-1
NUT
THREADED ROD
STEEL WASHER
RUBBER WASHER
STEEL WASHER
STEEL CUP
SPRING
THRUST RESTRAINT BULKHEAD OR
MOUNTING BRACKET BULKHEAD CLIP
(OR CLIP) LD09670
6. Slide threaded rod through thrust restraint 10. Push threaded rod through bulkhead (or bulkhead
mounting bracket on fan (or clip) toward clip) until spring parts are against thrust restraint
bulkhead (or bulkhead clip). mounting bracket on fan (or clip).
7. Add third flat steel washer and two nuts that will 11. Tighten nuts on both sides of bulkhead (or
lock together in a later step. bulkhead clip).
A pre-manufactured replacement
panel with your specified opening size
and location may be available through
L
Baltimore Parts Center—Airside or
Local Johnson Controls Service. 1.938"
8. Apply gray sealant to corner seams and all seams • Paint, touch-up spray, champagne, P/N 013-
inside the new opening. 03322-000.
9. Paint rivets and raw edges of sheet metal with • Clean up supplies.
cold galvanized paint.
10. If the panel was removed, clean away damaged
or residual gasket or sealing compound and
replace with appropriate material (see material
list above).
11. Install panel on air handling unit carefully using 5
panel screws (see material list above).
12. All re-installed panels and alterations of
panels must provide integrity equal to original
equipment specifications.
13. Reconnect any components, bulkheads or other
fixtures that were disconnected from panel in
step # 2.
14. Thoroughly clean up inside and outside air
unit.
PROCEDURE
1. Make sure any components; bulkheads or other 5. All re-installed panels must provide integrity
obstructions are disconnected from panel inside equal to original equipment specifications.
and out (see Fig. 5-92).
6. Seal all penetrations with caulk.
7. Reconnect any components, bulkheads or other
fixtures that were disconnected from panel in
step # 1.
8. Thoroughly clean up inside and outside air
unit.
MATERIAL REQUIRED
• MicroSealant seam strips, P/N 028-11888-010,
champagne, 4" w x 50 ft. roll.
• Caulk, Manus-Bond 75-AM, P/N 013-02966-
011.
• Paint, champagne, 12oz spray can, P/N 013-
03322-000.
• Isopropyl alcohol.
LD09672
PROCEDURE
See Fig. 5-98
1. Make sure any components; bulkheads or other
obstructions are disconnected from panel inside
FIG. 5-97 – APPLY PRESSURE - ROLLER and out.
RECCOMENDED
2. Layout location and dimensions of hole opening
to be cut. Do this on both sides of double wall
7. Once seams are repaired, check ALL of the roof panels.
screws and replace them if they are stripped out.
Apply caulking in the screw hole and install a 3. Carefully cut correct hole size for the application
1" X 17 screw, with rubber washer. (Fastenal # in panel, insuring cuts on both sides line up and
31917). a smooth clean cut is made.
4. Paint raw edges of sheet metal with cold
FIELD PENETRATIONS FOR PIPING & galvanized paint.
ELECTRICAL CONNECTIONS 5. Select appropriate grommet for new panel
For small sizes such as 1/2" iron pipe, hole and cut out appropriate hole diameter for
penetration with an Exacto knife.
1/2" conduit or 5/8" O.D. copper and
smaller; it is acceptable to use caulk 6. After paint dries, Install grommet into panel hole
instead of a grommet. opening.
7. Apply sealant all around new hole opening
behind lip of grommet, on both sides of panel.
Electrical conduits must be sealed
8. Run pipe or conduit through grommet and make
internally to prevent airflow and mois-
appropriate connections.
ture condensation.
9. All modified panels must provide integrity equal
to original equipment specifications.
10. Reconnect any components, bulkheads or other
TOOLS REQUIRED fixtures that were disconnected from panel in
step # 1.
• Drill motor.
11. Thoroughly clean up inside and outside air
• Pilot starter bit.
unit.
• Hole saws-approximately 2-1/2", 3-1/4" &
4-1/2" diameter for holes.
• Power cords as required.
5-56 johnson controls
FORM 102.20-NOM1 (909)
Ø E* NEOPRENE
ØB GROMMET***
PASSING ELEMENT
(CONDUIT, PIPE,
ØD ETC.)
3 OR 4 RINGS
SEALANT** ALL
AROUND,
ØC ØB BOTH SIDES OF
THE OPENING.
DIMENSIONS
MARKED
GROMMET GROMMET GROMMET PANEL
IRON COPPER GROMMET
THIN WALL USE HOLE LIP HOLE HOLE CUT
PIPE SIZE PIPE SIZE DEPTH
CONDUIT GROMMET P/N DIAMETER DIAMETER DIAMETER DIAMETER
(nominal) (O.D.) (A)
(ØB) (ØC) (CUT OUT) (ØE)
(ØD)
3/4”, 1” 7/8”, 1-1/8” 3/4”, 1” 028-11872-000 2.375” 0.500” 3.125” 0.749 2.50”
1-1/4”, 1-1/2” 1-3/8”, 1-5/8” 1’1/4”, 1-1/2” 028-11871-000 2.375” 1.000” 3.875” 1.249 3.25”
1-1/4”, 1-1/2” 1-3/8”, 1-5/8” 1’1/4”, 1-1/2” 028-11872-000 2.375” 0.500” 3.125” 1.249 2.50”
1-1/4”, 1-1/2” 1-3/8”, 1-5/8” 1’1/4”, 1-1/2” 028-11861-000 2.375” 1.000” 5.125” 1.251 4.50”
2” 2-1/8” 2” 028-11871-000 2.375” 1.000” 3.875” 1.749 3.25”
2” 2-1/8” 2” 028-11861-000 2.375” 1.000” 5.125” 1.751 4.50”
2” 2-1/8” 2” 028-11872-000 2.375” 0.500” 3.125” 1.875 2.50”
2-1/2” 2-5/8” 2-1/2” 028-11861-000 2.375” 1.000” 5.125” 2.251 4.50”
2-1/2” 2-5/8” 2-1/2” 028-11871-000 2.375” 1.000” 3.875” 2.375 3.25”
3” 3-1/8” 3” 028-11861-000 2.375” 1.000” 5.125” 2.875 4.50”
4" 4-1/8" 4" 2.251" 1.250" 6.125" 3.875" 5.50"
028-11881-000
5
FIG. 5-98 – PENETRATIONS AND GROMMET DETAILS
• Hole saw-approximately 1-1/2" diameter for • Caulk, P/N 013-02966-011 gray for indoor
starter holes. units or 013-03317-040 for outdoor units with
champagne paint.
• Power saw or power shear for metal cutting.
• Panel screws ¼" x ¾" pan head thread forming
• Power cords as required. sheet metal screw, P/N 021-17722-000.
MATERIAL REQUIRED • Clean up supplies.
• For door and panel flanges, use gasket, neoprene PROCEDURE
.75"w x .25" thk, P/N 028-11873-010.
1. Make sure any components; bulkheads or other
• Two prefabricated pieces of “C” channel (one obstructions are disconnected from panel inside
piece if door is to be mounted at a corner) used and out.
for stiffeners and insulation covers equal to the
height of the panel. This channel is 20 gauge 2. When removing panel, to prevent damage of
galvanized sheet metal, 1.938" wide with .750" outdoor unit remove panel slowly allowing butyl
legs. Available through Baltimore Parts Center- tape to release.
Airside (see Fig. 5-99).
3. Clean away damaged or residual gasket or All re-installed panels and alterations
sealing compound and replace with appropriate of panels must provide integrity equal
new material (see material list above).
to original equipment specifications.
4. Cut “C” Channel stiffener(s) to fit. Use to
strengthen the cut panel(s) and for sealing of
insulation and probable air leakage areas.
5. Layout location of door for cutting. Do this on 12. Reconnect any components, bulkheads or other
both sides of double wall panel. fixtures that were disconnected from panel in
step # 1.
6. Cut panel from top to bottom at desired location
ensuring cuts on both sides line up. 13. Apply gasket material to back of doorframe
along the outer edge. Use compound sealing
7. Insert stiffeners, legs first, by tapping into (butyl tape), P/N 013-02976-000 for outdoor
panel until flush with cut edges of panel. This unit and neoprene gasket, P/N 028-11873-010
simultaneously forces the legs of the “C” for indoor unit.
channels between the foam insulation and the
liner and between the foam insulation and
the outer sheet metal without damage to the New door assemblies are provided with
insulation. plastic spacers to maintain proper
8. Secure “C” channels with pop rivets at 3" alignment.
intervals on a line ¼" from the edge of the
cut panel(s). When fastening with pop rivets
avoid buckling or bulging of sheet metal by
applying rivets simultaneously on each side of
14. Install new door assembly with door closed and
cut panel(s), working from center to top and
latched with spacers in place (see Fig. 5-101).
bottom.
9. Apply gray sealant to seal the “C” channel to
cut edges.
10. Paint rivets and raw edges of sheet metal with
cold galvanized paint.
11. Install panel(s) on air handling unit carefully
using panel screws (see Fig. 5-100).
LD14264
17. Check operation of door with unit off. LIGHT ASSEMBLY REPLACEMENT
18. Check for obvious air leakage with air unit in TOOLS REQUIRED
operation
• Phillips screwdriver, # 2.
19. Thoroughly clean up inside and outside air
• Nut setter or socket, 1/4".
unit.
20. Touch up paint as needed. MATERIALS REQUIRED
• Light Fixture w/ Cover (P/N 025-39013-001).
LIGHT BULB REPLACEMENT PROCEDURE
TOOLS REQUIRED See Fig. 5-102
• Phillips screwdriver, #2. 1. Disconnect power from light assembly.
2. Remove wireway from where it fastens to top
MATERIALS REQUIRED
panel by removing all self drilling screws.
• Lamp, Incandescent, 75W or Fluorescent,
3. Disconnect “stake-on” electrical connectors (see
20W.
Fig. 5-103).
PROCEDURE
See Fig. 5-102
1. Disconnect power from light assembly.
2. Remove two #2 Phillips screws connecting cover
to base.
3. Remove cover and replace bulb.
4. Fasten cover to base with two #2 Phillips
screws.
LD09689
PRESS GROMMET
INTO WIREWAY STAKE-ON
CONNECTORS FIG. 5-103 – REMOVE ELECTRICAL
(3)
CONNECTORS
SELF DRILLING
SCREW
FIG. 5-102 – LIGHT ASSEMBLY PULL SWITCH 7. Install new light assembly by reversing steps 1
SHOWN) through 6.
FILTER ACCESS
DOOR OR UNIT
ADD SIDE PANEL
CAULK
MINIHELIC
GAGE
TOP VIEW
LD11693
2. Remove two #4-40 hex nuts and remove the liner 10 Secure gage by tightening two #4-40 hex nuts,
cover plate that holds the filter gage in place. making sure gage face is level.
3. Cut existing caulking from perimeter of gage. 11. Re-connect 3/16" tubing to barbed fittings on 5
the back of the gage.
4. Slide gage through front of filter access door or
unit side panel. 12. Remove lens by pressing finger tips firmly
against lens outer ring and turning CCW.
5. Clean old caulking from access panel.
13. Without any air applied, turn adjustment screw
until gage reads zero.
The replacement filter gage will be 14. Replace lens.
mounted to the liner cover plate by two
(2) #4-40 threaded inserts and hex
nuts that come with the gage.
FILTER GAGE INSTALLATION (FIELD CUT) The filter gage will require a 3" O.D.
TOOLS REQUIRED surface area on the door or panel for
mounting clearances and a minimum
• Adjustable wrench (4") or ignition wrench set. of 3" of depth behind the door panel,
• Drill. for proper tubing clearances.
• Punch.
2. Drill a 2-5/8" O.D. hole in the door or panel as
• Hole saw, 2-5/8" dia. close to the hinge side of the door as possible.
• Long, thin straight slot screwdriver. Center the hole as follows:
• For all units with multiple filter gages, each gage 4. Run a small bead of sealant around the exterior
should be labeled with a polyester printed label. perimeter of the gage where it will seal against
The labels should read as follows: the filter access or unit side panel.
The static pressure ports (eyelets) have filter track between the filters, that is tubed to
to be installed “out of the air stream” this tee. The remaining ports are treated just
to enable them to sense only static like above.
pressure and not velocity pressure. An • The prefilter is always the first filter bank in
“out of the air stream” location would the airstream and the final filters are always the
be above or beside the filters. Not last. There may also be an intermediate filter
mounted in the face of the filter. bank, which would be between the prefilters
and final filters. This configuration will require
9. Make Tubing Connections two filter segments in the same unit.
• The air entering side of the filter is always • When the gage is door mounted, clamp the
the high-pressure side. The downstream side tubing to the back of the door as you run it
is always the low-pressure side, of the filter along the hinge side. It will need to be looped
bank. so that there is enough tubing to flex around
the corner of the door when it is in its full
• If the filter gage is mounted on the upstream open position. The tubing will then need to
side of the filter bank then the “HI” port of the be clamped to the wall panel and neatly run to
gage is left as is to sense high-pressure and the the proper places.
“LO” port is tubed to the low-pressure side,
of the filter. 10. Re-connect 3/16" tubing to barbed fittings on
the back of the gage.
• If the filter gage is mounted on the downstream
side of the filter bank then the “LO” port is left 11. Remove lens by pressing finger tips firmly
as is, to sense low-pressure and the “HI” port against lens outer ring and turning CCW.
is tubed to the high-pressure side of the filter 12. Without any air applied, turn adjustment screw
bank. until gage reads zero.
• If the filter section is a combination filter 13. Replace lens.
assembly then the “LO” port of the prefilter
gage is always tee’d into the “HI” port of the
final filter gage and an eyelet is installed in the
HI
NOTE:
AIRFLOW IF FILTER GAGE IS MOUNTED
ON THE DOWNSTREAM SIDE
OF THE FILTER RACK, THEN
SIDE VIEW BACK VIEW THE LOW PRESSURE PORT IS
TO BE LEFT OPEN AND THE
HI PRESSURE PORT IS TO BE
TUBED THROUGH THE BULKHEAD
SINGLE / TOTAL FILTER GAGE ONLY
PRE AND FINAL FILTER GAGES
5
2-5/8" DIA. MOUNTING HOLE
LOW PRESSURE SIDE HIGH PRESSURE SIDE
MINIHELIC II 0-3"W.C.
RETAINER PREFILTER
EYELET
FRONT VIEW
3/16" DIA HOLE
POLYESTER GAGE LABEL
FINAL FILTER MINIHELIC II 0-3"W.C.
LINER COVER PLATE
PREFILTER
NOTE:
FILTER
FINAL
LD09675
FIG. 5-106 – FILTER GAGE DIAGRAMS
ENERGY RECOVERY WHEEL Wheel segments are secured to the wheel frame by
a segment retainer, The retainer pivots on the wheel
TOOLS REQUIRED
rim and is held in place by a segment retainer catch
• Standard mechanic’s hand tools. (see Fig. 5-108).
• Metric Allen wrenches.
• Hammer. SEGMENT RETAINER
CATCH
• Replacement segment.
WHEEL RIM
CENTER
REPLACING WHEEL SEGMENTS OF
WHEEL
REMOVAL OF SEGMENTS
WHEEL
ROTATION
BEARING SUPPORT
BEAM - PULLEY SIDE
BALL
BEARINGS (2)
BEARING ACCESS
COVER (2)
2
INSULATION
SEAL
PLATE
WHEEL
MOUNTING DRIVE
LD09676 BOLTS (4) MOTOR
BELT REPLACEMENT
BELT
Models ERC-36" Thru 110"
TAPE
Replacement consists of wrapping the belt around the
wheel rim, joining the ends by means of a single link
connector, and stretching the belt around the wheel
drive pulley.
1. Confirm the model number on the replacement
WHEEL
belt kit matches the model number on the energy
LD13356
recovery cassette label.
2. Remove any remnant of old belt from cassette. FIG. 5-112 – CROSS SECTIONAL VIEW OF HOOK
END OF BELT ATTACHED TO WHEEL
3. At location near pulley, attach the hook end of RIM WITH TAPE
belt to wheel rim with tape, making sure that
narrow side of “V” belt is positioned against rim 4. Rotate the wheel clockwise while feeding belt
and link is covered by the tape (see Fig. 5-111 & onto wheel rim (be careful not to twist belt) until
5-112). taped end returns to pulley location. Remove
tape from wheel.
5. Link belt ends together with belt wrapped
around wheel rim. (See Fig. 5-113).
LD09858
FIG. 5-111 – ATTACHING THE HOOK END OF BELT
TO WHEEL RIM WITH TAPE LD10016
7. At pulley location, insert the right angle belt- 8. Rotate wheel counterclockwise until belt
retaining clip between the rotatable segment retaining clip (red) is within a few inches of the
retainer latch and wheel rim at the left side of a bearing support beam (see Fig. 5-115).
spoke as shown in Fig. 5-114.
LD10018A
LD10017A FIG. 5-115 – RETAINING CLIP WITHIN A FEW
FIG. 5-114 – INSERT RIGHT ANGLE BELT INCHES OF THE BEARING SUPPORT
RETAINING CLIP BEAM
LD13360
FIG. 5-116 – STRETCHING BELT OVER PULLEY
TABLE 5-7 – CROSS REFERENCE; CONTINUOUS TO SINGLE LINK BELT/BELT PULLEY KITS
All Kits Includes V-belt, Belt Retaining Clip (Red) and Foil Tape. Contact local Johnson Controls Service to order parts.
BOLT SNAPS
COLD SHUTS
STEEL STAPLE PLATE WALL PANEL
PURCHASED DOOR
LD10211
JACKSHAFT TO
BLADE LINKAGE
DAMPER
ACTUATOR SELF
ACTUATOR DRILLING
SHAFT CLAMP SCREWS
BEARING PLATE
EDGE CLIP
025-39067-002
ROTATION
SELECTOR
ccw
cw
MOUNTING
GROOVES 5
MOUNTING BKT
JACKSHAFT
ACTUATOR
MANUAL
CRANK
SPRING HOSE
CLAMP(S)
LD12144
SIDE
PANEL A maximum spacing of 8" between
screws is recommended.
Install self tapping
screws through
flange on Mixing
Damper Wall into
Side Panel. Space
screws no more
than 8" apart
3. Once the mixing damper wall is properly
positioned and secured, install bracing (standard
Uni-strut or equivalent) vertically from ceiling
to floor (see Fig’s. 5-121 & 5-122).
LD12716
Fig. 5-120 – S
ECURE MIXING DAMPER WALL TO Install bracing on one side of the
SIDE PANEL mixing damper wall only. It is best
to install it on the flat side of the wall
PROCEDURE whenever possible.
1. Push mixing damper wall back into original
(vertical) position.
Install standard
Unistrut bracing
against ends of
dampers with damper
associated frame
hardware.
LD12717
LD12719
FIG. 5-121 – INSTALL BRACING TO MIXING DAMPER WALL ON EITHER SIDE OF DAMPERS
a. I nstall bracing on each end of the damper 4. Provide additional support by installing angle
and between dampers whenever possible brackets or gussets at the top and bottom of the
(see Fig’s. 5-121 & 5-124). bracing.
b. Center bracing between dampers and place
bracing up against each end of the damp-
ers.
Angle bracket installed
c. Secure all bracing to mixing damper wall between Uni-strut brac-
with associated hardware (3/8" or 1/2" bolts, ing and ceiling.
nuts and large washers).
Uni-strut bracing
centered between
dampers and installed
with associated
hardware.
Uni-strut bracing.
Angle bracket
installed between
Uni-strut bracing
and floor.
FIG. 5-122 – C
ENTER AND INSTALL BRACING
BETWEEN DAMPERS
US FAN
G
Exhaust on burner.
IN
Vent
HO ID Pressure
Switch
LD12903
Condensate
Line
FIG. 5-125 – OPEN FUSE DISCONNECTS
ID Fan ID Fan
Flange Gasket
2. Remove ID fan wires from terminals M-1 and M-2.
Remove ID airflow switch wires from terminals
LD12915
FIG. 5-124 – ID FAN ASSEMBLY COMPONENT ID-1 and ID-2 (see Fig. 5-126).
CALL OUT
TOOLS REQUIRED
• Standard mechanic’s hand tools.
• Allen wrench, 3/16".
Remove ID fan
• Pipe wrenches. wires from terminals
M-1 and M-2
• Socket wrench with 7/16" socket.
• Metal putty knife or equivalent.
• Razor knife or equivalent.
• Caulk gun.
MATERIALS REQUIRED
• Gasket material - Call Product Service and
provide (H) # to obtain proper P/N. Remove ID
airflow switch
• Sealant, Fiber Frax LDS moldable high temp wires from
sealant, 2500˚F max temp to apply, 40˚F min
terminals ID-1
and ID-2
5
temp, available at Grainger (P/N KM87).
LD12732
PROCEDURE
1. Disconnect power to the burner and ID fan at fuse FIG. 5-126 – REMOVE ID FAN WIRES AND ID
disconnects located in the control panel of the main AIRFLOW SWITCH WIRES
burner (see Fig. 5-125).
3. Remove wires completely from the control panel 5. Disconnect the ID fan condensate drain from the
area. Remove Greenfield ID fan conduit from main condensate line by loosening the union with
control panel (See Fig. 5-127). a pipe wrench as shown in Fig. 5-129.
ID Fan
Condensate Trap
Loose union
coupling to
MAIN disconnect ID
Remove wiring COND fan condensate
ENSA
and conduit from TE LIN trap from the
E
control panel main condensate
area. line.
LD12733 LD12716
FIG. 5-127 – R
EMOVE WIRING AND CONDUIT FIG. 5-129 – REMOVE CONDENSATE DRAIN TRAP
FROM CONTROL PANEL
6. Using a 7 /16" socket wrench or nut driver, loosen
4. With a 3/16" Allen wrench, remove the exhaust the top nut on the ID fan flange where it fastens to
vent locking collar cover from the exhaust vent the heat exchanger (do not remove). After remov-
(see Fig. 5-128). Then remove two of the 3/16" ing the remaining nuts, remove the top nut while
Allen bolts from the locking collar (not shown). supporting the ID fan housing (see Fig. 5-130).
Loosen the other two 3/16" Allen bolts and remove
the locking collar. Remove any old sealant from
the groove on the locking collar and set the locking
collar aside.
1 Loosen top
REMOVE 2 PC. LOCKING 7/16” nut but do
COLLAR COVER not remove.
Using 3/16” Allen wrench
remove exhaust vent
Upper locking collar cover by 2 Remove top 7/16” nut
Exhaust removing 2 bolts and
Vent loosening the other 2 bolts.
while supporting ID
fan housing.
Exhaust
Vent Lock- REMOVE 2 PC. LOCKING Id fan
ing Collar COLLAR
flange 3 Remove remaining
Cover After removing the cover, Heat 7/16” nuts.
remove the locking collar
by removing all 4 bolts with exchanger LD12735
FIG. 5-128 – R
EMOVE EXHAUST VENT LOCKING
COLLAR COVER AND LOCKING
COLLAr
7. Place your left hand under the extension tube be- 9. Before installing the ID fan housing, use a razor
tween ID fan and flange. Place the fingers of your knife or equivalent to trim the new gasket so that
right hand into the ID fan housing near the squirrel it will fit the heat exchanger opening (see Fig
cage fan. Lift and slide the ID fan housing from 5-133).
the threaded studs on the heat exchanger (see Fig
5-131).
Lift fan
housing
and slide
Place left off threaded
hand under studs.
extension LD12739
tube.
LD12736 FIG. 5-133 – TRIM GASKET
FIG. 5-131 – R
EMOVE ID FAN HOUSING FROM 10. Holding sheet metal cover panel 1/8" away from
HEAT EXCHANGER heat exchanger, apply moldable high temp sealant
(Fiber Frax LDS). See Fig 5-134.
8. Remove the old gasket from the ID fan flange.
Remove any remaining gasket material from the
ID fan flange and heat exchanger with a metal putty
knife or equivalent (see Fig 5-132).
HEAT
EXCHANGER
HEAT
EXCHANGER
COVER SHEET
METAL PANEL
Caulk with high temp
Remove all sealant between heat
old gasket exchanger and cover
material sheet metal panel. LD12740
from heat
exchanger
LD12737
FIG. 5-134 - C
AULK BETWEEN HEAT
5
EXCHANGER AND SHEET METAL
COVER SPANEL
ID FAN
FLANGE
Remove old
gasket from
ID fan flange.
LD12738
FIG. 5-132 – R
EMOVE OLD GASKET
johnson controls 5-77
Service & Repair
FORM 102.20-NOM1 (909)
11. Install new trimmed gasket over threaded studs 14. Apply moldable high temp sealant into both
on heat exchanger. Caulk the entire inner gasket grooves of the locking collar (see Fig. 5-137).
edge with moldable high temp sealant (see Fig.
5-135).
HEAT
EXCHANGER
Install new Caulk with high temp Apply moldable high temp
gasket over sealant around entire sealant to grooves in both
threaded edge of gasket. halves of locking collar.
studs on heat
exchanger. LD12741
HEAT LD12914
EXCHANGER
ID FAN
FLANGE FIG. 5-137 – APPLY SEALANT TO LOCKING
COLLAR GROOVES
LD12913
System not balanced properly. Balance system per design specifications. Pay close
attention to external static pressure “design” vs. “actual”. ►
Not enough length of straight duct at fan outlet before turn or restriction. Increase
length of straight duct at fan outlet or increase fan RPM to offset performance loss.
Note: Observe fan RPM limits per manufacturer's guidelines. ►
Obstructions in fan discharge duct. Remove obstructions. ►
Oversized ductwork. Reduce duct sizes or decrease fan RPM to obtain desired flow.
►
Unit access door open. Close all unit access doors.
System not balanced properly. Balance system per design specifications. Pay close
CFM HIGHER THAN REQUIRED
attention to external static pressure “design” vs. “actual”. ►
Registers or grilles not installed. Install all registers and grilles per design specific-
ations. ►
Unit air filters not in place. Install air filters. ►
Take ammeter readings on all three phases of motor to verify accuracy of ammeter.
►
High line voltage. Consult power company. Could possibly reduce voltage by using
lower transformer tap. ►
MOTOR-HIGH CURRENT DRAW Motor overloaded. Reduce load or use larger HP motor. ►
Low line voltage. Consult power company. Could possibly increase voltage by using
high transformer tap. ►
Re check air distribution system and air balance report for low static pressure or air
leaks in the unit or ductwork.
Unbalanced line voltage due to power supply, unbalanced electrical system loading
in building, high resistance connection or undersized power supply lines. Carefully
check voltage across each phase at the motor terminals with a quality, properly cali-
brated voltmeter. If the voltage per phase is more than 1 % out of balance, the current
will be out of balance by an even greater percentage. ►
MOTOR UNBALANCED If in doubt as to whether the problem is with the motor or incoming power supply lines
CURRENT DRAW perform the following test: Rotate all three input power lines to the motor by one posi-
tion - i.e., move line #1 to motor lead #2, line #2 to motor lead #3 and line #3 to motor
lead #1. If the unbalanced current draw pattern follows the input power lines the
problem is the power supply. Correct the voltage balance of the power supply. If the
unbalanced current draw pattern follows the motor leads the problem is a defective
motor. Replace motor. ►
Excessive starting or running load. Reduce load or install larger motor.
Inadequate power supply. Consult power company.
MOTOR-EXCESSIVE
VOLTAGE DROP Undersized power supply lines. Increase supply line sizes.
High resistance connections. Eliminate poor connections.
MOTOR - RUNS High ambient temperature over 40°C or 105°C. Reduce ambient temperature or pro-
EXCESSIVELY HOT vide outside source or cooler air.
Unbalanced current draw. Balance supply voltage. Check motor leads for tightness.
►
Motor single phase condition. Eliminate single phasing problem. 5
Motor single phase condition. Shut power off. Eliminate single phasing condition.
Check motor leads for tightness. ►
Rotor or bearings locked or frozen. Shut power off. Check shaft for freeness of opera-
MOTOR -WILL NOT START
tion. Replace bearings. Check overload relay sizing and verify overload relays are in
each of the 3 phases of the starter. ►
Motor single phase condition. If motor cannot be restarted it is single phased. Elimi-
nate single phasing condition.
Motor single phase condition. Check overload relay sizing and verify overload relays
MOTOR -RUNS NOISY are in each of the 3 phases of the starter.
UNDER LOAD Motor shaft bearing damaged. Replace bearing. ►
Supply voltage high or inconsistent supply frequency. Adjustable frequency control-
lers can generate motor noise.
Motor overloaded. Reduce load or increase voltage.
Excessively low voltage. A reasonable overload or voltage drop will reduce motor
MOTOR – LOAD SPEED CONSID-
speed only 1 - 2%. A drop of any greater magnitude would be questionable.
ERABLY BELOW NAMEPLATE
SPEED Inaccurate method of measuring RPM. Check motor using another RPM measuring
device or method. ►
Motor mounting loose. Check motor mounting and be sure it is tight and solid.
Load unbalanced. Disconnect belt and restart motor. If vibration stops, the load is
unbalanced. Balance the load.
MOTOR - EXCESSIVE VIBRATION Remove drive sheave and tape 1/2 key in shaft keyway and restart motor. If vibration
stops the sheave is unbalanced. Replace sheave. ►
If after checking all other options above and motor still has excessive vibration, the
motor is unbalanced. Replace motor. ►
High whine. Internal fit of bearing too tight. Replace bearing and check it. ►
Low rumble. Internal fit of bearing too loose. Replace bearing, check fit. ►
MOTOR - NOISY BEARINGS
Rough clatter. Bearing destroyed. Replace bearing. ► Avoid mechanical damage,
excessive greasing, wrong grease, ► solid contaminants and water running into
motor.
Determine if noise is from motor or fan. Isolate motor from fan and check difference in
noise level.
Fan noise transmitted to motor through drive. Reduce fan noise or dampen noise
transmission to motor.
MOTOR - MECHANICAL NOISE
Be sure fan vibration isolator shipping brackets are removed. If still in place remove
shipping brackets to allow vibration isolation of fan and motor. ►
Manual reset thermal cutout in electric heater control circuit tripped. Check reason for
tripping and correct. Reset manual cutout switch.
Airflow switch interlock not closed. Check airflow sensing tube for proper location in
airstream and for possible damage. Repair or replace airflow switch and / or sensing
tube as required.
NO ELECTRIC HEAT
Broken electric heating element. Replace element.
Heat limiters blown. Replace heat limiters.
Electric heater circuit fuses blown. Replace fuses.
Defective hot water or steam valve actuator motor. Replace actuator motor. ►
Broken control linkage from actuator to valve assembly. Repair or replace actuator
NO HOT WATER OR STEAM HEAT
linkage. ►
Defective hot water or steam control valve. Replace valve. ►
If unit shipped in more than one piece – Be sure these field reassembly joints are
properly sealed against rain water and air leaks. ► ►
If field piping or electrical conduits penetrate the unit – Be sure they are sealed prop-
WATER INSIDE UNIT
erly. The electrical conduits must be sealed internally to prevent airflow and moisture
condensation. ►
Be sure trap is installed and of correct size and construction. ►
Check for dirty filters. Filters may load much more rapidly if construction is on going
in the immediate area, if certain area vegetation releases airborne substances or if
insect swarms are present. ►
Check for wet filters or snow loading – See PRE-FILTERS ARE WET.
FILTERS OUT OF FILTER RACK Check for damage to the filter racks, filter frames, filter headers or filter tracks. ►
AIR MODULATOR (AIRMOD) WILL Verify control signal is wired in (or piped in if pneumatic) at correct terminals and is of
NOT OPERATE correct type.
Refer to Installation, Operation, Programming, Troubleshooting and Technical Support
information packed inside Airmod.
AIR LEAKS
UNIT SWEATING
DAMPERS NOT OPERATING
PROPERLY
Loose belts.
Vibration may be coming from a source other than the fan. Stop the fan and deter-
FAN VIBRATION ►
mine if the vibration still exists. Disconnect the driver motor from the fan and operate
it by itself to determine if it produces vibration.
Water accumulating in airfoil blades.
Check unit location for flat level surface of curb or housekeeping pad. Uneven sur-
face will rack unit causing door to bind.
DOOR BINDING Check door frame for bow or twist.
Measure corner to corner of door and frame independently. If frame is out of square,
remove and re-install door frame and door as an assembly. If door is out of square,
replace door frame assembly.
PDTB
L1
208/230/380/460VAC
3 PHASE INPUT
L2
50/60 HZ
L3
1 2
FU1 FU1
2L2 2L3
SEE TRANSFORMER 7
CONNECTION DIAGRAMS
1 2 FOR PROPER T1
FU2
2 1 X1 CONNECTIONS X2
A A
8 3
A
A,B OFF RUN/TIME 6
HAND AUTO CLOCK
OOX 5
SAFETIES
B A AB
1 3 A FIRESTAT FREEZESTAT
OL1 8 14 X2
2 XOO 6 7
M1
C C BC SS1 B A,B A,B
2 4
OPTIONAL B J J
REMOVE JUMPER WHEN
CONNECTING SAFETIES CONTROL
2 CONTROL POWER X2 POWER
C OPTION B 9 UP TO (4)
8 1 PANEL 2 100VA TRANS.
OR LOW TEMP.
RESET
20 M1 21 LTC
OPTION
PANEL
WIRED IN YELLOW
OPTION
DISC1 FU3
DISC1
L1 L1
208/230/380/460VAC
208/230/380/460VAC
3 PHASE INPUT
3 PHASE INPUT
L2
50/60 HZ
L2
50/60 HZ
L3 L3
OPTIONAL OPTIONAL
DISCONNECT FUSED DISCONNECT
NOTE: CUSTOMER SUPPLIED NOTE: CUSTOMER SUPPLIED
DISCONNECT MUST MEET DISCONNECT MUST MEET
LOCAL CODES. LOCAL CODES.
M1 OL1 T1
T2
3PH
MOTOR
T3
NOTES:
- TERMINAL POINT
- REMOTE DEVICE (BY OTHERS)
CT1 M1
CT2
3PH
MOTOR
CT3
OL1
ALTERNATE OL1 - USED WITH CT1,2,3 WHEN MOTOR
ALTERNATE OL1 FLA. IS GREATERTHAN 80 AMPS.
LD09683 6
DISC
L1
208/230/380/460VAC
3 PHASE INPUT
L2
50/60 HZ
L3
L2 L3
2L2 2L3
SEE TRANSFORMER E
CONNECTION DIAGRAMS T1 7
1 2 FU2 FOR PROPER 2KVA
2 1 X1 CONNECTIONS X2
A C AB ABD E
8 3 ABC
LINE X2
B B
GFI AC
LOAD
A A
SERVICE
LIGHT
SWITCH S
L N
B AB A A A C
6 A
A,B OFF RUN/TIME
HAND AUTO CLOCK
OOX 5
SAFETIES
B A AB
1 3 A FIRESTAT FREEZESTAT
OL1 8 14 X2
2 XOO 6 7 SUPPLY
M1
BC SS1 B A,B A,B FAN
4 A A,B
J J
OFF RUN/TIME REMOVE JUMPER WHEN
HAND AUTO CLOCK CONNECTING SAFETIES
OOX 9
CD A
5
OL2
2 XOO 10 RETURN
M2
E E DE SS1 B A,B B FAN
2 6
OPTIONAL B
CONTROL
2 CONTROL POWER X2 POWER
OPTION UP TO (4)
8 E 1 PANEL 2 B 9
100VA TRANS.
OR LOW TEMP.
RESET
20 M1 21 22 M2 23 LTC
OPTION
PANEL
WIRED IN YELLOW
OPTION
1 2
L2 150VA OR 500VA L3
TRANSFORMER
FU1 FU1
2L2 2L3
SEE TRANSFORMER
CONNECTION DIAGRAMS 7
FOR PROPER T1
FU2
1 X1 CONNECTIONS X2
3
FIG. 6-2 – FULL VOLTAGE STARTER WITH SINGLE POINT POWER CONNECTION (204195)
DISC2
FU3 M1 OL1 2T1
2T2
3PH SUPPLY FAN
MOTOR
2T3
2T2
3PH RETURN FAN
MOTOR
2T3
CT1 M1
CT2
3PH
MOTOR
CT3
SUPPLY FAN
OL1
ALTERNATE OL1 - USED WITH CT1,2,3 WHEN MOTOR
ALTERNATE OL1 FLA. IS GREATERTHAN 80 AMPS.
CT4 M1
CT5
3PH
MOTOR
CT6
SUPPLY FAN
OL2
ALTERNATE OL2 - USED WITH CT4,5,6 WHEN MOTOR
ALTERNATE OL2 FLA. IS GREATERTHAN 80 AMPS.
NOTES:
- TERMINAL POINT
- REMOTE DEVICE (BY OTHERS)
LD09684 6
Install Relay
LD12500
N.O. C
11 14 RUN COMMAND
R
LOCATED IN MB/FM
21 24 BO OAD-C
R R R BLK
3C 6C
SIGNAL COM
DEVICE TERMINAL
IDENTIFICATION IDENTIFICATION
TB1-13 A1
A B
NODE
NUMBER
14
14A A,B,C,D SUFFIX
ex: COMPLETED LETTER
WIRE NUMBER A2
A1
C
CR2
PLUG
1 2
2A X2A
TB2-1 TB2-2
BLK 2C X2C WHT
115V
A,C,D 2 T1 A,C,D X2
TB2-3 TB2-4 100VA TB2-5 TB2-6
J BLU 6D 2C YEL J
24V
5 6 7 8
B,C,D B,C,D B,C,D C,D
5D 8C
2 3
NOTES:
1. THIS DRAWING IS A TYPICAL AS WIRED DRAWING AND IS NOT CREATED ON A PER UNIT ORDER BASIS,
ONLY FACTORY PROVIDED OPTIONS ARE SHOWN.
2. THE LOW VOLTAGE TRANSFORMERS IN THE CONTROL ENCLOSURE ARE FOR
FACTORY PROVIDED END DEVICES ONLY.
LD09686A
FIG. 6-5 – YORK SOLUTION FPC WIRING (204197)
X2(B) S
LINE 1(B)
WHITE HOT
L(A)
WHITE HOT
N
LOAD L(A) L(B)
X1
X2(B)
X2(A) TO TRANSFORMER
2L2
2L3
GND
X1
GRD
N L S 1 X2
GND
N L(B) S 1(A) X2(A) 2L2 2L3 1(A) 1(B)
LD09691
1 2
L2 L3
LD09692
085-013-001 NEW
085-013-002 NEW
LD11599
FIG. 6-10 – GAS HEAT, SINGLE PHASE, 1500VA TRANSFORMER, WIRING DIAGRAM
LD11690
FIG. 6-11 – GAS HEAT, (1) THREE PHASE MOTOR, 1000VA TRANSFORMER, WIRING DIAGRAM
LD11691
FIG. 6-12 – GAS HEAT, (2) THREE PHASE MOTORS, 500VA TRANSFORMER, WIRING DIAGRAM
©2009 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53203 Printed in USA 102.20-NOM1 (909)
www.johnsoncontrols.com Replaces 102.20-NOM1 (105)
RIVET NUT
(installed by factory)
PIPE CHASE
3
IInstall
nstall with self drilling screws. Insert screws
into, and between, all pre-punched holes in
3 flange. Typical
Typical for
for both
both top
top and
and bottom
bottom
flanges.
FIG. 2 – APPLY GASKET TO PIPE CHASE
2 YORK INTERNATIONAL
FORM 102.20-NOM1 (LS01) (307)
AIR HANDLER
Caulk
Caulk as shown by PIPE CHASE
dotted line (visible)
and
dashed line (hidden).
A
Apply
pply caulk between
Pipe Chase and Air
Handler
AIR HANDLER
PIPE CHASE
AIR HANDLER
5
3
1
2
IInstall
nstall self-drilling
4
screws starting in
• Apply 2" x 3/16" neoprene gasket to contact
middle and working side of cover angle.
towards ends.
PIPE CHASE • Remove top and bottom self-drilling screws
from pipe chase and set aside for later use.
FIG. 6 – PIPE CHASE TO ROOF INSTALLATION
• Place cover angles in vertical corners of pipe
• Add a small bead of Sikaflex or Manus chase and unit wall.
champagne caulking to the exterior vertical
seam between the air handler and the pipe
chase to insure complete seal. Pay special
attention to the top & bottom corners,
raceway & baserail engagements and under
A
AIR
IR HANDLER
the roof overhang (see Fig.'s 5& 7). PIPE CHASE
• Starting at the center, and working toward
each end, run self-drilling screws down
through the air handler overhang into the top Install Cover
of the pipe chase through the gasket. Use Angle between
caution not to strip the 20-gage housing with Cover Angle Air Handler and
shown with Pipe Chase
the screws. Line up self-drilling screws with gasket side before caulk
double row of screws on top of unit raceway, out dries
plus one spaced evenly between each (see FIG. 8 – INSTALL COVER ANGLE
Fig. 6) (No caulking required here.)
5. Install the Cover Angles Notch on cover angle must be on the
air handler side (see Fig.9).
(See Fig. 8)
YORK INTERNATIONAL 3
Install (2) top and (2) bottom
AIR HANDLER
self-drilling screws first.
PIPE CHASE
PIPE CHASE
AIR HANDLER
Put
Put notch on cover angle
on Air Handler side.
P.O. Box 1592, York, Pennsylvania USA 17405-1592 Subject to change without notice. Printed in USA
Copyright © by Johnson Controls 2007 ALL RIGHTS RESERVED
Form 102.20-NOM1 (LS01) (307)
Replaces 102.20-NOM1 (LSO1) (606)
Form Number: 102.20-NOM1 (Ls02) 1108
3/8" Flat
Washer
Size = 3/16" 3/8" Lock Washer
Allen Wrench Baserail Lifting Lugs Assembled
LD11029A
Bracket p/n 086-11146-001
FIG. 1 – SECOND TIER TIE-DOWN FASTENER PACK P/n 1/2" x 4" Bolt
386-03419-000 (4 each per pack)
FIG. 3 – B
ASERAIL SHIPPING SPLIT FASTENER PACK P/n
386-03417-000 (4 each per pack)
SEAM CAP
• 1/4" x 2" Neoprene Gasket, P/N 028-15954-010
• 1/4"-14 x 1" Phillips Pan Head Tek Screw, P/N 021-19560-000
• 1/4"-14 x 1" Hex Head w/ Washer & Gasket Tek Screw
P/N 021-30530-052 for Outdoor Wall.
ROOF SEAM CAP
• 1/4" x 2" Neoprene Gasket, P/N 028-15954-010
Apply 2" Gasket • 1/4"-14 x 1" Hex Head w/ Washer & Gasket Tek Screw
& Caulk P/N 021-30530-052 for Outdoor Roof.
PIPE CHASE
• 1/4" x 2" Neoprene Gasket, P/N 028-15954-010
• 1/4"-14 x 1" Hex Head w/ Washer & Gasket Tek Screw
P/N 021-30530-052
Apply Caulk
Apply Caulk
PIPE CHASE BASERAIL COVER HOOD
P/N 086-23998-001
• 1/4"-14 x 1" Hex Head w/ Washer & Gasket Tek Screw
• 3/16" x 3/4" Butyl Tape
LD13770
2 YORK INTERNATIONAL
FORM 102.20-NOM1 (LS02)
HUMIDIFIERS
Optional Steam humidifiers, when selected are provided
with dispersion equipment factory mounted inside the
air handling unit. The steam injection or generating
equipment, metering devices & sundries are shipped
loose.
FLUE CAP
CONTAINMENT
BAND
UV
LIGHT
TUBE
YORK INTERNATIONAL 3
1/4” X 3-1/2” x 3-1/2” SHIPPING SPLIT
POLYURETHANE CAULK
CORNER GASKET
P/N 013-02966-011
P/N 028-11883-010
Never use silicone caulk/seal- (Outdoor Only)
ant or caulk/sealant contain-
ing silicone in or on any air
handling equipment. [Only
exception is when provided
(high temperature) with gas
heat venting] 12 OZ. TOUCH-UP SPRAY
P/N 013-03322-000
1/4”-14 X 1”
PHILLIPS PAN HEAD
SELF DRILLING SCREW
P/N 021-19560-000
1/4”-14 X 1”
SPARE FAN BELT HEX HEAD
(Attached to Fan)
SELF DRILLING SCREW
W/ EDPM WASHER
P/N 021-30530-052
ld13771
©2008 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53203 Printed in USA 102.20-NOM2 (LS02) (1108)
www.johnsoncontrols.com Supersedes 102.20-NOM2 (LS02) (605)
Form No.: 102.20-NOM1 (LS03) 506
Supersedes: None
ACTUATOR
ACTUATOR EXTENSION PIN
025-39032-002
025-39032-002
MOUNTING
FLANGES COLD DECK
DAMPER
• Damper blades are 6” wide and vary in height. • Duct connections are to be made at the zone
dividers without damper blade restriction.
• Calculate the torque by number and size of
blades in each individual zone. Remember there
are hot deck blades directly connected to cold MAINTENANCE
deck blades. Follow recommendation in IOM (see Section 4 of
• Blades per zone are to be determined by 102.20-NOM1 (105) “Economizer Segment (Damp-
system CFM and static pressure requirements ers)”.
for each zone by the Engineer’s construction
documents.
P.O. Box 1592, York, Pennsylvania USA 17405-1592 Tele. 800-861-1001 Subject to change without notice. Printed in USA
Copyright © by Johnson Controls 2006 www.York.com ALL RIGHTS RESERVED
Form 102.20-NOM1 (LS03)
New Release
Form No.: 102.20-NOM1 (LS04) 109
Subject: Indirect Fired Gas Heat Start Up - Eclipse Gas Burner Start Up 10:1 - 25:1 Turndown
& Powerflame Gas Burner Start Up 3:1 - 10:1 Turndown
For your safety and satisfaction, this Your gas burner has been carefully
product requires check, test and start- inspected and tested at the factory;
up adjustment by a qualified HVAC however, different conditions at the
technician. Do not use for temporary jobsite, including controls that have
heat prior to start-up. been added at time of installation,
require careful testing and final ad-
justment for satisfactory operation.
Review burner control literature, The Burner Test Report / Factory
including wiring, piping, cut sheets Specification Sheet in each unit shows
and drawings before attempting to the general data recorded during the
start this unit. operation and safety tests at the fac-
tory. This data should be used as a
general guide; with final data recorded
on the start-up form. Do not exceed
All factory test start up burner speci- 550°F flue temperature at the ID fan
fications are located on a laminated inlet. Do not exceed 200°F supply air
“Factory Specification Sheet" located temperature.
on the inside of the control panel
door”.
2 johnson controls
FORM 102.20-NOM1 (LS04) (109)
7. The flue (stack) damper is located at the discharge 10. Visually check that the high temperature safety
of the ID blower and closed for shipping. Release limit is set for a 200-230°F range. The limit switch
the locking mechanism and set the damper to match is typically mounted behind the burner control
the position indicated by the scribed markings. panel.
Lock in place (see Fig. 3-14).
11. Connect a 0-15" gas pressure gauge or other suit-
able instrument to the gas manifold port. The gas
Check Draft Test
ID fan Port
pressure will be measured when running (refer to
rotation step 4 of Burner Start-up Procedure).
Damper
Adjustment and On Powerflame burners this test port
Indicator Plate is downstream of the main regulator,
BURNER PANEL typically on a standard tee fitting in the
main gas line.
8. Inspect condensate drain trap to see that it is large 12. Connect a manometer or other suitable device to
enough, as described in this guideline (see Fig. the Heat Exchanger Draft Port located on the side
3-20). of the unit near the burner. The expected draft
should read slightly negative – about -.03" WC.
9. Measure the gas supply pressure coming into The draft port is typically made of ¾" steel pipe
the gas train (see Fig. 3-15). Gas pressure can be and may be plugged. Remove plug and add a small
greater than shown on the “Burner Test Report”, stop valve and a nipple for a rubber tube (see Fig.
but it must be between the min/max values listed 3-14 & 3-16).
in Table 3-2.
13. Install the Honeywell S7800 Test Module (display),
if available.
FIG. 3-15 – CHECK MAIN GAS SUPPLY PRESSURE System is now ready for start up.
johnson controls 3
FORM 102.20-NOM1 (LS04) (109)
4 johnson controls
FORM 102.20-NOM1 (LS04) (109)
7. Using the signal generator, cycle the burner to Do not change set up of factory preset
check capacity modulation. Observe valve/damper air inlet dampers on Power Flame
actuator operation. burner.
Damper
Actuator Any questions should be directed to
your local Service office or Johnson
Controls Product Tech Support, before
contacting the burner manufacturer.
Marked by
factory, future
reference for
actuator set up.
LD12909
johnson controls 5
FORM 102.20-NOM1 (LS04) (109)
BURNER
ASSY
ID
MOTOR
FLOW 2
1
3
4
2
3
PITCH
4 Foot
LD12912
1
Failure to follow these guidelines may 5. Condensate drain and trap discharge should be
cause excessive condensation build up pitched away from the equipment at a slope of 1/4”
resulting in water damage to the facil- per linear foot or as local code dictates.
ity and/or a cracked heat exchanger.
6. For outdoor or unconditioned space installations
local climate may dictate the need to heat trace
1. Observe local jurisdiction codes for gravity con-
and/or insulate the exposed drain lines and trap.
densate drainage requirements.
Frozen drain lines and/or trap will cause build up
of condensate inside the heat exchanger resulting
2. Be sure the air handler is installed at an elevation
in leakage and damage to the air handler and pos-
that enables proper condensate drainage and trap-
sibly to the facility.
ping dimensions as provided in Fig. 3-20. Mini-
mum trap dimensions MUST be accommodated. 7. Provide unions in drain lines to allow removal of
trap for periodic cleaning of drain lines as well
3. Condensate drain line size must be the full line size as the trap. When the burner is operated at low
of the heat exchanger drain connection. capacity for extended periods, more condensate
is generated and with it deposits of solids in the
4. Drain lines, fittings and supports should conform condensate drainage system.
to local codes and be suitable for the application. 8. Provide the ability to prime the trap. During initial
and seasonal start up, trap inspection and priming
is required. Condensate in the trap will evaporate
during long periods of non-use.
6 johnson controls
GAS HEAT SEGMENT MODEL NUMBER NOMENCLATURE
B 100 U 3 L G G A A
REV DF SIZE/ CODE BURNER UNIT HAND ID FAN UNIT CONTROL BURNER
LEVEL CAPACITY COMPLIANCE TDR YORK HOUSING VOLTAGE VOLTAGE MOD
MBH DESIGNATION (T'STAT VOLTAGE) CONTROL
johnson controls
A 15 150 A ANSI 3 3:1 L Left G Galvanized A 120/1/60 A 24 A 2-10 vdc
200 or
B 20 200 U UL 10 10:1 R Right S Stainless B B 120 B 4-20 mA
208/3/60
0-135
C 25 250 F FM 25 25:1 C 277/1/60 C
Ohms
230 or
30 300 R IRI D
240/3/60
35 350 E 380/3/60
40 400 F 440/3/50
45 450 G 460/3/60
380 or
50 500 H
415/3/50
60 600 J 575/3/60
75 750 K 220/3/50
85 850
100 1000
125 1250
150 1500
175 1750
200 2000
225 2250
250 2500
275 2750
300 3000
325 3250
350 3500
375 3750
400 4000
7
FORM 102.20-NOM1 (LS04) (109)
8
TABLE 3-2 – NATURAL GAS PRESSURE REQUIREMENTS (INCHES WC)
MAXIMUM ALLOW INLET PRESSURE Minimum Inlet Pressure to Fire
Nomenclature A03 U03 F03 R03 A10 U10 F10 R10 A25 U25 F25 R25 A03 U03 F03 R03 A10 U10 F10 R10 A25 U25 F25 R25
FEATURE GASBTUS GAS BURNER PIPING/GAS BURNER TD GASBURNER PIPING/ GAS BURNER TD
ANSI FM IRI ANSI FM IRI ANSI ANSI UL FM ANSI UL FM IRI
OPTION ANSI 3 UL 3 FM 3 IRI 3 UL 10 UL 25 UL 3 FM 3 IRI 3 IRI 10
10 10 10 25 25 25 3 10 10 10 25 25 25 25
Furnace Furnace
ANSI UL FM IRI ANSI UL FM IRI ANSI UL FM IRI ANSI UL FM IRI ANSI UL FM IRI ANSI UL FM IRI
Output Output
3:1 3:1 3:1 3:1 10:1 10:1 10:1 10:1 25:1 25:1 25:1 25:1 3:1 3:1 3:1 3:1 10:1 10:1 10:1 10:1 25:1 25:1 25:1 25:1
(X10K) (X10K)
015 14.00 NA NA NA 27.00 NA NA NA NA NA NA NA 015 4.00 NA NA NA 13.00 NA NA NA NA NA NA NA
020 14.00 NA NA NA 27.00 NA NA NA NA NA NA NA 020 4.00 NA NA NA 13.00 NA NA NA NA NA NA NA
025 14.00 NA NA NA 27.00 NA NA NA NA NA NA NA 025 4.00 NA NA NA 13.00 NA NA NA NA NA NA NA
030 14.00 NA NA NA 27.00 NA NA NA NA NA NA NA 030 4.00 NA NA NA 13.00 NA NA NA NA NA NA NA
035 NA 14.00 NA 27.00 NA 27.00 NA 27.00 NA NA NA NA 035 NA 5.00 NA 4.00 NA 4.00 NA 4.00 NA NA NA NA
040 NA 14.00 NA 27.00 NA 27.00 NA 27.00 NA 27.00 NA 27.00 040 NA 5.00 NA 5.00 NA 5.00 NA 5.00 NA 18.00 NA 18.00
045 NA 14.00 NA 27.00 NA 27.00 NA 27.00 NA 27.00 NA 27.00 045 NA 5.00 NA 5.00 NA 5.00 NA 5.00 NA 18.00 NA 18.00
050 NA 14.00 NA 27.00 NA 27.00 NA 27.00 NA 27.00 NA 27.00 050 NA 5.00 NA 5.00 NA 5.00 NA 5.00 NA 18.00 NA 18.00
060 NA 27.00 NA 27.00 NA 27.00 NA 27.00 NA 27.00 NA 27.00 060 NA 6.00 NA 6.00 NA 6.00 NA 6.00 NA 19.00 NA 19.00
075 NA 27.00 NA 27.00 NA 27.00 NA 27.00 NA 27.00 NA 27.00 075 NA 6.00 NA 7.00 NA 6.00 NA 7.00 NA 19.00 NA 19.00
085 NA 27.00 NA 27.00 NA 27.00 NA 27.00 NA 27.00 NA 27.00 085 NA 9.00 NA 8.00 NA 9.00 NA 8.00 NA 19.00 NA 19.00
100 NA 27.00 NA 27.00 NA 27.00 NA 27.00 NA 27.00 NA 27.00 100 NA 11.00 NA 9.00 NA 11.00 NA 9.00 NA 20.00 NA 20.00
125 NA 27.00 NA 27.00 NA 27.00 NA 27.00 NA 27.00 NA 27.00 125 NA 8.00 NA 7.00 NA 8.00 NA 7.00 NA 20.00 NA 20.00
150 NA 27.00 NA 27.00 NA 27.00 NA 27.00 NA 27.00 NA 27.00 150 NA 11.00 NA 9.00 NA 11.00 NA 9.00 NA 20.00 NA 20.00
175 NA 27.00 NA 27.00 NA 27.00 NA 27.00 NA 55.00 NA 55.00 175 NA 15.00 NA 12.00 NA 15.00 NA 12.00 NA 34.00 NA 34.00
200 NA 27.00 NA 27.00 NA 27.00 NA 27.00 NA 55.00 NA 55.00 200 NA 15.00 NA 12.00 NA 15.00 NA 12.00 NA 38.00 NA 38.00
225 NA NA 27.00 27.00 NA NA 27.00 27.00 NA NA 55.00 55.00 225 NA NA 8.00 11.00 NA NA 8.00 11.00 NA NA 34.00 34.00
250 NA NA 27.00 27.00 NA NA 27.00 27.00 NA NA 55.00 55.00 250 NA NA 8.00 11.00 NA NA 8.00 11.00 NA NA 35.00 35.00
275 NA NA 27.00 27.00 NA NA 27.00 27.00 NA NA 55.00 55.00 275 NA NA 11.00 10.00 NA NA 11.00 10.00 NA NA 39.00 39.00
300 NA NA 27.00 27.00 NA NA 27.00 27.00 NA NA 55.00 55.00 300 NA NA 11.00 11.00 NA NA 11.00 11.00 NA NA 40.00 40.00
325 NA NA 27.00 27.00 NA NA 27.00 27.00 NA NA 55.00 55.00 325 NA NA 8.00 9.00 NA NA 8.00 9.00 NA NA 41.00 41.00
350 NA NA 27.00 27.00 NA NA 27.00 27.00 NA NA 55.00 55.00 350 NA NA 8.00 9.00 NA NA 8.00 9.00 NA NA 48.00 48.00
375 NA NA 27.00 27.00 NA NA 27.00 27.00 NA NA 55.00 55.00 375 NA NA 8.00 10.00 NA NA 8.00 10.00 NA NA 49.00 49.00
400 NA NA 27.00 27.00 NA NA 27.00 27.00 NA NA 55.00 55.00 400 NA NA 9.00 10.00 NA NA 9.00 10.00 NA NA 48.00 48.00
Note: Gas pressure requirements at the inlet to the main manual shutoff cock of the gas train.
johnson controls
FORM 102.20-NOM1 (LS04) (109)
FORM 102.20-NOM1 (LS04) (109)
johnson controls 9
10
END OF FLUE PIPE FLUE CAP
CONTAINMENT FURNACE A
GAS FURNACE WITH CASING OUTPUT
BAND SET &
GASKET, 1" THK X 3"W X LG, 15 21.83
INSULATION FIBER 20 21.83
25 21.83
6"L SLIP JOINT 40 23.66
7.75 0.43" CLEARANCE 50 23.65
H
75 28.15
100 28.14
TRANSITION
PIECE 125 35.12
12" ID
EXT. FAN 150 35.12
175 35.12
200 35.12
A 250 41.36
300 41.36
350 47.36
400 47.36
HAT CHANNEL
NOTES:
1. SEE SECTION 026-004 TO
5.50 DETERMINE LENGTH OF IVSI PIPES.
FLOOR PANEL
W
LD13304
FIG. 3-21 – GAS FURNACE FUEL VENTING SYSTEM
johnson controls
FORM 102.20-NOM1 (LS04) (109)
STEP 3
STEP 1 FLUE CAP
STEP 2
42"L VSI PIPE SPLIT CLAMP
SPLIT PLATE (NOT INSULATED)
johnson controls
PIPE CHASE
CURB PIECE
RACEWAY
IVSI PIPE
SIDE PANEL (INSULATED PIPE)
SEE NOTE 1
CONTAINMENT
BAND SET &
GASKET, 1" THK X 3"W X LG,
INSULATION FIBER STEP 4
6"L SLIP
JOINT
12" ID
EXT. FAN TRANSITION
PIECE
STORM COLLAR
HAT CHANNEL
5.50
NOTES:
11
FORM 102.20-NOM1 (LS04) (109)
FORM 102.20-NOM1 (LS04) (109)
Connect Signal
Generator here for test
and start up
Jumper may be
required here for test
and start up
LD13315
12 johnson controls
FORM 102.20-NOM1 (LS04) (109)
INTERNAL INTERNAL
PRESSURE PRESSURE
CFM Temperature Rise (°F) CFM Temperature Rise (°F)
DROP “ DROP “
WC WC
johnson controls 13
Table 3-3 - BURNER TEMPERATURE RISE (CONT)
INTERNAL INTERNAL
PRESSURE PRESSURE
CFM Temperature Rise (°F) CFM Temperature Rise (°F)
DROP “ DROP “
WC WC
©2009 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53203 Printed in USA 102.20-NOM1 (LS04) (109)
www.johnsoncontrols.com Supersedes 102.20-NOM1 (LSO4) (208)