PV H1Z2Z2-K ETP-63

Construction Products Regulation (EU) No 305/2011 Ed. 11/2022 Rev. 2

Electric cables for photovoltaic systems

DESCRIPTION
Cables manufactured with cross linked elastomer insulation and outer sheath. Suitable for photovoltaic installations.
Construction is according to EN 50618 / IEC 62930
APLICATIONS
Indoor, outdoor, industrial, agricultural, fixed or mobile photovoltaic solar installations with trackers. It can be installed in trays, ducts
and equipment. Suitable for direct burial. Suitable for use with class II equipment.
CONSTRUCTION
1 ‐ Conductor: Tinned copper, flexible class 5 a/EN 60228

n2 ‐ Insulation: Cross linked compound, type Z2 a/EN 50618

3 – Outer sheath: Cross linked compound, type Z2 a/EN 50618


∙ Exterior colour: red, black or blue

TECHNICAL SPECIFICATIONS
Rated voltage: 1.000/1.000 V ac o 1.500/1.500 V dc
Max voltage: 1.200/1.200 V ac o 1.800/1.800 V dc
Test voltage: 6.500 V ac
Operating temperature: ‐40 to +120 ºC
Maximum short‐circuit temperature: 250 ºC (max. 5 s)
Bending radius: 5Ø
Water resistance: AD7 a/IEC 60364‐3
Contamination resistance: AF3 a/IEC 60364‐3
UV and ozone resistance: Complies a/EN 50618
Service life: 20.000 h at 120 ºC operating temperature a/IEC 60216
25 years at 90 ºC operating temperature

FIRE BEHAVIOUR SPECIFICATIONS


CPR classification (class): Dca‐s2, d2, a1 a/EN 50575

TEST STANDARDS VALUES

Flame retardant EN 60332‐1‐2, IEC 60332‐1‐2 O.K.


Low Smoke emission: EN 61034‐2, IEC 61034‐2 O.K., transmittance > 60%
Halogen free (HCl) EN 60754‐1, IEC 60754‐1 < 0,5, O.K.
Determination of degree of acidity of gases EN 60754‐2, IEC 60754‐2 pH ≥ 4,3 / Conductivity ≤ 10 µS/mm

page 1 of 2
PV H1Z2Z2-K ETP-63
Construction Products Regulation (EU) No 305/2011 Ed. 11/2022 Rev. 2

Electric cables for photovoltaic systems

DATA AND DIMENSIONS


Dimensions and weights are approximate, subject to small variations due to the process. Other sizes are possible on request.

Cross Section Insulation Outer sheath Outer Ø Weight


mm² thickness, mm thickness, mm mm Kg/km

1x2,5 0,7 0,8 5,0 43


1x4 0,7 0,8 5,6 59
1x6 0,7 0,8 6,4 81
1x10 0,7 0,8 7,1 123
1x16 0,7 0,9 8,7 192

Current carrying capacities have been calculated for the installations conditions provided for in the standard, for other installation
conditions must be used appropriated correction factors.

Conductor Insulation resistance Current carrying capacities


Cross Section MΩ∙km A (T. air 60 ºC – T. conductor 120 ºC)
resistance

Single cable free Single cable on a Two cables on a


mm² Ω/km at 20 ºC at 20 ºC at 90 ºC surface surface
in air

1x2,5 8,21 > 690 > 0,69 41 39 33


1x4 5,09 > 580 > 0,58 55 52 44
1x6 3,39 > 500 > 0,50 70 67 57
1x10 1,95 > 420 > 0,42 98 93 79
1x16 1,24 > 340 > 0,34 132 125 107