Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

FTP 4x2x22 AWG CAT. 5E FR (PH120) : Data Transmission Cables, Fire Resistant, Fire Retardant, Halogen Free

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

FTP 4x2x22 AWG CAT.

5E FR (PH120)
www.bericacavi.com

Data transmission cables, fire resistant, fire retardant, halogen free.

6 5 4 3 2 1
1. Conductor
2. Insulation
3. Flame protection
4. Drain wire
5. Shield
6. Sheath

APPLICATION: Used for the transmission of data at high frequency when there is the need to ensure the transmission of the signal even in the presence of a fire
(video security, interconnection of power plants for vocal evacuation and fire detection system).
INSTALLATION: For fixed indoor and outdoor installation (UV protection), in steel construction, cable trays, pipes, conduit and similar closed systems. Not for direct
burial. They can be installed in the same pipeline of electric circuits with 400V nominal ground voltage, typically 230/400V power systems.

FEATURES DESCRIPTION STANDARDS

Conductors : annealed red copper 0,63 mm (22AWG)


Insulation 1: low density polyethylene LDPE
Insulation 2: ceramifiable silicone rubber
Cores colour : white/blue - white/orange - white/green - white/brown
Flame protection : glass-fibre tape
Drain wire : annealed tinned copper
Shield : Al/Pet tape
Shield : braid of annealed tinned copper
Sheath : LSZH compound
Sheath colour : red RAL 3000
Fire retardant : CEI EN 60332-3-24
Halogen free : (< 0,5 mg/g - 0,5%) CEI EN 50267-2-1/2 - IEC 60754-1/2
Low smoke emission : (trasmittance > 60%) CEI EN 61034-2
Flame retardant : CEI EN 60332-1-2
Fire resistant : duration 120 min. at temperature of 830 °C (- 0 ÷ + 40 °C) CEI EN 50200
Fire resistant : duration 180 min. at temperature of 750 °C (FE180) IEC 60331-21 - VDE 472-814
DC resistance : < 120 Ω/km (loop) CEI EN 50288-2-1
Impedance : 100 ± 5Ω a 100 MHz
Cond-cond capacitance : of the order of 65 nF/km (1kHz)
Cond-shield capacitance : of the order of 85 nF/km (1kHz)
Inductance : of the order of 0,75 mH/km (1 kHz)
Testing voltage : 700 Vac x 1 min.
Max working temperature : 70 °C
Min. installation temperature : 0 °C
Bending radius : Øx8
Printing : BERICA CAVI S.P.A. ITALY S/FTP 4x2x22 AWG Cat.5E FR PH(120) Uo= 400V 100 OHM CE Year/Lot 00000 m

TYPE MEDIUM Ø OUTER MEDIUM WEIGHT PRODUCT CODE


mm kg/km
FTP 4x2x22AWG 10,2 108 B7504CA22FR

50