Phoenix Contact 3046090 en Item 1
Phoenix Contact 3046090 en Item 1
Phoenix Contact 3046090 en Item 1
block
3046090
https://www.phoenixcontact.com/ae/products/3046090
Please be informed that the data shown in this PDF document is generated from our online catalog. Please find the complete data in the user
documentation. Our general terms of use for downloads are valid.
Fuse modular terminal block, fuse type: Glass / ceramics / ..., fuse type: G / 5 x 20, nom. voltage:
24 V, nominal current: 6.3 A, connection method: Screw connection, Rated cross section: 4
mm2, cross section: 0.14 mm2- 6 mm2, mounting type: NS 35/7,5, NS 35/15, color: black
Your advantages
• An extremely compact design
• Test pick-off on both sides in the fuse lever
• Tested for railway applications
Commercial data
Item number 3046090
Packing unit 50 pc
Minimum order quantity 50 pc
Sales key BE1
Product key BE1134
Catalog page Page 161 (C-1-2019)
GTIN 4017918956585
Weight per piece (including packing) 17.27 g
Weight per piece (excluding packing) 16.4 g
Customs tariff number 85369095
Country of origin DE
Technical data
Notes
General The current is determined by the fuse used, the voltage by the
selected LED.
If the fuse is faulty, the downstream circuit will not be
disconnected.
Product properties
Product type Fuse terminal block
Area of application Railway industry
Machine building
Plant engineering
Number of connections 2
Number of rows 1
Potentials 1
Insulation characteristics
Overvoltage category III
Degree of pollution 3
Electrical properties
Fuse type Glass / ceramics / ...
Rated surge voltage 6 kV
Maximum power dissipation for nominal condition 1.02 W
Fuse G / 5 x 20
LED voltage range 12 V AC/DC ... 30 V AC/DC
LED current range 0.31 mA ... 0.95 mA
Maximum power dissipation max. 1.6 W (with single arrangement of the fuse terminal block in
the event of overload)
max. 1.6 W (With interconnected arrangement of several fuse
terminal blocks in the event of overload)
max. 4 W (with single arrangement of the fuse terminal block in
the event of a short-circuit)
max. 2.5 W (With interconnected arrangement of several fuse
terminal blocks in the event of a short-circuit)
Input data
LED voltage range 12 V AC/DC ... 30 V AC/DC
Connection data
Number of connections per level 2
Nominal cross section 4 mm²
Stripping length 9 mm
Internal cylindrical gage A4
Connection in acc. with standard IEC 60947-7-3
Conductor cross section rigid 0.14 mm² ... 6 mm²
Cross section AWG 26 ... 10 (converted acc. to IEC)
Conductor cross section flexible 0.14 mm² ... 6 mm²
Conductor cross section, flexible [AWG] 26 ... 10 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve) 0.14 mm² ... 4 mm²
Flexible conductor cross section (ferrule with plastic sleeve) 0.14 mm² ... 4 mm²
2 conductors with same cross section, solid 0.14 mm² ... 1.5 mm²
2 conductors with same cross section, flexible 0.14 mm² ... 1.5 mm²
2 conductors with same cross section, flexible, with ferrule 0.14 mm² ... 1.5 mm²
without plastic sleeve
2 conductors with the same cross section, flexible, with TWIN 0.5 mm² ... 2.5 mm²
ferrule with plastic sleeve
Nominal current 6.3 A
Maximum load current 6.3 A (the current is determined by the fuse used)
Nominal voltage 24 V
Nominal cross section 4 mm²
Dimensions
Width 6.2 mm
Height 57.8 mm
Depth on NS 35/7,5 75.6 mm
Depth on NS 35/15 83.1 mm
Material specifications
Color black
Flammability rating according to UL 94 V0
Insulating material group I
Insulating material PA
Static insulating material application in cold -60 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 125 °C
0304-21))
Relative insulation material temperature index (Elec., UL 746 B) 130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26 HL 1 - HL 3
Calorimetric heat release NFPA 130 (ASTM E 1354) 27,5 MJ/kg
Surface flammability NFPA 130 (ASTM E 162) passed
Specific optical density of smoke NFPA 130 (ASTM E 662) passed
Smoke gas toxicity NFPA 130 (SMP 800C) passed
Mechanical properties
Mechanical data
Open side panel No
Ambient conditions
Ambient temperature (operation) -60 °C ... 105 °C (max. short-term operating temperature RTI
Elec.)
Ambient temperature (storage/transport) -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to
+70 °C)
Ambient temperature (assembly) -5 °C ... 70 °C
Ambient temperature (actuation) -5 °C ... 70 °C
Permissible humidity (storage/transport) 30 % ... 70 %
Mounting
Mounting type NS 35/7,5
NS 35/15
Drawings
Application drawing
Circuit diagram
Application drawing
Approvals
To download certificates, visit the product detail page: https://www.phoenixcontact.com/ae/products/3046090
DNV
Approval ID: TAE00001S9
CSA
Approval ID: 13631
Nominal voltage UN Nominal current IN Cross section AWG Cross section mm2
Use group B
600 V 6.3 A - -
Use group C
600 V 6.3 A - -
IECEE CB Scheme
Approval ID: NL-65056
Nominal voltage UN Nominal current IN Cross section AWG Cross section mm2
500 V 6.3 A - 0.14 - 4
EAC
Approval ID: RU C-DE.BL08.B.00534
cULus Recognized
Approval ID: E60425
Nominal voltage UN Nominal current IN Cross section AWG Cross section mm2
Use group B
600 V 10 A 26 - 10 -
Multi-conductor 600 V 10 A 26 - 14 -
connection
Use group C
600 V 10 A 26 - 10 -
Multi-conductor 600 V 10 A 26 - 14 -
connection
KEMA-KEUR
Approval ID: 71-113330
Nominal voltage UN Nominal current IN Cross section AWG Cross section mm2
500 V 6.3 A - 0.14 - 4
LR
Approval ID: LR2003762TA
RS
Approval ID: 22.44.01.00083.250
CSA
Approval ID: 13631
Nominal voltage UN Nominal current IN Cross section AWG Cross section mm2
Use group B
24 V 6.3 A - -
Use group C
24 V 6.3 A - -
Classifications
ECLASS
ECLASS-11.0 27141116
ECLASS-12.0 27141116
ECLASS-13.0 27250113
ETIM
ETIM 9.0 EC000899
UNSPSC
UNSPSC 21.0 39121400