SABRE LITE SERIES

3kVA HOT-SWAP INVERTERS


WITH BUILT-IN ø RU AC PDU

DESCRIPTION

UNIPOWER’s SABRE LITE Series


INV1048 & INV1548 are 1000VA/800W and
1500VA/1200W, sine wave, hot-swap inverter
modules which are available with a number of
different compatible, two-unit 19-inch shelves.

These shelves are 1RU high (1.75 inches)


and provide various AC output termination
& distribution types as detailed in the table
opposite. 2006/95/EC

Operating from a 48VDC (40.5-58V range) input FEATURES


these units produce either 120VAC or 230VAC  Hot-Swap Replacement in Shelf
nominal output. Two units in the shelf can provide  One Rack Spaces High: 1.75”
either twice the capacity of a single unit or operate  19-Inch or 23-Inch Rack Mounting
fully automatically in an N+1 model. The low  1000 or 1500 VA Module Output
distortion 50 or 60Hz sine wave is produced using  2000 or 3000 VA for Two Units in 19” Shelf
an advanced DSP controlled architecture which  10.5 VA per Cubic Inch Density
achieve better than 89% efficiency and 10.5VA  120VAC or 230VAC
per cubic inch power density. Front panel LEDs  Low Distortion 50 or 60Hz Sine Wave
indicate inverter status and the units are self-  40.5 to 58 VDC Input
cooled by internal variable speed fans.  Form C Alarm Output
 >89% Efficiency
SABRE Series inverters can also be integrated
with a matching Controller and Static Transfer
INVERTER MODULES
Switch along with a Power Distribution &
MODEL OUTPUT OUTPUT FREQ. ²
Maintenance By-Pass unit and multiple inverter
POWER ¹ VOLTS
shelves can be connected together in parallel
INV1048 1000VA @ 0.8PF 120VAC 60Hz (50Hz)
to provide up to a maximum 18kVA output.
INV1048H 800W @ 1PF 230VAC 50Hz (60Hz)
When the controller is employed a remote
communications option provides connection to a INV1548 1500VA @ 0.8PF 120VAC 60Hz (50Hz)
PC via TCP/IP Ethernet, USB, RS232 or RS485 INV1548H 1200W @ 1PF 230VAC 50Hz (60Hz)
serial connections. Notes:
1. If in doubt about load PF (Power Factor) assume that it is 1.0PF.
2. The frequency shown in brackets can be requested at time of order.
See separate SABRE system brochure for
information about these additional features. INVERTER SHELVES
(FOR STAND-ALONE USE)
MODEL OUTPUT CIRCUIT OPERATING
CONNECTIONS BREAKERS VOLTAGE
INVR1U2-LN 2 x NEMA 5-15 2 x 15A 120V
INVR1U2-LE 2 x IEC320-C13 2 x 10A 120V/230V
TWO-YEAR WARRANTY
INVR1U2-LE20 1 x IEC320-C20 1 x 20A 120V/230V
INVR1U2-LBL 2 xTerminal Block 2 x 15A 120V
SAFETY COMPLIANCE INVR1U2-LBH 2 xTerminal Block 2 x 10A 120/230V
UL60950-1 2nd Edition INVR1U2-LB20 2 xTerminal Block 1 x 20A 120/230V
CSA22.2, No. 60950-1 2nd Edition
INVR1U2-LB30 2 xTerminal Block 1 x 30A 120/230V
EN60950-1 2nd Edition
Notes:
1. Module types may not be mixed in the same shelf or system.
2. For inverter systems requiring higher output capacities or ‘system’ level features as
www.unipowerco.com described opposite please consult the separate SABRE Series Systems Brochure.

NORTH AMERICA CALL: +1-954-346-2442 • EUROPE CALL: +44 (0)1903 768200


SABRE LITE SERIES 3kVA HOT-SWAP INVERTERS - 2

INVERTER MODULE SPECIFICATIONS


Typical at 48V Input, Full Load and 25°C Unless Otherwise Noted.

INPUT Dynamic Response........................................................................... <±10%


Voltage Range...........................................................................40.5-58VDC Isolation, Output to Chassis...... Basic Isolation (Pri-Gnd) 2121 VDC/1 min.
Undervoltage Warning Threshold...................................................... 45VDC Surge Protection...................................................................... EN61000-4-5
Undervoltage Threshold.................................................................... 40VDC Telcordia GR-1089 Core ANSI C62.41-IEEE, STD 587-1980
Overvoltage Warning Threshold........................................................ 58VDC
Overvoltage Threshold...................................................................... 60VDC CONTROL/STATUS
Input Current, 48VDC Input @ Full Load Load Sharing..................................................................<5% of Rated Load
INV1048......................................................................................... 19.0A LED Indicators
INV1548......................................................................................... 28.4A Inverter Status.........................................................Green OK, Red FAIL
Input Protection...................................... Fused Reverse Polarity Protection Overload.......................................................Off OK, Yellow for Overload
Inrush Current........................... Less than 2x Rated Iin (IEC62040-3-1999) Reverse Polarity............................................. Off OK, Red for Reversed
Isolation Status/Alarm Information
Input to Output............................. Reinforced Pri-Sec, 4242VDC / 1 min. Inverter Failure...........................................................Relay, Dry Contact
Input to Ground........................707VDC (Varistor & filter caps removed)
Psophometric Noise Voltage................... <1mV ITU-T 0.41 (16.66-6000Hz) ENVIRONMENTAL
Reflected Psophometrics Noise Current...................... <1% YD/T 777-2006 Operating Temp. Range
Reflected Relative Band Wide Current....... <10% YD/T 777-2006 (0-2MHz) Without Derating.................................................................. -5°C to 50°C
Wide Band Noise.................................................. <20mVrms (25Hz-20kHz) With Derating..................................................................... -20°C to 70°C
Peak to Peak Noise..................................................<150mV up to 100MHz Storage Temp. Range........................................................... -40°C to +85°C
Humidity......................................................... 0% to 95%, Non-Condensing
OUTPUT Cooling........................... Variable Speed Internal Fans (Field Replaceable)
AC Waveform......................................................................Pure Sine Wave
Output Power REGULATORY
INV1048............................................ 1000VA @ 0.8PF or 800W @ 1PF Safety..........................................UL60950-1 2nd Ed., EN60950-1 2nd Ed.,
INV1548.......................................... 1500VA @ 0.8PF or 1200W @ 1PF .IEC60950-1 2nd Ed.
Power Factor or Load................................................................. -0.8 to +0.8 EMC...................................................................... EN300 386:2001 Class B
Rated Output Voltage....................... 120VAC or 230VAC (see model table) Acoustic Noise................................................ 55dB ETS300 753, Class 3.1
Output Voltage Variation...................................................................... <±2%
Output Frequency.......................................50Hz or 60Hz (see model table) PHYSICAL SPECIFICATIONS (Shelf)
Frequency Variation.......................................................................... <±0.5% Case Material....................................................................................... Steel
Crest Factor.....................................................................................3:1 max. Dimensions, Inches (mm)
THD of Voltage Waveform Module................................................................ 1.59H x 8.46W x 10.6D
Linear Load...................................................................................... <3% .(40.4 x 214.9 x 269.2)
Non-Linear Load............................................................................... <5% Front Panel...........................................................................1.72H (43.7)
Capacitive/Inductive Load....................................................+0.8 to +0.8 PF Shelf.................................................................. 1.72H x 17.3W x 15.4”D
without exceeding permissible distortion for resistive load .(43.7 x 439.4 x 390.0)
Efficiency............................................................................................. >89% Rack Mounting............................................................. 19” or 23”, 1U High
Overload Protection..... Electronic Current Limit at Overload & Short Circuit Weights
1.25 x Rated Current, Temperature Controlled Module................................................................................5.7lbs (2.6kg)
1.50 x Rated Current for Periods <20 Seconds Shelf...................................................................................7.0lbs (3.2kg)

FRONT VIEW

17.3 (439.4)

1.72
(43.7)

LED
LOCKING INDICATORS
LATCH

REAR VIEW EXAMPLE (INVR1U2-LE)

B+ A A C C
J2 J1 C C B B
1 2 1 2
B-

FRAME GROUND DC INPUT ALARM AC OUTLETS OUTPUT O/LOAD


CONNECTIONS IEC60320-C13 PROTECTION
(see following page for alternate
connection options)

NORTH AMERICA • 3900 Coral Ridge Drive, Coral Springs, Florida 33065, USA • Tel: +1-954-346-2442 • Fax: +1-954-340-7901 • Sales-NorthAmerica@unipowerco.com
EUROPE • Parkland Business Centre, Chartwell Road, Lancing, BN15 8UE, ENGLAND • Tel: +44(0)1903 768200 • Fax: +44(0)1903 764540 • Sales-Europe@unipowerco.com
SABRE LITE SERIES 3kVA HOT-SWAP INVERTERS - 3

SHELF CONFIGURATIONS
(REAR VIEWS)
INVR1U2-LN

C C
B B
L1 N1 L2 N2 1 2
G1 G2

2 NEMA 5-15 load circuits protected by individual 15A circuit breakers - suitable to 120VAC operation only.
C C
INVR1U2-LE B B
1 2
AC1 AC2
C C
B B
L1 N1 L2 N2 1 2
G1 G2

L1 N1to L2
2 IEC60320-C13 load circuits protected by a individual 10A circuit breakers - suitable N2
120VAC or 230VAC operation.
C LOAD CB C
G1 G2
INVR1U2-LE20 B B
1 2
AC1 AC2
C C
B B
AC1L1 N1 L2 N2
AC2 1 LOAD CB
2
G1 G2

1 IEC60320-C19 load circuit protected by a single 20A circuit breakers - suitableL1to 120VAC
N1 L2 N2
or 230VAC operation.
C LOAD CB C
G1 G2
INVR12U-LBL & INVR1U2-LBH B
C B
C
1
B 2
B
(Top view shown with safety cover removed to show cable terminations)
AC1 AC2 1 2

C C
AC1 AC2 B LOAD CB B
L1 N1 L2 N2 1 2
G1 G2
C C
L1 N1 L2 N2 B B
1 LOAD CB 2
Type LB - 2 load circuits protected by individual 15A circuit breakers. G1 G2
(suitable to 120VAC operation only) C C
B B
Type LBH - 2 load circuits protected by individual 10A circuit breakers. 1 2
(suitable to 120VAC or 230VAC operation) AC1 AC2

INVR1U2-LB20 & INVR1U2-LB30 AC1 AC2 LOAD CB


(Top view shown with safety cover removed to show cable terminations)
C LOAD CB C
B B
L1 N1 L2 N2 1
C 2
C
B B
G1 L1 G2
N1 L2 N2 C
1 LOAD CB C
2
B B
G1 G2 1 2

Type LB20 - 2 load circuits protected by a single 20A circuit breakers.


(suitable to 120VAC or 230VAC operation) C C
B B
Type LB30 - 2 load circuits protected by a single 30A circuit breakers. AC1 AC2 1 LOAD CB 2
(suitable to 120VAC or 230VAC operation) AC1 AC2 C LOAD CB C
B B
1 2
INVR1U2-LB20 INVR1U2-LB30
LOCKING CABLE KITS LOCKING CABLE KITS C C
B B
USER VOLTS / ORDER USER VOLTS / ORDER 1 2
inv1000-ds-revM-0814.indd

TERMINATION AMPS CODE TERMINATION AMPS CODEL1 N1 L2 N2

L5-20R 120 / 20 775-1498-0000 L5-30R 120 / 30 775-1498-0010


G1 G2
LOAD CB
24” ±1”
L6-20R 240 / 20 775-1498-0020 L6-30R 240 / 30 775-1498-0030
LOAD CB
© 2014 UNIPOWER LLC
C to change without notice.
This document is believed to be correct at time of publication and Unipower LLC accepts no responsibility for consequences from printing errors or inaccuracies. All specifications subject C
B B
NORTH AMERICA • 3900 Coral Ridge Drive, Coral Springs, Florida 33065, USA • Tel: +1-954-346-2442 • Fax: +1-954-340-7901 • Sales-NorthAmerica@unipowerco.com 1 2
AC1 AC2 LOAD CB
EUROPE • Parkland Business Centre, Chartwell Road, Lancing, BN15 8UE, ENGLAND • Tel: +44(0)1903 768200 • Fax: +44(0)1903 764540 • Sales-Europe@unipowerco.com

You might also like