Perete +22 +5 Beton30 Tencuit
Perete +22 +5 Beton30 Tencuit
Perete +22 +5 Beton30 Tencuit
outside
20 3
340
300 2
www.ubakus.de
Commercial use only with Plus-, PDF- or Profi-Option (from 2.99 € / month plus VAT).
20 1
inside
1 Cement plaster (20 mm) 2 Concrete (300 mm) 3 Cement plaster (20 mm)
Cement plaster
Concrete
Cement plaster Equivalent
insulation thickness
(WLS 040)
08 95 Ti ba
u 5 ,15
41 O ige 0,2 nd 0
N tzV dr eu =
U sta U=
DI u ie 4 N u s 40
ch dn 1 Be nd uba au W
es n EV E V t a e 0,2 r-H u Kf
rm sta En En Be 16 N bau V U= .
s it e a
W
ä
V
Be 20 EV eu M ßn 3-L eub
En
E 20 En 20 N San lma N
G E e 5
GE 20 inz fW 5 G BW
G E
GE W K e
Kf bau ärm
u W
Ne E
*Vergleich mit dem Höchstwert gemäß GEG 2020 für erstmaligen Einbau, Ersatz oder Erneuerung von Außenwänden (Anlage 7, Zeile 1a,1b). Page 1
All statements without guarantee
Temperature profile
Temperature profile
22 Temperature
20 1 2 3 Dew point
18 Condensate
16 1 Cement plaster (20 mm)
Temperature [°C]
14
2 Concrete (300 mm)
12
3 Cement plaster (20 mm)
10
8
6
4
2
0
-2
0 50 100 150 200 250 300 350
Inside [mm]
Commercial use only with Plus-, PDF- or Profi-Option (from 2.99 € / month plus VAT).
www.ubakus.de Outside
Temperature and dew-point temperature in the component. The dew-point indicates the temperature, at which water vapour
condensates. As long as the temperature of the component is everywhere above the dew-point temperature, no
condensation occurs. If the curves have contact, condensation occurs at the corresponding position.
Page 2
All statements without guarantee
Moisture proofing
For the calculation of the amount of condensation water, the component was exposed to the following constant climate for
90 days: inside: 22°C und 60% Humidity; outside: 5°C und 60% Humidity (Climate according to user input).
On the inside of this component, humidity will condense because the surface temperature (12,9°C) is below the dew point
temperature (13,9°C). This will lead to mold formation in the long term.
You can prevent this by reducing the relative humidity of the room air or increasing the surface temperature by (additional)
thermal insulation. The reduction in humidity is only recommended in exceptional cases or as a short-term measure.
Condensation areas
Commercial use only with Plus-, PDF- or Profi-Option (from 2.99 € / month plus VAT).
1 Condensate: Affected layers: Cement plaster, Concrete
Humidity
The temperature of the inside surface is 12,9 °C leading to a relative humidity on the surface of 100%.Most kinds of moulds
start to grow at relative air humidities of 80% or more. Mould grow is expected! To avoid mould formation, the surface
temperature should be increased by (additional) insulation.
The following figure shows the relative humidity inside the component.
Page 3
All statements without guarantee
Heat protection
The following results are properties of the tested component alone and do not make any statement about the heat protection
of the entire room:
Temperature profile
This document has been generated by the U-value calculator on www.ubakus.de. If you are harmed by the free use of these contents, the service provider is only liable in case of
30
1 Cement plaster (20 mm)
28
Temperature [°C]
24
22
20
Commercial use only with Plus-, PDF- or Profi-Option (from 2.99 € / month plus VAT).
18
28
26
24
22
20
18
Phase shift: 8.5h
12 14 16 18 20 22 24 2 4 6 8 10 12
[time of day]
Top:Temperature profile within the component at different times. From top to bottom, brown lines: at 3 pm, 11 am and 7 am
and red lines at 7 pm , 11 pm and 3 am.
Bottom:Temperature on the outer ( red ) and inner ( blue ) surface in the course of a day. The arrows indicate the location of
the temperature maximum values . The maximum of the inner surface temperature should preferably occur during the
second half of the night.
Phase shift* 8,5 h Heat storage capacity (whole component): 764 kJ/m²K
Amplitude attenuation ** 4,6 Thermal capacity of inner layers: 220 kJ/m²K
TAV *** 0,216
* The phase shift is the time in hours after which the temperature peak of the afternoon reaches the component interior.
** The amplitude attenuation describes the attenuation of the temperature wave when passing through the component. A value of 10
means that the temperature on the outside varies 10x stronger than on the inside, e.g. outside 15-35 °C, inside 24-26 °C.
*** The temperature amplitude ratio TAV is the reciprocal of the attenuation: TAV = 1 / amplitude attenuation
Note: The heat protection of a room is influenced by several factors, but essentially by the direct solar radiation through windows and the
total amount of heat storage capacity (including floor, interior walls and furniture). A single component usually has only a very small
influence on the heat protection of the room.
Page 4